RFIs - 5.31.2023 (update 1) - Electrical and Comm. Equipment Install.pdf
PDF 103 KB Posted
- Attached to
- AFIMSC DET. 9 ELECTRICAL & COMM. EQUIPMENT PROCUREMENT and INSTALLATION Federal contract opportunity
- Solicitation number
- FA440723QDW02
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Attachment with RFI 2 - Electrical Panel Report Attachment.pdf | ||
| Attachment with RFI 3 - Electrical Configuration Diagram (2).pdf | ||
| Attachment with RFI 3 - Electrical Configuration Diagram (1).pdf | ||
| RFIs - 5.31.2023 - Electrical and Comm. Equipment Install.pdf | ||
| RFQ Amendment 1 - AFIMSC DET 09 Communication and Electrical Equipment.pdf | ||
| Site Visit Provided Attachment_2.pdf | ||
| Site Visit Provided Attachment_3.pdf | ||
| Site Visit Sign In Sheet - 18 May 2023.pdf | ||
| Site Visit Provided Attachment_1.pdf | ||
| SOO Det 9 Office Elec and Comm Rev 13 Apr 23.pdf | ||
| RFQ Attachment 1 - FAR DFARS Clauses and Provisions.pdf | ||
| RFQ - AFIMSC DET 09 Communication and Electrical Equipment.pdf | ||
| RFQ Attachment 2 - Wage Determination.pdf |
Show all 13
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
RFI # Date Recv'd Date Sent to Technical Expert
RFI Response Date
Answered
1 25‐May‐23 25‐May‐23 Are furniture faceplates for data/electrical provided with the furniture contract, or are these to be provided by contractor?
Comm faceplates and jacks are not included.
2 25‐May‐23 25‐May‐23 Can we get a report of loads that are on each circuit (to ensure that the circuits can support the scheduled furniture and anything else on that circuit).
Panel study provided to 375 CONS.
From installer: I personally use about 1.4 to 1.7 amps steady state all day with a clock radio, phone, headset, two LED monitors and a laptop running. If I move my electrically adjustable Genesis table up or down I can add at most 5 amps during the movement.
3 25‐May‐23 25‐May‐23 What type of wire and connection is the whip and what size are the overcurrent protection devices (OCPD) for each corresponding circuit?
From Installer: Each circuit can have up to 20 amps of power. Depending on how many circuits are available in the building you could have a 622 infeed/whip with 6 circuits x20 amps = 120 amps.
From installer: The whip/infeeds are 6’ long and have 10 wires. Either 442 or 622 configuration. 4 x 20 amps or 6 x 20 amps.
4 25‐May‐23 25‐May‐23 Is the current whip that is being pulled back for later use compatible with new furniture or will connection/termination need to be replaced?
Per CES, the cables/connection should be able to be reused.
5 25‐May‐23 25‐May‐23 Will the security boxes for the switches be government provided or are they expected to be provided materials?
Security boxes will be provided
6 25‐May‐23 25‐May‐23 Is there a requirement for a licensed electrician on this job?
Yes
Requests For Information (RFIs) ‐ Electrical and Comm. Equipment Det. 9