AIR-COOLED SCROLL PACKAGED CHILLER

SPECIFICATIONS:

• Model # CGAM040A2 2AX-2A1A1A1-XXA1C1A4XXXXXXA1A5A1D1X-C-X OR

EQUAL TO

• Air-cooled scroll packaged chiller

• 1-year labor warranty

• 40 nominal tons

• 60 hertz

• 2 refrigeration circuit

• 4 scroll compressors

• 3 inch grooved chilled evap. Connection

• 208 volt 3 phases

• High efficiency/performance

• Full factory refrigerant charge (HFC-410A)

• Factory installed freeze protection

• Refrigerant isolation valves (discharge valve)

• UL listed to US and Canadian safety standard

• ASHRAE 90.1 2010 compliant

• AHRI certified

• Factory installed flow switch

• Set point 15cm/sec

• Phase reversal protection

• Std cooling (40 to 65F/4.44 to 18C)

• Grooved pipe connection

• Factory insulation 0.75” all cold parts

• Performance based on propylene glycol

• Extreme low ambient (-20F.-28.9C)

• Microchannel coil

• Across the line starter/direct on line single point connection main line unit power

• Ancillary items require other power circuit breaker

• Enclosure type UL 1995 rated for outdoor applications

• BACnet Interface

• Default A short circuit rating

• Elastomeric isolators with water strainer factory installed

• Comprehensive acoustic package

• Architectural louvered panels