STATEMENT OF WORK
400 Hz Solid-State Converter Installation
BLGD. 226
6 May 2008
1. SCOPE:
The existing 400 Hz KMG Generator located in Bldg 226C, Room 112 is mismatched between phases by 10-12 volts which is causing an increase in the number of LRU repairs and has obsolescence and supportability issues. It is proposed to replace the KMG with a 400 Hz Solid-State Frequency Converter of the correct specifications and voltage.
2. TASKS:
Provide 150 KVA Solid-State Frequency Converter (SSFC). Supply input: 480V/3ph/60Hz with a 12 Pulse Rectification circuit, output: 400/230V/3ph/400Hz (230VAC/3ph/400Hz Phase-Neutral & 400VAC/3ph/400Hz Phase-Phase) which will comply with the UFGS-16268. Contractor will not be responsible for installation.
Inspect installation of the 400 Hz SSFC which will be performed by 402 MXSG, Industrial Services Group. Include Freight, in-Factory Testing, Initial Startup, On- Site Training, Operation Manuals and 12/18 month Warranty.
Contractor shall perform all required tests, and checkouts necessary to demonstrate the converters are operational and up to manufacturer’s specifications.
3. CONTROLLED AREA REQUIRMENTS:
This project involves work in a controlled area, and contractors must be US citizens and must register at Building 231 (Access Control Center) upon any entrance or exit of the Software Facility, Building 226. Escorts are required for contractors at all times while working. Alternative work times, other than listed below, may be discussed with 402 SMXG.
All contractors shall obtain proper contractor’s badge from Robins Air Force Base Pass and ID Unit and shall present a picture ID to Access Control Center personnel prior to each entry to the Software Facility.
Visit Authorization Letters are required for all contractor visitors. They must be furnished at least 24 hours prior to the visit. Requests must be in writing (by or fax) from the Contractor on company letterhead or company form to the Access Control Center. The following information must be received in sufficient time for review prior to the visit:
Access Control Center - Building 231/226 Tel (478) 926-9774
FAX (478) 926-7894
Full Name of Contractor Personnel
Date of Birth
Place of Birth
Job Title
Citizenship
Security Clearance Level, Date and Issuing Agency
Software Facility Personnel to be visited (Not the Security Manager)
Existing Contract Number
Purpose of Visit
Date and Duration of Visit (Not to Exceed One Year)
Contractor Security Officer Name and Signature, Address, Phone Number
3. HOURS OF WORK:
The standard hours of work shall be Monday through Friday 7:00 AM to 4:30 PM EST except Federal Holidays unless otherwise agreed upon.
Other files
| File | Type | Posted |
|---|---|---|
| Combined Synopsis-F3QCCM8080A002-KVA CONVERTER.doc | DOC document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
File details come from the government source that posted it. Updated .