Exhibit D-JFHQ CoonskinArmory Drill Hall RTU-Specifications.pdf

PDF 2 MB Posted

Attached to
JFHQ Coonskin Armory Drill Hall RTU Replacement
Solicitation number
CRFQ 0603 ADJ2600000023 5
Issued by
Kanawha County, West Virginia

About this file

This is a technical specification document for a rooftop-mounted HVAC unit for the West Virginia Air National Guard (WV ANG) Coonskin Armory Drill Hall RTU replacement project. The specification details an AAON model RN-018-C-A-8 rooftop unit designed to provide cooling and heating for the drill hall facility. The unit is configured as an 18-ton air-cooled packaged system with a cooling capacity of 206 megabytes per hour (MBH) and natural gas heating capacity of 270 MBH with four-stage staging for both cooling and heating. The RTU features a single 7.5-horsepower supply fan delivering 7,000 cubic feet per minute (CFM) of airflow, an evaporator coil with standard 4-row configuration, R-454B refrigerant charge of 229 ounces, and MERV 8 filters in a 25x20x2-inch cartridge format with six units. The unit is equipped with an economizer for outside air control, DDC (direct digital controls) with isolation relays, a clogged filter switch, and remote safety shutdown capabilities.

The RTU specifications include detailed performance ratings indicating cooling efficiency rating (EER) of 12.05 BTU/hW at AHRI standard conditions and application EER of 9.2 BTU/hW, with a total system static pressure of 3.17 inches water gauge and maximum duct static pressure of 3.52 inches when airway is blocked. The unit is specified for 208 volts, 3-phase, 60-hertz power with total full-load amperage of 85 amps and minimum circuit amperage of 91 amps. The cabinet is galvanized double-wall construction with R-16 foam insulation and premium AAON gray paint finish. The unit measures 138 inches wide by 64 inches long by 60 inches high with an approximate operating weight of 3,229 pounds. The document includes comprehensive acoustic data, electrical specifications, control terminal descriptions, dimensional drawings showing clearance requirements and gas heat exchanger access details, and roof live load rating certification indicating the unit can support maximum concentrated loads of 200 pounds and uniform loads of 35 pounds per square foot.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Job Name WV ANG Coonskin Drill Hall - Scenario 1 Job Number 1 Elevation 0 ft Refrigerant R-454B Design System Charge (oz) 229 / 229

Job Information Unit Information Approx. Weight (Op./Ship) 3229 / 3229 lbs (±5%) Base Dimensions (WxLxH) 138.0 x 64.0 x 60.0 in Coil Filter FV / Qty 336.0 fpm / 6 Min. Room Area/Height/Airflow** 215 ft² / 7 ft / 388 SCFM Ambient Temperature 95.0 / 75.0 °F DB/WB Supply Airflow / ESP 7000 SCFM / 1.75 in. w.g.

Return Airflow / ESP 7000 SCFM / 0.25 in. w.g.

Return Temperature 75.0 / 62.0 °F DB/WB Outside Airflow 1400 SCFM

Static Pressure External 1.75 in. w.g.

Cooling Coil 0.30 in. w.g.

Filters (Clean) 0.13 in. w.g.

Dirt Allowance 0.35 in. w.g.

Economizer 0.18 in. w.g.

Heater 0.24 in. w.g.

Cabinet 0.22 in. w.g.

Total 3.17 in. w.g.

Rating Information Listing Model RN-018-3-0-FAAY-S0-21-000-A Cooling Capacity 206.0 MBH Cooling EER 12.05 BTU/h·W Cooling IEER 18.42 BTU/h·W *Rated in accordance with AHRI Standard 340/360 (I-P)

Application EER @ Op. Conditions 9.2 BTU/h·W

Gross Net

Mixed Air Temp 79.0 / 64.9 °F DB/WB Ent Air Temp 79.0 / 64.9 °F DB/WB Lvg Air Temp (Coil) 55.5 / 54.7 °F DB/WB Lvg Air Temp (Unit) 57.8 / 55.7 °F DB/WB

Supply Air Fan 1 x 270 @ 6.60 BHP Ea.

