This document is a specification for water utility distribution piping for the renovation of Building 90063 at Hurlburt Field in Florida. The project includes raising the main floor area with a new flooring system to run wiring underneath. The support area will contain office space, a breakroom, lactation room, and restrooms. Movable partition walls will divide the main floor area and be supported from manufacturer's steel supports attached to the existing slab. A new fire sprinkler and mass notification system will be installed along with a new mechanical system. Three exit doors will have new ramps to accommodate the raised floor. All new interior finishes are included. The specification provides requirements for water piping materials including ductile iron, PVC, polyethylene, steel, and plastic for service lines. It also specifies valves, fittings, joints, couplings, and installation methods. Testing requirements include hydrostatic and leakage tests.
View the file
Other files
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Renovate Bldg 90063, 505 OTS Hurlburt Field, Florida
SECTION 33 11 00
WATER UTILITY DISTRIBUTION PIPING
02/18
PART 1 GENERAL
1.1 UNIT PRICES
Measurement and payment will be based on completed work performed in accordance with the drawings, specifications, and the Contract payment schedules.
1.1.1 Measurement
The length of water lines will be determined by measuring along the centerlines of the various sizes of pipe provided. Pipe will be measured from center of fitting to center of fitting, from center of water main to center of fire hydrant and from center of water main to end of service connection. No deduction will be made for the space occupied by valves or fittings.
1.1.2 Payment
Payment will be made for water lines at the Contract unit price per linear foot for the various types and sizes of water lines, and will be full compensation for all pipes, joints, specials, and fittings, complete and in place. Payment for fire hydrants, valves, and valve boxes will be made at the respective Contract unit price each for such items complete and in place. Payment will include providing all testing, plant, labor, and material and incidentals necessary to complete the work, as specified and as shown.
1.2 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN SOCIETY OF MECHANICAL ENGINEERS (ASME)
ASME B16.1 (2020) Gray Iron Pipe Flanges and Flanged Fittings Classes 25, 125, and 250
AMERICAN WATER WORKS ASSOCIATION (AWWA)
AWWA C104/A21.4 (2016) Cement-Mortar Lining for Ductile-Iron Pipe and Fittings for Water
AWWA C110/A21.10 (2012) Ductile-Iron and Gray-Iron Fittings for Water
AWWA C111/A21.11 (2017) Rubber-Gasket Joints for Ductile-Iron Pressure Pipe and Fittings
AWWA C115/A21.15 (2020) Flanged Ductile-Iron Pipe With Ductile-Iron or Gray-Iron Threaded Flanges
SECTION 33 11 00 Page 1
AWWA C151/A21.51 (2017) Ductile-Iron Pipe, Centrifugally Cast
AWWA C153/A21.53 (2019) Ductile-Iron Compact Fittings for Water Service
AWWA C200 (2012) Steel Water Pipe - 6 In. (150 mm) and Larger
AWWA C203 (2008) Coal-Tar Protective Coatings and Linings for Steel Water Pipelines - Enamel and Tape - Hot-Applied
AWWA C205 (2018) Cement-Mortar Protective Lining and Coating for Steel Water Pipe - 4 In. (100
mm) and Larger - Shop Applied
AWWA C206 (2017) Field Welding of Steel Water Pipe
AWWA C208 (2017) Dimensions for Fabricated Steel Water Pipe Fittings
AWWA C500 (20019) Metal-Seated Gate Valves for Water Supply Service
AWWA C509 (2015) Resilient-Seated Gate Valves for Water Supply Service
AWWA C515 (2015) Reduced-Wall, Resilient-Seated Gate Valves for Water Supply Service
AWWA C550 (2017) Protective Interior Coatings for Valves and Hydrants
AWWA C600 (2017) Installation of Ductile-Iron Mains and Their Appurtenances
AWWA C604 (2011) Installation of Buried Steel Water Pipe—4 In. (100 mm) and Larger
AWWA C605 (2014) Underground Installation of Polyvinyl Chloride (PVC) and Molecularly Oriented Polyvinyl Chloride (PVCO) Pressure Pipe and Fittings
AWWA C606 (2015) Grooved and Shouldered Joints
AWWA C800 (2014) Underground Service Line Valves and Fittings
AWWA C900 (2016) Polyvinyl Chloride (PVC) Pressure Pipe, and Fabricated Fittings, 4 In.
