EXHIBIT_H_Stringing_Report_By_Tension.pdf
PDF 260 KB Posted
- Solicitation number
- FKEC BID #25-04
- Issued by
- Florida
About this file
The provided document is a Stringing Report by Tension for the Tavernier - Key Largo 138kV Line, prepared by Welty Energy & Infrastructure, detailing electrical line installation specifications for the Florida Keys Electric Cooperative (FKEC). The report comprehensively documents stringing data for multiple circuit sections, including line 3 KCI 25kV and Neutral lines, covering various structure segments from locations such as structure #273 to #280B, #508 to Tav 25kV, and multiple intermediate points. The report provides detailed technical information including ruling spans, cable files, voltage levels, sagging conditions, horizontal tensions, and temperature-related tension variations across different structural segments.
The stringing report presents precise engineering data for each circuit section, with calculations performed at an initial reference temperature of 60 degrees Fahrenheit. Each section includes detailed horizontal tension measurements at temperature ranges from 30°F to 100°F, catenary measurements, and specific cable characteristics. The documentation includes sections for both primary electrical lines (line 3 KCI 25kV) and neutral lines, providing engineers and construction teams with critical technical specifications needed for precise electrical infrastructure installation. The level of detail suggests this is a critical component of a comprehensive electrical distribution infrastructure project, offering granular insights into cable tension, structural loading, and environmental performance characteristics.
View the file
Other files
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
STRINGING REPORT
- BY TENSION
Welty Energy & Infrastructure Page 1/25
PLS-CADD Version 20.01x64 4:04:24 PM Friday, December 27, 2024 Welty Energy & Infrastructure Project Name: 'C:\Users\jwalker\Documents\FKEC\PLS_Rev2\Project\Test\Line 3 NESC 2023.don' Line Title: Tavernier - Key Largo 138kV Line
Selected sections include:
Structures: 188 - TAVERNIER SUBSTATION Circuits: Neutral line 3 KCI 25kV
Section Sagging Data
Circuit Sec. Cable From To Voltage Ruling -----------Sagging Data------------- ---------------Display----------------- No. File Str. Str. Span Condition Temp. Catenary Horiz. Weather Condition Catenary Name Constant Tension Case Constant (kV) (ft) (deg F) (ft) (lbs) (ft) line 3 KCI 25kV 8 tulip_aac.wir 273 280B 25 383.5 Initial RS 60.0 8799.4 2780.6 Maximum Operating Creep RS 1815.8 line 3 KCI 25kV 10 tulip_aac.wir 508 Tav 25kV 25 114.3 Initial RS 60.0 5545.3 1752.3 Maximum Operating Creep RS 558.8 Neutral 14 Neu 7#8.wir 273 280B 0 383.5 Initial RS 60.0 5117.3 1339.7 Maximum Operating Creep RS 2304.0 Neutral 16 Neu 7#8.wir 508 Tav 25kV 0 115.1 Initial RS 60.0 5006.1 1310.6 Maximum Operating Creep RS 855.8 line 3 KCI 25kV 84 tulip_aac.wir 202A 203 25 312.0 Load RS 60.0 4863.9 1537.0 Maximum Operating