About this file
This Salient Characteristics document outlines requirements for purchasing a DV Power Battery DC Capacity and Discharge Tester (Model # BLU 400C) for the Moored Training Ship 701. The mission-critical battery tester is designed to confirm operational functionality of engineering safety features, specifically capacity testing battery discharges and charger performance. The device requires specific technical specifications including 300VDC capacity, 270A discharge, 20KW power, and the ability to test batteries while in service.
Key technical features include a 7-inch color touch screen display, fan cooling system, emergency stop button, and comprehensive protection mechanisms for overcurrent, overheat, and overvoltage scenarios. The tester must be mobile, with one worker able to carry it (up to 50 lbs), and includes 3-meter current cables with alligator clamps. The device can discharge batteries in four modes: constant current, power, resistance, and voltage, with an accuracy of ±0.5% of reading ± 0.1 V for DC voltage measurements between 0-800V. The procurement is dated 05 Sep 2025, with a specific focus on marine engineering safety equipment.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SALIENT CHARACTERISTICS
Battery Capacity and Discharge Tester
Brand Name or Equal 05 Sep 2025
1. GENERAL OVERVIEW.
The purpose of this requirement is to purchase one (1) DV Power Brand Name or equal Battery DC Capacity and Discharge Tester (Model # BLU 400C).
2. APPLICATION.
This is a mission critical battery tester that will confirm operational functionality of engineering safety features for the Moored Training Ship 701, specifically capacity testing the discharges and battery charger overcurrent and overvoltage.
3. SPECIFICATIONS.
• 300VDC
• 270A discharge
• 20KW Power
• Ground plug-in
• With parallel operation ability
• Enables testing batteries while in service
• Ambient temperature measurement
• DC Battery Capacity and Tester shall be capable of discharging in four different modes: constant current, power, resistance and voltage.
• Mobile and hand carriable with one worker able to carry up to 50 lbs.
• Accuracy: ±0.5% of reading ± 0.1 V (0 - 800 V DC)
• Display: 7 inch color touch screen display
• Cooling System: Fan cooled
• Thermal cut-outs and automatic overload protection
• Emergency Stop button
• Overcurrent, overheat and overvoltage protection
• Current cables 2 x 3 m 70 mm2 (9.84 ft, 00 AWG) with alligator clamps (A4) isolated.