Exhibit D-JFHQ CoonskinArmory Drill Hall RTU-Specifications.pdf
PDF 2 MB Posted
- Attached to
- JFHQ Coonskin Armory Drill Hall RTU Replacement
- Solicitation number
- CRFQ 0603 ADJ2600000023 5
- Issued by
- Kanawha County, West Virginia
About this file
This is a technical specification document for a rooftop-mounted HVAC unit for the West Virginia Air National Guard (WV ANG) Coonskin Armory Drill Hall RTU replacement project. The specification details an AAON model RN-018-C-A-8 rooftop unit designed to provide cooling and heating for the drill hall facility. The unit is configured as an 18-ton air-cooled packaged system with a cooling capacity of 206 megabytes per hour (MBH) and natural gas heating capacity of 270 MBH with four-stage staging for both cooling and heating. The RTU features a single 7.5-horsepower supply fan delivering 7,000 cubic feet per minute (CFM) of airflow, an evaporator coil with standard 4-row configuration, R-454B refrigerant charge of 229 ounces, and MERV 8 filters in a 25x20x2-inch cartridge format with six units. The unit is equipped with an economizer for outside air control, DDC (direct digital controls) with isolation relays, a clogged filter switch, and remote safety shutdown capabilities.
The RTU specifications include detailed performance ratings indicating cooling efficiency rating (EER) of 12.05 BTU/hW at AHRI standard conditions and application EER of 9.2 BTU/hW, with a total system static pressure of 3.17 inches water gauge and maximum duct static pressure of 3.52 inches when airway is blocked. The unit is specified for 208 volts, 3-phase, 60-hertz power with total full-load amperage of 85 amps and minimum circuit amperage of 91 amps. The cabinet is galvanized double-wall construction with R-16 foam insulation and premium AAON gray paint finish. The unit measures 138 inches wide by 64 inches long by 60 inches high with an approximate operating weight of 3,229 pounds. The document includes comprehensive acoustic data, electrical specifications, control terminal descriptions, dimensional drawings showing clearance requirements and gas heat exchanger access details, and roof live load rating certification indicating the unit can support maximum concentrated loads of 200 pounds and uniform loads of 35 pounds per square foot.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Job Name WV ANG Coonskin Drill Hall - Scenario 1 Job Number 1 Elevation 0 ft Refrigerant R-454B Design System Charge (oz) 229 / 229
Job Information Unit Information Approx. Weight (Op./Ship) 3229 / 3229 lbs (±5%) Base Dimensions (WxLxH) 138.0 x 64.0 x 60.0 in Coil Filter FV / Qty 336.0 fpm / 6 Min. Room Area/Height/Airflow** 215 ft² / 7 ft / 388 SCFM Ambient Temperature 95.0 / 75.0 °F DB/WB Supply Airflow / ESP 7000 SCFM / 1.75 in. w.g.
Return Airflow / ESP 7000 SCFM / 0.25 in. w.g.
Return Temperature 75.0 / 62.0 °F DB/WB Outside Airflow 1400 SCFM
Static Pressure External 1.75 in. w.g.
Cooling Coil 0.30 in. w.g.
Filters (Clean) 0.13 in. w.g.
Dirt Allowance 0.35 in. w.g.
Economizer 0.18 in. w.g.
Heater 0.24 in. w.g.
Cabinet 0.22 in. w.g.
Total 3.17 in. w.g.
Rating Information Listing Model RN-018-3-0-FAAY-S0-21-000-A Cooling Capacity 206.0 MBH Cooling EER 12.05 BTU/h·W Cooling IEER 18.42 BTU/h·W *Rated in accordance with AHRI Standard 340/360 (I-P)
Application EER @ Op. Conditions 9.2 BTU/h·W
Gross Net
Mixed Air Temp 79.0 / 64.9 °F DB/WB Ent Air Temp 79.0 / 64.9 °F DB/WB Lvg Air Temp (Coil) 55.5 / 54.7 °F DB/WB Lvg Air Temp (Unit) 57.8 / 55.7 °F DB/WB
Supply Air Fan 1 x 270 @ 6.60 BHP Ea.
