Contractor Questions

FA462022QA102-ECU Units

Q1: “Compatible with standard small shelter system” – What kind of shelter is this for? Are you looking to install/mount these units to the shelter in a particular way?

A1: Alaskan Small Shelter or the CAMSS Q Series Shelters, exterior / ground placed

Q2: What dimensions are we limited to?

A2: none

Q3: Would the government accept ECUs of equal technical specification with a different color?

A3: any color is fine

Q4: Is this system going to be palletized?

A4: Yes, it should be able to be palletized for military transport

Q5: “Stackable” – how high / how many units high?

A5: The units should be able to support stacking of 4 units for storage and shipment

Q6: “Ruggedized” – Can you expand on this?

A6: Meaning – Can endure and operate is a wide range of operational climates (-25F to +125F)

Q7: For noise level Is it 69 decibels ducted or unducted? How many decibels above ambient is acceptable?

A7: Ducted and Noise level of 69 decibels or less at a distance of 3 feet away

Q8: Any EMI requirements?

A8: No

Q9: Do you prefer COTS, or are you open to a custom design?

A9: No

Q10: Is the remote control box wired or wireless?

A10: Wired

Q11: Remote Cable Thermostat – Can you please provide more clarification here? Are you just looking for a sensor that is 15 ft away from the unit?

A11: The thermostat will be required to be in the shelter and the unit can be up to 15’ away on the outside.

Q12: Any other required mil-spec components? Any other spec sheets?

A12: MIL-C-22992 Class L 60 Amp connector, 3-ph, 208/230V-120/208V 60Hz 12.5kW

Q13: Do these ECUs require any heating?

A13: Yes

File details come from the government source that posted it. Updated .