STATEMENT OF WORK (SOW)

FOR

Temporary DFAC Shelter

Ali Al Salem AB, KW 08 November 2017

STATEMENT OF WORK

FOR

PURCHASE REQUIREMENTS OF ALTERNATE FEEDING LOCATION

1. DESCRIPTION OF SHELTER REQUIREMENTS

1.1 Contractor shall provide all design, production, and delivery of items in order to provide a

“tent” style shelter that will serve as an alternate feeding location for Ali Al Salem AB Kuwait.

1.2 Overall Requirements:

All offered shelter products are required to meet the specifications forthwith.

- The temporary DFAC shelter system shall be a complete, quick deployment structure that can be installed on a concrete surface with a seating capacity of 400-600 personnel / 3,000 – 5,000 meals per day

- All units shall be shipped in ISO certified 20’ containers

- The shelter offered shall be clear span, frame-supported tension fabric structure of modular design with open, gable or round ends with accessories of; personnel doors, electrical lighting systems, tool kits, ventilation (HVAC, dehumidifiers, vents), and liners (insulating or decorative)

- Fabric shall be flame resistant, as required by NFPA 701

- Shelters offered shall include the options of laminate or coated fabric, desert tan exterior/white interior

- Shelters offered shall be Berry Amendment compliant

- Shelters offered shall be 115 mph IBC (International Building Code) wind load certified

- The shelter offered shall consist of two shelter systems, connectable by a vestibule system

- Dimensions offered shall range between 65’, 75’, 85’ by 120’ length and 16’ eave height for equipment access

- The shelter system shall include the options of 8 multiple single and double aluminum door placements with view windows, approx. (3’0”x6’6”h) and (6’0”x6’8”h) respectively

1.3 Electrical Requirements

- Electrical panel per tent o 200A 3-Phase, 4-Wire 42-Space Ground Bus Bar Panel o 240V/415V 50 Hz o 20A single pull breakers o Copper clad Aluminum bus bars o Panel, Circuits, and Breakers be provided by same manufacturer

- Lighting o LED, 240V/415V 50 Hz o Minimum 50 foot candles of lighting for adequate food prep requirements

- Outlets o Sufficient outlets, mounting equipment, and wiring to the panel to be provided for compliance with NFPA distances (6ft between outlets) o Sufficient quantity for 1 tent: UK 13A-250V, 50Hz GFCI (RCD) Duplex Power Outlets (UK1-13R), 30Ma Trip, BS136A Type G Sockets, Shuttered Contacts, 2 Pole-3 Wire Grounding, (2P+E) White o Sufficient quantity for 1 tent: UK 13A-250V, Duplex Power Outlet (UK1-13R), BS136A Type G Sockets, Single Pole On/Off Switch Control Outlet, Shuttered Contacts, 2-Pole 3-Wire Grounding (2P+E) White

1.4 HVAC Requirements

- Duct system capable of distributing 16,000 CFM of cooling air.