Through 60 In. (100 mm Through 1,500 mm)
AWWA C906 (2015) Polyethylene (PE) Pressure Pipe and Fittings, 4 In. (100 mm) through 65 In., (1,575 mm) for Water Distribution and Transmission
SECTION 33 11 00 Page 2
AWWA M9 (2008; Errata 2013) Manual: Concrete Pressure Pipe
AWWA M11 (2016) Steel Pipe: A Guide for Design and Installation
AWWA M23 (2020) Manual: PVC Pipe - Design and Installation - Third Edition
AWWA M41 (2009; 3rd Ed) Ductile-Iron Pipe and Fittings
AWWA M55 (2020; 2nd Ed) PE Pipe - Design and Installation
ASTM INTERNATIONAL (ASTM)
ASTM A536 (1984; R 2019; E 2019) Standard Specification for Ductile Iron Castings
ASTM B32 (2020) Standard Specification for Solder Metal
ASTM D1784 (2020) Standard Specification for Rigid Poly(Vinyl Chloride) (PVC) Compounds and Chlorinated Poly(Vinyl Chloride) (CPVC) Compounds
ASTM D1785 (2015; E 2018) Standard Specification for Poly(Vinyl Chloride) (PVC), Plastic Pipe, Schedules 40, 80, and 120
ASTM D2241 (2015) Standard Specification for Poly(Vinyl Chloride) (PVC) Pressure-Rated Pipe (SDR Series)
ASTM D2466 (2017) Standard Specification for Poly(Vinyl Chloride) (PVC) Plastic Pipe Fittings, Schedule 40
ASTM D2467 (2015) Standard Specification for Poly(Vinyl Chloride) (PVC) Plastic Pipe Fittings, Schedule 80
ASTM D2774 (2012) Underground Installation of Thermoplastic Pressure Piping
ASTM D2855 (2015) Standard Practice for Making Solvent-Cemented Joints with Poly(Vinyl Chloride) (PVC) Pipe and Fittings
ASTM D3035 (2015) Polyethylene (PE) Plastic Pipe (DR-PR) Based on Controlled Outside Diameter
ASTM D3139 (2019) Joints for Plastic Pressure Pipes Using Flexible Elastomeric Seals
ASTM F402 (2005; R 2012) Safe Handling of Solvent
SECTION 33 11 00 Page 3
Cements, Primers, and Cleaners Used for Joining Thermoplastic Pipe and Fittings
ASTM F477 (2014) Standard Specification for Elastomeric Seals (Gaskets) for Joining Plastic Pipe
ASTM F714 (2021) Standard Specification for Polyethylene (PE) Plastic Pipe (DR-PR) Based on Outside Diameter
ASTM F2164 (2018) Standard Practice for Field Leak Testing of Polyethylene (PE) and Crosslinked Polyethylene (PEX) Pressure Piping Systems Using Hydrostatic Pressure
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 24 (2019; TIA 19-1) Standard for the Installation of Private Fire Service Mains and Their Appurtenances
NSF INTERNATIONAL (NSF)
NSF 372 (2016) Drinking Water System Components - Lead Content
NSF/ANSI 14 (2020) Plastics Piping System Components and Related Materials
NSF/ANSI 61 (2020) Drinking Water System Components - Health Effects
UNDERWRITERS LABORATORIES (UL)
UL 262 (2004; Reprint Oct 2011) Gate Valves for Fire-Protection Service
1.3 DEFINITIONS
1.3.1 Water Transmission Mains
Water transmission mains include water piping having diameters greater than 14 inch, specific materials, methods of joining and any appurtenances deemed necessary for a satisfactory system.
1.3.2 Water Mains
Water mains include water piping having diameters 4 through 14 inch, specific materials, methods of joining and any appurtenances deemed necessary for a satisfactory system.
1.3.3 Water Service Lines
Water service lines include water piping from a water main to a building service at a point approximately 5 feet from building or the point indicated on the drawings, specific materials, methods of joining and any appurtenances deemed necessary for a satisfactory system.
SECTION 33 11 00 Page 4
1.3.4 Additional Definitions
For additional definitions refer to the definitions in the applicable referenced standard.
1.4 SUBMITTALS
Government approval is required for submittals with a "G" or "S" classification. Submittals not having a "G" or "S" classification are for Contractor Quality Control approval. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-01 Preconstruction Submittals
Connections; G
SD-03 Product Data
Pipe, Fittings, Joints and Couplings; G
Valves; G [, [_____]]
SD-06 Test Reports
Leakage Test
Hydrostatic Test
SD-08 Manufacturer's Instructions
Ductile Iron Piping
PVC Piping
1.5 QUALITY CONTROL
1.5.1 Regulatory Requirements
Comply with NSF/ANSI 14 or NSF/ANSI 61 and NSF 372 for materials for potable water systems; comply with lead content requirements for "lead-free" plumbing as defined by the U.S. Safe Drinking Water Act effective January 2014. Provide materials bearing the seal of the National Sanitation Foundation (NSF) for potable water service.