Creep RS 1487.8 line 3 KCI 25kV 86 tulip_aac.wir 215 229A 25 371.1 Initial RS 60.0 8535.8 2697.3 Maximum Operating Creep RS 1753.7 line 3 KCI 25kV 87 tulip_aac.wir 229A 232 25 257.8 Load RS 60.0 4838.9 1529.1 Maximum Operating Creep RS 1233.8 line 3 KCI 25kV 89 tulip_aac.wir 258A 260 25 264.3 Load RS 60.0 4800.6 1517.0 Maximum Operating Creep RS 1262.7 line 3 KCI 25kV 90 tulip_aac.wir 260 264 25 224.4 Load RS 60.0 4851.9 1533.2 Maximum Operating Creep RS 1080.5 line 3 KCI 25kV 91 tulip_aac.wir 264 271 25 388.0 Load RS 60.0 4852.5 1533.4 Maximum Operating Creep RS 1836.0 line 3 KCI 25kV 92 tulip_aac.wir 271 271A 25 220.0 Load RS 60.0 4863.3 1536.8 Maximum Operating Creep RS 1061.8 line 3 KCI 25kV 93 tulip_aac.wir 271A 272 25 200.0 Load RS 60.0 4829.4 1526.1 Maximum Operating Creep RS 971.1 line 3 KCI 25kV 94 tulip_aac.wir 273 496 25 337.1 Initial RS 60.0 8391.5 2651.7 Maximum Operating Creep RS 1609.3 Neutral 103 Neu 7#8.wir 202A 203 1 311.0 Load RS 60.0 4851.0 1270.0 Maximum Operating Creep RS 1981.2 Neutral 105 Neu 7#8.wir 215 229A 1 371.1 Load RS 60.0 4854.1 1270.8 Maximum Operating Creep RS 2253.1 Neutral 106 Neu 7#8.wir 229A 232 1 257.9 Load RS 60.0 4852.2 1270.3 Maximum Operating Creep RS 1713.9 Neutral 108 Neu 7#8.wir 258A 260 1 264.2 Load RS 60.0 4845.3 1268.5 Maximum Operating Creep RS 1748.0 Neutral 109 Neu 7#8.wir 260 264 1 224.0 Load RS 60.0 4850.6 1269.9 Maximum Operating Creep RS 1530.0 Neutral 110 Neu 7#8.wir 264 271 1 388.0 Load RS 60.0 4842.6 1267.8 Maximum Operating Creep RS 2322.5 Neutral 111 Neu 7#8.wir 271 271A 1 219.9 Load RS 60.0 4840.3 1267.2 Maximum Operating Creep RS 1505.8 Neutral 112 Neu 7#8.wir 271A 272 1 198.7 Load RS 60.0 4836.1 1266.1 Maximum Operating Creep RS 1386.0 Neutral 113 Neu 7#8.wir 273 496 0 336.9 Initial RS 60.0 5134.8 1344.3 Maximum Operating Creep RS 2103.8
Section Geometry Data
Notes: Lengths are arc lengths along the wire at 60 (deg F), Initial.
Lengths are adjusted for the number of phases, the number of subconductors and to exclude the length of strain insulators.
Lengths are computed with any concentrated loads removed.
Circuit Sec. Cable From To Number Wires Min. Max. Ruling Total No. File Str. Str. of Per Span Span Span Cable Name Phases Phase Length
(ft) (ft) (ft) (ft) line 3 KCI 25kV 8 tulip_aac.wir 273 280B 3 1 24.6 465.8 383.5 9098.6 line 3 KCI 25kV 10 tulip_aac.wir 508 Tav 25kV 3 1 72.3 133.5 114.3 629.6 Neutral 14 Neu 7#8.wir 273 280B 1 1 23.8 465.8 383.5 3037.5 Neutral 16 Neu 7#8.wir 508 Tav 25kV 1 1 73.3 133.5 115.1 208.4 line 3 KCI 25kV 84 tulip_aac.wir 202A 203 3 1 48.3 333.3 312.0 1125.9 line 3 KCI 25kV 86 tulip_aac.wir 215 229A 3 1 49.0 470.8 371.1 17628.8 line 3 KCI 25kV 87 tulip_aac.wir 229A 232 3 1 48.4 350.4 257.8 3266.3 line 3 KCI 25kV 89 tulip_aac.wir 258A 260 3 1 55.6 318.2 264.3 1689.1 line 3 KCI 25kV 90 tulip_aac.wir 260 264 3 1 162.2 299.1 224.4 3089.0 line 3 KCI 25kV 91 tulip_aac.wir 264 271 3 1 301.7 428.6 388.0 7974.2 line 3 KCI 25kV 92 tulip_aac.wir 271 271A 3 1 220.0 220.0 220.0 641.0 line 3 KCI 25kV 93 tulip_aac.wir 271A 272 3 1 200.8 200.8 200.0 586.0