SA Fan RPM / Width 1279 RPM / 6.13 in SA Fan FEI 0.98
Evaporator Coil 19.9 ft² / 4 Rows / 14 FPI Evaporator Face Velocity 352.4 fpm
Cooling Section
Total Capacity 208.5 MBH 189.9 MBH Sensible Capacity 176.7 MBH 158.1 MBH Latent Capacity 31.8 MBH
Heating Section Preheat Type Std (No Preheat) Auxiliary Heating Type Nat. Gas Heat Heating Airflow 7000 SCFM Total Capacity 218.7 MBH Entering Air Temp 54.4 / 44.2 °F DB/WB Leaving Air Temp 83.1 / 56.8 °F DB/WB Consumption 270.0 MBH Total Turndown Ratio 2.8:1
R N A - 0 1 8 - C - A - 8 -
A1
F
A2
A
A3
A
A4
A5
4 -
B1
D
B2
B
B3
B4
D
B5
0 :
1 -
3A
3B
A
3C
G
3D
3E
J -
4A
E
4B
4C
0 -
5A
5B
5C
5D
5E
0 -
6A
6B
6C
6D
6E
0 -
E
A -
9A
9B
9C
9D
A -
A
B
0 -
A
B
0 -
A -
A
A
B
R
C
0 -
E
B -
A
N
B
C
D
0 -
A
B
0 -
A
B
C
0 -
A
A
0 -
E
B -
B
RTU_1RTU Tag
Unit Rating ECat v365.0 2425 S Yukon Ave • Tulsa, OK 74107 • 918-583-2266 • www.aaon.com
Last Modified By Chris Hess Date Created/Modified 5/18/2026 10:20 AM Date Printed 5/18/2026 10:27:13 AM
PerformanceValues Version 365.0 https://www.aaon.com/
Cabinet Sound Power Levels* Octave Bands 63 125 250 500 1000 2000 4000 8000 Discharge LW (dB) 88 87 89 91 87 86 85 81 Return LW (dB) 77 76 73 67 69 69 64 59 *Sound data is generated by a propriety acoustics model validated through unit testing in accordance with AHRI 260, utilizing tested fan sound data in accordance with AMCA 300.
Electrical Data Power Point 1
VAC/Ph/Hz FLA
MCA
MOP
Qty Power VAC Phase RPM FLA RLA Compressor 1 2 208 3 3500 26.8 Condenser Fan 2 0.75 hp 208 3 1080 3.4 Supply Fan 1 7.5 hp 208 3 1170 24.2 Combustion 1 0.1 hp 208 1 3200 0.4
208 / 3 / 60 85
SCCR 10 KAIC
The minimum floor area is based on the Lower Flammability Limit (LFL) and calculated in accordance with UL60335-2-40 4th ed. (operating or storage). For UL60335-2-40 3rd ed. double the airflow and minimum floor area listed.
The minimum airflow (Qmin) is the minimum allowable airflow for any operating condition.