Comply with NFPA 24 for materials, installation, and testing of fire main piping and components.
1.6 DELIVERY, STORAGE, AND HANDLING
1.6.1 Delivery and Storage
Inspect materials delivered to site for damage. Unload and store with minimum handling and in accordance with manufacturer's instructions.
Store materials on site in enclosures or under protective covering. Store plastic piping, jointing materials and rubber gaskets under cover out of direct sunlight. Do not store materials directly on the ground. Keep inside of pipes, fittings, valves, fire hydrants, and other accessories
SECTION 33 11 00 Page 5 free of dirt and debris.
1.6.2 Handling
Handle pipe, fittings, valves, fire hydrants, and other accessories in accordance with manufacturer's instructions and in a manner to ensure delivery to the trench in sound undamaged condition. Avoid injury to coatings and linings on pipe and fittings; make repairs if coatings or linings are damaged. Do not place other material, hooks, or pipe inside a pipe or fitting after the coating has been applied. Inspect the pipe for defects before installation. Carry, do not drag pipe to the trench. Use of pinch bars and tongs for aligning or turning pipe will be permitted only on the bare ends of the pipe. Clean the interior of pipe and accessories of foreign matter before being lowered into the trench and keep them clean during laying operations by plugging. Replace defective material without additional expense to the Government. Store rubber gaskets, not immediately installed, under cover or out of direct sunlight.
Handle ductile iron pipe, fittings, and accessories in accordance with AWWA C600 and AWWA M41. Handle PVC and PVCO pipe, fittings, and accessories in accordance with AWWA C605. Handle PE pipe, fittings, and accessories in accordance with AWWA M55. Handle steel pipe, fittings and accessories in accordance with AWWA C604.
PART 2 PRODUCTS
2.1 MATERIALS
Provide all materials in accordance with AWWA C800 and as indicated herein. Provide valves and fittings with pressure ratings equivalent to the pressure ratings of the pipe.
2.1.1 Pipe, Fittings, Joints And Couplings
Submit manufacturer's standard drawings or catalog cuts, except submit both drawings and cuts for push-on [and rubber-gasketed bell-and-spigot] joints. Include information concerning gaskets with submittal for joints and couplings.
2.1.1.1 Ductile-Iron Piping
2.1.1.1.1 Pipe and Fittings
Pipe, except flanged pipe, AWWA C151/A21.51 , . Flanged pipe, AWWA C115/A21.15 . Fittings, AWWA C110/A21.10 or AWWA C153/A21.53 .
Provide fittings with pressure ratings equivalent to that of the pipe.
Provide compatible pipe ends and fittings for the specified joints.
Provide cement-mortar lining, AWWA C104/A21.4 , twice the standard thickness on pipe and fittings.
2.1.1.1.2 Joints and Jointing Material
Provide push-on joints or mechanical joints for pipe and fittings unless otherwise indicated. Provide mechanical joints where indicated. Provide flanged joints where indicated. Provide mechanically coupled type joints using a sleeve-type mechanical coupling where indicated. Provide grooved or shouldered type joints where indicated. Sleeve-type mechanical couplings in lieu of push-on joints are acceptable, subject to the limitations specified in the paragraph SLEEVE-TYPE MECHANICAL COUPLINGS
SECTION 33 11 00 Page 6
Utilize grooved or shouldered type joints in lieu of push-on joint, except where joint is buried.
a. Push-On Joints: Shape of pipe ends and fitting ends, gaskets, and lubricant for joint assembly as recommended in AWWA C111/A21.11 .
b. Mechanical Joints: Dimensional and material requirements for pipe ends, glands, bolts and nuts, and gaskets as recommended in
AWWA C111/A21.11 .
c. Flanged Joints: Bolts, nuts, and gaskets for flanged connections as recommended in Appendix A of AWWA C115/A21.15 . Provide AWWA C115/A21.15 ductile iron flanges and conform to ASME B16.1 , Class
125. Provide ASTM A536 epoxy coated steel set screw flanges. Gasket and lubricants for set screw flanges, in accordance with mechanical-joint gaskets specified in AWWA C111/A21.11 .
d. Insulating Joints: Designed to prevent metal-to-metal contact at the joint between adjacent sections of piping. Provide flanged type joint with insulating gasket, insulating bolt sleeves, and insulating washers. Provide full face dielectric type gaskets, as recommended in the Appendix to AWWA C115/A21.15 . Bolts and nuts, as recommended in the Appendix to AWWA C115/A21.15 .
e. Sleeve-Type Mechanical Coupled Joints: As specified in the paragraph
SLEEVE-TYPE MECHANICAL COUPLINGS.
