F3YCAW6118A101 – UPS Maintenance Questions & Answers Q1. What is the model number of the batteries?

A1. Refer to A3 Q2. What is the number of battery strings in each UPS system and how many batteries are in each string?

A2. Refer to A3 Q3. What is the age of each battery/string for each UPS system?

A3.160PWHR12200W4FRAug2009
80PWHR12230W4FRJul2011
80PWHR12500W4FRAug2011
120PWHR12390W4FRSep2011
80PWHR12280W4FROct2012
108PWHR1234W4FRJan2013
80PWHR12280W4FRSep2013
400PWHR12280W4FRNov2013
80PWHR12200W4FRMar2014
72PWHR12120W4FRJan2015
80PWHR12500W4FRJune2016

Q4. How many PM visits are required?

A4. Two visits, one coordinated with an Eaton Technical Representative. All batteries will be tested during both visits.

Q5. Page 2 Section 1.3. reads that "maintenance will include remedial replacement or repair of UPS batteries but Page 2 section 1.4.1. excludes the batteries, provide further explanation.

A5. Number of battery strings in each UPS system and how many batteries are in each string Q6. Identify all of the AC and DC caps by quantity and part number in each unit if you wish to have those items covered under the maintenance agreement.

A6. Interested contractors will be required to contact Eaton for all hardware and device specifications, per Appendix A.