This document is a combined synopsis/solicitation for a Firm Fixed Price contract for a Cost Per Reportable (CPR) Automated Chemistry and Immunoassay system for the David Grant Medical Center at Travis Air Force Base, California. The Department of the Air Force Air Mobility Command is seeking to award a contract with a base year and four 12-month option periods, with a possible 6-month extension. The NAICS code is 334516 - Analytical Laboratory Instrument Manufacturing, with a small business size standard of 1,000 employees. Contractors must provide quotes by 12 July 2024 and attend a site visit on 18 June 2024. The contract will be priced on a Cost Per Reportable basis, and the selected contractor will be responsible for providing all equipment. The government will use simplified acquisition procedures under FAR Part 13.5.

View the file

Other files

Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

For the best experience, open this PDF portfolio in

Acrobat X or Adobe Reader X, or later.

Get Adobe Reader Now!

http://www.adobe.com/go/reader

120/208V MAIN CB: 100A

ROOM # 2B316 C.B. CKT CKT C.B. FED FROM: 2AY2

R/2B316 REFRIGERATOR 20A 1 2 20A R/2B316 REFRIGERATOR

R/2B316 REFRIGERATOR 20A 3 4 20A R/2B316

R/2B316 20A 5 6 20A R/2B316

R/2B316 20A 7 8 20A R/2B316

R/2B316 20A 9 10 20A R/2B316

R/2B316 20A 11 12 20A R/2B316

R/2B316 20A 13 14 20A R/2B316

R/2B316 20A 15 16 20A R/2B316

R/2B316 20A 17 18 20A R/2B316

R/2B316 REFRIGERATOR 20A 19 20 20A R/2B316

R/2B316 20A 21 22 20A R/2B316

23 24

25 26

R/2B316 REFRIGERATOR 20A 27 28 20A R/2B316

SPARE 20A 29 30 20A SPARE

SPARE 20A 31 32 20A SPARE

SPACE 33 34 SPACE

SPACE 35 36 SPACE

SPACE 37 38 SPACE

SPACE 39 40 SPACE

SPACE 41 42 SPACE

L = Lighting E = EquipmentR = Receptacles

PREVIOUS UNIDENTIFIED CIRCUITS WERE INVESTIGATED AND LOADS IDENTIFIED

ON 4-6-15. HOWEVER, DUE TO THE AGE OF THE BUILDING AND NUMBER OF PROJECTS

THAT HAVE TAKEN PLACE, NO CIRCUIT SHOULD BE CONSIDERED GUARANTEED.

REVISIONS/COMMENTS

100A

PANEL SCHEDULE

3P4W

PANEL: 2ALY5

2B316 BLOOD STORAGE

FREEZER

20A 2P

2B316 BLOOD STORAGE

FREEZER

California Proposition 65 WARNING The vinyl holder may contain a chemical known to the State of California to cause

Cancer or Birth Defects or Other Reproductive Harm.