2.1.1.2 Plastic Piping
2.1.1.2.1 PVC Piping
2.1.1.2.1.1 PVC Piping
AWWA C900 plain end or gasket bell end pipe meeting or exceeding ASTM D1784 cell class 12454, with a minimum Pressure Class 150 (DR27.5), 165 (DR25), 200 (DR21), 235 (DR 18), 250 (DR17) 305 (DR 14) with ductile iron outside diameter (DIOD).
2.1.1.2.1.2 Fittings for PVC and PVCO Pipe
Gray iron or ductile iron fittings, AWWA C110/A21.10 with special fittings in accordance with Appendix B or AWWA C153/A21.53 , with cement-mortar lining for fittings, AWWA C104/A21.4 , standard thickness. Fittings with push-on joint ends are to conform to the same requirements as fittings with mechanical-joint ends, except for the factory modified bell design compatible for use with PVC pipe as specified.
Fittings from material that meets or exceeds ASTM D1784 cell class 12454 and is the same material as the pipe with elastomeric gaskets, in conformance with AWWA C605 and AWWA C900.
2.1.1.2.1.3 Joints and Jointing Material for PVC
a. Push-on joints: Use jointing material in accordance with ASTM D3139 and AWWA C111/A21.11 between pipes, pipes and metal fittings, valves, and other accessories or compression-type joints/mechanical joints.
Provide each joint connection with an elastomeric gasket compatible for the bell or coupling used. Gaskets for push-on joints for pipe, ASTM F477. Gaskets for push-on joints and compression-type
SECTION 33 11 00 Page 7 joints/mechanical joints for joint connections between pipe and metal fittings, valves, and other accessories, AWWA C111/A21.11 , respectively, for push-on joints and mechanical joints.
b. Mechanical Joint: Use mechanically coupled joints having a sleeve-type mechanical coupling, as specified in the paragraph SLEEVE-TYPE MECHANICAL COUPLINGS, as an optional jointing method for plain-end PVC pipe, subject to the limitations specified for mechanically coupled joints using a sleeve-type mechanical coupling as specified for compression-type joints in ASTM D3139. Provide jointing material in accordance with AWWA C111/A21.11 between pipe and sleeve-type mechanical couplings.
2.1.1.2.2 PVC Piping for Service Lines
2.1.1.2.2.1 Pipe and Fittings
Provide ASTM D1784 cell class 12454 pipe and fittings of the same PVC material.
a. ASTM D1785, Schedule 40 with ASTM D2466 Schedule 40 or ASTM D2467 Schedule 80 fittings.
b. ASTM D2241 pipe and fittings with SDR as necessary to provide 150 psi minimum pressure rating with ASTM D2466 Schedule 40 or ASTM D2467 Schedule 80 fittings.
2.1.1.2.2.2 Joints and Connections
Fittings may be joined by the solvent-cement method or threading.
2.1.1.2.2.3 Solvent Joining
Provide solvent joints in accordance with ASTM D2855.
2.1.1.2.3 Polyethylene (PE) Pipe
AWWA C906, ASTM D3035, PE4710, material designation code CC2 with a minimum Pressure Class 200 (DR11) with ductile iron outside diameter
(DIOD).
2.1.1.2.3.1 Fittings For PE Pipe
AWWA C906, AWWA M55, ASTM D3035, molded and manufactured to comply with
ASTM F714.
2.1.1.2.3.2 Joints and Jointing Materials
Mechanical Joint: AWWA C111/A21.11 DIOD Mechanical joint adapter and gaskets for mechanical joints for joint connections between pipe and metal fittings, valves, and other accessories.
2.1.1.3 Steel Piping
2.1.1.3.1 Pipe and Fittings
Pipe, AWWA C200. Fittings, AWWA C208 and AWWA C200, with reference to the requirements specified therein for "Special Sections." Provide cement-mortar lining and coating on pipe and fittings for underground
SECTION 33 11 00 Page 8 lines in accordance with applicable AWWA standard. Provide cement-mortar lining. Utilize pipe ends and fittings compatible for the joints and jointing materials used.
a. Utilize welded or seamless pipe with plain, or shouldered and grooved ends in accordance with AWWA C606 for use with mechanical couplings or bell-and-spigot ends with rubber gaskets. Provide bell-and-spigot ends for sizes less than 6 inches diameter in accordance with AWWA C200.
b. Provide fittings and specials made of the same material as the pipe.