Notices
Type / Efficiency Rating Cartridge / MERV 8 Size (Qty) 25x20x2 in (6)
Mixed Air (Main) Filters
Unit Rating ECat v365.0 2425 S Yukon Ave • Tulsa, OK 74107 • 918-583-2266 • www.aaon.com
Last Modified By Chris Hess Date Created/Modified 5/18/2026 10:20 AM Date Printed 5/18/2026 10:27:13 AM
Charge of Largest Circuit
[oz]
Minimum Circulation
Airflow (Q min )†*
[CFM]
Minimum Room Area, ft²
6 ft Ceiling/Release
Height
7.2 ft Ceiling/Release
Height
10 ft Ceiling/Release
Height
12 ft Ceiling/Release
Height
Minimum Circulation Airflow and Room Area RN Series C-box (Horizontal Configuration)
133 225* 152 125 91 74 149 252* 171 140 102 83 165 279* 189 155 113 92 181 306* 207 170 124 101 197 333* 226 185 135 110 213 360* 244 200 146 119 229 387* 262 215 157 128 245 414* 281 230 168 137 261 441* 299 245 179 145 277 468* 317 260 190 154 293 496* 336 275 201 163 309 523* 354 290 212 172 325 550* 372 305 223 181
† The minimum circulation airflow (Qmin) is the minimum airflow required to dilute refrigerant in the event of a leak
* Minimum heating airflow is 820 CFM to maintain the required air velocity of 1 m/s across heating element(s)
Douglas Ruggiano, P.E., P.A.
10059 SW 156th Avenue
Miami, FL. 33196 786-210-0881
Reference: Equipment Roof Live Load Rating Certification Statement Rooftop Mounted Mechanical Equipment
AAON A/C Unitary Large Package Unit (11 to 30 Tons) Model No.: RN-C* Cabinets
Based on the manufacturers cut sheets for the referenced rooftop equipment, I have performed a rational analysis to determine the equipment roof live load rating capacity for compliance with minimum requirements per UL 60335 and UL 1995.
Analysis results demonstrate that the roof component for the referenced equipment exceeds minimum said requirements with the following maximum concentrated and uniform load rating capacities and panel deflections less than 0.6”:
a. Max static concentrated force of 200 lbs applied in the vertical direction at the most unfavorable location, distributed over a 6” diameter circular area.
b. Max uniform load of 35 psf distributed over the entire roof surface.
Douglas J. Ruggiano, P.E.
Florida License No. 51497
This item has been electronically signed and sealed by Douglas J. Ruggiano, PE on the signature date using a SHA authentication code.
Printed copies of this document are not considered signed and sealed and the SHA authentication code must be verified on any electronic copies.
Job Information Job Name WV ANG Coonskin Drill Hall -
Scenario 1
Unit Tag RTU_1
Last Modified Date 5/18/2026
Elevation 0 ft
Operating Conditions Application Supply
Total Airflow 7000 CFM
Fan Airflow 1 @ 7000 CFM Ea.
Static Pressure 3.17 in. w.g.
Fan Performance
RPM 1279
BHP 6.60 BHP
Fan Energy Index (FEI) 0.98
Efficiency 53.0%
Max Duct SP with Blocked Airway 3.52 in. w.g.
Motor Selection Rated HP / Bypass 7.5 hp / No
Frame Size 254T
Nominal RPM 1170
VAC/Ph/Hz 208 / 3 / 60
Enclosure Type ODP
Wheel Specification Model / Quantity 270 / 1
Type Backward-curved plenum
Blade Quantity 14
Diameter 27.4 in
