AT0490 -PFC072- Specs.pdf
PDF 240 KB Posted
- Solicitation number
- FA442725QZ006
About this file
This document is an operation and maintenance manual for the FCX Systems Extreme Series power generator. It provides detailed specifications for the physical dimensions, electrical inputs and outputs, cooling system, environmental requirements, and control/indicator features of the SSFC model generator.
The key details include:
- Physical dimensions (64 x 36 x 34 inches, 1,240 lbs)
- Electrical input (480VAC, 99A, 3-phase, 60Hz) and output (200/115VAC, 260A, 3-phase, 400Hz, 90kVA/72kW)
- Cooling system requirements (340-1,240 CFM airflow)
- Environmental operating range (-25F to 131F, up to 9,842 ft altitude, 90 mph winds)
- Control and indicator features (LED/LCD display, keypads, status lights)
This manual provides comprehensive technical specifications for the FCX Systems power generator, which appears to be required for an upcoming repair and maintenance contract opportunity at Travis AFB.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FCX SYSTEMS EXTREME SERIES OPERATION & MAINTENANCE MANUAL (AMA911) REV 000 (12/09/2020) 8
2. General Information and Theory of Operation:
2.2 SSFC Specifications:
Physical Specifications:
Parameter SSFC Height (in/mm) 64 in 1626 mm Width (in/mm) 36 in 914 mm Depth (in/mm) 34 in 864 mm Mass (lbs./kg) 1240 lbs 562 kg
Input Electrical Specifications:
Parameter SSFC Voltage (±10%) 480VAC Current 99A Frequency (Hz) 60Hz Phase 3ph Phase Rotation Any (ABC or CBA) Inrush None, Soft Charge to Rated Power Protection Overload, Short Circuit, Over/Under Voltage, Phase
Loss, Over-Temperature, & Door Interlock(s)
Output Electrical Specifications:
Parameter SSFC Voltage (±1%) 200/115VAC Current 260A Frequency (±0.01%) 400Hz Phase 3ph Power Factor 0.8pf Power (KVA/KW) 90KVA 72KW Overload 110% (1 Hour), 150% (2 Min), 200% (20 Sec) Voltage Adjust (Trim) ±15% of Nominal Line Drop Compensation (LDC) 0-7% Protection Overload, Short Circuit, Over/Under Voltage, &
Over-Temperature
System Cooling Specifications:
Parameter SSFC Rectifier 340CFM Inverter (IGBT) 340CFM Magnetic Intake 1240CFM Magnetic Exhaust N/A
FCX SYSTEMS EXTREME SERIES OPERATION & MAINTENANCE MANUAL (AMA911) REV 000 (12/09/2020) 9
System Environmental Specifications:
Parameter SSFC Operating Temperature Range (⁰F/⁰C) -25⁰F(-31⁰C) to 131⁰F(55⁰C) Storage Temperature Range (⁰F/⁰C) -40⁰F(-40⁰C) to 160⁰F(70⁰C) Humidity 10% to 100% without condensation Max Altitude w/out De-Rate (ft./m) 9842ft / 3000m Max Wind (mile/hr. / km/hr.) ≤90 mile/hr. / 145 km/hr.
Audible Noise ≤68dB @ 3ft (1m) Normal Operation Pollution Degree PD2 (Non-conductive with occasional temporary condensation) Degree of Ingress Protection
System Control and Indicator Specifications:
Parameter SSFC Display 4-line x 20-character LED / LCD Buttons 16 key matrix keypad (Menu Functions)
4 key matrix keypad (Operation Functions) Indicators Power On, Converter On, Module Fault, Input
Voltage Fault, Output Voltage Fault, Overload, 28VDC E/F Present, 28VDC E/F Bypass Mode, Output #1 On, Output #2 On Voltage Adjust (Trim) Via keypad menu Line Drop Compensation (LDC) Via keypad menu