2ALY5

120/208V MAIN CB: 100A

R/2B316 20A 1 2 20A R/2B316

R/2B316 20A 3 4 20A R/2B316

R/2B316 REFRIGERATOR 20A 5 6 20A R/2B316

R/2B316 20A 7 8 20A R/2B316

R/2B316 20A 9 10 20A R/2B316

R/2B316 20A 11 12 20A R/2B316

R/2B316 20A 13 14 20A R/2B316

R/2B316 20A 15 16 20A R/2B316

R/2B316 20A 17 18 20A R/2B316

R/2B316 20A 19 20 20A R/2B316

R/2B316 20A 21 22 20A R/2B303

R/2B303 20A 23 24 20A SPARE

R/2B316 REFRIGERATOR 20A 25 26 20A SPARE

SPARE 20A 27 28

29 30

31 32

33 34 20A R/2B303

R/2B316 20A 35 36 20A SPARE

R/2B316 20A 37 38 20A SPARE

SPARE 20A 39 40 20A SPARE

L = Lighting E = Equipment

3P20A

3P

NOT ON THE ONE LINE

R = Receptacles

PANEL: 2ALY6

R/2B303

R/2B303

2ALY6

120/208 MLO: 100A

1 2 20A R/2B316

3 4 20A R/2B316

5 6

7 8

9 10 UNKNOWN

11 12 UNKNOWN

R/2B316 20A 13 14 UNKNOWN

SPARE 20A 15 16 UNKNOWN

17 18 UNKNOWN

19 20 UNKNOWN

21 22 UNKNOWN

23 24 UNKNOWN

SPACE 25 26 UNKNOWN

SPACE 27 28 UNKNOWN

SPACE 29 30 UNKNOWN

SPACE 31 32 UNKNOWN

SPACE 33 34 UNKNOWN

SPACE 35 36 UNKNOWN

SPACE 37 38 UNKNOWN

SPACE 39 40 SPACE

L = Lighting E = Equipment

PANEL: 2ALY7

E/2B316 COBAS ANALYZER

30A

R = Receptacles

E/2B316

E/2B316

2ALY7

ARCHITECT

i2000SR

Flammable Cabinet

Frig Freezer

A l i n t y

U

P S

K v a

Heme Bench

CCC

PPPP

ELGA

MEDICA

Pro

PP

Existing Power pole and DI water valve

PNEUMATIC PLATE

Existing Compressed airline

Will need to be removed

Existing Drain

ST

A-

R

STA-R

IOM TIM

(tube identification module)

Sealer Desealer

Decapper

CentrifugeCentrifugeCentrifuge

WASTE

BIN

SRM 9000

i n i n i

C

I i n i n i

CISCO

ROUTER

HUB

AUX-BOX

MAIN POWER DISTRIBUTION

PLATE

400V

Architect/Alinity

UPS 4Kva SP2

G

D

D D

T

Summary from Utility on Pole

400V Service from track UPS/Transformer

(3) 208V 30A L6-30R Analyzer UPS Power: "E" Power

(6) 120V 20A 5-20R General Power: "E" Power

(11) Data Lines

Compresses Air Feed

DI Water Loop with 2 valves

400V Distribution Panel

This is included with the track hardware

Track Pneumatic Panel

This is included with the track hardware

(11) Data lines

Terminated using using armored flex conduit with 4x4 "J" box w/cover plate

Mounted on lower shelf in track

General Power: "E" Power

(2) 120V 20A Quad 5-20R per location

(Dedicated circuit per location)

Terminated using armored flex or sealtite conduit with 4x4 "J" box w/cover plate.

Compressed Air supply

Pipe and termination Detail:

" Feed line from compressor terminated 18" from floor with

" ball valve FNPT and gauge 0-150psi

Abbott to provide tubing between supply valve at pole and the track main input air panel

9"

120V 20A r c u e d a t

5-20R

400V / 230V400V / 230V400V / 230V400V / 230V400V / 230V400V / 230V400V / 230V400V / 230V400V / 230V

120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a

208v 30a 208v 30a 208v 30a 208v 30a 208v 30a

120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a

120v 20a 120v 20a r a t

Quad 5-20R

120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a r a t r a t

DataData

X 11

Terminated using armored flex or sealtite

(2) DI Water Feed Valve

Each terminated with Ball valve, pressure regulator 0-30 psi and gauge 0-30 psi

208v 30a 208v 30a 208v 30a 208v 30a 208v 30a

208v 30a 208v 30a 208v 30a

Air Compressor

Power requirements:

208v

3 phase service

Air tank drain and Disiccant dryer

Power requirements:

(1) 120V 20A Duplex 5-20R

Floor drain

80 Gal.

Tank

Desiccent

Dryer

SET1007

15HP

Compressor

PowerEx

FRONT PANEL ** Location TBD **

Air Compressor **Location TBD**

Power Requirements

Input: 208v 3 phase service "E" Power

18"W x 30"D x 26"H12"W x 34"D x 40"H

I

S e r i e s o w r

C o n d i t i o n

K v t o w v a r a c k k

Track UPS / Transformer

W e

L p e

DI Water LoopDI Water LoopDI Water LoopDI Water LoopDI Water LoopDI Water LoopDI Water LoopDI Water LoopDI Water LoopDI Water Loop

DI Water Loop DI Water Loop DI Water Loop DI Water Loop DI Water Loop DI Water Loop DI Water Loop DI Water Loop DI Water Loop DI Water Loop e e r a t

208V 30A

L6-30R a t r a t r r a t r a t r a t

Analyzer UPS Power: "E" Power

(3) 208V 30A L6-30R conduit with a 4x4 "J" box w/cover plate.

r a t r a t

STA-R Power: "E" Power

(4) 120V 20A Duplex (2 per module seperate circuits)

Terminated using Armored flex conduit

4x4 "J" box w/cover plate a t r r a t

Duplex 5-20R

General Power r a t

ELGA Power: "E" Power

(2) 120V 20A Duplex 5-20R

Summary from Utility on Pole for ELGA systems

(6) 120V 20A 5-20R General Power: "E" Power

Cold Water feed with 2 valves

Unless noted Dimension = mm

Layout Designer:

