This document is a Request for Chiller Replacement at Patrick Space Force Base, Building 1500. The current 80-ton chiller system has reached its end of life due to a corrosive environment and defective condenser tubes, requiring replacement. The required replacement is an air-cooled scroll packaged chiller with specific salient characteristics, including 80 nominal tons, 208 volt 3 phase power, R-454B refrigerant, factory installed freeze protection, and a 10-year parts, labor and refrigerant warranty. The solicitation has a due date for quotes of at least 60 days, and requires submission of the vendor's Representations and Certifications. This procurement is being conducted by the Department of the Air Force Space Command.

View the file

Other files

File Type Posted
24R0028 Q and A.docx DOCX document
24R0028 - Clause Set.pdf PDF
24R0028 - JandA.pdf PDF
24R0028 - Combined Synopsis-Solicitation Final.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PATRICK SPACE FORCE BASE BUILDING 1500 REPLACEMENT

CHILLER

Abstract Salient Characteristics for Replacement of Trane Chiller

NEED/ REQUEST FOR HANGER 313 CHILLER REPLACEMENT

The request for a water-cooled chiller is required to maintain air conditioning operations at Building 1500. The current system has reached its manufacture end of life usage due to corrosive environment and defective condenser tubes. The chiller provides necessary comfort cooling to the facility that is home to the 45th FSS Golf Course Club House.

COMMODITY REPLACEMENT

An air cooled chiller is a machine that that removes heat via the refrigeration cycle. Providing a range of cooling to a condition space.

SALIENT CHARACTRERISTIC

Air-Cooled Scroll Packaged Chiller Startup Included - Trane Service must start equipment for warranty to be honored.

80 nominal tons 208 volt 3 phases High efficiency/performance Refrigerant Charge R-454B With factory installed freeze protection Refrigerant isolation valves (discharge valve) ETL Listed to US/Canadian Safety Standard ASHRAE 90.1/CSA C743 - 2019 Compliance AHRI certified.

Factory installed flow switch - set point 60 cm/sec Grooved pipe connection Factory insulation 1.25" - high humidity/low evaporator temperature Performance based on water.

High Ambient

Complete Coat lanced aluminum fins 10,000 Hour Coating on Cabinet Across the line starter/direct online Single point connection main line unit power-ancillary items require other power.

Circuit breaker-high fault rated control panel.

Enclosure Type UL 60335 Rated for Outdoor Applications BACnet MS/TP Interface High A short circuit rating With water strainer factory installed architectural louvered panels 10 year parts, labor and refrigerant warranty whole unit