Use specials and fittings made of standard steel tube turns or segmentally welded sections, with ends to accommodate the type of couplings or joints specified for the pipe. Match the thickness rating of pipe fittings and specials to the thickness specified and the pressure rating calculated for the pipe with which they are used.
Provide identical protective materials for fittings and specials as specified for the pipe. Hand wrap, line, or coat specials and fittings that cannot be mechanically wrapped, lined, or coated using the same material used for the pipe with the same number of applications of each material, smoothly applied.
2.1.1.3.2 Joints and Jointing Material
Provide rubber-gasketed pipe and fitting bell-and-spigot joints or the mechanically coupled type using a sleeve-type mechanical coupling.
a. Rubber-Gasketed Bell-and-Spigot Joints: Provide joints and pipe ends in accordance with the pipe manufacturer's standard for this type of joint, except that the joint is to also meet the requirements specified for rubber-gasketed joints and rubber gaskets in AWWA C200.
b. Welded Joints: Provide electrodes of the quality specified in
AWWA C206.
c. Sleeve-Type Mechanical Coupled Joints: As specified in paragraph
SLEEVE-TYPE MECHANICAL COUPLINGS.
2.1.2 Valves
Provide a protective interior coating in accordance with AWWA C550.
2.1.2.1 Gate Valves 3 Inch Size and Larger on Buried Piping
AWWA C500, AWWA C509, AWWA C515, or UL 262 and:
a. AWWA C500: nonrising stem type with double-disc gate and mechanical-joint ends or push-on joint ends compatible for the adjoining pipe
b. AWWA C509 or AWWA C515: nonrising stem type with mechanical-joint ends
c. UL 262 : inside-screw type with operating nut, double-disc or split-wedge type gate, designed for a hydraulic working pressure of 175 psi, and have mechanical-joint ends or push-on joint ends as appropriate for the pipe to which it is joined.
SECTION 33 11 00 Page 9
2.1.2.2 Gate Valves 3 Inch Size and Larger in Valve Pit(s)
AWWA C500, AWWA C509, AWWA C515, or UL 262 and:
a. AWWA C500: outside-screw-and-yoke rising-stem type with double-disc gates and flanged ends
b. AWWA C509 or AWWA C515: outside-screw-and-yoke rising-stem type with flanged ends
c. UL 262 : outside-screw-and-yoke type, with type gate and flanged ends, and designed for a hydraulic working pressure of 175 psi
PART 3 EXECUTION
3.1 PREPARATION
3.1.1 Connections to Existing System
Perform all connections to the existing water system in the presence of the Contracting Officer.
3.1.2 Operation of Existing Valves
Do not operate valves within or directly connected to the existing water system unless expressly directed to do so by the Contracting Officer.
3.2 INSTALLATION
Install all materials in accordance with the applicable reference standard, manufacturers instructions and as indicated herein.
3.2.1 Piping
3.2.1.1 General Requirements
Install pipe, fittings, joints and couplings in accordance with the applicable referenced standard, the manufacturer's instructions and as specified herein.
3.2.1.1.1 Termination of Water Lines
Terminate the work covered by this section at a point approximately 5 feet from the building, unless otherwise indicated.
Do not lay water lines in the same trench with gas lines, fuel lines, electric wiring, or any other utility. Do not install copper tubing in the same trench with ferrous piping materials. Where nonferrous metallic pipe (i.e., copper tubing) crosses any ferrous piping, provide a minimum vertical separation of 12 inches between pipes.
3.2.1.1.2 Pipe Laying and Jointing
Remove fins and burrs from pipe and fittings. Before placing in position, clean pipe, fittings, valves, and accessories, and maintain in a clean condition. Provide proper facilities for lowering sections of pipe into trenches. Under no circumstances is it permissible to drop or dump pipe, fittings, valves, or other water line material into trenches. Cut pipe cleanly, squarely, and accurately to the length established at the site
SECTION 33 11 00 Page 10 and work into place without springing or forcing. Replace a pipe or fitting that does not allow sufficient space for installation of jointing material. Blocking or wedging between bells and spigots is not permitted. Lay bell-and-spigot pipe with the bell end pointing in the direction of laying. Grade the pipeline in straight lines; avoid the formation of dips and low points. Support pipe at the design elevation and grade. Secure firm, uniform support. Wood support blocking is not permitted. Lay pipe so that the full length of each section of pipe and each fitting rests solidly on the pipe bedding; excavate recesses to accommodate bells, joints, and couplings. Provide anchors and supports for fastening work into place. Make provision for expansion and contraction of pipelines. Keep trenches free of water until joints have been assembled. At the end of each work day, close open ends of pipe temporarily with wood blocks or bulkheads. Do not lay pipe when conditions of trench or weather prevent installation. Provide a minimum of 2 1/2 feet depth of cover over top of pipe.
