FA252124QB096 - Salient Characteristics B989 AHU.pdf

PDF 209 KB Posted

Attached to
B989 AIR HANDLER UNIT REPLACEMENT Federal contract opportunity
Solicitation number
FA252124QB096
Issued by
Department of the Air Force Space Command

About this file

This document is a set of salient characteristics for a commodity purchase to replace the Air Handler Unit (AHU) on the 3rd floor of Building 989 at Patrick Space Force Base. The key details are:

The current AHU has reached the end of its useful life and can no longer be repaired. The replacement AHU must meet the following specifications: supply fan airflow of 7,500 CFM, total static pressure of 3.069 in H2O, and 1,873 RPM; overall dimensions of 101" H x 72" W x 78.8" L; 17-ton capacity; 460VAC/3-phase/60Hz power with 12.81 FLA and 14.35 MCA; 6-row cooling coil with 269.8 MBh capacity, 53.77 GPM water flow, and 11.49-gallon volume; and 1-row heating coil with 244.01 MBh capacity, 24.41 GPM water flow, and 2.67-gallon volume. The requested replacement AHU is a Trane Performance Climate Changer CSAA017 or equivalent.

View the file

Other files for this federal contract opportunity

Other files attached to B989 AIR HANDLER UNIT REPLACEMENT, newest first.
File Type Posted
FA252124QB096 - Combined Synopsis Solicitation.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PATRICK SPACE FORCE BASE B989 AIR HANDLER UNIT

REPLACEMENT

Rafael R. Lopez, NJ-03 USSF 45 CES/CEOER Rafael.lopez.18@spaceforce.mil

Abstract Salient Characteristics for the purchase Air Handler Unit

Building 989 3rd Floor Air Handler Replacement (AHU)

This is a commodity purchase to replace REAL property equipment (AHU) at building 989 3rd floor.

The current AHU has reached its end of usefulness and cannot no longer be repaired.

We are seeking a Trane Performance Climate Changer Air Handler CSAA017 or equivalent .

SALIENT CHARACTRERISTICS:

Supply Fan o Airflow‐ 7500 CFM o Total Static Pressure‐ 3.069 in H2O o 1873 RPM

External Dimensions o 101.” H o 72.0” W o 78.8 L

17 Ton

Power o 460VAC/3 Phase/ 60 HZ o 12.81 FLA o 14.35 MCA

Cooling Coil o 6 Rows o Capacity ‐ 269.80 MBh o Fluid/ water flow ‐ 53.77 GPM o Volume‐ 11.49 gallons

Heating Coil o 1 Row o Capacity – 244.01 MBh o Fluid/ water flow – 24.41 GPM o Volume 2.67 gallons

File details come from the government source that posted it. Updated .