Design Requester:

David Grant Medical Center

Travis Air Force Base

SHOP DRAWING

Notes:

1. This a3600 configuration is preliminary and subject to revision upon final manufacturing review.

2. Floorplan derived from converted data, dimensions to building structure or fixtures is for reference only.

10/13/2021 DD

Final Layout

AutoCAD SHX Text

B

L.Marquez

2021/10/08

Scale=1:30

Opt 3.2

S.Pritchett

Sheets and Views

OPT 3.2

IOM TIM

(tube identification module)

Sealer Desealer

Decapper

CentrifugeCentrifugeCentrifuge

WASTE

BIN

SRM 9000

Flammable

Frig Freezer

K

Heme

Command Center

Server

PNEUMATIC PLATE

Existing Compressed airline

**Will need to be removed**

CISCO

ROUTER

HUB

MAIN POWER DISTRIBUTION

PLATE

400V

D D

9" r a t

400V / 230V400V / 230V400V / 230V400V / 230V400V / 230V400V / 230V400V / 230V400V / 230V400V / 230V

120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a

208v 30a 208v 30a 208v 30a 208v 30a 208v 30a 208v 30a 208v 30a

120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a

120v 20a 120v 20a r a t

120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a 120v 20a r a t r a t

DataData

X 11

208v 30a 208v 30a 208v 30a 208v 30a 208v 30a 208v 30a 208v 30a 208v 30a 208v 30a e e

DI Water LoopDI Water LoopDI Water LoopDI Water LoopDI Water LoopDI Water LoopDI Water LoopDI Water LoopDI Water LoopDI Water Loop

DI Water Loop DI Water Loop DI Water Loop DI Water Loop DI Water Loop DI Water Loop DI Water Loop DI Water Loop DI Water Loop DI Water Loop e e r a t a t r a t r r a t r a t r a t

STA-R 120V 20A

r a t r a t a t r r a t r a t

New Power poles for

Command Center and Server Cabinet

(4) 120v 20a Quads

Existing Power Pole #1 **Remove**

Existing Power Pole #2

Existing Power Pole #7

Existing Power Pole #8

Existing Power Pole #6

Existing Power Pole #3

Existing Power Pole #4

Existing Power Pole #5

Existing Power Pole #9

Existing Power Pole #12 Not needed for Abbott

Could remain

Existing Power Pole #13 Not needed for Abbott

Could remain

Existing Power Pole #10 Remain to power Heme

Bench Existing Power Pole #11 Remain to power Heme

Existing Cold water supply

**Will need to be removed**

Existing DI Water valve Near Power Pole #9

New Power pole For New ELGA Water systems

(2) 120v 20a Duplex

(2) Cold water Feed

Valves

** Relocate compressed airline to track utility pole location **

** Relocate cold water feed to the ELGA water system utility pole location **

Unless noted Dimension = mm

Layout Designer:

Design Requester:

David Grant Medical Center

Travis Air Force Base

Notes:

1. This a3600 configuration is preliminary and subject to revision upon final manufacturing review.

2. Floorplan derived from converted data, dimensions to building structure or fixtures is for reference only.

Power Pole Locations

12/01/2021 DD

Final Layout

L.Marquez

2021/10/08

Scale=1:30

Opt 3.2

S.Pritchett

Sheets and Views

Power Pole Locations

E

COULTER

5.1 VITROS

V

IT

R O S

E

IQ

5.1 VITROS

O U

LT

4'-8"

4' 2"

1' 1"

2ALY1-6

2ALY1-7

2ALY1-8

2ALY1-9

2ALY1-10

2ALY1-11

2ALY1-12

2ALY1-13

G/LF LF LF LF LF LFLF

2ALY1-17 2ALY1-18 2ALY1-19

2ALY1-23 2ALY1-22 2ALY1-21 2ALY1-20

LF LFLF LF LF LF G/LF G/LFLF

2ALY1-30 2ALY1-29 2ALY1-28 2ALY1-27

G/LF LF LF LF LF LFLF

2ALY1-32 2ALY1-33

2ALY1-37 2ALY1-36 2ALY1-35 2ALY1-34

G/LF G/LF LF LF LFLF LF LF LF

LF LF LF G/LFLF LF LF G/LF

G/LF LF LF LF LFLFLFLFG/LF

2ALY1-25 2ALY1-26

2ALY1-15 2ALY1-14

2ALY1-16

2ALY1

+48"

