FA466125Q0010 Questions and Answers.docx

DOCX document 17 KB Posted

Attached to
High Voltage Cable Federal contract opportunity
Solicitation number
FA466125Q0010
Issued by
Department of the Air Force Global Strike Command

About this file

This document is a Questions and Answers (Q&A) file related to Solicitation Number FA466125Q0010 for High Voltage Cable. The solicitation is for 6 spools of 1000-foot high voltage wire cable, with detailed salient characteristics provided in Attachment 3.

The Q&A addresses several technical specifications for the cable, including the conductor AWG size of #2 AWG, 15kV voltage rating, 133% insulation level, full concentric neutral with 16 #14 wires, and a requirement for uncompacted copper conductor rather than compact copper. The solicitation is being issued by the Department of the Air Force Global Strike Command.

View the file

Other files for this federal contract opportunity

Other files attached to High Voltage Cable, newest first.
File Type Posted
Attachment 3 - Revised Sailent Characteristics.docx DOCX document
Attachment 3 - Sailent Characteristics.docx DOCX document
RFQ FA466125Q0010.docx DOCX document
Attachment 1 - Provisions and Clauses.pdf PDF
Attachment 2 - 52.212-5.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

November 6, 2024 7 CES High Voltage Cables Q&A

1. What is the conductor AWG size required?

Answer - The size is #2 AWG.

2. What’s the size #8 or 1500 kcmil?

Answer – Size is 15Kv. Information provided below to clarify the specifications. The salient characteristics attachment has been updated as well:

15kV CU 133% EPR Full Neutral LLDPE Primary UD Single Conductor #2 AWG, 220 Mils Ethylene Propylene Rubber (EPR). 133% Insulation Level, Full Concentric Neutral, Linear Low-Density Polyethylene (LLDP E) Jacket with red stripe

3. What is the number of neutrals?

Answer - The cable will contain 16 EA #14 wires that serve as the full concentric neutral within the cable.

4. Can the conductor be compact copper rather than compressed copper?

Answer – No.

File details come from the government source that posted it. Updated .