EXHIBIT_D_FKEC_Construction_Unit_Book.pdf
PDF 24 MB Posted
- Solicitation number
- FKEC BID #25-04
- Issued by
- Florida
About this file
The document is a Construction Manual for Florida Keys Electric Cooperative (FKEC), detailing comprehensive construction specifications and technical guidelines for electrical infrastructure deployment. The manual provides extensive technical documentation for single-phase, two-phase, and three-phase primary pole top assembly units, including detailed specifications for conductor installation, grounding assemblies, transformer assemblies, and secondary assembly units. The manual covers construction standards for various pole types (wood, ductile iron, and concrete), with specific technical drawings and specifications for 24.9/14.4 kV electrical systems, including guidelines for maximum line angles, insulator configurations, and installation requirements.
The manual emphasizes compliance with the National Electrical Safety Code (NESC) and provides technical specifications for materials, installation methods, and equipment selection. It includes detailed tables for maximum line angles based on conductor sizes, loading districts, and transverse loads, with specific recommendations for conductor handling, splicing, and installation. The document is designed to provide a comprehensive technical reference for electrical infrastructure construction, offering engineers and contractors precise guidelines for equipment selection, installation techniques, and safety considerations. The manual was revised on 06/16/2023 and includes provisions for notifying the FAA of new pole installations exceeding 50 feet in height.
View the file
Other files
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Revised 06/16/2023
CONSTRUCTION MANUAL
FLORIDA KEYS ELECTRIC
---COOPERATIVE
www.FKEC.com
This Page Intentionally Left Blank.
SECTION
A
B
C
E
F
G
H
J
K
INDEX
CATEGORY PE§CBIPTIONS
General Construction Specifications
Conductor Installation Specifications
SINGLE-PHASE PRIMARY POLE TOP ASSEMBLY UNITS
Index A
Construction Specifications for Pole Top Assemblies
Grounding Guide
Tables I - V: Maximum Line Angles Pin Insulators
Tables VI - VII: Maximum Line Angles Spool Insulators
Single-Phase Primary Pole Top Construction Drawings
TWO-PHASE PRIMARY POLE TOP ASSEMBLY UNITS
lndexB
Two-Phase Primary Pole Top Construction Drawings
THREE-PHASE PRIMARY POLE TOP ASSEMBLY UNITS
lndexC
Three-Phase Primary Pole Top Construction Drawings
GUYING ASSEMBLY UNITS
lndexE
Construction Specifications for Guys
Guying Construction Drawings
ANCHOR ASSEMBLY UNITS
Index F
Construction Specifications for Anchoring
Table F: Soil Classifications
Anchor Construction Drawings
TRANSFORMER ASSEMBLY UNITS
lndexG
Construction Specifications for Taps, Jumpers, and Arresters
Transformer Construction Drawings
Meter Can Wiring Drawings
GROUNDING ASSEMBLY UNITS
lndexH
Construction Specifications for Grounding
Grounding Construction Drawings
SECONDARY ASSEMBLY UNITS
lndexJ
Construction Specifications for Secondaries and Service Drops
Secondary Construction Drawings
SERVICE ASSEMBLY UNITS
lndexK
Service Construction Drawings
INDEX
SECTION CATEGORY DESCRIPTIONS
M MISCELLANEOUS ASSEMBLY UNITS AND GUIDES
lndexM
Miscellaneous Construction Drawings and Guides
S SECTIONALIZING ASSEMBLY UNITS
lndexS
Sectionalizing Construction Drawings
Y VOLTAGE ALTERATION EQUIPMENT ASSEMBLY UNITS
lndexY
Voltage Alteration Equipment Construction Drawings
APPENDICES
TABLE OF SELECTED SI TO METRIC CONVERSIONS
DERIVATION OF MAXIMUM PERMISSIBLE LINE ANGLES
(Continued)
GENERAL CONSTRUCTION SPECIFICATIONS
All construction work shall be done in a safe, thorough, and workmanlike manner in accordance with the staking sheets, plans and specifications, and the construction drawings.
The provision of 7 CFR section 1724.50 "Compliance with National Electrical Safety Code (NESC)" applies to all borrower electric system facilities regardless of the source of financing.
A borrower must ensure that its electric system, including all electric distribution, transmission, and generating facilities, is designed, constructed, operated, and maintained in accordance with all applicable provisions of the most current and accepted criteria of the National Electrical Safety Code (NESC) and all applicable and current electrical and safety requirements of any State or local governmental entity. This requirement applies to the borrower's electric system regardless of the source of financing. Copies of the NESC may be obtained from the Institute of Electrical and Electronic Engineers, Inc. at the following address:
IEEE Customer Service 445 Hoes Lane, PO Box 1331 Piscataway, NJ 088555-1331
Any electrical standard requirements established by RUS are in addition to, and not in substitution for or a modification of, the most current and accepted criteria of the NESC and any applicable electrical or safety requirements of any State or local governmental entity.
Overhead distribution circuits shall be constructed with not less than the Grade C strength requirements as described in section 26, Strength Requirements, of the NESC when subjected to the loads specified in NESC Section 25, Loadings for Grades Band C.
Overhead transmission circuits shall be constructed with not less than the Grade B strength requirements as described in NESC Section 26.
The drawings of equipment and materials used in the construction assemblies are meant to depict the general categories of items found in RUS Informational Publication 202-1, "List of Materials Acceptable for Use on Systems of RUS Electrification Borrowers," ("List of Materials"). Any drawing of any piece of equipment or material that resembles a specific product of a manufacturer is unintentional.
Materials to be used for construction are designated by one or more small alphabetic characters shown on the drawings and in the "ITEM" column in the material blocks. The borrower may use any material contained in the "List of Materials" from the category of material as designated by the corresponding small letter(s).
For example, "b" designates a steel, pole top pin. The borrower may use, at its discretion, any of the applicable pole top pins from category "b" of the "List of Materials."
Similarly, the drawings of the bulletin show the use of three, 4 1/4 inch, ANSI Class 52-9A suspension insulators for 24.9/14.4 kV primary deadends. The borrower may use three, 6 inch, ANSI Class 52-1 or two, 9 inch, ANSI Class 52-4 suspension insulators, or one polymer distribution insulator, all of which are contained in category "k" in the "List of Materials." In the latter cases, the quantity ("QTY") of the insulators to be used must be modified accordingly.
Florida Keys Electric Cooperative will notify the FAA of any new pole installations that exceed 50 feet (including insulator) above ground level.
CONDUCTOR INSTALLATION SPECIFICATIONS
Conductors must be handled with care. Conductors shall neither be trampled on nor run over by vehicles. Each reel shall be examined and the wire inspected for cuts, kinks, or other injuries. Injured portions shall be cut out and the conductor spliced. The conductors shall be pulled over suitable rollers or stringing blocks properly mounted on the pole or crossarm if necessary to prevent binding while stringing.
Conductors shall be sagged in accordance with the conductor manufacturer's recommendations. All conductors shall be sagged evenly. The air temperature at the time and place of sagging shall be determined by a certified thermometer.
The sag of all conductors after stringing shall be in accordance with the engineer's instructions.
Conductors shall be spliced and dead-ended as shown on the construction drawings. There shall be not more than one splice per conductor in any span and splices shall be located at least 10 feet from the conductor support. No splices shall be located in Grade B crossing spans and preferably not in adjacent spans.
Splices shall be installed in accordance with the manufacturer's specifications and recommendations.
All conductors shall be cleaned thoroughly by wirebrushing before splicing or installing connectors or clamps. A suitable inhibitor shall be used before splicing or applying connectors over aluminum conductor.
Connectors and hot-line clamps suitable for the purpose shall be installed as shown on the drawings and also in accordance with the manufacturer's specifications and recommendations. On all hot-line clamp installations, the clamp and jumper shall be installed so that they are permanently bonded to the load side of the line, allowing the jumper to be de-energized when the clamp is disconnected.
The use of stirrups to connect tap conductors (jumper wires) to primary conductors may be used if the following criteria are met:
• The stirrup and hot line clamp shall be sized to meet or exceed the current carrying capacity of the tap conductor or equipment jumper;
• All stirrup conductors shall be made of copper or bronze;
• All stirrup conductors shall be made of #2 copper equivalent or larger;
• All-purpose or aluminum hot line clamps shall not be used with stirrups;
• All stirrups, connectors, and clamps shall be installed in accordance with the manufacturer's specifications;
• Stirrups with two compression connectors are not to be used in areas of vibrating conductors;
• Stirrups are not to be used to connect main lines or heavily loaded tap lines.
Stirrups are not recommended to be used to connect reclosers, autotransformers, or line regulators. Stirrups and hot line clamps should not be used for sectionalizing tap and especially main lines for operational or maintenance purposes. Permanent compression or bolted type connectors should be used because of their better current carrying capabilities and reliability. Line switches, fused cutouts, or solid blade cutouts should be used at line locations where occasional line sectionalizing may be required.
At locations where permanent connections using compression or bolted type connectors are not desired, and where the installation or sectionalizing equipment is also not desired, then the standards specify the installation of hot line clamps (over armor rod on aluminum conductors).