SA Fan RPM / Width 1279 RPM / 6.13 in SA Fan FEI 0.98

Evaporator Coil 19.9 ft² / 4 Rows / 14 FPI Evaporator Face Velocity 352.4 fpm

Cooling Section

Total Capacity 208.5 MBH 189.9 MBH Sensible Capacity 176.7 MBH 158.1 MBH Latent Capacity 31.8 MBH

Heating Section Preheat Type Std (No Preheat) Auxiliary Heating Type Nat. Gas Heat Heating Airflow 7000 SCFM Total Capacity 218.7 MBH Entering Air Temp 54.4 / 44.2 °F DB/WB Leaving Air Temp 83.1 / 56.8 °F DB/WB Consumption 270.0 MBH Total Turndown Ratio 2.8:1

R N A - 0 1 8 - C - A - 8 -

A1

F

A2

A

A3

A

A4

A5

4 -

B1

D

B2

B

B3

B4

D

B5

0 :

1 -

3A

3B

A

3C

G

3D

3E

J -

4A

E

4B

4C

0 -

5A

5B

5C

5D

5E

0 -

6A

6B

6C

6D

6E

0 -

E

A -

9A

9B

9C

9D

A -

A

B

0 -

A

B

0 -

A -

A

A

B

R

C

0 -

E

B -

A

N

B

C

D

0 -

A

B

0 -

A

B

C

0 -

A

A

0 -

E

B -

B

RTU_1RTU Tag

Unit Rating ECat v365.0 2425 S Yukon Ave • Tulsa, OK 74107 • 918-583-2266 • www.aaon.com

Last Modified By Chris Hess Date Created/Modified 5/18/2026 10:20 AM Date Printed 5/18/2026 10:27:13 AM

PerformanceValues Version 365.0 https://www.aaon.com/

Cabinet Sound Power Levels* Octave Bands 63 125 250 500 1000 2000 4000 8000 Discharge LW (dB) 88 87 89 91 87 86 85 81 Return LW (dB) 77 76 73 67 69 69 64 59 *Sound data is generated by a propriety acoustics model validated through unit testing in accordance with AHRI 260, utilizing tested fan sound data in accordance with AMCA 300.

Electrical Data Power Point 1

VAC/Ph/Hz FLA

MCA

MOP

Qty Power VAC Phase RPM FLA RLA Compressor 1 2 208 3 3500 26.8 Condenser Fan 2 0.75 hp 208 3 1080 3.4 Supply Fan 1 7.5 hp 208 3 1170 24.2 Combustion 1 0.1 hp 208 1 3200 0.4

208 / 3 / 60 85

SCCR 10 KAIC

The minimum floor area is based on the Lower Flammability Limit (LFL) and calculated in accordance with UL60335-2-40 4th ed. (operating or storage). For UL60335-2-40 3rd ed. double the airflow and minimum floor area listed.

The minimum airflow (Qmin) is the minimum allowable airflow for any operating condition.

Notices

Type / Efficiency Rating Cartridge / MERV 8 Size (Qty) 25x20x2 in (6)

Mixed Air (Main) Filters

Unit Rating ECat v365.0 2425 S Yukon Ave • Tulsa, OK 74107 • 918-583-2266 • www.aaon.com

Last Modified By Chris Hess Date Created/Modified 5/18/2026 10:20 AM Date Printed 5/18/2026 10:27:13 AM

Charge of Largest Circuit

[oz]

Minimum Circulation

Airflow (Q min )†*

[CFM]

Minimum Room Area, ft²

6 ft Ceiling/Release

Height

7.2 ft Ceiling/Release

Height

10 ft Ceiling/Release

Height

12 ft Ceiling/Release

Height

Minimum Circulation Airflow and Room Area RN Series C-box (Horizontal Configuration)