3.2.1.1.3 Tracer Wire
Install a continuous length of tracer wire for the full length of each run of nonmetallic pipe. Attach wire to top of pipe in such manner that it will not be displaced during construction operations.
3.2.1.1.4 Connections to Existing Water Lines
Make connections to existing water lines after coordination with the facility and with a minimum interruption of service on the existing line.
Make connections to existing lines under pressure in accordance with the recommended procedures of the manufacturer of the pipe being tapped and as indicated , except as otherwise specified, tap concrete pipe in accordance with AWWA M9 for tapping concrete pressure pipe .
3.2.1.1.5 Sewer Manholes
No water piping is to pass through or come in contact with any part of a sewer manhole.
3.2.1.1.6 Water Piping Parallel With Sewer Piping
Where the location of the water line is not clearly defined by dimensions on the drawings, do not lay water line closer than 10 feet, horizontally, from any sewer line.
3.2.1.1.7 Water Piping Crossing Sewer Piping
Provide at least 18 inches above the top (crown) of the sewer piping and the bottom (invert) of the water piping whenever possible. Measure the distance edge-to-edge. Where water lines cross under gravity sewer lines, construct sewer line of AWWA compliant ductile iron water piping with rubber-gasketed joints and no joint located within 10 feet, horizontally, of the crossing.
3.2.1.1.8 Penetrations
Provide ductile-iron or Schedule 40 steel wall sleeves for pipe passing through walls of valve pits and structures. Fill annular space between walls and sleeves with rich cement mortar. Fill annular space between pipe and sleeves with mastic.
SECTION 33 11 00 Page 11
3.2.1.1.9 Flanged Pipe
Only install flanged pipe aboveground or with the flanges in valve pits.
3.2.1.2 Ductile-Iron Piping
Unless otherwise specified, install pipe and fittings in accordance with the paragraph GENERAL REQUIREMENTS and with the requirements of AWWA C600 for pipe installation, joint assembly, valve-and-fitting installation, and thrust restraint.
a. Jointing: Make mechanical joints with the gaskets, glands, bolts, and nuts specified for this type joint; assemble in accordance with the applicable requirements of AWWA C600 and AWWA M41 for joint assembly and the recommendations of Appendix A to AWWA C111/A21.11 .
b. Allowable Deflection: Follow AWWA C600 and AWWA M41 for the maximum allowable deflection. If the alignment requires deflection in excess of the above limitations, provide special bends or a sufficient number of shorter lengths of pipe to achieve angular deflections within the limit set forth.
3.2.1.3 PVC Water Main Pipe
Unless otherwise specified, install pipe and fittings in accordance with the paragraph GENERAL REQUIREMENTS and with the requirements of AWWA C605 for laying of pipe, joining PVC pipe to fittings and accessories, setting of fire hydrants, valves, and fittings; and with the recommendations for pipe joint assembly and appurtenance installation in AWWA M23, Chapter 7, "Installation."
a. Jointing: Make push-on joints with the elastomeric gaskets specified for this type joint, using either elastomeric-gasket bell-end pipe or elastomeric-gasket couplings. For pipe-to-pipe push-on joint connections, use only pipe with push-on joint ends having factory-made bevel; for push-on joint connections to metal fittings, valves, and other accessories, cut spigot end of pipe off square and re-bevel pipe end to a bevel approximately the same as that on ductile-iron pipe used for the same type of joint. Use a lubricant recommended by the pipe manufacturer for push-on joints. Assemble push-on joints for pipe-to-pipe joint connections in accordance with the requirements of AWWA C605 for laying the pipe and the recommendations in AWWA M23, Chapter 7, "Installation," for pipe joint assembly. Assemble push-on joints for connection to fittings, valves, and other accessories in accordance with the requirements of AWWA C605 for joining PVC pipe to fittings and accessories and with the requirements of AWWA C600 for joint assembly. Make compression-type joints/mechanical joints with the gaskets, glands, bolts, nuts, and internal stiffeners previously specified for this type joint; assemble in accordance with the requirements of AWWA C605 for joining PVC pipe to fittings and accessories, with the requirements of AWWA C600 for joint assembly, and with the recommendations of Appendix A to AWWA C111/A21.11 . Cut off spigot end of pipe for compression-type joint/mechanical-joint connections and do not re-bevel. Assemble joints made with sleeve-type mechanical couplings in accordance with the recommendations of the coupling manufacturer using internal stiffeners as previously specified for compression-type joints.