VA1-P
INDEX A
SINGLE-PHASE PRIMARY POLE TOP ASSEMBLY UNITS
DRAWING NUMBER
VAl-P
VA2-P
VA3-P
VA4-P
VA5-P
VA5-2P
VA6-P
VA6-1P
VA7-P
VAS-P
VA9-P
VA17-P
VA33-1P
DRAWING TITLE (DESCRIPTION)
SINGLE INSULATOR 0-12
ANGLE
DOUBLE INSULATOR 12-30
ANGLE
SINGLE INSULATOR 30-60
ANGLE
SINGLE INSULATOR DDE 60-90
ANGLE
SINGLE INSULATOR DEADEND
CROSSARM MOUNTED DEADEND POLY
SAME-BOLT DOUBLE DEADEND WITH FEED-THROUGH
SAME-BOLT DOUBLE DEADEND WITH HORIZONTAL POST
INSULATOR FEED-THROUGH
CROSSARM CONSSTRUCTION SINGLE PRIMARY DEADEND
CROSSARM DOUBLE DEADEND WITH FEED-THROUGH
SINGLE INSULATOR 0-12
ANGLE
HORIZONTAL LINE POST 0-12
ANGLE
ALLEY ARM CONSTRUCTION 0-12
ANGLE
CONSTRUCTION SPECIFICATIONS FOR POLE TOP ASSEMBLIES
Line designs which use high poles to clear obstacles such as railroads, must avoid upstrain on pin-type or post-type insulators on adjacent shorter poles.
The neutral conductor should be installed on the same side (preferably the road side) of all of the tangent and small angle poles throughout the length of the line.
Prior RUS approval is given if it is under the circumstances necessary to lower the neutral attachment on standard construction pole top assemblies an additional distance not exceeding 2 feet for the purpose of economically meeting conductor clearance requirements of the NESC.
Prior RUS approval is given if it is under the circumstances necessary to lower the neutral attachment on standard construction pole top assemblies an additional distance of up to 6 feet for the purpose of performing construction and future line maintenance on these assemblies from bucket trucks designed for such work.
With pin-type or post-type insulators, the conductor must be tied to the top groove of the insulator on tangent poles and on the side of the insulator away from the strain at angles. Pin-type and post-type insulators must be tight on the pins and bracket, respectively, and the top groove must be in line with the conductor after tying.
Factory-formed ties must be installed in accordance with the manufacturer's specifications and recommendations.
A 3 inch by 3 inch (minimum), square, curved washer, item "ddd", shall be used abutting the pole when installing primary or neutral conductor deadend assemblies directly to the pole to mitigate the crushing of wood fibers and to facilitate the allowable longitudinal loading as given in the design parameters on the construction drawings.
A locknut must be installed with each nut and eyenut, on all machine, upset and double arming bolts, and all other threaded hardware such as insulator pins and studs.
The calculated "maximum line angle" values in the tables are based on the "designated maximum" transverse loading on insulator pins as specified by RUS, and the application of the appropriate overload factors from the 1997 edition of the NESC.
"Allowable longitudinal (or transverse) loading" values in the design parameters were derived from known or designated maximum strengths of materials to which the appropriate NESC safety factors have already been applied.
TYPICAL WOOD
CROSSARM GROUNDING
IQ)
TYPICAL STEEL
CROSSARM GROUNDING
e DATE: 06/14 /23 DWN BY: CCV
SCALE: NTS APPV D BY: GEJ
DATE: REVISION:
DATE: REVISION:
ELEcfllJPltofflliTIVE DATE: REVISION:
TAAff~fi'flO1jJ/flJbA ~D=AT=E=:====~RE=V=l=SI=O=N.=· ========
ENGINEERING DATE: REVISION:
V
.- GROUNDING FOR
ATTACHERS
TYPICAL FIBERGLASS
CROSSARM GROUNDING
GROUNDING GUIDE
FOR CROSSARM
TYPES
STANDARD
NUMBER
GROUNDING
GUIDE
SHEET: 1 OF 1
AutoCAD SHX Text
TYPICAL WOOD CROSSARM GROUNDING
AutoCAD SHX Text
GROUNDING FOR ATTACHERS
AutoCAD SHX Text
TYPICAL FIBERGLASS CROSSARM GROUNDING
AutoCAD SHX Text
TYPICAL STEEL CROSSARM GROUNDING
AutoCAD SHX Text
ELECTRIC COOPERATIVE
AutoCAD SHX Text
TAVERNIER, FLORIDA
AutoCAD SHX Text
ASSOCIATION INC.
AutoCAD SHX Text
FLORIDA KEYS
AutoCAD SHX Text
ENGINEERING
AutoCAD SHX Text
SERVICES
AutoCAD SHX Text
GROUNDING GUIDE
AutoCAD SHX Text
STANDARD NUMBER
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
REVISION:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
REVISION:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
REVISION:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
REVISION:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
REVISION:
AutoCAD SHX Text
SHEET: 1 OF 1
AutoCAD SHX Text
DWN BY: CGV
AutoCAD SHX Text
DATE: 06/14/23
AutoCAD SHX Text
APPVD BY: GEJ
AutoCAD SHX Text
SCALE: NTS
AutoCAD SHX Text
GROUNDING GUIDE FOR CROSSARM TYPES
TABLE I
MAXIMUM LINE ANGLES ON PIN INSULATOR ASSEMBLIES
Designated Maximum Transverse Load = 500 Lbs./Conductor ll'llltHJ ~ea~ (fH1)
CONDUCTOR SIZE 150 200 250 300 350 400
LIGHT LOADING DISTRICT
4ACSR (7/1) 13 13 12 12 11 11
2ACSR (6/1) 11 10 10 9 8 8
2ACSR (7/1) 8 8 7 7 6 6
1/0 ACSR (6/1) 7 6 6 5 5 4
123.3 AAAC (7) 7 6 6 5 5 4
2/0 ACSR (6/1) 6 6 5 5 4 4
3/0 ACSR (6/1) 5 5 4 4 3 3
4/0 ACSR (6/1) 5 4 4 3 3 2
246.9 AAAC (7) 5 4 4 3 3 2
336.4 ACSR (18/1) 4 4 3 2 2 1
336.4 ACSR (26n) 3 2 2 2 1 1
MEDIUM LOADING DISTRICT
4ACSR (7/1) 13 12 11 11 10 9
2ACSR (6/1) 11 10 9 8 8 7
2ACSR (7/1) 8 8 7 7 6 6
1/0 ACSR (6/1) 7 6 6 5 5 4
123.3 AAAC (7) 7 6 6 5 5 4
2/0 ACSR (6/1) 7 6 6 5 5 4
3/0 ACSR (6/1) 5 5 4 4 3 3
4/0 ACSR (6/1) 5 5 4 4 3 3
246.9 AAAC (7) 5 5 4 4 3 3
336.4 ACSR (18/1) 5 4 4 3 3 2
336.4 ACSR (26n) 3 3 3 2 2 2
HEAVY LOADING DISTRICT
4ACSR (7/1) 11 10 9 8 6 5
2ACSR (6/1) 9 8 7 6 5 4
2ACSR (7/1) 7 6 6 5 4 3
1/0 ACSR (6/1) 6 5 4 4 3 2
123.3 AAAC (7) 6 5 4 4 3 2
2/0 ACSR (6/1) 6 5 4 3 3 2
3/0 ACSR (6/1) 5 4 3 3 2 1
4/0 ACSR (6/1) 4 4 3 2 2 1
246.9 AAAC (7) 4 4 3 2 2 1
336.4 ACSR (18/1) 4 3 3 2 1 1
336.4 ACSR (26n) 3 2 2 1 1 0
TABLE II
Designated Maximum Transverse Load = 750 Lbs./Conductor ll'llltHJ ~ea~ (fH1)
CONDUCTOR SIZE 150 200 250 300 350 400
LIGHT LOADING DISTRICT
4ACSR (7/1) 21 21 20 19 19 18
2ACSR (6/1) 17 17 16 15 15 14
2ACSR (7/1) 13 13 12 12 11 11
1/0 ACSR (6/1) 11 10 10 9 9 8
123.3 AAAC (7) 11 10 10 9 9 8
2/0 ACSR (6/1) 11 10 9 9 8 8
3/0 ACSR (6/1) 8 8 7 7 6 6
4/0 ACSR (6/1) 8 8 7 6 6 5
246.9 AAAC (7) 8 7 7 6 6 5
336.4 ACSR (18/1) 7 7 6 5 5 4
336.4 ACSR (26n) 5 5 4 4 3 3
MEDIUM LOADING DISTRICT
4ACSR (7/1) 21 20 19 18 18 17
2ACSR (6/1) 17 16 16 15 14 13
2ACSR (7/1) 13 13 12 12 11 10
1/0 ACSR (6/1) 11 10 10 9 9 8
123.3 AAAC (7) 11 10 10 9 9 8
2/0 ACSR (6/1) 11 10 10 9 9 8
3/0 ACSR (6/1) 8 8 8 7 7 6
4/0 ACSR (6/1) 8 8 7 7 6 6
246.9 AAAC (7) 8 8 7 7 6 6
336.4 ACSR (18/1) 8 7 7 6 6 5
336.4 ACSR (26n) 5 5 5 4 4 4
HEAVY LOADING DISTRICT
4ACSR (7/1) 19 18 17 15 14 13
2ACSR (6/1) 16 15 13 12 11 10
2ACSR (7/1) 12 11 10 10 9 8
1/0 ACSR (6/1) 10 9 8 8 7 6
123.3 AAAC (7) 10 9 8 8 7 6
2/0 ACSR (6/1) 10 9 8 7 7 6
3/0 ACSR (6/1) 8 7 7 6 5 5
4/0 ACSR (6/1) 8 7 6 6 5 4
246.9 AAAC (7) 7 7 6 6 5 4
336.4 ACSR (18/1) 7 7 6 5 4 4
336.4 ACSR (26n) 5 5 4 4 3 3
TABLE Ill
Designated Maximum Transverse Load = 1,000 Lbs./Conductor ll'llltHJ ~ea~ (fH1)
