1143 Boiler Site Visit-Questions and Answers.pdf
PDF 105 KB Posted
- Attached to
- Boiler Rental Maxwell Air Force Base B1143
- Solicitation number
- F2X3CEB1143
About this file
This document is a Questions and Answers memorandum related to the federal contract opportunity for Boiler Rental at Maxwell Air Force Base, solicitation number F2X3CEB1143.
The key details are: The requirement is for a hydronic heating boiler that will use natural gas. The boiler will have a maximum water pressure. The solicitation is being issued as a Request for Quote (RFQ) under a Firm Fixed Price award. The NAICS code is 532490 with a $40M size standard. The contracting agency is the Department of the Air Force, Air Education and Training Command.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DEPARTMENT OF THE AIR FORCE
42D AIR BASE WING (AETC)
MAXWELL AIR FORCE BASE ALABAMA
19 Apr 2024
MEMORANDUM FOR RECORD
SUBJECT: F2X3CEB1143 Site Visit-Questions and Answers
1. The following questions were submitted to the USG for the subject requirement. There USG hereby responds to questions as appropriate:
a) Would this be a steam or hot water boiler?
Hydronic Heating Boiler (closed loop)
b) If the rental is steam, is it boiler only or complete plant? (Complete plant includes feed system, blowdown separator & water softener)
N/A
c) If the rental is hot water, is it hydronic or domestic?
Hydronic Heating
d) What fuel will you be firing? (oil, gas, electric, propane)
Natural Gas
e) What would be your operating pressure?
Max Water Pressure <150psi, Operating Range 45-60 psi.
f) If you need hose, what footage and diameter is needed?
100ft each supply & return. 200 ft total. Diameter depends on the rental size inlet/outlet
g) Are there any space concerns?
No space concerns.
h) What permits/ business licenses will be required for this job?
Only base requirement is licensed electrician for electrical and a hot permit for welding or torch work i.) Will this job be tax exempt?
Not applicable
j) How many gallons per minute is the pump supplying the air handler?
Pump is 160 GPM
i) If needed, can we tap into the existing duct supply / return with the flex ducts to the rental air handler?
Yes, but would still need existing AHU blocking
DONALD A. CRAWFORD, DAF, GS-13
Contracting Officer
| 2024-04-19T11:18:05-0500 | |
| CRAWFORD.DONALD.A.1061850399 |
File details come from the government source that posted it. Updated .