Contractor Questions
FA462022QA102-ECU Units
Q1: “Compatible with standard small shelter system” – What kind of shelter is this for? Are you looking to install/mount these units to the shelter in a particular way?
A1: Alaskan Small Shelter or the CAMSS Q Series Shelters, exterior / ground placed
Q2: What dimensions are we limited to?
A2: none
Q3: Would the government accept ECUs of equal technical specification with a different color?
A3: any color is fine
Q4: Is this system going to be palletized?
A4: Yes, it should be able to be palletized for military transport
Q5: “Stackable” – how high / how many units high?
A5: The units should be able to support stacking of 4 units for storage and shipment
Q6: “Ruggedized” – Can you expand on this?
A6: Meaning – Can endure and operate is a wide range of operational climates (-25F to +125F)
Q7: For noise level Is it 69 decibels ducted or unducted? How many decibels above ambient is acceptable?
A7: Ducted and Noise level of 69 decibels or less at a distance of 3 feet away
Q8: Any EMI requirements?
A8: No
Q9: Do you prefer COTS, or are you open to a custom design?
A9: No
Q10: Is the remote control box wired or wireless?
A10: Wired
Q11: Remote Cable Thermostat – Can you please provide more clarification here? Are you just looking for a sensor that is 15 ft away from the unit?
A11: The thermostat will be required to be in the shelter and the unit can be up to 15’ away on the outside.
Q12: Any other required mil-spec components? Any other spec sheets?
A12: MIL-C-22992 Class L 60 Amp connector, 3-ph, 208/230V-120/208V 60Hz 12.5kW
Q13: Do these ECUs require any heating?
A13: Yes
File details come from the government source that posted it. Updated .