CONDUCTOR SIZE 150 200 250 300 350 400
LIGHT LOADING DISTRICT
4ACSR (7/1) 29 28 28 27 27 26
2ACSR (6/1) 24 23 22 22 21 21
2ACSR (7/1) 18 18 17 17 16 16
1/0 ACSR (6/1) 15 14 14 13 13 13
123.3 AAAC (7) 15 14 14 13 13 12
2/0 ACSR (6/1) 15 14 14 13 12 12
3/0 ACSR (6/1) 12 11 11 10 10 9
4/0 ACSR (6/1) 11 11 10 10 9 9
246.9 AAAC (7) 11 10 10 9 9 8
336.4 ACSR (18/1) 11 10 9 9 8 7
336.4 ACSR (26n) 7 7 6 6 5 5
MEDIUM LOADING DISTRICT
4ACSR (7/1) 28 28 27 26 25 24
2ACSR (6/1) 23 23 22 21 21 20
2ACSR (7/1) 18 18 17 17 16 15
1/0 ACSR (6/1) 15 14 14 13 13 12
123.3 AAAC (7) 15 14 14 13 13 12
2/0 ACSR (6/1) 15 14 14 13 13 12
3/0 ACSR (6/1) 12 11 11 10 10 10
4/0 ACSR (6/1) 12 11 11 10 10 9
246.9 AAAC (7) 11 11 10 10 9 9
336.4 ACSR (18/1) 11 10 10 9 9 8
336.4 ACSR (26n) 8 7 7 7 6 6
HEAVY LOADING DISTRICT
4ACSR (7/1) 27 26 24 23 22 20
2ACSR (6/1) 22 21 20 19 18 16
2ACSR (7/1) 17 16 15 15 14 13
1/0 ACSR (6/1) 14 13 13 12 11 10
123.3 AAAC (7) 14 13 12 12 11 10
2/0 ACSR (6/1) 14 13 12 12 11 10
3/0 ACSR (6/1) 11 10 10 9 8 8
4/0 ACSR (6/1) 11 10 10 9 8 8
246.9 AAAC (7) 11 10 9 9 8 7
336.4 ACSR (18/1) 10 10 9 8 8 7
336.4 ACSR (26n) 7 7 6 6 5 5
TABLE IV
Designated Maximum Transverse Load = 1,500 Lbs./Conductor ll'llltHJ ~ea~ (fH1)
CONDUCTOR SIZE 150 200 250 300 350 400
LIGHT LOADING DISTRICT
4ACSR (7/1) 45 44 44 43 42 42
2ACSR (6/1) 37 36 35 35 34 33
2ACSR (7/1) 28 28 27 27 26 26
1/0 ACSR (6/1) 23 23 22 22 21 21
123.3 AAAC (7) 23 22 22 21 21 20
2/0 ACSR (6/1) 23 22 22 21 21 20
3/0 ACSR (6/1) 18 18 17 17 16 16
4/0 ACSR (6/1) 18 17 17 16 16 15
246.9 AAAC (7) 17 17 16 16 15 15
336.4 ACSR (18/1) 17 16 15 15 14 14
336.4 ACSR (26n) 12 11 11 10 10 9
MEDIUM LOADING DISTRICT
4ACSR (7/1) 44 44 43 42 41 40
2ACSR (6/1) 36 36 35 34 33 33
2ACSR (7/1) 28 28 27 27 26 25
1/0 ACSR (6/1) 23 23 22 22 21 21
123.3 AAAC (7) 23 22 22 21 21 20
2/0 ACSR (6/1) 23 22 22 21 21 20
3/0 ACSR (6/1) 18 18 17 17 17 16
4/0 ACSR (6/1) 18 18 17 17 16 16
246.9 AAAC (7) 18 17 17 16 16 15
336.4 ACSR (18/1) 17 17 16 16 15 15
336.4 ACSR (26n) 12 12 11 11 11 10
HEAVY LOADING DISTRICT
4ACSR (7/1) 43 41 40 39 37 36
2ACSR (6/1) 35 34 33 32 30 29
2ACSR (7/1) 27 26 25 25 24 23
1/0 ACSR (6/1) 22 22 21 20 19 19
123.3 AAAC (7) 22 21 21 20 19 18
2/0 ACSR (6/1) 22 21 21 20 19 18
3/0 ACSR (6/1) 18 17 16 16 15 14
4/0 ACSR (6/1) 17 17 16 15 15 14
246.9 AAAC (7) 17 16 16 15 14 14
336.4 ACSR (18/1) 17 16 15 14 14 13
336.4 ACSR (26n) 12 11 11 10 10 9
TABLE V
Designated Maximum Transverse Load = 2,000 Lbs./Conductor ll'llltHJ ~ea~ (fH1)
CONDUCTOR SIZE 150 200 250 300 350 400
LIGHT LOADING DISTRICT
4ACSR (7/1) 60 60 60 60 59 59
2ACSR (6/1) 50 50 49 48 48 47
2ACSR (7/1) 39 38 38 37 37 36
1/0 ACSR (6/1) 32 31 31 30 30 29
123.3 AAAC (7) 31 31 30 30 29 29
2/0 ACSR (6/1) 31 31 30 30 29 28
3/0 ACSR (6/1) 25 24 24 23 23 22
4/0 ACSR (6/1) 24 24 23 23 22 22
246.9 AAAC (7) 24 23 23 22 22 21
336.4 ACSR (18/1) 23 22 22 21 20 20
336.4 ACSR (26n) 16 16 15 15 14 14
MEDIUM LOADING DISTRICT
4ACSR (7/1) 60 60 60 59 58 57
2ACSR (6/1) 50 49 48 48 47 46
2ACSR (7/1) 39 38 37 37 36 36
1/0 ACSR (6/1) 32 31 31 30 30 29
123.3 AAAC (7) 31 31 30 30 29 29
2/0 ACSR (6/1) 31 31 30 30 29 29
3/0 ACSR (6/1) 25 24 24 24 23 23
4/0 ACSR (6/1) 25 24 24 23 23 22
246.9 AAAC (7) 24 24 23 23 22 22
336.4 ACSR (18/1) 24 23 23 22 22 21
336.4 ACSR (26n) 16 16 16 15 15 15
HEAVY LOADING DISTRICT
4ACSR (7/1) 60 58 57 55 54 52
2ACSR (6/1) 49 47 46 45 44 43
2ACSR (7/1) 38 37 36 35 34 33
1/0 ACSR (6/1) 31 30 29 28 28 27
123.3 AAAC (7) 30 30 29 28 27 26
2/0 ACSR (6/1) 30 30 29 28 27 26
3/0 ACSR (6/1) 24 24 23 22 22 21
4/0 ACSR (6/1) 24 23 23 22 21 21
246.9 AAAC (7) 23 23 22 21 21 20
336.4 ACSR (18/1) 23 22 21 21 20 19
336.4 ACSR (26n) 16 16 15 14 14 13
TABLE VI
MAXIMUM LINE ANGLES ON SPOOL INSULATOR ASSEMBLIES
(ANSI Clss 53-2 Spool Insulator)
Designated Maximum Transverse Load = 1,500 Lbs./Conductor
WIND SPAN (feet)
CONDUCTOR SIZE 150 200 250 300 350 400
LIGHT LOADING DISTRICT
4ACSR (7/1) 45 44 44 43 42 42
2ACSR (6/1) 37 36 35 35 34 33
2ACSR (7/1) 28 28 27 27 26 26
1/0 ACSR (6/1) 23 23 22 22 21 21
123.3 AAAC (7) 23 22 22 21 21 20
2/0 ACSR (6/1) 23 22 22 21 21 20
3/0 ACSR (6/1) 18 18 17 17 16 16
4/0 ACSR (6/1) 18 17 17 16 16 15
246.9 AAAC (7) 17 17 16 16 15 15
336.4 ACSR (18/1) 17 16 15 15 14 14
336.4 ACSR (26n) 12 11 11 10 10 9
MEDIUM LOADING DISTRICT
4ACSR (7/1) 44 44 43 42 41 40
2ACSR (6/1) 36 36 35 34 33 33
2ACSR (7/1) 28 28 27 27 26 25
1/0 ACSR (6/1) 23 23 22 22 21 21
123.3 AAAC (7) 23 22 22 21 21 20
2/0 ACSR (6/1) 23 22 22 21 21 20
3/0 ACSR (6/1) 18 18 17 17 17 16
4/0 ACSR (6/1) 18 18 17 17 16 16
246.9 AAAC (7) 18 17 17 16 16 15
336.4 ACSR (18/1) 17 17 16 16 15 15
336.4 ACSR (26n) 12 12 11 11 11 10
HEAVY LOADING DISTRICT
4ACSR (7/1) 43 41 40 39 37 36
2ACSR (6/1) 35 34 33 32 30 29
2ACSR (7/1) 27 26 25 25 24 23
1/0 ACSR (6/1) 22 22 21 20 19 19
123.3 AAAC (7) 22 21 21 20 19 18
2/0 ACSR (6/1) 22 21 21 20 19 18
3/0 ACSR (6/1) 18 17 16 16 15 14
4/0 ACSR (6/1) 17 17 16 15 15 14
246.9 AAAC (7) 17 16 16 15 14 14
TABLE VII
MAXIMUM LINE ANGLES ON SPOOL INSULATOR ASSEMBLIES
(ANSI Clss 53-4 Spool Insulator)
Designated Maximum Transverse Load = 1,500 Lbs./Conductor
WIND SPAN (feet)
CONDUCTOR SIZE 150 200 250 300 350 400
LIGHT LOADING DISTRICT
4ACSR (7/1) 45 44 44 43 42 42
2ACSR (6/1) 37 36 35 35 34 33
2ACSR (7/1) 28 28 27 27 26 26
1/0 ACSR (6/1) 23 23 22 22 21 21
123.3 AAAC (7) 23 22 22 21 21 20
2/0 ACSR (6/1) 23 22 22 21 21 20
3/0 ACSR (6/1) 18 18 17 17 16 16
4/0 ACSR (6/1) 18 17 17 16 16 15
246.9 AAAC (7) 17 17 16 16 15 15
336.4 ACSR (18/1) 17 16 15 15 14 14
336.4 ACSR (26n) 12 11 11 10 10 9
MEDIUM LOADING DISTRICT
4ACSR (7/1) 44 44 43 42 41 40
2ACSR (6/1) 36 36 35 34 33 33
2ACSR (7/1) 28 28 27 27 26 25
1/0 ACSR (6/1) 23 23 22 22 21 21
123.3 AAAC (7) 23 22 22 21 21 20
2/0 ACSR (6/1) 23 22 22 21 21 20
3/0 ACSR (6/1) 18 18 17 17 17 16
4/0 ACSR (6/1) 18 18 17 17 16 16
246.9 AAAC (7) 18 17 17 16 16 15
336.4 ACSR (18/1) 17 17 16 16 15 15
336.4 ACSR (26n) 12 12 11 11 11 10
HEAVY LOADING DISTRICT
4ACSR (7/1) 43 41 40 39 37 36
2ACSR (6/1) 35 34 33 32 30 29
2ACSR (7/1) 27 26 25 25 24 23
1/0 ACSR (6/1) 22 22 21 20 19 19
123.3 AAAC (7) 22 21 21 20 19 18
2/0 ACSR (6/1) 22 21 21 20 19 18
3/0 ACSR (6/1) 18 17 16 16 15 14
4/0 ACSR (6/1) 17 17 16 15 15 14
246.9 AAAC (7) 17 16 16 15 14 14
NOTE:
ALL COPPER CONDUCTORS ~ILL HAVE ARMOR RODS
dd Nut provided b
DETAIL
'A' DETAIL
'B' cc b
' 4" I 4" 1'-0"
6"
1 '-0" SEE DETAIL 'A'
8" 8" c-d-ek
1'-6" 1'-6"
4'-o" /- 4'-o" ----\ Position of Guy Position of Guy
(when req'd) (when req'd) ek-d~
"'bs-cm ~T w· 1e ire
NOTES:
1. The 5 foot neutral separation is intended to be used for new construction. This configuration may not be applicable to existing pole construction. Only when proper separation from other attachments and ground clearance will this be applied.
