DIVISION OF ADMINISTRATION AIR-COOLED, ROTARY-SCREW WATER CHILLER
Solicitation number
ITB-03975
Issued by
Leon County, Florida

About this file

This document is an equipment design specification for a 300-ton air-cooled, rotary-screw water chiller requested by the Florida Department of Agriculture and Consumer Services (FDACS) for the Central Energy Plant at the Doyle Conner Complex in Tallahassee. The chiller must meet detailed technical requirements, including minimum cooling capacity, power consumption, efficiency, operating temperature range, and other specifications. The chiller must include variable speed compressors, permanent magnet fan motors, and a factory control panel with BACnet connectivity. The chiller must also include sound attenuation, freeze protection, and a 10-year parts, labor, and refrigerant warranty.

The related state and local contract opportunity is for the outright purchase and delivery of the new chiller. The jurisdictions involved are Leon County and the City of Tampa. No additional details are provided on the contract terms, response requirements, or award process.

View the file

Other files

File Type Posted
EXHIBIT I - SPECIFICATIONS.pdf PDF
Addendum 2.pdf PDF
Addendum 1.pdf PDF
64ITB CHILLER FINAL.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

EXHIBIT II

Department of Agriculture and Consumer Services

Central Energy Plant Air-Cooled Chiller Replacement

EXHIBIT II Equipment Design Specifications

AIR COOLED ROTARY SCREW CHILLER

DESIGNATION

CH-3

MANUFACTURER

TRANE

MODEL

ACRB300

REFRIGERANT / OPERATING CHARGE HFC-134a / 650 LBS

COOLING CAPACITY (NOMINAL) TONS 300

UNIT POWER CONSUMPTION KW 307.5

FULL LOAD EFFICIENCY / EER (MIN) BTUH / W 11.5

INTEGRATED PART LOAD VALUE (MIN) kW / TON 21.6

AMBIENT CONDITIONS °F 95°

EVAPORATOR FLOW RATE (NOMINAL) GPM 590

ENTERING WATER TEMPERATURE °F 54°

LEAVING WATER TEMPERATURE °F 42°

SYSTEM PRESSURE DROP (MAX) FT 13.6

AVAILABLE HEAD PRESSURE for CHWS TDH N/A

EXPANSION TANK GAL N/A

BUFFER TANK GAL N/A

FOULING FACTOR HR-SF-°F/

BTU

0.00010

INDEPENDENT REFRIGERANT CIRCUITS MIN 2

COMPRESSORS MAX 2

CAPACITY CONTROL DOWN TO MIN. % 15%

CHILLER ELECTRICAL CHARACTERISTICS V/Ø/HZ 460 / 3 / 60

UNIT POWER REQUIREMENT (MAX) MCA/MOP 496 / 600

SHORT CIRCUIT CURRENT RATING (MIN) A 23,160

EVAP HEAT POWER ELECTRICAL V/Ø/HZ 120 / 1 /60

EVAP HEAT POWER REQUIREMENT MCA 15

A-WEIGHTED SOUND PRESSURE 100/75/50/25 dBA 71 / 67 / 61 / 58

SHIPPING WEIGHT LBS 18,500

UNIT DIMENSIONS L x W x H IN 442 x 88 x 98

EXHIBIT II

Department of Agriculture and Consumer Services

Central Energy Plant Air-Cooled Chiller Replacement

NOTES:

1. HIGH-EFFICIENCY AIR-COOLED SCREW CHILLER; INCLUDES VARIABLE SPEED COMPRESSORS &

VARIABLE SPEED PERMANENT MAGNET MOTORS FOR CONDENSER FANS.

2. SINGLE-POINT POWER CONNECTION. FREEZE PROTECTION WILL HAVE INDEPENDENT CIRCUIT.

3. FACTORY CONTROL PANEL WITH DISPLAY & BACNET CARD. BACNET OVER MS/TP OR IP AS REQUIRED

BY CONTROLS CONTRACTOR.

4. LOW AMBIENT TEMPERATURE OPERATION: 0°-105°F

5. FREEZE PROTECTION TO -20°F.

6. INCLUDE EVAPORATOR INSULATION FOR HIGH HUMIDITY CLIMATE; MIN. 1.25" THICK

7. PROVIDE NECESSARY SOUND ATTENUTAION TO MEET SCHEDULED SOUND PRESSURES.

8. PROVIDE ELASTOMERIC ISOLATORS FOR MOUNTING TO CONCRETE PAD.

9. PROVIDE COPPER TUB AND ALUMINUM FIN TYPE CONDENSER COILS

10. PROVIDE 20A - 110V CONVENIENCE OUTLET.

11. PROVIDE FACTORY MOUNTED CIRCUIT BREAKER.

12. PROVIDE COMPLETE MANUFACTURER 10-YEAR PARTS, LABOR & REFRIGERANT WARRANTY.