133 225* 152 125 91 74 149 252* 171 140 102 83 165 279* 189 155 113 92 181 306* 207 170 124 101 197 333* 226 185 135 110 213 360* 244 200 146 119 229 387* 262 215 157 128 245 414* 281 230 168 137 261 441* 299 245 179 145 277 468* 317 260 190 154 293 496* 336 275 201 163 309 523* 354 290 212 172 325 550* 372 305 223 181

† The minimum circulation airflow (Qmin) is the minimum airflow required to dilute refrigerant in the event of a leak

* Minimum heating airflow is 820 CFM to maintain the required air velocity of 1 m/s across heating element(s)

Douglas Ruggiano, P.E., P.A.

10059 SW 156th Avenue

Miami, FL. 33196 786-210-0881

Reference: Equipment Roof Live Load Rating Certification Statement Rooftop Mounted Mechanical Equipment

AAON A/C Unitary Large Package Unit (11 to 30 Tons) Model No.: RN-C* Cabinets

Based on the manufacturers cut sheets for the referenced rooftop equipment, I have performed a rational analysis to determine the equipment roof live load rating capacity for compliance with minimum requirements per UL 60335 and UL 1995.

Analysis results demonstrate that the roof component for the referenced equipment exceeds minimum said requirements with the following maximum concentrated and uniform load rating capacities and panel deflections less than 0.6”:

a. Max static concentrated force of 200 lbs applied in the vertical direction at the most unfavorable location, distributed over a 6” diameter circular area.

b. Max uniform load of 35 psf distributed over the entire roof surface.

Douglas J. Ruggiano, P.E.

Florida License No. 51497

This item has been electronically signed and sealed by Douglas J. Ruggiano, PE on the signature date using a SHA authentication code.

Printed copies of this document are not considered signed and sealed and the SHA authentication code must be verified on any electronic copies.

Job Information Job Name WV ANG Coonskin Drill Hall -

Scenario 1

Unit Tag RTU_1

Last Modified Date 5/18/2026

Elevation 0 ft

Operating Conditions Application Supply

Total Airflow 7000 CFM

Fan Airflow 1 @ 7000 CFM Ea.

Static Pressure 3.17 in. w.g.

Fan Performance

RPM 1279

BHP 6.60 BHP

Fan Energy Index (FEI) 0.98

Efficiency 53.0%

Max Duct SP with Blocked Airway 3.52 in. w.g.

Motor Selection Rated HP / Bypass 7.5 hp / No

Frame Size 254T

Nominal RPM 1170

VAC/Ph/Hz 208 / 3 / 60

Enclosure Type ODP

Wheel Specification Model / Quantity 270 / 1

Type Backward-curved plenum

Blade Quantity 14

Diameter 27.4 in

Max RPM 1800

Inertia 16 WR²

Fan Sound Power (Inlet/Outlet) Octave Band (Re 10^-12 watts)

1 2 3 4 5 6 7 8 86 84 83 81 80 83 82 81 88 87 89 91 88 88 87 83

SOUND POWER A-Weighted: 94 dB

— Static Pressure — Efficiency — Power -- Stall — System

27.4" STAR Plenum ECat v365.0 2425 S Yukon Ave • Tulsa, OK 74107 • 918-583-2266 • www.aaon.com

Last Modified By Chris Hess Date Created/Modified 5/18/2026 10:20 AM Date Printed 5/18/2026 10:27:13 AM

R N A - 0 1 8 - C - A - 8 -

A1

F

A2

A

A3

A

A4

A5

4 -

B1

D

B2

B

B3

B4

D

B5

0 :