2. Attachers are to maintain 43 inches of separation from utility space.
e
DATE: 06 /14 /23 DWN BY: CCV
SCALE: NTS APPV D BY: GEJ
DATE: REVISION:
DATE: REVISION:
REVISION:
WOOD POLE
SINGLE INSULATOR
0-12° ANGLE
ELEcfllJPltofflliTIVE DATE:
ASSOCIATION INC. 1------+----------+-------------------1
TAVERNIER. FLORIDA DATE: REVISION: 1 - PHASE PRIMARY
ENGINEERING 1-D-A-TE-:---+RE-V-IS_I_O_N._· ----- 24.9/14.4 kV
STANDARD
NUMBER
VA1-P
SHEET: 1 OF 2
AutoCAD SHX Text bs-cm
AutoCAD SHX Text ek-d
AutoCAD SHX Text b
AutoCAD SHX Text a
AutoCAD SHX Text c-d-ek
AutoCAD SHX Text Position of Guy (when req'd)
AutoCAD SHX Text Position of Guy (when req'd)
AutoCAD SHX Text
DETAIL "A"
AutoCAD SHX Text gr
AutoCAD SHX Text n
AutoCAD SHX Text Nut provided
AutoCAD SHX Text ek
AutoCAD SHX Text c
AutoCAD SHX Text dd
AutoCAD SHX Text
SEE DETAIL "A"
AutoCAD SHX Text d
AutoCAD SHX Text
SEE DETAIL "B"
AutoCAD SHX Text
DETAIL "B"
AutoCAD SHX Text cc
AutoCAD SHX Text a
AutoCAD SHX Text b
AutoCAD SHX Text ek*
AutoCAD SHX Text Tie Wire
AutoCAD SHX Text The 5 foot neutral separation is intended to be used for new construction. This configuration may not be applicable to existing pole construction. Only when proper separation from other attachments and ground clearance will this be applied. Attachers are to maintain 43 inches of separation from utility space.
AutoCAD SHX Text
1. 2.
AutoCAD SHX Text
NOTES:
AutoCAD SHX Text 4"
AutoCAD SHX Text 8"
AutoCAD SHX Text 4"
AutoCAD SHX Text 8"
AutoCAD SHX Text
ELECTRIC COOPERATIVE
AutoCAD SHX Text
TAVERNIER, FLORIDA
AutoCAD SHX Text
ASSOCIATION INC.
AutoCAD SHX Text
FLORIDA KEYS
AutoCAD SHX Text
ENGINEERING
AutoCAD SHX Text
SERVICES
AutoCAD SHX Text
SINGLE INSULATOR 0-12° ANGLE
AutoCAD SHX Text
STANDARD NUMBER
AutoCAD SHX Text
DWN BY: CGV
AutoCAD SHX Text
DATE: 06/14/23
AutoCAD SHX Text
APPVD BY: GEJ
AutoCAD SHX Text
SCALE: NTS
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
REVISION:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
REVISION:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
REVISION:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
REVISION:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
REVISION:
AutoCAD SHX Text
SHEET: 1 OF 2
AutoCAD SHX Text
VA1-P
AutoCAD SHX Text 1 - PHASE PRIMARY 24.9/14.4 kV
AutoCAD SHX Text
WOOD POLE
NOTE: ALL COPPER CONDUCTORS WILL HAVE ARMOR RODS
VAl-P ITEM PART No, DESCRIPTION QTY,
a. E34259050 46kV INSULATDR1 LINE POST 'vi I K-CL (AS REQ'D) 1
a. E34259025 69kV INSULATDR1 LINE POST VERT (AS REQ'D) 1
TBD CLAMP TOP (AS NEEDED) 1
b C7807500 BRACKET I VERTICAL LINE POST INSULATOR 1
C C6380512 BDL TI MACHINE/ 5/8' x 12' REQ'D LENGTH 3 cc C06330003 BDLT1 INSUL STUD1 3/4' x 3' x 3/4' 1 d C71020441 'v/ASHER1 FLAT SQ 2-1/ 4' x 3/ 4' HOLE 5 dd C71037451 'vi ASHER/ FLAT ROUND 1 5/8' HOLE/ G 2
CM [34262013 IN SULA TORI 3' SPOOL 1
bs C6390512 BDL TI SINGLE UPSET 1 5/8' x 12' DR REQ'D LENGTH 1 gr C17371300 CONNI GROUNDING LUG/ 13/16' HOLE 1 n NOT IN INVENTORY NUT I GAL V 1 5/8' 1 ek C42903063 LOCKNUT 1 5/8' 3 ekllE C42903075 LOCKNUT 1 3/ 4' 1
TBD ARMOR RODS (AS NEEDED)
e
DATE: 06 /14 /23 I DWN BY: CCV WOOD POLE STANDARD SCALE: NTS I APPV D BY: GEJ
DATE: REVISION: SINGLE INSULATOR NUMBER
DATE: REVISION: 0-12° ANGLE FLORIDA KEYS VA1-P ELECTRIC COOPERATIVE DATE: REVISION:
ASSOCIATION INC.
TAVERNIER. FLORIDA DATE: REVISION: 1 - PHASE PRIMARY
ENGINEERING DATE: REVISION: 24.9/14.4 kV SHEET: 2 OF 2 .~li'RVTr'li'.~
AutoCAD SHX Text
VA1-P
AutoCAD SHX Text
ITEM
AutoCAD SHX Text PART No.
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
QTY.
AutoCAD SHX Text a
AutoCAD SHX Text E34259050
AutoCAD SHX Text 46kV INSULATOR, LINE POST W/ K-CL (AS REQ'D)
AutoCAD SHX Text
AutoCAD SHX Text a
AutoCAD SHX Text E34259025
AutoCAD SHX Text 69kV INSULATOR, LINE POST VERT (AS REQ'D)
AutoCAD SHX Text
AutoCAD SHX Text
TBD
AutoCAD SHX Text
CLAMP TOP (AS NEEDED)
AutoCAD SHX Text
AutoCAD SHX Text b
AutoCAD SHX Text C7807500
AutoCAD SHX Text
BRACKET, VERTICAL LINE POST INSULATOR
AutoCAD SHX Text
AutoCAD SHX Text c
AutoCAD SHX Text C6380512
AutoCAD SHX Text BOLT, MACHINE, 5/8" x 12" REQ'D LENGTH
AutoCAD SHX Text
AutoCAD SHX Text cc
AutoCAD SHX Text C06330003
AutoCAD SHX Text BOLT, INSUL STUD, 3/4" x 3" x 3/4"
AutoCAD SHX Text
AutoCAD SHX Text d
AutoCAD SHX Text C71020441
AutoCAD SHX Text WASHER, FLAT SQ 2-1/4" x 3/4" HOLE
AutoCAD SHX Text
AutoCAD SHX Text dd
AutoCAD SHX Text C71037451
AutoCAD SHX Text
WASHER, FLAT ROUND, 5/8" HOLE, G
AutoCAD SHX Text
AutoCAD SHX Text cm
AutoCAD SHX Text C34262013
AutoCAD SHX Text
INSULATOR, 3" SPOOL
AutoCAD SHX Text
AutoCAD SHX Text bs
AutoCAD SHX Text C6390512
AutoCAD SHX Text BOLT, SINGLE UPSET, 5/8" x 12" OR REQ'D LENGTH
AutoCAD SHX Text
AutoCAD SHX Text gr
AutoCAD SHX Text C17371300
AutoCAD SHX Text
CONN, GROUNDING LUG, 13/16" HOLE
AutoCAD SHX Text
AutoCAD SHX Text n
AutoCAD SHX Text
NOT IN INVENTORY
AutoCAD SHX Text
NUT, GALV, 5/8"
AutoCAD SHX Text
AutoCAD SHX Text ek
AutoCAD SHX Text C42903063
AutoCAD SHX Text
LOCKNUT, 5/8"
AutoCAD SHX Text
AutoCAD SHX Text ek*
AutoCAD SHX Text C42903075
AutoCAD SHX Text
LOCKNUT, 3/4"
AutoCAD SHX Text
AutoCAD SHX Text
TBD
AutoCAD SHX Text
ARMOR RODS (AS NEEDED)
AutoCAD SHX Text
ELECTRIC COOPERATIVE
AutoCAD SHX Text
TAVERNIER, FLORIDA
AutoCAD SHX Text
ASSOCIATION INC.
