FA4528‐17‐Q‐4033
Attachment 2
80 Ton Chill Specifications
Refrigerant isolation valves -to store refrigerant in condenser Nominal load value 16.09 nplv Low ambient lock out to 30 f Flow gpm 216, net cooling 76.98 evaporator pressure drop 9.68 Ul and fcc approved isn micro-computer control 40 character lcd touch screen display Louvered hail guard panels Bacnet bas control interface R410a refrigerant Ul listed 3r enclosure ul listed ground fault protection 208 3 ph 60 hz 3 phase motor overcurrent protection Disconnect switch with lockable handle 110 volt gfi protected mechanics outlet Low sound fan motors 3/4 inch thick insulation on evaporator Neoprene isolators Flow switch High efficiency rotory scroll compressors Hfc-410 a factory refrigerant and oil charge Hermetic high efficiency induction motor