Max RPM 1800
Inertia 16 WR²
Fan Sound Power (Inlet/Outlet) Octave Band (Re 10^-12 watts)
1 2 3 4 5 6 7 8 86 84 83 81 80 83 82 81 88 87 89 91 88 88 87 83
SOUND POWER A-Weighted: 94 dB
— Static Pressure — Efficiency — Power -- Stall — System
27.4" STAR Plenum ECat v365.0 2425 S Yukon Ave • Tulsa, OK 74107 • 918-583-2266 • www.aaon.com
Last Modified By Chris Hess Date Created/Modified 5/18/2026 10:20 AM Date Printed 5/18/2026 10:27:13 AM
R N A - 0 1 8 - C - A - 8 -
A1
F
A2
A
A3
A
A4
A5
4 -
B1
D
B2
B
B3
B4
D
B5
0 :
1 -
3A
3B
A
3C
G
3D
3E
J -
4A
E
4B
4C
0 -
5A
5B
5C
5D
5E
0 -
6A
6B
6C
6D
6E
0 -
E
A -
9A
9B
9C
9D
A -
A
B
0 -
A
B
0 -
A -
A
A
B
R
C
0 -
E
B -
A
N
B
C
D
0 -
A
B
0 -
A
B
C
0 -
A
A
0 -
E
B -
B
RTU Tag RTU_1 WV ANG Coonskin Drill Hall - Scenario 1Job Name 1Job Number
Customer Name Date 5/18/2026
Feature Option Description 0 F1 Unit Orientation Standard Access - Hinged Access Doors with Lockable Handles
1 F2 Supply & Return Locations Horizontal Configuration - End Supply--End Return
0 F3A Supply Fan Quantity 1 Fan
A F3B Supply Fan Configuration 1 Fan per VFD + Full Width Fan
G F3C Supply Fan Size 27" Direct Drive Backward Curved Aluminum
0 F3D Supply Fan Motor Type High Efficiency Open Motor (1,200 nominal rpm)
J F3E Supply Fan Motor Size 7.5 hp
E F4A Outside Air Section Economizer
0 F4B Energy Recovery Type No Energy Recovery
0 F4C Energy Recovery Size No Energy Recovery
0 F5A Return Fan Quantity 0 Return Fans
0 F5B Return Fan Configuration No Return Fan
0 F5C Return Fan Size No Return Fan
0 F5D Return Fan Motor Type No Return Fan
0 F5E Return Fan Motor Size No Return Fan
0 F6A Exhaust Fan Quantity 0 Exhaust Fans
0 F6B Exhaust Fan Configuration No Exhaust Fan
Base Option Description RN Generation RN Series
A Major Revision Major Revision A
018 Unit Size Eighteen
C Series C Series
A Minor Revision Minor Revision A
8 Voltage 208V/3φ/60Hz
F Compressor Style R-454B Two-Step Scroll Compressor
A Condenser Style Microchannel Air-Cooled Condenser
A Indoor Coil Configuration Standard Evaporator
0 Cooling Heat Exchanger Construction Standard
4 Cooling Staging 4 Stage
D Heat Type Natural Gas
B Heat Construction Stainless Steel Heat Exchanger, Gas Piping to the Valve
1 Heat Designation 270 MBH
D Heat Staging 4 Stage
0 Heat Pump Auxiliary Heating No Auxiliary Heat
Unit Submittal ECat v365.0 • Pricing v365 2425 S Yukon Ave • Tulsa, OK 74107 • 918-583-2266 • www.aaon.com
Last Modified By Chris Hess Date Created/Modified 5/18/2026 10:20 AM Date Printed 5/18/2026 10:27:13 AM
Feature Option Description 0 F6C Exhaust Fan Size No Exhaust Fan
0 F6D Exhaust Fan Motor Type No Exhaust Fan
0 F6E Exhaust Fan Motor Size No Exhaust Fan
E F7 Outside Air Control DDC Actuator
A F8 Return and Exhaust Air Options Standard Return Opening without EA Opening
0 F9A Unit Filter Type 2" Pleated - MERV 8
0 F9B Unit Filter Size & Location Standard Filters in Standard Position
0 F9C Final Filter Type No Final Filters
A F9D Filter Options Clogged Filter Switch - Unit Filters
0 F10A Refrigeration Control A Standard - Fixed 55°F Comp. Cooling Lock Out