AutoCAD SHX Text
FLORIDA KEYS
AutoCAD SHX Text
ENGINEERING
AutoCAD SHX Text
SERVICES
AutoCAD SHX Text
VA1-P
AutoCAD SHX Text
STANDARD NUMBER
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
REVISION:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
REVISION:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
REVISION:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
REVISION:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
REVISION:
AutoCAD SHX Text
SHEET: 2 OF 2
AutoCAD SHX Text
DWN BY: CGV
AutoCAD SHX Text
DATE: 06/14/23
AutoCAD SHX Text
APPVD BY: GEJ
AutoCAD SHX Text
SCALE: NTS
AutoCAD SHX Text
WOOD POLE
AutoCAD SHX Text
SINGLE INSULATOR 0-12° ANGLE
1 - PHASE PRIMARY 24.9/14.4 kV b
DETAIL
'A'
SEE DETAIL 'A'
' 4" I 4" 1'-0"
8" c-ddd-ek* 1'-0" 8" = 0
1 '-6" 1 '-6"
4'-o" /- 4'-o" --\ Position of Guy
(when req'd)
/bs-cm ek-ddd~
'p Tie Wire
.-- GROUNDING FOR - --
'P ATTACHERS
NOTES:
1. The 5 foot neutral separation is intended to be used for new construction. This configuration may not be applicable to existing pole construction. Only when proper separation from other attachments and ground clearance will this be applied.
2. Attachers are to maintain 43 inches of separation from utility space.
Position of Guy (when req'd)
GROUNDING FOR
ATTACHERS
e
DATE: 06 /14 /23 DWN BY: CCV DUCTILE IRON POLE STANDARD SCALE: NTS APPVD BY: GEJ
DATE: REVISION: SINGLE INSULATOR NUMBER
DATE: REVISION: 0-12° ANGLE FLORIDA KEYS VA1-P ELECTRIC COOPERATIVE DATE: REVISION:
ASSOCIATION INC.
TAVERNIER. FLORIDA DATE: REVISION: 1 - PHASE PRIMARY
ENGINEERING DATE: REVISION: 24.9/14.4 kV SHEET: 1 OF 2
AutoCAD SHX Text bs-cm
AutoCAD SHX Text ek-ddd
AutoCAD SHX Text b
AutoCAD SHX Text a
AutoCAD SHX Text c-ddd-ek*
AutoCAD SHX Text Position of Guy (when req'd)
AutoCAD SHX Text
SEE DETAIL "A"
AutoCAD SHX Text Position of Guy (when req'd)
AutoCAD SHX Text
DETAIL "A"
AutoCAD SHX Text cc
AutoCAD SHX Text a
AutoCAD SHX Text b
AutoCAD SHX Text p
AutoCAD SHX Text ek*
AutoCAD SHX Text Tie Wire
AutoCAD SHX Text The 5 foot neutral separation is intended to be used for new construction. This configuration may not be applicable to existing pole construction. Only when proper separation from other attachments and ground clearance will this be applied. Attachers are to maintain 43 inches of separation from utility space.
AutoCAD SHX Text
1. 2.
AutoCAD SHX Text
NOTES:
AutoCAD SHX Text p
AutoCAD SHX Text 4"
AutoCAD SHX Text 8"
AutoCAD SHX Text 4"
AutoCAD SHX Text 8"
AutoCAD SHX Text
GROUNDING FOR ATTACHERS
AutoCAD SHX Text
GROUNDING FOR ATTACHERS
AutoCAD SHX Text p
AutoCAD SHX Text p
AutoCAD SHX Text
ELECTRIC COOPERATIVE
AutoCAD SHX Text
TAVERNIER, FLORIDA
AutoCAD SHX Text
ASSOCIATION INC.
AutoCAD SHX Text
FLORIDA KEYS
AutoCAD SHX Text
ENGINEERING
AutoCAD SHX Text
SERVICES
AutoCAD SHX Text
VA1-P
AutoCAD SHX Text
STANDARD NUMBER
AutoCAD SHX Text
DWN BY: CGV
AutoCAD SHX Text
DATE: 06/14/23
AutoCAD SHX Text
APPVD BY: GEJ
AutoCAD SHX Text
SCALE: NTS
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
REVISION:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
REVISION:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
REVISION:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
REVISION:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
REVISION:
AutoCAD SHX Text
SHEET: 1 OF 2
AutoCAD SHX Text
DUCTILE IRON POLE
AutoCAD SHX Text
SINGLE INSULATOR 0-12° ANGLE
AutoCAD SHX Text 1 - PHASE PRIMARY 24.9/14.4 kV
0. E34259050 46kV INSULATOR) LINE POST \JI K-CL CAS REQ'D) 1
0. E34259025 69kV INSULATOR) LINE POST VERT (AS REQ'D) 1
TBD CLAMP TOP CAS NEEDED) 1
b C7807500 BRACKET) VERTICAL LINE POST INSULATOR 1
C C6380612 BDL T) MACHINE) 3/ 4' x 12' DR REQ'D LENGTH 2 cc C06330003 BOLT) INSUL STUD) 3/4' x 3' x 3/4' 1 cicici C71011551 \J ASHER) CURVED SQ 3' x 3/ 4' HOLE 3
CM C34262013 INSULATOR) 3' SPOOL 1
bs C6390512 BDL T) SINGLE UPSET) 5/8' x 12' DR REQ'D LENGTH 1 ek C42903063 LOCKNUT) 5/8' 1 ek* C42903075 LOCKNUT) 3/ 41 3 p C17761500 CONNECTOR) GROUND 2
TBD ARMOR RODS CAS NEEDED)
e DATE: 06 /14 /23 I DWN BY: CCV DUCTILE IRON POLE STANDARD SCALE: NTS I APPV D BY: GEJ
DATE: REVISION: SINGLE INSULATOR NUMBER
DATE: REVISION: 0-12° ANGLE FLORIDA KEYS VA1-P ELECTRIC COOPERATIVE DATE: REVISION:
ASSOCIATION INC.
TAVERNIER. FLORIDA DATE: REVISION: 1 - PHASE PRIMARY
ENGINEERING DATE: REVISION: 24.9/14.4 kV SHEET: 2 OF 2 .~li'RVTr'li'.~
AutoCAD SHX Text
VA1-P
AutoCAD SHX Text
ITEM
AutoCAD SHX Text PART No.
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
QTY.
AutoCAD SHX Text a
AutoCAD SHX Text E34259050
AutoCAD SHX Text 46kV INSULATOR, LINE POST W/ K-CL (AS REQ'D)
AutoCAD SHX Text
AutoCAD SHX Text a
AutoCAD SHX Text E34259025
AutoCAD SHX Text 69kV INSULATOR, LINE POST VERT (AS REQ'D)
AutoCAD SHX Text
AutoCAD SHX Text
TBD
AutoCAD SHX Text
CLAMP TOP (AS NEEDED)
AutoCAD SHX Text
AutoCAD SHX Text b
AutoCAD SHX Text C7807500
AutoCAD SHX Text
BRACKET, VERTICAL LINE POST INSULATOR
AutoCAD SHX Text
AutoCAD SHX Text c
AutoCAD SHX Text C6380612
AutoCAD SHX Text BOLT, MACHINE, 3/4" x 12" OR REQ'D LENGTH
AutoCAD SHX Text
AutoCAD SHX Text cc
AutoCAD SHX Text C06330003
AutoCAD SHX Text BOLT, INSUL STUD, 3/4" x 3" x 3/4"
AutoCAD SHX Text
AutoCAD SHX Text ddd
AutoCAD SHX Text C71011551
AutoCAD SHX Text WASHER, CURVED SQ 3" x 3/4" HOLE
AutoCAD SHX Text
AutoCAD SHX Text cm
AutoCAD SHX Text C34262013
AutoCAD SHX Text
INSULATOR, 3" SPOOL
AutoCAD SHX Text
AutoCAD SHX Text bs
AutoCAD SHX Text C6390512
AutoCAD SHX Text BOLT, SINGLE UPSET, 5/8" x 12" OR REQ'D LENGTH
AutoCAD SHX Text
AutoCAD SHX Text ek
AutoCAD SHX Text C42903063
AutoCAD SHX Text
LOCKNUT, 5/8"
AutoCAD SHX Text
AutoCAD SHX Text ek*
AutoCAD SHX Text C42903075
AutoCAD SHX Text
LOCKNUT, 3/4"
AutoCAD SHX Text
AutoCAD SHX Text p
AutoCAD SHX Text C17761500
AutoCAD SHX Text
CONNECTOR, GROUND
AutoCAD SHX Text
AutoCAD SHX Text
TBD
AutoCAD SHX Text
ARMOR RODS (AS NEEDED)
AutoCAD SHX Text
ELECTRIC COOPERATIVE
AutoCAD SHX Text
TAVERNIER, FLORIDA
AutoCAD SHX Text
ASSOCIATION INC.