Welty Energy & Infrastructure Page 2/25 line 3 KCI 25kV 94 tulip_aac.wir 273 496 3 1 338.1 338.1 337.1 998.2 Neutral 103 Neu 7#8.wir 202A 203 1 1 48.0 332.2 311.0 378.3 Neutral 105 Neu 7#8.wir 215 229A 1 1 49.0 470.7 371.1 5881.0 Neutral 106 Neu 7#8.wir 229A 232 1 1 48.4 350.4 257.9 1091.5 Neutral 108 Neu 7#8.wir 258A 260 1 1 55.6 317.9 264.2 566.6 Neutral 109 Neu 7#8.wir 260 264 1 1 162.0 298.6 224.0 1032.2 Neutral 110 Neu 7#8.wir 264 271 1 1 301.6 428.6 388.0 2663.1 Neutral 111 Neu 7#8.wir 271 271A 1 1 219.9 219.9 219.9 217.9 Neutral 112 Neu 7#8.wir 271A 272 1 1 199.5 199.5 198.7 198.3 Neutral 113 Neu 7#8.wir 273 496 1 1 337.4 337.4 336.9 336.0
Welty Energy & Infrastructure Page 3/25
Stringing Chart Report
Circuit 'line 3 KCI 25kV' Section #8 from structure #273 to structure #280B, start set #4 '', end set #14 '' Cable 'C:\Users\jwalker\Documents\FKEC\PLS_Rev2\Cables\tulip_aac.wir', Ruling span (ft) 383.518 Sagging data: Catenary (ft) 8799.37, Horiz. Tension (lbs) 2780.6 Condition I Temperature (deg F) 60 Results below for condition 'Initial RS' Calculations done using actual span lengths and vertical projections
Horiz Horiz Horiz Horiz Horiz Horiz Horiz Horiz Tension Tension Tension Tension Tension Tension Tension Tension 30 F 40 F 50 F 60 F 70 F 80 F 90 F 100 F (lbs) (lbs) (lbs) (lbs) (lbs) (lbs) (lbs) (lbs) 3264 3107 2946 2778 2609 2437 2263 2090
Welty Energy & Infrastructure Page 4/25
Circuit 'line 3 KCI 25kV' Section #10 from structure #508 to structure #Tav 25kV, start set #4 '', end set #4 '' Cable 'C:\Users\jwalker\Documents\FKEC\PLS_Rev2\Cables\tulip_aac.wir', Ruling span (ft) 114.288 Sagging data: Catenary (ft) 5545.25, Horiz. Tension (lbs) 1752.3 Condition I Temperature (deg F) 60 Results below for condition 'Initial RS' Calculations done using actual span lengths and vertical projections
Horiz Horiz Horiz Horiz Horiz Horiz Horiz Horiz Tension Tension Tension Tension Tension Tension Tension Tension 30 F 40 F 50 F 60 F 70 F 80 F 90 F 100 F
2363 2166 1960 1752 1539 1327 1118 920
Welty Energy & Infrastructure Page 5/25
Circuit 'Neutral' Section #14 from structure #273 to structure #280B, start set #7 '', end set #17 '' Cable 'C:\Users\jwalker\Documents\FKEC\PLS_Rev2\Cables\Neu 7#8.wir', Ruling span (ft) 383.544 Sagging data: Catenary (ft) 5117.27, Horiz. Tension (lbs) 1339.7 Condition I Temperature (deg F) 60 Results below for condition 'Initial RS' Calculations done using actual span lengths and vertical projections
Horiz Horiz Horiz Horiz Horiz Horiz Horiz Horiz Tension Tension Tension Tension Tension Tension Tension Tension 30 F 40 F 50 F 60 F 70 F 80 F 90 F 100 F
1614 1515 1424 1340 1259 1187 1119 1058
Welty Energy & Infrastructure Page 6/25
Circuit 'Neutral' Section #16 from structure #508 to structure #Tav 25kV, start set #7 '', end set #7 '' Cable 'C:\Users\jwalker\Documents\FKEC\PLS_Rev2\Cables\Neu 7#8.wir', Ruling span (ft) 115.068 Sagging data: Catenary (ft) 5006.11, Horiz. Tension (lbs) 1310.6 Condition I Temperature (deg F) 60 Results below for condition 'Initial RS' Calculations done using actual span lengths and vertical projections