2B302

MICROBIOLOGY

2ALY1-31

2ALY1-382ALY1-39

?G

2ALY1-4

G/LF G/LF

G/LF

2ALY1-40

2ALY1-24

2ALY1-42

2ALY1-41

2ALY2E-1,3,5,2

2ALY1-2

2ALY2

2ALY2-1

2ALY2-9

2ALY2-2

2ALY2-4

2ALY2-3

2ALY2-5

2ALY2-6

2ALY2-7

2ALY2-8

2ALY2-14

2ALY2-12

2ALY2-17

2ALY2-18

2ALY2-19

2ALY2-21

LF

2B404

BLOOD

BANK

2ALY2-25

6-15R

2ALY2-29,31

G/LF 2ALY2-30

2ALY2-11

2ALY2-32

2ALY2-15

2ALY2-16

2ALY2-33

2ALY2-13

DT

2ALY2-23

2ALY2E-4,6,8,12

2ALY6 2ALY5

2ALY6-52ALY6-42ALY6-32ALY6-22ALY6-1

LF LF

2ALY5-1

2ALY5-2

2ALY5-3

2ALY6-6 2ALY6-7 2ALY6-8

2ALY6-92ALY6-102ALY6-11 2ALY6-16

LF LFLF LF LF

LFLFLFLFLFLF LFLF

2ALY6-22

2ALY5-4 2ALY5-5 2ALY5-6

G/LF LF LF LF LF LF LFLF LF

2ALY5-11 2ALY5-10 2ALY5-9 2ALY5-8 2ALY5-7

G/LF G/LF LF LF LF LF LFG/LF LF LF LF LF

2ALY5-122ALY5-132ALY5-142ALY5-152ALY5-162ALY5-17

G/OC

OC

2ALY5-22

2ALY5-21

2ALY5-20

2B303

OFFICE

G/LF LF LF LFG/LFG/LF

LF LFLFLF LFLF

TV

2AN2.2-61

2AN2.2-632AN2.2-71

2B304

BREAKROOM

2AN2.2-66

2AN2.2-64

2AN2.2-62

G G+48"

OC OC

2ALY5-23,25

2ALY5-24,26

2B316

LABORATORY

20 21 22 23

H

2AN2.1-34

2ALY5-182ALY5-19

2ALY5-28

2ALY6-12 2ALY6-13 2ALY6-14 2ALY6-15

2ALY6-17,18,19 2ALY6-20,21,35

3 6

2ALY6-28,30,32,34

2ALY6-23,29,31,33

10 3

2ALY6-37

2AN2.2-78

2ALY7-6,8

2ALY7-9,11

2ALY7

2ALY7-2

2ALY7-4

2ALY7-1,3,5,7

2ALY5-27

2ALY3

G/LF G/LF G/LF G/LF LF LF

LFG/LFG/LFG/LF

LF LFLFLFLFLF

LF LF

LFLFLFLF

LFLFLFLF

G/LFG/LF

2ALY3-2

2ALY3-3

2ALY3-1

2ALY3-9

2ALY3-10

2ALY3-5 2ALY3-62ALY3-4

2ALY3-11

2ALY3-8 2ALY3-7

2ALY3-15

2ALY3-16

2ALY3-12

2ALY3-13

2ALY3-14

2ALY3-192ALY3-18

2ALY3-20 2ALY3-21 2ALY3-25

2ALY3-23

2ALY3-22

2ALY3-17

2ALY4

G G/LF+48"

2ALY4-1

2ALY4-2

2ALY4-3

2ALY4-4

2ALY4-5

2ALY4-6

2ALY4-7

2ALY4-8

2ALY4-112ALY4-122ALY4-13

2ALY3-27

2B405

HISTOPATHOLOGY

2ALY3-26 2ALY3-24

2ALY4-14

2ALY4-15

2ALY3-282ALY3-29

2ALY4-16

2ALY4-9

7 7

2ALY4-20

2ALY4-18

2ALY3-30 7

THESE RECORD DRAWINGS HAVE BEEN PREPARED, IN

PART, ON THE BASIS OF INFORMATION COMPILED AND

FURNISHED BY OTHERS. THE ENGINEER WILL NOT BE

RESPONSIBLE FOR ANY ERRORS OR OMISSIONS WHICH

HAVE BEEN INCORPORATED INTO THIS DOCUMENT AS A

RESULT.