AutoCAD SHX Text
FLORIDA KEYS
AutoCAD SHX Text
ENGINEERING
AutoCAD SHX Text
SERVICES
AutoCAD SHX Text
VA1-P
AutoCAD SHX Text
STANDARD NUMBER
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
REVISION:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
REVISION:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
REVISION:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
REVISION:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
REVISION:
AutoCAD SHX Text
SHEET: 2 OF 2
AutoCAD SHX Text
DWN BY: CGV
AutoCAD SHX Text
DATE: 06/14/23
AutoCAD SHX Text
APPVD BY: GEJ
AutoCAD SHX Text
SCALE: NTS
AutoCAD SHX Text
DUCTILE IRON POLE
AutoCAD SHX Text
SINGLE INSULATOR 0-12° ANGLE
1'-0"
4'-0"
NOTES:
Nut provided
4"
1'-6"
Position of Guy
(when req'd) dd
DETAIL
'A' ek-d~ "" c-d-ek bs-cm b
DETAIL cc 'B'
4" 1'-0"
4'-0"
1. The 5 foot neutral separation is intended to be used for new construction. This configuration may not be applicable to existing pole construction. Only when proper separation from other attachments and ground clearance will this be applied.
2. Attachers are to maintain 43 inches of separation from utility space.
DATE: 06 /14 /23 DWN BY: CCV CONCRETE POLE SCALE: NTS APPVD BY: GEJ
SEE DETAIL 'B'
SEE DETAIL 'A'
1'-6"
Position of Guy (when req'd)
STANDARD e DATE: REVISION: SINGLE INSULATOR NUMBER DATE: REVISION: 0-12° ANGLE FLORIDA KEYS VA1-P ELECTRIC COOPERATIVE DATE: REVISION:
ASSOCIATION INC.
TAVERNIER. FLORIDA DATE: REVISION: 1 - PHASE PRIMARY
ENGINEERING DATE: REVISION: 24.9/14.4 kV SHEET: 1 OF 2
AutoCAD SHX Text bs-cm
AutoCAD SHX Text ek-d
AutoCAD SHX Text b
AutoCAD SHX Text a
AutoCAD SHX Text c-d-ek
AutoCAD SHX Text Position of Guy (when req'd)
AutoCAD SHX Text
SEE DETAIL "B"
AutoCAD SHX Text Position of Guy (when req'd)
AutoCAD SHX Text
SEE DETAIL "A"
AutoCAD SHX Text
DETAIL "A"
AutoCAD SHX Text gr
AutoCAD SHX Text n
AutoCAD SHX Text Nut provided
AutoCAD SHX Text ek
AutoCAD SHX Text c
AutoCAD SHX Text dd
AutoCAD SHX Text d
AutoCAD SHX Text
DETAIL "B"
AutoCAD SHX Text cc
AutoCAD SHX Text a
AutoCAD SHX Text b
AutoCAD SHX Text 4"
AutoCAD SHX Text 8"
AutoCAD SHX Text ek*
AutoCAD SHX Text Tie Wire
AutoCAD SHX Text The 5 foot neutral separation is intended to be used for new construction. This configuration may not be applicable to existing pole construction. Only when proper separation from other attachments and ground clearance will this be applied. Attachers are to maintain 43 inches of separation from utility space.
AutoCAD SHX Text
1. 2.
AutoCAD SHX Text
NOTES:
AutoCAD SHX Text 4"
AutoCAD SHX Text 8"
AutoCAD SHX Text
ELECTRIC COOPERATIVE
AutoCAD SHX Text
TAVERNIER, FLORIDA
AutoCAD SHX Text
ASSOCIATION INC.
AutoCAD SHX Text
FLORIDA KEYS
AutoCAD SHX Text
ENGINEERING
AutoCAD SHX Text
SERVICES
AutoCAD SHX Text
VA1-P
AutoCAD SHX Text
STANDARD NUMBER
AutoCAD SHX Text
DWN BY: CGV
AutoCAD SHX Text
DATE: 06/14/23
AutoCAD SHX Text
APPVD BY: GEJ
AutoCAD SHX Text
SCALE: NTS
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
REVISION:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
REVISION:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
REVISION:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
REVISION:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
REVISION:
AutoCAD SHX Text
SHEET: 1 OF 2
AutoCAD SHX Text
CONCRETE POLE
AutoCAD SHX Text
SINGLE INSULATOR 0-12° ANGLE
AutoCAD SHX Text 1 - PHASE PRIMARY 24.9/14.4 kV
Q E34259050 46kV INSULATOR, LINE POST 'vi I K-CL <AS REQ'D) 1 Q E34259025 69kV INSULATOR, LINE POST VERT (AS REQ'D) 1
TBD CLAMP TOP <AS NEEDED) 1
b C7807500 BRACKET, VERTICAL LINE POST INS ULA TOR 1
C C6380612 BDL T, MACHINE, 3/ 4' x 12' DR REQ'D LENGTH 2 cc C06330003 BOLT, INSUL STUD, 3/4' x 3' x 3/4' 1 ci C71020441 'vi ASHER, FLAT SQ 2-1/ 4' x 3/ 4' HOLE 3 cici C71037451 WASHER, FLAT ROUND, 3/ 4" HOLE 2
CM C34262013 INSULATOR, 3' SPOOL 1
bs C6390512 BDL T, SINGLE UPSET, 5/8' x 12' DR REQ'D LENGTH 1 gr C17371300 CONN, GROUNDING LUG, 13/16' HOLE 1 n NOT IN INVENTORY NUT, GALV, 3/4' 1 ek C42903063 LOCKNUT, 5/8' 1 ek* C42903075 LOCKNUT, 3/ 4' 3
TBD ARMOR RODS <AS NEEDED)
e DATE: 06 /14 /23 I DWN BY: CCV CONCRETE POLE STANDARD SCALE: NTS I APPV D BY: GEJ
DATE: REVISION: SINGLE INSULATOR NUMBER
DATE: REVISION: 0-12° ANGLE FLORIDA KEYS VA1-P ELECTRIC COOPERATIVE DATE: REVISION:
ASSOCIATION INC.
TAVERNIER. FLORIDA DATE: REVISION: 1 - PHASE PRIMARY
ENGINEERING DATE: REVISION: 24.9/14.4 kV SHEET: 2 OF 2 .~li'RVTr'li'.~
AutoCAD SHX Text
VA1-P
AutoCAD SHX Text
ITEM
AutoCAD SHX Text PART No.
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
QTY.
AutoCAD SHX Text a
AutoCAD SHX Text E34259050
AutoCAD SHX Text 46kV INSULATOR, LINE POST W/ K-CL (AS REQ'D)
AutoCAD SHX Text
AutoCAD SHX Text a
AutoCAD SHX Text E34259025
AutoCAD SHX Text 69kV INSULATOR, LINE POST VERT (AS REQ'D)
AutoCAD SHX Text
AutoCAD SHX Text
TBD
AutoCAD SHX Text
CLAMP TOP (AS NEEDED)
AutoCAD SHX Text
AutoCAD SHX Text b
AutoCAD SHX Text C7807500
AutoCAD SHX Text
BRACKET, VERTICAL LINE POST INSULATOR
AutoCAD SHX Text
AutoCAD SHX Text c
AutoCAD SHX Text C6380612
AutoCAD SHX Text BOLT, MACHINE, 3/4" x 12" OR REQ'D LENGTH
AutoCAD SHX Text
AutoCAD SHX Text cc
AutoCAD SHX Text C06330003
AutoCAD SHX Text BOLT, INSUL STUD, 3/4" x 3" x 3/4"
AutoCAD SHX Text
AutoCAD SHX Text d
AutoCAD SHX Text C71020441
AutoCAD SHX Text WASHER, FLAT SQ 2-1/4" x 3/4" HOLE
AutoCAD SHX Text
AutoCAD SHX Text dd
AutoCAD SHX Text C71037451
AutoCAD SHX Text
WASHER, FLAT ROUND, 3/4" HOLE
AutoCAD SHX Text
AutoCAD SHX Text cm
AutoCAD SHX Text C34262013
AutoCAD SHX Text
INSULATOR, 3" SPOOL
AutoCAD SHX Text
AutoCAD SHX Text bs
AutoCAD SHX Text C6390512
AutoCAD SHX Text BOLT, SINGLE UPSET, 5/8" x 12" OR REQ'D LENGTH
AutoCAD SHX Text
AutoCAD SHX Text gr
AutoCAD SHX Text C17371300
AutoCAD SHX Text
CONN, GROUNDING LUG, 13/16" HOLE
AutoCAD SHX Text
AutoCAD SHX Text n
AutoCAD SHX Text
NOT IN INVENTORY
AutoCAD SHX Text
NUT, GALV, 3/4"
AutoCAD SHX Text
AutoCAD SHX Text ek
AutoCAD SHX Text C42903063
AutoCAD SHX Text
LOCKNUT, 5/8"
AutoCAD SHX Text
AutoCAD SHX Text ek*
AutoCAD SHX Text C42903075
AutoCAD SHX Text
LOCKNUT, 3/4"
AutoCAD SHX Text
AutoCAD SHX Text
TBD
AutoCAD SHX Text
ARMOR RODS (AS NEEDED)
AutoCAD SHX Text
ELECTRIC COOPERATIVE
AutoCAD SHX Text
TAVERNIER, FLORIDA
AutoCAD SHX Text
ASSOCIATION INC.