1 -

3A

3B

A

3C

G

3D

3E

J -

4A

E

4B

4C

0 -

5A

5B

5C

5D

5E

0 -

6A

6B

6C

6D

6E

0 -

E

A -

9A

9B

9C

9D

A -

A

B

0 -

A

B

0 -

A -

A

A

B

R

C

0 -

E

B -

A

N

B

C

D

0 -

A

B

0 -

A

B

C

0 -

A

A

0 -

E

B -

B

RTU Tag RTU_1 WV ANG Coonskin Drill Hall - Scenario 1Job Name 1Job Number

Customer Name Date 5/18/2026

Feature Option Description 0 F1 Unit Orientation Standard Access - Hinged Access Doors with Lockable Handles

1 F2 Supply & Return Locations Horizontal Configuration - End Supply--End Return

0 F3A Supply Fan Quantity 1 Fan

A F3B Supply Fan Configuration 1 Fan per VFD + Full Width Fan

G F3C Supply Fan Size 27" Direct Drive Backward Curved Aluminum

0 F3D Supply Fan Motor Type High Efficiency Open Motor (1,200 nominal rpm)

J F3E Supply Fan Motor Size 7.5 hp

E F4A Outside Air Section Economizer

0 F4B Energy Recovery Type No Energy Recovery

0 F4C Energy Recovery Size No Energy Recovery

0 F5A Return Fan Quantity 0 Return Fans

0 F5B Return Fan Configuration No Return Fan

0 F5C Return Fan Size No Return Fan

0 F5D Return Fan Motor Type No Return Fan

0 F5E Return Fan Motor Size No Return Fan

0 F6A Exhaust Fan Quantity 0 Exhaust Fans

0 F6B Exhaust Fan Configuration No Exhaust Fan

Base Option Description RN Generation RN Series

A Major Revision Major Revision A

018 Unit Size Eighteen

C Series C Series

A Minor Revision Minor Revision A

8 Voltage 208V/3φ/60Hz

F Compressor Style R-454B Two-Step Scroll Compressor

A Condenser Style Microchannel Air-Cooled Condenser

A Indoor Coil Configuration Standard Evaporator

0 Cooling Heat Exchanger Construction Standard

4 Cooling Staging 4 Stage

D Heat Type Natural Gas

B Heat Construction Stainless Steel Heat Exchanger, Gas Piping to the Valve

1 Heat Designation 270 MBH

D Heat Staging 4 Stage

0 Heat Pump Auxiliary Heating No Auxiliary Heat

Unit Submittal ECat v365.0 • Pricing v365 2425 S Yukon Ave • Tulsa, OK 74107 • 918-583-2266 • www.aaon.com

Last Modified By Chris Hess Date Created/Modified 5/18/2026 10:20 AM Date Printed 5/18/2026 10:27:13 AM

Feature Option Description 0 F6C Exhaust Fan Size No Exhaust Fan

0 F6D Exhaust Fan Motor Type No Exhaust Fan

0 F6E Exhaust Fan Motor Size No Exhaust Fan

E F7 Outside Air Control DDC Actuator

A F8 Return and Exhaust Air Options Standard Return Opening without EA Opening

0 F9A Unit Filter Type 2" Pleated - MERV 8

0 F9B Unit Filter Size & Location Standard Filters in Standard Position

0 F9C Final Filter Type No Final Filters

A F9D Filter Options Clogged Filter Switch - Unit Filters

0 F10A Refrigeration Control A Standard - Fixed 55°F Comp. Cooling Lock Out

0 F10B Refrigeration Control B Standard

0 F11A Refrigeration Options A None

0 F11B Refrigeration Options B Standard Packaged Unit

A F12 Refrigeration Accessories Sight Glass

A F13A Unit Disconnect Type Single Point Power - Non-fused Disconnect Power Switch