b. Joint Offset: Construct joint offset in accordance AWWA C605. Do not
SECTION 33 11 00 Page 12 exceed the minimum longitudinal bending as indicated by AWWA C605.
c. Fittings: Install in accordance with AWWA C605.
3.2.1.4 Steel Piping
Unless otherwise specified, install pipe and fittings in accordance with AWWA C604 and AWWA M11, Chapter 12, "Transportation, Installation, and Testing."
a. Jointing: Make rubber-gasketed bell-and-spigot joints with the gaskets previously specified for this type joint, using a lubricant recommended by the pipe manufacturer; assemble in accordance with the recommendations of the pipe manufacturer. Assemble joints made with sleeve-type mechanical couplings in accordance with the recommendations of the coupling manufacturer.
b. Allowable Offsets: For pipe with bell-and-spigot rubber-gasket joints, maximum allowable deflections from a straight line or grade, as required by vertical curves, horizontal curves, or offsets is 5 degrees unless a lesser amount is recommended by the manufacturer.
Form short-radius curves and closures with short lengths of pipe or fabricated specials specified.
c. Cement Mortar Lining: AWWA C205, shop applied.
3.2.1.5 Metallic Piping for Service Lines
Install pipe and fittings in accordance with the paragraph GENERAL REQUIREMENTS and with the applicable requirements of AWWA C600 for pipe installation, unless otherwise specified.
3.2.1.5.1 Screwed Joints
Make screwed joints up tight with a stiff mixture of graphite and oil, inert filler and oil, or graphite compound; apply to male threads only or with PTFE Tape, for use with threaded pipe. Threads are to be full cut;
do not leave more than three threads on the pipe exposed after assembling the joint.
3.2.1.5.2 Joints for Copper Tubing
Cut copper tubing with square ends; remove fins and burrs. Replace dented, gouged, or otherwise damaged tubing with undamaged tubing. Make solder joints using ASTM B32, 95-5 tin-antimony or Grade Sn96 solder. Use solder and flux containing less than 0.2 percent lead. Before making joint, clean ends of tubing and inside of fitting or coupling with wire brush or abrasive. Apply a rosin flux to the tubing end and on recess inside of fitting or coupling. Insert tubing end into fitting or coupling for the full depth of the recess and solder. For compression joints on flared tubing, insert tubing through the coupling nut and flare tubing.
3.2.1.5.3 Flanged Joints
Make flanged joints up tight, avoid undue strain on flanges, valves, fittings, and accessories.
SECTION 33 11 00 Page 13
3.2.1.5.4 Protection of Buried Steel Service Line Piping
Prepare, prime, and coat exterior surface of zinc-coated steel pipe and associated fittings to be buried with hot-applied coal-tar enamel with a bonded single layer of felt wrap in accordance with AWWA C203. For the felt wrap material, use fibrous-glass mat as specified in AWWA C203; use of asbestos felt will not be permitted. Use solvent wash only to remove oil, grease, and other extraneous matter from zinc-coated pipe and fittings.
3.2.1.6 Plastic Service Piping
Install pipe and fittings in accordance with the paragraph GENERAL REQUIREMENTS and with the applicable requirements of ASTM D2774 and ASTM D2855, unless otherwise specified. Handle solvent cements used to join plastic piping in accordance with ASTM F402.
3.2.1.6.1 Jointing
Make solvent-cemented joints for PVC piping using the solvent cement previously specified for this material; assemble joints in accordance with ASTM D2855. Make plastic pipe joints to other pipe materials in accordance with the recommendations of the plastic pipe manufacturer.
3.2.1.6.2 Plastic Pipe Connections to Appurtenances
Connect plastic service lines to corporation stops and gate valves in accordance with the recommendations of the plastic pipe manufacturer.