AutoCAD SHX Text
FLORIDA KEYS
AutoCAD SHX Text
ENGINEERING
AutoCAD SHX Text
SERVICES
AutoCAD SHX Text
VA1-P
AutoCAD SHX Text
STANDARD NUMBER
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
REVISION:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
REVISION:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
REVISION:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
REVISION:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
REVISION:
AutoCAD SHX Text
SHEET: 2 OF 2
AutoCAD SHX Text
DWN BY: CGV
AutoCAD SHX Text
DATE: 06/14/23
AutoCAD SHX Text
APPVD BY: GEJ
AutoCAD SHX Text
SCALE: NTS
AutoCAD SHX Text
CONCRETE POLE
AutoCAD SHX Text
SINGLE INSULATOR 0-12° ANGLE
dd Nut provided b
DETAIL
'A' DETAIL cc
'B'
SEE DETAIL 'B'
1'-0" 1 '-0" 4"
8"
6"
1'-6" 1'-6"
4'-0" Position of Guy
( when req' d)
4'-0"
SEE/
DETAIL 'A'
Position of Guy
( when req' d) c-d-ek ~ ~Tie Wire
NOTES:
1. The 5 foot neutral separation is intended to be used for new construction. This configuration may not be applicable to existing pole construction. Only when proper separation from other attachments and ground clearance will this be applied.
2. Attachers are to maintain 43 inches of separation from utility space.
e
DATE: 06 /14 /23 DWN BY: CCV WOOD POLE SCALE: NTS APPVD BY: GEJ
DATE: REVISION: DOUBLE INSULATOR
DATE: REVISION: 12-30° ANGLE FLORIDA KEYS
ELECTRIC COOPERATIVE DATE: REVISION:
ASSOCIATION INC. - PHASE PRIMARY TAVERNIER. FLORIDA DATE: REVISION: 1
ENGINEERING DATE: REVISION: 24.9/14.4 kV
STANDARD
NUMBER
VA2-P
SHEET: 1 OF 2
AutoCAD SHX Text cm-da
AutoCAD SHX Text c-d-ek
AutoCAD SHX Text b
AutoCAD SHX Text a
AutoCAD SHX Text Position of Guy (when req'd)
AutoCAD SHX Text
SEE DETAIL "B"
AutoCAD SHX Text Position of Guy (when req'd)
AutoCAD SHX Text
SEE DETAIL "A"
AutoCAD SHX Text
DETAIL "A"
AutoCAD SHX Text gr
AutoCAD SHX Text n
AutoCAD SHX Text Nut provided
AutoCAD SHX Text ek
AutoCAD SHX Text c
AutoCAD SHX Text dd
AutoCAD SHX Text
DETAIL "B"
AutoCAD SHX Text cc
AutoCAD SHX Text a
AutoCAD SHX Text b
AutoCAD SHX Text ek*
AutoCAD SHX Text 4"
AutoCAD SHX Text 8"
AutoCAD SHX Text 4"
AutoCAD SHX Text 8"
AutoCAD SHX Text c-ek
AutoCAD SHX Text Tie Wire
AutoCAD SHX Text The 5 foot neutral separation is intended to be used for new construction. This configuration may not be applicable to existing pole construction. Only when proper separation from other attachments and ground clearance will this be applied. Attachers are to maintain 43 inches of separation from utility space.
AutoCAD SHX Text
1. 2.
AutoCAD SHX Text
NOTES:
AutoCAD SHX Text d-c-ek
AutoCAD SHX Text d
AutoCAD SHX Text
ELECTRIC COOPERATIVE
AutoCAD SHX Text
TAVERNIER, FLORIDA
AutoCAD SHX Text
ASSOCIATION INC.
AutoCAD SHX Text
FLORIDA KEYS
AutoCAD SHX Text
ENGINEERING
AutoCAD SHX Text
SERVICES
AutoCAD SHX Text
STANDARD NUMBER
AutoCAD SHX Text
DWN BY: CGV
AutoCAD SHX Text
DATE: 06/14/23
AutoCAD SHX Text
APPVD BY: GEJ
AutoCAD SHX Text
SCALE: NTS
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
REVISION:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
REVISION:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
REVISION:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
REVISION:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
REVISION:
AutoCAD SHX Text
SHEET: 1 OF 2
AutoCAD SHX Text
VA2-P
AutoCAD SHX Text
WOOD POLE
AutoCAD SHX Text
DOUBLE INSULATOR 12-30° ANGLE
AutoCAD SHX Text 1 - PHASE PRIMARY 24.9/14.4 kV
VA2-P
a. E34259050 46kV INSULATOR1 LINE POST 'vi I K-CL <AS REQ'D) 2
a. E34259025 69kV INSULATOR/ LINE POST VERT (AS REQ'D) 2
TBD CLAMP TOP (AS NEEDED) 2
b C7807500 BRACKET1 VERTICAL LINE POST INSULATOR 2
C C6380518 BOLT I MACHINE/ 5/8' x 12' REQ'D LENGTH 4 cc C06330003 BOLT1 INSUL STUD1 3/4' x 3' x 3/4' 2
CM C34262013 INSULATOR1 3' SPOOL 1
d C71020441 'vi ASHER/ FLAT SQ 2-1/ 4' x 3/ 4' HOLE 2
do. C7804500 BRACKET I CURVED BASE CLEVIS 1 dd C71037451 'vi ASHER/ FLAT ROUND 1 5/8' HOLE/ G 2 ek C42903063 LOCKNUT 1 5/8' 4 ek* C42903075 LOCKNUT 1 3/ 4' 2 gr C17371300 CONNI GROUNDING LUG, 13/16' HOLE 1 n NOT IN INVENTORY NUT I GAL V 1 5/8' 1
TBD ARMOR RODS (AS NEEDED)
e
DATE: 06 /14 /23 I DWN BY: CCV WOOD POLE STANDARD SCALE: NTS I APPV D BY: GEJ
DATE: REVISION: DOUBLE INSULATOR NUMBER
DATE: REVISION: 12-30° ANGLE FLORIDA KEYS VA2-P ELECTRIC COOPERATIVE DATE: REVISION:
ASSOCIATION INC. 1 - PHASE PRIMARY TAVERNIER. FLORIDA DATE: REVISION:
ENGINEERING DATE: REVISION: 24.9/14.4 kV SHEET: 2 OF 2 .~li'RVTr'li'.~
AutoCAD SHX Text
VA2-P
AutoCAD SHX Text
ITEM
AutoCAD SHX Text PART No.
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
QTY.
AutoCAD SHX Text a
AutoCAD SHX Text E34259050
AutoCAD SHX Text 46kV INSULATOR, LINE POST W/ K-CL (AS REQ'D)
AutoCAD SHX Text
AutoCAD SHX Text a
AutoCAD SHX Text E34259025
AutoCAD SHX Text 69kV INSULATOR, LINE POST VERT (AS REQ'D)
AutoCAD SHX Text
AutoCAD SHX Text
TBD
AutoCAD SHX Text
CLAMP TOP (AS NEEDED)
AutoCAD SHX Text
AutoCAD SHX Text b
AutoCAD SHX Text C7807500
AutoCAD SHX Text
BRACKET, VERTICAL LINE POST INSULATOR
AutoCAD SHX Text
AutoCAD SHX Text c
AutoCAD SHX Text C6380518
AutoCAD SHX Text BOLT, MACHINE, 5/8" x 12" REQ'D LENGTH
AutoCAD SHX Text
AutoCAD SHX Text cc
AutoCAD SHX Text C06330003
AutoCAD SHX Text BOLT, INSUL STUD, 3/4" x 3" x 3/4"
AutoCAD SHX Text
AutoCAD SHX Text cm
AutoCAD SHX Text C34262013
AutoCAD SHX Text
INSULATOR, 3" SPOOL
AutoCAD SHX Text
AutoCAD SHX Text d
AutoCAD SHX Text C71020441
AutoCAD SHX Text WASHER, FLAT SQ 2-1/4" x 3/4" HOLE
AutoCAD SHX Text
AutoCAD SHX Text da
AutoCAD SHX Text C7804500
AutoCAD SHX Text
BRACKET, CURVED BASE CLEVIS
AutoCAD SHX Text
AutoCAD SHX Text dd
AutoCAD SHX Text C71037451
AutoCAD SHX Text
WASHER, FLAT ROUND, 5/8" HOLE, G
AutoCAD SHX Text
AutoCAD SHX Text ek
AutoCAD SHX Text C42903063
AutoCAD SHX Text
LOCKNUT, 5/8"
AutoCAD SHX Text
AutoCAD SHX Text ek*
AutoCAD SHX Text C42903075
AutoCAD SHX Text
LOCKNUT, 3/4"
AutoCAD SHX Text
AutoCAD SHX Text gr
AutoCAD SHX Text C17371300
AutoCAD SHX Text
CONN, GROUNDING LUG, 13/16" HOLE
AutoCAD SHX Text
AutoCAD SHX Text n
AutoCAD SHX Text
NOT IN INVENTORY
AutoCAD SHX Text
NUT, GALV, 5/8"
AutoCAD SHX Text
AutoCAD SHX Text
TBD
AutoCAD SHX Text
ARMOR RODS (AS NEEDED)
AutoCAD SHX Text
ELECTRIC COOPERATIVE
AutoCAD SHX Text
TAVERNIER, FLORIDA
AutoCAD SHX Text
ASSOCIATION INC.