R F13B Disconnect 1 Size 150 Amps

0 F13C Disconnect 2 Size Standard - None

E F14 Safety Options Remote Safety Shutdown Terminals

B F15 Electrical Accessories Phase & Brown Out Protection

N F16A Control Sequence Field Installed DDC Controls + Isolation Relays

0 F16B Control Supplier None

0 F16C Control Supplier Options None

0 F16D BMS Connection & Diagnostics None

0 F17A Preheat Configuration Standard - None

0 F17B Preheat Sizing Standard - None

0 F18A Option Box Location None

0 F18B Option Box Size None

0 F18C Option Box Accessories None

A F19 Outside Air Accessories Outside Air Hood

0 F20 Cabinet Options Standard - None

0 F21 Accessories Standard

A F22 Maintenance Accessories Factory Wired 115V Convenience Outlet

0 F23 Code Options Standard - ETL U.S.A. Listing

0 F24 Shipping Splits Standard

E F25 Air-Cooled Condenser Accessories VFD Condenser Fan Head Pressure Control

0 F26 Evap-Cooled Condenser Accessories Standard

0 F27 Water-Cooled Condenser Accessories None

0 F28 Energy Recovery Accessories None

0 F29 VFD Options Standard

B F30 Miscellaneous Options SCCR (10kA)

0 F31 Exterior Cabinet Options Standard

0 F32 Blank Standard

0 F33 Blank Standard

Unit Submittal ECat v365.0 • Pricing v365 2425 S Yukon Ave • Tulsa, OK 74107 • 918-583-2266 • www.aaon.com

Last Modified By Chris Hess

Feature Option Description 0 F34 Blank Standard

0 F35 Warranty Standard Warranty

0 F36 Cabinet Material Galvanized Cabinet - Double Wall + R-16 Foam Insulation

B F37 Specials & Paint Premium AAON Gray Paint Exterior Paint

Unit Submittal ECat v365.0 • Pricing v365 2425 S Yukon Ave • Tulsa, OK 74107 • 918-583-2266 • www.aaon.com

Last Modified By Chris Hess

R N A - 0 1 8 - C - A - 8 -

A1

F

A2

A

A3

A

A4

A5

4 -

B1

D

B2

B

B3

B4

D

B5

0 :

1 -

3A

3B

A

3C

G

3D

3E

J -

4A

E

4B

4C

0 -

5A

5B

5C

5D

5E

0 -

6A

6B

6C

6D

6E

0 -

E

A -

9A

9B

9C

9D

A -

A

B

0 -

A

B

0 -

A -

A

A

B

R

C

0 -

E

B -

A

N

B

C

D

0 -

A

B

0 -

A

B

C

0 -

A

A

0 -

E

B -

B

RTU Tag RTU_1 WV ANG Coonskin Drill Hall - Scenario 1Job Name 1Job Number

Customer Name Date 5/18/2026

Terminals Available/Required for Controlling the Unit Terminal(s) Description

[R] 24VAC Control Voltage

[C] Common

[G] Supply Fan Enable + Isolation Relay

[Y1] Cooling Stage 1 Enable + Isolation Relay

[Y2] Cooling Stage 2 Enable + Isolation Relay

[Y3] Cooling Stage 3 Enable + Isolation Relay

[Y4] Cooling Stage 4 Enable + Isolation Relay

[W1] Heating Stage 1 Enable + Isolation Relay

[W2] Heating Stage 2 Enable + Isolation Relay

[W3] Heating Stage 3 Enable + Isolation Relay

[W4] Heating Stage 4 Enable + Isolation Relay

[Q1] & [Q2] Gas Heat Alarm

Dry contact terminals for alarm output (NC)

[S1-] & [S2+] Supply Fan 1 - w/ 1 VFD: Signal (0-10VDC)

VFD frequency reference signal control point must handle a rated 20k ohm input impedance.