0 F10B Refrigeration Control B Standard
0 F11A Refrigeration Options A None
0 F11B Refrigeration Options B Standard Packaged Unit
A F12 Refrigeration Accessories Sight Glass
A F13A Unit Disconnect Type Single Point Power - Non-fused Disconnect Power Switch
R F13B Disconnect 1 Size 150 Amps
0 F13C Disconnect 2 Size Standard - None
E F14 Safety Options Remote Safety Shutdown Terminals
B F15 Electrical Accessories Phase & Brown Out Protection
N F16A Control Sequence Field Installed DDC Controls + Isolation Relays
0 F16B Control Supplier None
0 F16C Control Supplier Options None
0 F16D BMS Connection & Diagnostics None
0 F17A Preheat Configuration Standard - None
0 F17B Preheat Sizing Standard - None
0 F18A Option Box Location None
0 F18B Option Box Size None
0 F18C Option Box Accessories None
A F19 Outside Air Accessories Outside Air Hood
0 F20 Cabinet Options Standard - None
0 F21 Accessories Standard
A F22 Maintenance Accessories Factory Wired 115V Convenience Outlet
0 F23 Code Options Standard - ETL U.S.A. Listing
0 F24 Shipping Splits Standard
E F25 Air-Cooled Condenser Accessories VFD Condenser Fan Head Pressure Control
0 F26 Evap-Cooled Condenser Accessories Standard
0 F27 Water-Cooled Condenser Accessories None
0 F28 Energy Recovery Accessories None
0 F29 VFD Options Standard
B F30 Miscellaneous Options SCCR (10kA)
0 F31 Exterior Cabinet Options Standard
0 F32 Blank Standard
0 F33 Blank Standard
Unit Submittal ECat v365.0 • Pricing v365 2425 S Yukon Ave • Tulsa, OK 74107 • 918-583-2266 • www.aaon.com
Last Modified By Chris Hess
Feature Option Description 0 F34 Blank Standard
0 F35 Warranty Standard Warranty
0 F36 Cabinet Material Galvanized Cabinet - Double Wall + R-16 Foam Insulation
B F37 Specials & Paint Premium AAON Gray Paint Exterior Paint
Unit Submittal ECat v365.0 • Pricing v365 2425 S Yukon Ave • Tulsa, OK 74107 • 918-583-2266 • www.aaon.com
Last Modified By Chris Hess
R N A - 0 1 8 - C - A - 8 -
A1
F
A2
A
A3
A
A4
A5
4 -
B1
D
B2
B
B3
B4
D
B5
0 :
1 -
3A
3B
A
3C
G
3D
3E
J -
4A
E
4B
4C
0 -
5A
5B
5C
5D
5E
0 -
6A
6B
6C
6D
6E
0 -
E
A -
9A
9B
9C
9D
A -
A
B
0 -
A
B
0 -
A -
A
A
B
R
C
0 -
E
B -
A
N
B
C
D
0 -
A
B
0 -
A
B
C
0 -
A
A
0 -
E
B -
B
RTU Tag RTU_1 WV ANG Coonskin Drill Hall - Scenario 1Job Name 1Job Number
Customer Name Date 5/18/2026
Terminals Available/Required for Controlling the Unit Terminal(s) Description
[R] 24VAC Control Voltage
[C] Common
[G] Supply Fan Enable + Isolation Relay
[Y1] Cooling Stage 1 Enable + Isolation Relay
[Y2] Cooling Stage 2 Enable + Isolation Relay
[Y3] Cooling Stage 3 Enable + Isolation Relay
[Y4] Cooling Stage 4 Enable + Isolation Relay
[W1] Heating Stage 1 Enable + Isolation Relay
[W2] Heating Stage 2 Enable + Isolation Relay
[W3] Heating Stage 3 Enable + Isolation Relay
[W4] Heating Stage 4 Enable + Isolation Relay
[Q1] & [Q2] Gas Heat Alarm
Dry contact terminals for alarm output (NC)
[S1-] & [S2+] Supply Fan 1 - w/ 1 VFD: Signal (0-10VDC)
VFD frequency reference signal control point must handle a rated 20k ohm input impedance.
