This document includes as-built drawings and specifications for replacing HVAC controls at several facilities. The project involves providing new SmartStruxture automation servers at five buildings located at Cape Canaveral Space Force Station and Jonathan Dickinson Missile Tracking Annex. Integration to the existing EMCS server is required. Graphical user interface screens, data logs, and alarms must be provided. The estimated value is between $500,000 and $1,000,000. This is a competitive solicitation set aside for Service-Disabled Veteran-Owned Small Businesses being issued by the Department of the Air Force Space Command. Funds are contingent upon availability, and the government reserves the right to cancel the solicitation.
View the file
Other files for this federal contract opportunity
Show all 32
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Total Building Integrations, Inc.
Date:
Project:
MECHANICAL: Precision Air Conditioning
DRAWN BY: JRJ
SYSTEM: LOYTEC
REV #: Asbuilts
REV. DATE: 5/29/16
ISSUE DATE: ENGINEER: Allen Engineering
SHEET OF
May 29, 2016 As-Builts
Hanger G CCAFS, FL
9/26/15
Controls As-Builts May 29, 2016 Hanger G, FAC 1606
USAF 45th Civil Engineer Squadron CCAFS, FL Contract No: FA2521-13-D0005-0055
Project:
MECHANICAL: Precision Air Conditioning
DRAWN BY: JRJ
SYSTEM: LOYTEC
REV #: Asbuilts
REV. DATE: 5/29/16
ISSUE DATE: ENGINEER: Allen Engineering
SHEET OF
May 29, 2016 As-Builts
Hanger G CCAFS, FL
9/26/15
Sa Fa n En a bl e
FilterStatus
Ex Fa nE na b le
C om p1 En ab le
24v24v 24v 24v
24v
Trans-1
C om p2 En ab le
24v 24v
H tg
St g1
H tg
St g2
DaTemp
HtgStg2
HtgStg1
SaFanEnable
SaFanStatus
ClgCoilTemp
RaTemp
O/A
R/A
120Volt
D aT em p
R aT em p
R aR h M aT e m p
R oo m Te m p
R oo m Rh
AHU System - 1N & 1S
FilterStatus PressureTap on LIOB-484
OaDamper
RaRh MaTemp
R oo m St p t
Comp1Enable
Comp1Status
C om p1 St a tu s C om p2
St a tu s
RmTemp
Override
RmRh
RmTempStpt
Emergency Shutdown
HotGasControl
24v
H ot
G as
B yp as s
SaFlow
Sa Fl o w
St at io n
Sa Fa n St at us
C lg
C oi lT em p
Comp2Status
Comp2Enable
24v
O aD am p er O p en
Em er ge n cy Sh ut do w n
24v
O aD am p er C lo se
Project:
MECHANICAL: Precision Air Conditioning
DRAWN BY: JRJ
SYSTEM: LOYTEC
REV #: Asbuilts
REV. DATE: 5/29/16
ISSUE DATE: ENGINEER: Allen Engineering
SHEET OF
May 29, 2016 As-Builts
Hanger G CCAFS, FL
9/26/15
VSD
Static Pressure Pressure Tap on LIOB-484
DaTemp SaFanEnable
SaFanStatus
SaFanSpeed
RaDamper
RaTemp
R/A
120Volt
D aT em p
R aT em p
M aT e m p
Sa Fa n St at us
C om p1 St a tu s
Sa Fa n sp e ed
AHU System – 2N & 2S
HiStatic
VFD FaultFilterStatus PressureTap on LIOB-454
RaRh
R aR h
C om p2 St a tu s
FilterStatus
V
FD
Fa ul t Em er ge n cy
Sh td ow n
HiStatic switch will be wired to both the VFD drive and to the LIOB controller via a relay.
O aT e m p OaTemp will be mounted on outside wall at Ahu-2N and then globaled to all units.
Emergency Shutdown
Comp1Enable
Comp1Status
Comp2Enable
Comp2Status
Sa Fa n En a bl e
StaticPressure
Ex Fa nE na b le
C om p1 En ab le
C om p2 En ab le
24v24v 24v 24v
120v24v
Trans-1
R aD a m p er
H iS ta ti c
Project:
MECHANICAL: Precision Air Conditioning
DRAWN BY: JRJ
SYSTEM: LOYTEC
REV #: Asbuilts
REV. DATE: 5/29/16
ISSUE DATE: ENGINEER: Allen Engineering
SHEET OF
May 29, 2016 As-Builts
Hanger G CCAFS, FL
9/26/15
DaTemp
RmTemp
HtgStg1
HtgStg2
VAV (Typ -17)
Override
R m
T e m p
D a T e m p
1- 2+ 3+
Bl u
Ye l
W ht
Re d
Pu r
Factory wiring in VAV
Field Wiring in VAV
Project:
MECHANICAL: Precision Air Conditioning
DRAWN BY: JRJ
SYSTEM: LOYTEC
REV #: Asbuilts
REV. DATE: 5/29/16
ISSUE DATE: ENGINEER: Allen Engineering
SHEET OF
May 29, 2016 As-Builts
Hanger G CCAFS, FL
9/26/15
Network
AHU-1N
LIOB 484
Web
Server
LINX 100
VAV-1 VAV-2 VAV-3 VAV-4 VAV-5
nd
Floor North VAVs
VAV-6 VAV-7 VAV-8 VAV-9
AHU-1N
LIOB 454
AHU-2N
LIOB 484
AHU-2N
LIOB 454
AHU-1S
LIOB 484
AHU-1S
LIOB 454
AHU-2S
LIOB 484
AHU-2S
LIOB 454
VAV-1 VAV-2 VAV-3 VAV-4 VAV-5 VAV-6 VAV-7 VAV-8
nd
Floor South VAVs
ETHERNET CAT-5E
BETWEEN NORTH
AND SOUTH
NETWORK IS A FLAT
LONWORKS IP-709
STANDARD ETHERNET SWITCH. TYPICAL
OF 2. ONE IN NORTH 1ST FLOOR
MECHANICAL ROOM AND 1 IN SOUTH 1ST
FLOOR MECHANICAL ROOM
File details come from the government source that posted it. Updated .