Horiz Horiz Horiz Horiz Horiz Horiz Horiz Horiz Tension Tension Tension Tension Tension Tension Tension Tension 30 F 40 F 50 F 60 F 70 F 80 F 90 F 100 F
1707 1572 1439 1308 1183 1058 940 828
Welty Energy & Infrastructure Page 7/25
Circuit 'line 3 KCI 25kV' Section #84 from structure #202A to structure #203, start set #14 '', end set #4 '' Cable 'C:\Users\jwalker\Documents\FKEC\PLS_Rev2\Cables\tulip_aac.wir', Ruling span (ft) 311.97 Sagging data: Catenary (ft) 4863.92, Horiz. Tension (lbs) 1537 Condition L Temperature (deg F) 60 Results below for condition 'Initial RS' Calculations done using actual span lengths and vertical projections
Horiz Horiz Horiz Horiz Horiz Horiz Horiz Horiz Tension Tension Tension Tension Tension Tension Tension Tension 30 F 40 F 50 F 60 F 70 F 80 F 90 F 100 F
3031 2865 2692 2514 2332 2152 1971 1793
Welty Energy & Infrastructure Page 8/25
Circuit 'line 3 KCI 25kV' Section #86 from structure #215 to structure #229A, start set #14 '', end set #4 '' Cable 'C:\Users\jwalker\Documents\FKEC\PLS_Rev2\Cables\tulip_aac.wir', Ruling span (ft) 371.077 Sagging data: Catenary (ft) 8535.76, Horiz. Tension (lbs) 2697.3 Condition I Temperature (deg F) 60 Results below for condition 'Initial RS' Calculations done using actual span lengths and vertical projections
Horiz Horiz Horiz Horiz Horiz Horiz Horiz Horiz Tension Tension Tension Tension Tension Tension Tension Tension 30 F 40 F 50 F 60 F 70 F 80 F 90 F 100 F
3189 3030 2866 2695 2525 2348 2175 2000
Welty Energy & Infrastructure Page 9/25
Circuit 'line 3 KCI 25kV' Section #87 from structure #229A to structure #232, start set #14 '', end set #4 '' Cable 'C:\Users\jwalker\Documents\FKEC\PLS_Rev2\Cables\tulip_aac.wir', Ruling span (ft) 257.797 Sagging data: Catenary (ft) 4838.92, Horiz. Tension (lbs) 1529.1 Condition L Temperature (deg F) 60 Results below for condition 'Initial RS' Calculations done using actual span lengths and vertical projections
Horiz Horiz Horiz Horiz Horiz Horiz Horiz Horiz Tension Tension Tension Tension Tension Tension Tension Tension 30 F 40 F 50 F 60 F 70 F 80 F 90 F 100 F
2829 2652 2471 2285 2095 1908 1720 1539
Welty Energy & Infrastructure Page 10/25
Circuit 'line 3 KCI 25kV' Section #89 from structure #258A to structure #260, start set #14 '', end set #4 '' Cable 'C:\Users\jwalker\Documents\FKEC\PLS_Rev2\Cables\tulip_aac.wir', Ruling span (ft) 264.293 Sagging data: Catenary (ft) 4800.63, Horiz. Tension (lbs) 1517 Condition L Temperature (deg F) 60 Results below for condition 'Initial RS' Calculations done using actual span lengths and vertical projections
Horiz Horiz Horiz Horiz Horiz Horiz Horiz Horiz Tension Tension Tension Tension Tension Tension Tension Tension 30 F 40 F 50 F 60 F 70 F 80 F 90 F 100 F
2843 2666 2485 2300 2113 1923 1736 1556
Welty Energy & Infrastructure Page 11/25