3.2.2 Valves
3.2.2.1 Gate Valves
Install gate valves, AWWA C500 and UL 262 , in accordance with the requirements of AWWA C600 for valve-and-fitting installation and with the recommendations of the Appendix ("Installation, Operation, and Maintenance of Gate Valves") to AWWA C500. Install gate valves, AWWA C509 or AWWA C515, in accordance with the requirements of AWWA C600 for valve-and-fitting installation and with the recommendations of the Appendix ("Installation, Operation, and Maintenance of Gate Valves") to AWWA C509 or AWWA C515.
Install gate valves on PVC water mains in accordance with the recommendations for appurtenance installation in AWWA M23, Chapter 7, "Installation." Make and assemble joints to gate valves as specified for making and assembling the same type joints between pipe and fittings.
3.2.2.2 Check Valves
Install check valves in accordance with the applicable requirements of AWWA C600 for valve-and-fitting installation. Make and assemble joints to check valves as specified for making and assembling the same type joints between pipe and fittings.
3.2.2.3 Air Release, Air/Vacuum, and Combination Air Valves
Install pressure vacuum assemblies of type, size, and capacity indicated.
Include valves and test cocks. Install according to the requirements of plumbing and health department and authorities having jurisdiction. Do not install pressure vacuum breaker assemblies in vault or other space subject to flooding.
SECTION 33 11 00 Page 14
3.3 FIELD QUALITY CONTROL
3.3.1 Tests
Notify the Contracting Officer a minimum of five days in advance of hydrostatic testing. Coordinate the proposed method for disposal of waste water from hydrostatic testing. Perform field tests, and provide labor, equipment, and incidentals required for testing. Provide documentation that all items of work have been constructed in accordance with the Contract documents.
3.3.1.1 Hydrostatic Test
Test the water system in accordance with the applicable AWWA standard specified below. Where water mains provide fire service, test in accordance with the special testing requirements given in the paragraph SPECIAL TESTING REQUIREMENTS FOR FIRE SERVICE. Test ductile-iron water mains in accordance with the requirements of AWWA C600 for hydrostatic testing. The amount of leakage on ductile-iron pipelines with mechanical-joints or push-on joints is not to exceed the amounts given in AWWA C600; no leakage will be allowed at joints made by any other methods. Test PVC and PVCO plastic water systems made with PVC pipe in accordance with the requirements of AWWA C605 for pressure and leakage tests. The amount of leakage on pipelines made of PVC water main pipe is not to exceed the amounts given in AWWA C605, except that at joints made with sleeve-type mechanical couplings, no leakage will be allowed. Test concrete water mains in accordance with the recommendations in AWWA M9, "Hydrostatic Testing and Disinfection of Mains." The amount of leakage on concrete pipelines is not to exceed 20 gallons per 24 hours per inch of pipe diameter per mile of pipeline. Test steel water mains in accordance with applicable requirements of AWWA C600 for hydrostatic testing. The amount of leakage on steel pipelines with rubber-gasketed bell-and-spigot joints is not to exceed 20 gallons per 24 hours per inch of pipe diameter per mile of pipeline; no leakage will be allowed at joints made by any other method. To stop leakage, repair welded joints only by welding.
Test water service lines in accordance with requirements of AWWA C600 for hydrostatic testing. No leakage will be allowed at copper pipe joints, copper tubing joints (soldered, compression type, brazed), plastic pipe joints, flanged joints, and screwed joints . Do not backfill utility trench or begin testing on any section of a pipeline where concrete thrust blocks have been provided until at least 7 days after placing of the concrete.
3.3.1.2 Leakage Test
For leakage test, use a hydrostatic pressure not less than the maximum working pressure of the system. Leakage test may be performed at the same time and at the same test pressure as the pressure test.
For PE perform leak testing in accordance with ASTM F2164.
3.3.1.3 Special Testing Requirements for Fire Service
Test water mains and water service lines providing fire service or water and fire service in accordance with NFPA 24 . The additional water added to the system must not exceed the limits given in NFPA 24
SECTION 33 11 00 Page 15
3.3.1.4 Tracer Wire Continuity Test
Test tracer wire for continuity after service connections have been completed and prior to final pavement or restoration. Verify that tracer wire is locatable with electronic utility locating equipment. Repair breaks or separations and re-test for continuity.
3.4 SYSTEM STARTUP
Water mains and appurtenances must be completely installed, disinfected, flushed, and satisfactory bacteriological sample results received prior to permanent connections being made to the active distribution system.
Obtain approval by the Contracting Officer prior to the new water piping being placed into service.
3.5 CLEANUP
Upon completion of the installation of water lines and appurtenances, remove all debris and surplus materials resulting from the work.
-- End of Section --