FA460824QS022- Attachment 3 Photos of the Tanks.pdf

PDF 6 MB Posted

Attached to
Cathodic Protection Maintenance Barksdale AFB
Solicitation number
FA460824QS022
Issued by

About this file

This document is an attachment containing photos of various water tanks and their associated cathodic protection systems. The tanks are located at Barksdale Air Force Base and range in size and type, including ground storage tanks and elevated water storage tanks. The photos show the tanks' dimensions, cathodic protection rectifiers, anodes, and other system components.

The related federal contract opportunity is for the survey and repair of the cathodic protection systems on these tanks, as described in the Performance Work Statement. The solicitation number is FA460824QS022, and the contracting agency is the Department of the Air Force Global Strike Command. The requirement is for work on 4 elevated portable water storage tanks and 5 ground storage fire protection water tanks in accordance with the Performance Work Statement and MIL-HDBK-1136.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Tank 6800

Dimensions: 70’Ø x 20’ tall

Tank 6800 is equipped with an internal cathodic protection system to protect the submerged tank surfaces again corrosion. The cathodic protection system is an impressed current system with 9 type FW cast iron anodes suspended from the tank roof.

Figure 1 Location of Tank on Base

Tank 6800

Rectifier located inside building.

FA460824QS022

Attachment 3- Photos of the Tanks

Page 1 0f 35

Photo 1 Tank 6800 Rectifier

Photo 2 Tank 6800 Rectifier Interior

FA460824QS022

Page 2 0f 35

Photo 3 Roof of Tank

Photo 4 Anode Hole (Cover Removed)

FA460824QS022

Page 3 0f 35

Photo 5 Anode Removed for Inspection

Photo 6 Closeup of Typical Anode Segment

FA460824QS022

Page 4 0f 35

Tank 5857

Dimensions: 64’Ø x 21’ tall

Tank 5857 is equipped with an internal cathodic protection system to protect the submerged tank surfaces again corrosion as well as a soil-side cathodic protection system to protect the bottom against corrosion. Records indicate that the interior cathodic protection system is an impressed current system with 24 type FW cast iron anodes suspended from the tank roof. Field Inspection shows that the interior tank anodes are mixed metal oxide wires. The soilside system is an impressed current cathodic protection system consisting of 4 vertically installed anodes.

Figure 2 Location of Tank on Base

Tank 5857

Both rectifiers located inside building.

FA460824QS022

Page 5 0f 35

Photo 7 Tank 5857 Rectifiers and Terminal Box

Photo 8 Tank 5857 Interior System Rectifier

FA460824QS022

Page 6 0f 35

Photo 9 Tank 5857 Soil-Side System Rectifier Interior

Photo 10 Roof of Tank 5857

FA460824QS022

Page 7 0f 35

Photo 11 Typical Hand Hole Cover on Roof of Tank 5857

Photo 12 Tank 5857 Permanent Reference Electrode

TYPICAL ANODE

HAND HOLE

COVER

FA460824QS022

Page 8 0f 35

Photo 13 Tank 5857 Anode String Removed for Inspection

MMO ANODE

WIRE

FACTORY SPLICE

BETWEEN MMO

ANODE WIRE AND

LEAD WIRE

ANODE LEAD

WIRE

FA460824QS022

Page 9 0f 35

Elevated Water Storage Tank 4490

Riser Height = 100 feet Bowl Height = 50 feet

Elevated water storage tank 4490 is protected by an automatic potential controlled rectifier with a separate circuit for the riser and bowl.

Figure 3 Location of Tank on Base

Elevated Water

Storage Tank 4490

Rectifier and terminal box at base of water tower.

FA460824QS022

Page 10 0f 35

Photo 15 Overall View of Elevated Water Storage Tank 4490

Photo 16 Elevated Water Storage Tank 4490 Rectifier and terminal box

FA460824QS022

Page 11 0f 35

Photo 17 Elevated Water Storage Tank 4490 Rectifier Interior

Photo 18 Elevated Water Storage Tank 4490 Roof Terminal Box Interior

FA460824QS022

Page 12 0f 35

Photo 19 Roof of Elevated Water Storage Tank 4490

Photo 20 Roof of Elevated Water Storage Tank 4490

MMO ANODE

WIRE

ANODE LEAD

WIRE

FACTORY SPLICE

BETWEEN MMO

ANODE AND LEAD

WIRE

FA460824QS022

Page 13 0f 35

Tank 7562

Dimensions: 32’Ø x 45’ tall

Tank 7562 is equipped with an internal cathodic protection system to protect the submerged tank surfaces again corrosion. Records indicate that the interior cathodic protection system is an impressed current system with 5 type TA-FW cast iron anodes suspended from the tank roof.

Figure 4 Location of Tank on Base

Tank 7562

Rectifier located on exterior wall of tank.