AutoCAD SHX Text
FLORIDA KEYS
AutoCAD SHX Text
ENGINEERING
AutoCAD SHX Text
SERVICES
AutoCAD SHX Text
VA2-P
AutoCAD SHX Text
STANDARD NUMBER
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
REVISION:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
REVISION:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
REVISION:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
REVISION:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
REVISION:
AutoCAD SHX Text
SHEET: 2 OF 2
AutoCAD SHX Text
DWN BY: CGV
AutoCAD SHX Text
DATE: 06/14/23
AutoCAD SHX Text
APPVD BY: GEJ
AutoCAD SHX Text
SCALE: NTS
AutoCAD SHX Text
WOOD POLE
AutoCAD SHX Text
DOUBLE INSULATOR 12-30° ANGLE
1 '-0"
4'-0"
NOTES:
4"
8"
1'-6"
Position of Guy (when req'd) c-ddd-ek ~ c-ek
GROUNDING FOR
--- ATTACHERS
p b
DETAIL
'A'
4" 1'-0"
8"
4'-0" p
1. The 5 foot neutral separation is intended to be used for new construction. This configuration may not be applicable to existing pole construction. Only when proper separation from other attachments and ground clearance will this be applied.
2. Attachers are to maintain 43 inches of separation from utility space.
cc
SEE DETAIL 'A'
1'-6"
Position of Guy (when req'd)
GROUNDING FOR
ATTACHERS
e
DATE: 06 /14 /23 DWN BY: CCV DUCTILE IRON POLE STANDARD SCALE: NTS APPVD BY: GEJ
DATE: REVISION: DOUBLE INSULATOR NUMBER
DATE: REVISION: 12-30° ANGLE FLORIDA KEYS VA2-P ELECTRIC COOPERATIVE DATE: REVISION:
ASSOCIATION INC. - PHASE PRIMARY TAVERNIER. FLORIDA DATE: REVISION: 1
ENGINEERING DATE: REVISION: 24.9/14.4 kV SHEET: 1 OF 2
AutoCAD SHX Text cm-da
AutoCAD SHX Text c-ddd-ek
AutoCAD SHX Text b
AutoCAD SHX Text a
AutoCAD SHX Text c-ek
AutoCAD SHX Text Position of Guy (when req'd)
AutoCAD SHX Text
SEE DETAIL "A"
AutoCAD SHX Text Position of Guy (when req'd)
AutoCAD SHX Text
DETAIL "A"
AutoCAD SHX Text cc
AutoCAD SHX Text a
AutoCAD SHX Text b
AutoCAD SHX Text ek
AutoCAD SHX Text 4"
AutoCAD SHX Text 8"
AutoCAD SHX Text 4"
AutoCAD SHX Text 8"
AutoCAD SHX Text Tie Wire
AutoCAD SHX Text p
AutoCAD SHX Text The 5 foot neutral separation is intended to be used for new construction. This configuration may not be applicable to existing pole construction. Only when proper separation from other attachments and ground clearance will this be applied. Attachers are to maintain 43 inches of separation from utility space.
AutoCAD SHX Text
1. 2.
AutoCAD SHX Text
NOTES:
AutoCAD SHX Text
GROUNDING FOR ATTACHERS
AutoCAD SHX Text
GROUNDING FOR ATTACHERS
AutoCAD SHX Text p
AutoCAD SHX Text p
AutoCAD SHX Text
ELECTRIC COOPERATIVE
AutoCAD SHX Text
TAVERNIER, FLORIDA
AutoCAD SHX Text
ASSOCIATION INC.
AutoCAD SHX Text
FLORIDA KEYS
AutoCAD SHX Text
ENGINEERING
AutoCAD SHX Text
SERVICES
AutoCAD SHX Text
VA2-P
AutoCAD SHX Text
STANDARD NUMBER
AutoCAD SHX Text
DWN BY: CGV
AutoCAD SHX Text
DATE: 06/14/23
AutoCAD SHX Text
APPVD BY: GEJ
AutoCAD SHX Text
SCALE: NTS
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
REVISION:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
REVISION:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
REVISION:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
REVISION:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
REVISION:
AutoCAD SHX Text
SHEET: 1 OF 2
AutoCAD SHX Text
DUCTILE IRON POLE
AutoCAD SHX Text
DOUBLE INSULATOR 12-30° ANGLE
AutoCAD SHX Text 1 - PHASE PRIMARY 24.9/14.4 kV
ITEM PART No. DESCRIPTION QTY,
0. E34259050 46kV INSULATOR) LINE POST \JI K-CL CAS REQ'D) 2
0. E34259025 69kV INSULATOR) LINE POST VERT CAS REQ'D) 2
TBD CLAMP TOP CAS NEEDED) 2
b C7807500 BRACKET) VERTICAL LINE POST INSULATOR 2
C C6380612 BDL T J MACHINE) 3/ 4' x 12' DR REQ'D LENGTH 3 cc C06330003 BOLT) INSUL STUD) 3/4' x 3' x 3/4' 2
CM [34262013 INSULATOR) 3' SPOOL 1
do. [7804500 BRACKET) CURVED BASE CLEVIS 1 cicici C71011551 \J ASHER) CURVED SQ 3' x 3/ 4' HOLE 1 ek C42903075 LOCKNUT) 3/ 4' 5 p C17761500 CONNECTOR) GROUND 2
TBD ARMOR RODS (AS NEEDED)
e DATE: 06 /14 /23 I DWN BY: CCV DUCTILE IRON POLE STANDARD SCALE: NTS I APPV D BY: GEJ
DATE: REVISION: DOUBLE INSULATOR NUMBER
DATE: REVISION: 12-30° ANGLE FLORIDA KEYS VA2-P ELECTRIC COOPERATIVE DATE: REVISION:
ASSOCIATION INC. 1 - PHASE PRIMARY TAVERNIER. FLORIDA DATE: REVISION:
ENGINEERING DATE: REVISION: 24.9/14.4 kV SHEET: 2 OF 2 .~li'RVTr'li'.~
AutoCAD SHX Text
VA2-P
AutoCAD SHX Text
ITEM
AutoCAD SHX Text PART No.
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
QTY.
AutoCAD SHX Text a
AutoCAD SHX Text E34259050
AutoCAD SHX Text 46kV INSULATOR, LINE POST W/ K-CL (AS REQ'D)
AutoCAD SHX Text
AutoCAD SHX Text a
AutoCAD SHX Text E34259025
AutoCAD SHX Text 69kV INSULATOR, LINE POST VERT (AS REQ'D)
AutoCAD SHX Text
AutoCAD SHX Text
TBD
AutoCAD SHX Text
CLAMP TOP (AS NEEDED)
AutoCAD SHX Text
AutoCAD SHX Text b
AutoCAD SHX Text C7807500
AutoCAD SHX Text
BRACKET, VERTICAL LINE POST INSULATOR
AutoCAD SHX Text
AutoCAD SHX Text c
AutoCAD SHX Text C6380612
AutoCAD SHX Text BOLT, MACHINE, 3/4" x 12" OR REQ'D LENGTH
AutoCAD SHX Text
AutoCAD SHX Text cc
AutoCAD SHX Text C06330003
AutoCAD SHX Text BOLT, INSUL STUD, 3/4" x 3" x 3/4"
AutoCAD SHX Text
AutoCAD SHX Text cm
AutoCAD SHX Text C34262013
AutoCAD SHX Text
INSULATOR, 3" SPOOL
AutoCAD SHX Text
AutoCAD SHX Text da
AutoCAD SHX Text C7804500
AutoCAD SHX Text
BRACKET, CURVED BASE CLEVIS
AutoCAD SHX Text
AutoCAD SHX Text ddd
AutoCAD SHX Text C71011551
AutoCAD SHX Text WASHER, CURVED SQ 3" x 3/4" HOLE
AutoCAD SHX Text
AutoCAD SHX Text ek
AutoCAD SHX Text C42903075
AutoCAD SHX Text
LOCKNUT, 3/4"
AutoCAD SHX Text
AutoCAD SHX Text p
AutoCAD SHX Text C17761500
AutoCAD SHX Text
CONNECTOR, GROUND
AutoCAD SHX Text
AutoCAD SHX Text
TBD
AutoCAD SHX Text
ARMOR RODS (AS NEEDED)
AutoCAD SHX Text
ELECTRIC COOPERATIVE
AutoCAD SHX Text
TAVERNIER, FLORIDA
AutoCAD SHX Text
ASSOCIATION INC.
AutoCAD SHX Text
FLORIDA KEYS
AutoCAD SHX Text
ENGINEERING
AutoCAD SHX Text
SERVICES
AutoCAD SHX Text
VA2-P
AutoCAD SHX Text
STANDARD NUMBER
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
REVISION:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
REVISION:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
REVISION:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
REVISION:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
REVISION:
AutoCAD SHX Text
SHEET: 2 OF 2
AutoCAD SHX Text
DWN BY: CGV
AutoCAD SHX Text
DATE: 06/14/23
AutoCAD SHX Text
APPVD BY: GEJ
AutoCAD SHX Text
SCALE: NTS
AutoCAD SHX Text
DUCTILE IRON POLE
AutoCAD SHX Text
DOUBLE INSULATOR 12-30° ANGLE
dd Nut provided b
DETAIL
'A' DETAIL
'B' cc
SEE DETAIL 'B'
4" 4" 1 '-0"
8" c-ek 1 '-0" 8"
SEE DETAIL 'A'
1 '-6" 1 '-6"
4'-0" Position of Guy
( when req' d)
4'-0" ----\ c-d-ek ~
"'cm-do
NOTES:
1. The 5 foot neutral separation is intended to be used for new…