THE ELECTRONIC FILE OF THIS SHEET WILL DETERIORATE

OVER TIME. THEREFOR, THE HARDCOPY PLANS TAKE

PRECEDENCE OVER THE ELECTRONIC FILES. RLF DOES

NOT ACCEPT ANY RESPONSIBILITY FOR UNAUTHORIZED

CHANGES TO THE ELECTRONIC FILES MADE BY THE

OWNER OR OTHERS.

AD L

EK

N

LL

F

IS EN

GI

O N A

EC NIL

S E

No 0052705

STATE OF

ROLF

I D A

EE

AS

M

ON

1/4"=1'-0" GRAPHIC SCALE

15'10'5'1'01'

09/16/2011

NOTE: IF THIS DRAWING IS LESS THAN 30" X 42"

IT IS A REDUCED SIZE DRAWING.

DA

VI

D

RA

ED

IC

AL

EN

TE

RE

CO

RD

RA

IN

th ed ic al G ro up

TR

AV

IS

FB

, C

FY

H

SP

IT

AL

DE

RN

IZ

AT

IO

RO

JE

CT

SHEET

REFERENCE

NO:

SHEET OF

DRAWN BY:

CHECKED BY:

DATE:

SCALE:

WJE PROJECT NO. :

CONTRACT NO. :

TASK ORDER NO. :

W9126-08-D-0055

Copyright c 2008, WJE HEALTHCARE ARCHITECTS and RLF, All Rights Reserved

WJE HEALTHCARE ARCHITECTS

UNITED EXCEL CORPORATION

ROGERS, LOVELOCK & FRITZ, INC.

FORT WORTH DISTRICT

wje‐architects.com Fx: (913) 438‐2660

Lenexa, Kansas 66214 8207 Melrose Dr., Suite 145

Ph: (913) 438‐9095 unitedexcel.com Fx: (913) 647‐9500

Merriam, Kansas 66202 5425 Antioch Drive

Ph: (913) 647‐9400 rlfae.com Fx: (407) 629‐9409

Winter Park, Florida 32789 145 Lincoln Avenue

Ph: (407) 647‐1039

Architecture, Engineering, Interior Design

REVISION BY

PROFESSIONAL SEAL

KEY NOTES

1 2 3 4 5

1 2 3 4 5

As indicated

PARTIAL 2ND FLOOR

ENLARGED ROOM

PLANS - LABORATORY

DRS

DRD

LB-EP401

SCALE: 1/4" = 1'-0"

B22B302 MICROBIOLOGY ENLARGED POWER PLAN

B42B404 BLOOD BANK ENLARGED POWER PLAN

D42B316 LABORATORY ENLARGED POWER PLAN

B52B405 HISTOPATHOLOGY ENLARGED POWER PLAN

1 PROVIDE WALL MOUNTED JUNCTION BOX AT

+84"AFF. HARD WIRED CONNECTION TO THE BLOOD

STORAGE FREEZER, 208V/1PH, 13.8 FLA.

2 PROVIDE 4#10 PHASE CONDUCTORS, 2#10 NEUTRAL

CONDUCTORS, AND 1#12 GROUND CONDUCTOR.

ONE NEUTRAL IS SHARED BETWEEN THE FIRST

THREE CIRCUITS. THE SECOND NEUTRAL IS

DEDICATED TO THE FOURTH CIRCUIT. INSTALL

CONDUCTORS IN A 1" CONDUIT.

3 CONNECT TWO RECEPTACLES PER CIRCUIT.

4 1"C - 4#8 + 2 #10 GROUND.

5 COORDINATE EXACT LOCATION WITH EQUIPMENT

INSTALLATION.

6 CONNECT ONE SIMPLEX L6-30R RECEPTACLE TO

CIRCUIT 2ALY6-24,26 AND ONE SIMPLEX L6-30R

RECEPTACLE TO CIRCUIT 2ALY6-36,38

7 CONDUITS SHALL ENTER FURNITURE FROM CEILING

THROUGH VERTICAL UTILITY CHASE PROVIDED

WITH FURNITURE.

8 3/4"C - 2#12 + 1#12 GND

9 PROVIDE HARDWIRED CONNECTION FOR GROSSING

STATION, JSN U2020AR.

10 CONNECT ONE RECEPTACLE PER CIRCUIT.

11 SEE DETAIL C1/NF-EP101 FOR THE DOOR BUZZER

CONNECTION DIAGRAM.

12 PROVIDE (4) 1" EMPTY CONDUITS STUBBED OUT

ABOVE CEILING.

13 3/4" C - 2#12 + 1#12 GND.

26 ASI #11 02/10/10 KGG

28 ASI #13 03/24/10 KGG