Circuit 'line 3 KCI 25kV' Section #90 from structure #260 to structure #264, start set #14 '', end set #4 '' Cable 'C:\Users\jwalker\Documents\FKEC\PLS_Rev2\Cables\tulip_aac.wir', Ruling span (ft) 224.358 Sagging data: Catenary (ft) 4851.9, Horiz. Tension (lbs) 1533.2 Condition L Temperature (deg F) 60 Results below for condition 'Initial RS' Calculations done using actual span lengths and vertical projections
Horiz Horiz Horiz Horiz Horiz Horiz Horiz Horiz Tension Tension Tension Tension Tension Tension Tension Tension 30 F 40 F 50 F 60 F 70 F 80 F 90 F 100 F
2743 2562 2375 2185 1990 1797 1604 1421
Welty Energy & Infrastructure Page 12/25
Circuit 'line 3 KCI 25kV' Section #91 from structure #264 to structure #271, start set #14 '', end set #4 '' Cable 'C:\Users\jwalker\Documents\FKEC\PLS_Rev2\Cables\tulip_aac.wir', Ruling span (ft) 387.985 Sagging data: Catenary (ft) 4852.53, Horiz. Tension (lbs) 1533.4 Condition L Temperature (deg F) 60 Results below for condition 'Initial RS' Calculations done using actual span lengths and vertical projections
Horiz Horiz Horiz Horiz Horiz Horiz Horiz Horiz Tension Tension Tension Tension Tension Tension Tension Tension 30 F 40 F 50 F 60 F 70 F 80 F 90 F 100 F
3274 3119 2959 2792 2623 2449 2278 2105
Welty Energy & Infrastructure Page 13/25
Circuit 'line 3 KCI 25kV' Section #92 from structure #271 to structure #271A, start set #14 '', end set #4 '' Cable 'C:\Users\jwalker\Documents\FKEC\PLS_Rev2\Cables\tulip_aac.wir', Ruling span (ft) 219.961 Sagging data: Catenary (ft) 4863.29, Horiz. Tension (lbs) 1536.8 Condition L Temperature (deg F) 60 Results below for condition 'Initial RS' Calculations done using actual span lengths and vertical projections
Horiz Horiz Horiz Horiz Horiz Horiz Horiz Horiz Tension Tension Tension Tension Tension Tension Tension Tension 30 F 40 F 50 F 60 F 70 F 80 F 90 F 100 F
2747 2564 2379 2188 1993 1800 1607 1421
Welty Energy & Infrastructure Page 14/25
Circuit 'line 3 KCI 25kV' Section #93 from structure #271A to structure #272, start set #14 '', end set #4 '' Cable 'C:\Users\jwalker\Documents\FKEC\PLS_Rev2\Cables\tulip_aac.wir', Ruling span (ft) 199.999 Sagging data: Catenary (ft) 4829.43, Horiz. Tension (lbs) 1526.1 Condition L Temperature (deg F) 60 Results below for condition 'Initial RS' Calculations done using actual span lengths and vertical projections
Horiz Horiz Horiz Horiz Horiz Horiz Horiz Horiz Tension Tension Tension Tension Tension Tension Tension Tension 30 F 40 F 50 F 60 F 70 F 80 F 90 F 100 F
2716 2532 2343 2150 1954 1754 1560 1371
Welty Energy & Infrastructure Page 15/25
Circuit 'line 3 KCI 25kV' Section #94 from structure #273 to structure #496, start set #14 '', end set #4 '' Cable 'C:\Users\jwalker\Documents\FKEC\PLS_Rev2\Cables\tulip_aac.wir', Ruling span (ft) 337.113 Sagging data: Catenary (ft) 8391.46, Horiz. Tension (lbs) 2651.7 Condition I Temperature (deg F) 60 Results below for condition 'Initial RS' Calculations done using actual span lengths and vertical projections
