The document provided is a set of Questions and Answers (Q&A) related to a 75 KVA Transformer Solicitation for Holloman AFB, NM. The key details are:
The solicitation (FA480124Q0422) is seeking a 75 KVA Transformer in accordance with the Statement of Work (Attachment 1). Reconditioned transformers are not acceptable, but a radial feed transformer is acceptable in lieu of a loop feed transformer. FR3 oil is an acceptable specification, in addition to KNAN. The federal agency involved is the Department of the Air Force Air Combat Command.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Combined Synopsis_Solicitation.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TG Transformer
Questions and Answers 04 April 2024
1. Are reconditioned transformers acceptable? No, the windings in the transformer are to be copper and have a switch on the primary side.
2. Is a radial feed transformer acceptable in lieu of a loop feed transformer? Yes
3. Specifications state KNAN, is a Midel, or FR3, or mineral oil acceptable? FR3
File details come from the government source that posted it. Updated .