ACTION; NOTED: C = Concur; D = Deferred for Further Investigation; N = Not Provided / Non Agreement

______Nov 17 22__

RFI # _______ RFI SUBJECT: BLDG 954 LAN DROP______ CONTRACT # __Pending_ W/O# Pending____

Planning/Construction: __Pending___PRIME CONTRACTOR: _Pending_________

SUBCONTRACTOR: ______________ PROJECT MANAGER: _______________ PROJECT MONITOR: ________________

PROJECT: BLDG 954 LAN DROP____________________________________________________

LOCATION: _BLDG 954 EGLIN AFB________________

REQUEST: Official questions from vendors in regards to SAM NOTICE FA282323QA004 on PAGE 2___________________________________________________________________________________________________

DESIGN SPEC SECTION: ____________________________________________________________________________

DESIGN DRAWINGS: ______________________________________________________________________________

PRODUCT SUBMITTAL(S): _________________________________________________________________________

REQUESTOR’S NAME/EMAIL: ________________________________________________________

PHONE:

A = APPROVED

D = DISAPPROVED

/W COMMENTS

GOVERNMENT RESPONSE/RECOMMENDATION

ACTION

NOTED INITAL

1 Yes the ceilings are drop ceiling MAS

2 No MAS

Approx. 50‐feet of EMT for a 6awg ground wire and 2‐inch conduit for the wall penetration’s

MAS

No cable tray is installed. J‐hooks will be required. Refer to the Floor plan T001 for pathway

MAS

The 96CS does not provide cable footages. Refer to the Eglin Cyber Infrastructure

Standards and Installation Specifications for the type of cable to be used

MAS

/// /// ///Last Item/// /// ///

NOTE: THE RFI SYSTEM IS INTENDED TO PROVIDE AN EFFICIENT MECHANISM FOR RESPONDING TO REQUESTS FOR INFORMATION. IT DOES NOT PROVIDE AUTHORITY TO PROCEED WITH ADDITIONAL WORK. IF RESPONDENT CONSIDERS THE RFI RESPONSE A CHANGED CONDITION, PROVIDE WRITTEN NOTICE TO THE CONTRACTING OFFICER'S

REPRESENTATIVE IN ACCORDANCE WITH CONTRACT PROVISIONS.

1. Are ceilings drop ceiling?

2. Will lift be required?

3. How much conduit will be required?

4. Is there a cable tray installed?

5. We will need to know the amount of wire needed and the type.