Horiz Horiz Horiz Horiz Horiz Horiz Horiz Horiz Tension Tension Tension Tension Tension Tension Tension Tension 30 F 40 F 50 F 60 F 70 F 80 F 90 F 100 F
3153 2992 2824 2652 2475 2296 2117 1941
Welty Energy & Infrastructure Page 16/25
Circuit 'Neutral' Section #103 from structure #202A to structure #203, start set #17 '', end set #7 '' Cable 'C:\Users\jwalker\Documents\FKEC\PLS_Rev2\Cables\Neu 7#8.wir', Ruling span (ft) 310.96 Sagging data: Catenary (ft) 4851.03, Horiz. Tension (lbs) 1270 Condition L Temperature (deg F) 60 Results below for condition 'Initial RS' Calculations done using actual span lengths and vertical projections
Horiz Horiz Horiz Horiz Horiz Horiz Horiz Horiz Tension Tension Tension Tension Tension Tension Tension Tension 30 F 40 F 50 F 60 F 70 F 80 F 90 F 100 F
1653 1544 1439 1340 1247 1163 1084 1013
Welty Energy & Infrastructure Page 17/25
Circuit 'Neutral' Section #105 from structure #215 to structure #229A, start set #17 '', end set #7 '' Cable 'C:\Users\jwalker\Documents\FKEC\PLS_Rev2\Cables\Neu 7#8.wir', Ruling span (ft) 371.06 Sagging data: Catenary (ft) 4854.09, Horiz. Tension (lbs) 1270.8 Condition L Temperature (deg F) 60 Results below for condition 'Initial RS' Calculations done using actual span lengths and vertical projections
Horiz Horiz Horiz Horiz Horiz Horiz Horiz Horiz Tension Tension Tension Tension Tension Tension Tension Tension 30 F 40 F 50 F 60 F 70 F 80 F 90 F 100 F
1623 1524 1429 1340 1259 1184 1115 1052
Welty Energy & Infrastructure Page 18/25
Circuit 'Neutral' Section #106 from structure #229A to structure #232, start set #17 '', end set #7 '' Cable 'C:\Users\jwalker\Documents\FKEC\PLS_Rev2\Cables\Neu 7#8.wir', Ruling span (ft) 257.855 Sagging data: Catenary (ft) 4852.18, Horiz. Tension (lbs) 1270.3 Condition L Temperature (deg F) 60 Results below for condition 'Initial RS' Calculations done using actual span lengths and vertical projections
Horiz Horiz Horiz Horiz Horiz Horiz Horiz Horiz Tension Tension Tension Tension Tension Tension Tension Tension 30 F 40 F 50 F 60 F 70 F 80 F 90 F 100 F
1680 1562 1448 1340 1238 1141 1054 973
Welty Energy & Infrastructure Page 19/25
Circuit 'Neutral' Section #108 from structure #258A to structure #260, start set #17 '', end set #7 '' Cable 'C:\Users\jwalker\Documents\FKEC\PLS_Rev2\Cables\Neu 7#8.wir', Ruling span (ft) 264.21 Sagging data: Catenary (ft) 4845.3, Horiz. Tension (lbs) 1268.5 Condition L Temperature (deg F) 60 Results below for condition 'Initial RS' Calculations done using actual span lengths and vertical projections
Horiz Horiz Horiz Horiz Horiz Horiz Horiz Horiz Tension Tension Tension Tension Tension Tension Tension Tension 30 F 40 F 50 F 60 F 70 F 80 F 90 F 100 F
1674 1556 1445 1337 1238 1143 1056 976
Welty Energy & Infrastructure Page 20/25