[EC1-] & [EC2+] Economizer Signal (0-10VDC)
[C1] & [C2] Clogged Filter Switch (Standard Filters)
[BI1] & [BI2] Remote Safety Shutdown
[PBO1] & [PBO2] Phase & Brown Out
Terminations Found on VFD(s) [AM] & [AC] Current Feedback (0-10VDC = 0-100%)
Supply Fan VFD(s)
[MA] & [MC] Fault
A2L Terminals
[ALM1] & [ALM2] A2L Airstream Alarm & Cabinet Alarm
A2L Mitigation Board 1
P/N: ASM0763
A2L Mitigation Board 2
P/N: ASM0763
Control Terminals ECat v365.0 • Pricing v365 2425 S Yukon Ave • Tulsa, OK 74107 • 918-583-2266 • www.aaon.com
Last Modified By Chris Hess
SA BLOWER COIL
FILTERS
UNITS WITH
HEAT VEST
C O
IL
FI
LT
ER
CONTROLS
VEST
RA
IN
H O
O D
OUTSIDE
AIR
ECONOMIZER
INSIDE
BASE RAILS
INSIDE
BASE RAILS
(4) LIFTING LUGS
SUPPLY
AIR
RETURN
AIR
POWER SWITCH
ACCESS COVER
DETAIL A
CLEARANCES
LOCATION
OUTSIDE AIR 20*(BACK)
SUPPLY AIR
(FRONT)
LEFT SIDE
RIGHT SIDE
TOP UNOBSTRUCTED
*CLEARANCE IS MEASURED FROM
THE END OF THE OUTSIDE AIR
RAIN HOOD
SUPPLY
AIR
36 123
ALL TOP VIEW DIMENSIONS ARE FROM OUTSIDE BASE RAILS
HXC
ACCESS
(SEE DETAIL
FOR GAS HEAT)
4 52
RETURN
AIR
FRONT VIEW
RIGHT SIDE VIEW
BACK VIEW
TOP VIEW
CONDENSER
SECTION
NOT SHOWN
ø25 ø13 ø25
LOW VOLT
ENTRY
HIGH VOLT
ENTRY
DETAIL A
RN SERIES
C- CABINET HORIZONTAL AIR COOLED
ECONOMIZER
RNC-H0005 REV:C 03/08/23 JWC
ALL DIMENSIONS ARE IN INCHES
TOLERANCE IS +/- 14
CONDENSER FAN CONFIGURATION
11 - 20 TON - 2 FANS
25 & 30 TON - 3 FANS
NOTE: NO RELIEF DAMPER
INSTALLED ON UNIT
1" MPT STAINLESS STEEL CONDENSATE
CONNECTION.
FLUE OUTLETS X(2)
(GAS HEAT ONLY)
COMBUSTION AIR INLETS
(GAS HEAT ONLY)
HXC ACCESS
DETAIL
GAS
ø11
ENTRY
FIELD GAS PIPING DETAILS
RNA SERIES C - CABINET
11-30 TON
270 MBH
4 STAGE, HIGH TURNDOWN
Field gas piping is required to the internal gas valves.
Piping should be installed adhering to building codes.
Perform leak check prior to operation.
Reference IOM for additonal information, and details on optional gas entry through base.
HEAT
EXCHANGER 1
CAT000438 RNC REV A 05/03/23 JAS
ALL DIMENSIONS ARE IN INCHES
HXC 1
FRONTSIDE
32 3/16
33 3/4
3 3/8
8 1/16
4 1/16
4 3/16
AAON
RNA-018-C-A-8-FAA04-DB1D0:01-0AG0J-E00-00000-00000-EA-000A-00-00-A-AR0-EB-N000-00-000-A00A00-E0000B-000000B
RNC HORIZONTAL CABINET
AIR COOLED CONDENSING UNIT
Front Right Corner:
817 lbs
Back Left Corner:
779 lbs
Back Right Corner:
645 lbs
CGx: 60.9" CGy: 35.0"
Total Weight:
3229 lbs
+X
+Y
Disclaimer:
This weight estimate does not account for any SPAs.
Front Left Corner:
988 lbs
0"
0"
138"
64"