Does the building have a sprinkler system? Yes, and it needs to remain functional during the new alarm installation.
Is it being required to have co detection in just the sleeping rooms and lounges? Or everywhere, including the corridors? Everywhere, as stated in the SOW.
Just to verify, only 2 LOC’s, one in the north vestibule and south vestibule? Reason, Building 222 has one on each floor. UFC 4-021-01 requires an LOC on each floor and that occupants do not need to travel more than 200’ horizontally to reach it. Comply with this requirement.
One more clarification on the LOC. The UFC below is for Mass Notification. The Fire Alarm only need an LOC in the two vestibules.