Circuit 'Neutral' Section #109 from structure #260 to structure #264, start set #17 '', end set #7 '' Cable 'C:\Users\jwalker\Documents\FKEC\PLS_Rev2\Cables\Neu 7#8.wir', Ruling span (ft) 224.038 Sagging data: Catenary (ft) 4850.65, Horiz. Tension (lbs) 1269.9 Condition L Temperature (deg F) 60 Results below for condition 'Initial RS' Calculations done using actual span lengths and vertical projections
Horiz Horiz Horiz Horiz Horiz Horiz Horiz Horiz Tension Tension Tension Tension Tension Tension Tension Tension 30 F 40 F 50 F 60 F 70 F 80 F 90 F 100 F
1689 1568 1448 1334 1227 1122 1029 941
Welty Energy & Infrastructure Page 21/25
Circuit 'Neutral' Section #110 from structure #264 to structure #271, start set #17 '', end set #7 '' Cable 'C:\Users\jwalker\Documents\FKEC\PLS_Rev2\Cables\Neu 7#8.wir', Ruling span (ft) 388.028 Sagging data: Catenary (ft) 4842.63, Horiz. Tension (lbs) 1267.8 Condition L Temperature (deg F) 60 Results below for condition 'Initial RS' Calculations done using actual span lengths and vertical projections
Horiz Horiz Horiz Horiz Horiz Horiz Horiz Horiz Tension Tension Tension Tension Tension Tension Tension Tension 30 F 40 F 50 F 60 F 70 F 80 F 90 F 100 F
1608 1512 1421 1337 1259 1187 1121 1061
Welty Energy & Infrastructure Page 22/25
Circuit 'Neutral' Section #111 from structure #271 to structure #271A, start set #17 '', end set #7 '' Cable 'C:\Users\jwalker\Documents\FKEC\PLS_Rev2\Cables\Neu 7#8.wir', Ruling span (ft) 219.882 Sagging data: Catenary (ft) 4840.34, Horiz. Tension (lbs) 1267.2 Condition L Temperature (deg F) 60 Results below for condition 'Initial RS' Calculations done using actual span lengths and vertical projections
Horiz Horiz Horiz Horiz Horiz Horiz Horiz Horiz Tension Tension Tension Tension Tension Tension Tension Tension 30 F 40 F 50 F 60 F 70 F 80 F 90 F 100 F
1689 1565 1448 1331 1224 1119 1024 936
Welty Energy & Infrastructure Page 23/25
Circuit 'Neutral' Section #112 from structure #271A to structure #272, start set #17 '', end set #7 '' Cable 'C:\Users\jwalker\Documents\FKEC\PLS_Rev2\Cables\Neu 7#8.wir', Ruling span (ft) 198.731 Sagging data: Catenary (ft) 4836.13, Horiz. Tension (lbs) 1266.1 Condition L Temperature (deg F) 60 Results below for condition 'Initial RS' Calculations done using actual span lengths and vertical projections
Horiz Horiz Horiz Horiz Horiz Horiz Horiz Horiz Tension Tension Tension Tension Tension Tension Tension Tension 30 F 40 F 50 F 60 F 70 F 80 F 90 F 100 F
1698 1571 1451 1331 1218 1111 1010 918
Welty Energy & Infrastructure Page 24/25
Circuit 'Neutral' Section #113 from structure #273 to structure #496, start set #17 '', end set #7 '' Cable 'C:\Users\jwalker\Documents\FKEC\PLS_Rev2\Cables\Neu 7#8.wir', Ruling span (ft) 336.853 Sagging data: Catenary (ft) 5134.84, Horiz. Tension (lbs) 1344.3 Condition I Temperature (deg F) 60 Results below for condition 'Initial RS' Calculations done using actual span lengths and vertical projections
Horiz Horiz Horiz Horiz Horiz Horiz Horiz Horiz Tension Tension Tension Tension Tension Tension Tension Tension 30 F 40 F 50 F 60 F 70 F 80 F 90 F 100 F
1644 1538 1439 1343 1256 1175 1100 1033
Welty Energy & Infrastructure Page 25/25