FA301624Q0025 Questions and Answers 27 Feb 2024.xlsx
XLSX spreadsheet 11 KB Posted
- Attached to
- Trane Chiller Purchase and Install
- Solicitation number
- FA301624Q0025
About this file
This document provides details on a federal contract opportunity for the purchase and installation of Trane chillers. The solicitation number is FA301624Q0025 and is being issued by the Department of the Air Force Air Education and Training Command. The opportunity is for the brand name purchase and installation of Trane chillers, with additional details available in the attached questions and answers document dated February 27, 2024. The response is seeking the acquisition of chillers from the named manufacturer to be installed at an Air Force facility.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sheet1
| FA301624Q0025 | Questions | Answers |
| ROUND 1 | ||
| Please confirm that the government is not accepting proposals with other than Trane brand chillers and that review of Product Literature will be a part of the evaluation of proposals. | Offers shall contain the brand “Trane” for it to be considered. |
Are Bid Bonds or Payment & Performance Bonds required? Bid Bonds, Payment Bonds, and Performance Bonds will not be required for this effort.
| ROUND 2 | ||
| Is a DUNS number a requirement to bid or to be considered? | No, but offeror must have an active SAM Resigtration. |
Can you confirm that 454B Refrigerant is acceptable? Yes, 454B Refrigerant is acceptable.
To confirm, the Government has requested a 35T unit correct? Yes per Amendment 0004, the Government is requesting a 35-45 ton unit.
We are not aware of any spare capacity available in Panel BA. The revised scope of work states, “Contractor shall add a dedicated 120-volt circuit at the chiller for the electric heat strips and a dedicated outdoor electric 120-volt receptacle outlet.” Please verify what panel and circuit is to be utilized for these additional electrical items. Since the new chillers come with a dedicated electric heater strip to protect the chiller in case there is a freeze, a dedicated 120 volt power source and power receptacle outlet is required per code. There is another electrical panel in the mechanical room or in the building with a power source available for the 120 volt installations however 120 ft of conduit may be required.