[EC1-] & [EC2+] Economizer Signal (0-10VDC)

[C1] & [C2] Clogged Filter Switch (Standard Filters)

[BI1] & [BI2] Remote Safety Shutdown

[PBO1] & [PBO2] Phase & Brown Out

Terminations Found on VFD(s) [AM] & [AC] Current Feedback (0-10VDC = 0-100%)

Supply Fan VFD(s)

[MA] & [MC] Fault

A2L Terminals

[ALM1] & [ALM2] A2L Airstream Alarm & Cabinet Alarm

A2L Mitigation Board 1

P/N: ASM0763

A2L Mitigation Board 2

P/N: ASM0763

Control Terminals ECat v365.0 • Pricing v365 2425 S Yukon Ave • Tulsa, OK 74107 • 918-583-2266 • www.aaon.com

Last Modified By Chris Hess

SA BLOWER COIL

FILTERS

UNITS WITH

HEAT VEST

C O

IL

FI

LT

ER

CONTROLS

VEST

RA

IN

H O

O D

OUTSIDE

AIR

ECONOMIZER

INSIDE

BASE RAILS

INSIDE

BASE RAILS

(4) LIFTING LUGS

SUPPLY

AIR

RETURN

AIR

POWER SWITCH

ACCESS COVER

DETAIL A

CLEARANCES

LOCATION

OUTSIDE AIR 20*(BACK)

SUPPLY AIR

(FRONT)

LEFT SIDE

RIGHT SIDE

TOP UNOBSTRUCTED

*CLEARANCE IS MEASURED FROM

THE END OF THE OUTSIDE AIR

RAIN HOOD

SUPPLY

AIR

36 123

ALL TOP VIEW DIMENSIONS ARE FROM OUTSIDE BASE RAILS

HXC

ACCESS

(SEE DETAIL

FOR GAS HEAT)

4 52

RETURN

AIR

FRONT VIEW

RIGHT SIDE VIEW

BACK VIEW

TOP VIEW

CONDENSER

SECTION

NOT SHOWN

ø25 ø13 ø25

LOW VOLT

ENTRY

HIGH VOLT

ENTRY

DETAIL A

RN SERIES

C- CABINET HORIZONTAL AIR COOLED

ECONOMIZER

RNC-H0005 REV:C 03/08/23 JWC

ALL DIMENSIONS ARE IN INCHES

TOLERANCE IS +/- 14

CONDENSER FAN CONFIGURATION

11 - 20 TON - 2 FANS

25 & 30 TON - 3 FANS

NOTE: NO RELIEF DAMPER

INSTALLED ON UNIT

1" MPT STAINLESS STEEL CONDENSATE

CONNECTION.

FLUE OUTLETS X(2)

(GAS HEAT ONLY)

COMBUSTION AIR INLETS

(GAS HEAT ONLY)

HXC ACCESS

DETAIL

GAS

ø11

ENTRY

FIELD GAS PIPING DETAILS

RNA SERIES C - CABINET

11-30 TON

270 MBH

4 STAGE, HIGH TURNDOWN

Field gas piping is required to the internal gas valves.

Piping should be installed adhering to building codes.

Perform leak check prior to operation.

Reference IOM for additonal information, and details on optional gas entry through base.

HEAT

EXCHANGER 1

CAT000438 RNC REV A 05/03/23 JAS

ALL DIMENSIONS ARE IN INCHES

HXC 1

FRONTSIDE

32 3/16

33 3/4

3 3/8

8 1/16

4 1/16

4 3/16

AAON

RNA-018-C-A-8-FAA04-DB1D0:01-0AG0J-E00-00000-00000-EA-000A-00-00-A-AR0-EB-N000-00-000-A00A00-E0000B-000000B

RNC HORIZONTAL CABINET

AIR COOLED CONDENSING UNIT

Front Right Corner:

817 lbs

Back Left Corner:

779 lbs

Back Right Corner:

645 lbs

CGx: 60.9" CGy: 35.0"

Total Weight:

3229 lbs

+X

+Y

Disclaimer:

This weight estimate does not account for any SPAs.

Front Left Corner:

988 lbs

0"

0"

138"

64"