FA460824QS022

Page 14 0f 35

Photo 21 Tank 7562 Rectifier

Photo 22 Tank 7562 Anode Hand Hole Covers on Roof of Tank

TYPICAL ANODE

HAND HOLE

COVER

FA460824QS022

Page 15 0f 35

Photo 23 Tank 7562 Anode

MMO ANODE WIRE

ANODE LEAD WIRE

FACTORY SPLICE

BETWEEN MMO

ANODE WIRE AND

ANODE LEAD WIRE

FA460824QS022

Page 16 0f 35

Spheroid Elevated Water Storage Tank 7298

Bowl Height = 28 feet, total height unknown

This elevated water storage tank is protected against internal corrosion by an impressed current cathodic protection system with 5 mixed metal oxide ribbon anodes.

Figure 6 Location of Tank on Base

Elevated Water

Storage Tank 7298

Rectifier located inside base of elevated water storage tank.

FA460824QS022

Page 17 0f 35

Photo 33 Tank 7298 Rectifier

Photo 34 Tank 7298 Rectifier Interior

FA460824QS022

Page 18 0f 35

Photo 35 Tank 7298 Anode Hand Hole Covers

Photo 36 Tank 7298 Anode

TYPICAL

ANODE HAND

HOLE COVER

MMO ANODE

WIRE

CERAMIC

WEIGHT

FA460824QS022

Page 19 0f 35

Tank 7722

Dimensions: 35’Ø x 22’ tall

Tank 7722 is equipped with an internal cathodic protection system to protect the submerged tank surfaces again corrosion as well as a soil-side cathodic protection system to protect the bottom against corrosion.

Figure 2 Location of Tank on Base

Tank 7722

Both rectifiers located on exterior wall of tank.

FA460824QS022

Page 20 0f 35

Photo 37 Tank 7722 Rectifiers

FA460824QS022

Page 21 0f 35

Photo 40 Roof of Tank 7722

Page 22 0f 35

Photo 41 Tank 7722 Anode

Photo 42 Anode Close Up

ANODE LEAD

WIRE

TYPE FW CAST

IRON ANODE

(1 OF 5)

FA460824QS022

Page 23 0f 35

Elevated Water Storage Tank 7417

Bowl Height = 18 feet Riser Height = 104 feet

This elevated water storage tank is protected against internal corrosion by an impressed current cathodic protection system.

Figure 7 Location of Tank on Base

Elevated Water

Storage Tank 7417

Rectifier located inside base of elevated water storage tank.

FA460824QS022

Page 24 0f 35

Photo 43 Tank 7417 Rectifier

Photo 44 Tank 7417 Rectifier Interior

FA460824QS022

Page 25 0f 35

Photo 45 Tank 7417 -Power Cable Very Close to Ladder

Photo 46 Anode Hand Hole Covers on Roof of Tank 7417

Cable so close to ladder that tank cannot be climbed without touching the cable. The power was turned off while climbing.

TYPICAL ANODE

HAND HOLE

COVER

FA460824QS022

Page 26 0f 35

Photo 47 Tank 7417 -Anodes Visible through Roof Hatch

Photo 48 Tank 7417 Anode Close Up

TYPE F CAST IRON

ANODE SEGMENT

(1 OF 5)

ANODE LEAD WIRE

FA460824QS022

Page 27 0f 35

Elevated Water Storage Tank 1358

Dimensions unknown

This elevated water storage tank is protected against internal corrosion by an impressed current cathodic protection system.

Figure 8 Location of Tank on Base

Elevated Water

Storage Tank 1358

Rectifier located inside base of elevated water storage tank.

FA460824QS022

Page 28 0f 35

Photo 49 Tank 1358 Rectifier and Terminal Box

Photo 50 Tank 1358 Rectifier Interior

FA460824QS022

Page 29 0f 35

Photo 51 Tank 1358 Terminal Box Interior

Photo 52 Tank 1358 Roof (Anode Hand Hole Covers)

Typical anode hand hole cover

FA460824QS022

Page 30 0f 35

Photo 53 Tank 1358 Anode

ANODE LEAD

WIRE

MMO ANODE

WIRE

FACTORY SPLICE

BETWEEN

ANODE AND

LEAD WIRE

FA460824QS022

Page 31 0f 35

Elevated Water Storage Tank 6209

Dimensions: 26’Ø x 11’

This elevated water storage tank is protected against internal corrosion by an impressed current cathodic protection system.

Figure 8 Location of Tank on Base

Tank 6209

Rectifier located on wall adjacent to tank

FA460824QS022

Page 32 0f 35

Photo 55 Tank 6209 Rectifier

Photo 56 Tank 6209 Rectifier Interior

FA460824QS022

Page 33 0f 35

Photo 57 Tank 6209 Roof

Photo 58 Tank 6209 Anode

Typical anode hand hole cover

TYPE FW CAST

IRON ANODE

SEGMENT (1 OF 4)

ANODE LEAD

WIRE

FA460824QS022

Page 34 0f 35

Photo 59 Tank 6209 Anode Close Up

Page 35 0f 35

File details come from the government source that posted it. Updated .