This is a recloser specifications document prepared by Florida Keys Electric Cooperative (FKEC) for their 2027 Recloser projects, which involve installing new recloser systems throughout their service area. The specification details a SEL 0651R22D1GAXAE1112B4XX control unit designed for a nominal voltage of 24.9 kV with a maximum design voltage of 27 kV rms and a rated continuous current minimum of 800A. Key technical requirements include a maximum symmetrical interrupting capacity of 12.5 kA at maximum design voltage, impulse voltage withstand of 150 kV crest, low frequency withstand of 60 kV rms dry and 50 kV rms wet, and ambient operating temperature range of -30°C to 40°C. The equipment must include 40-foot control and potential transformer cables with connectorized interfaces, silicone shed insulators rated for 38 kV minimum with 30 inches creepage on both sides, and 4-hole NEMA copper-tinned aerial lugs. Parameter sensing requires low energy analog (LEA) voltage sensing on both phases with 10 VAC maximum output at a 10,000:1 ratio and 2 percent or better accuracy, plus three-phase internal current sensing at a 1000:1 ratio. Minimum spacing requirements specify 19.5 inches phase-to-phase and 15 inches phase-to-ground.
The specification mandates that all poles include animal guards with the bid identifying the type and including related drawings. Seven lightning arresters total are required—one for each of the six bushings plus one additional unit—manufactured by Siemens (Model 3EK7 210-4AF4-P12 P31 M83) or equivalent, with animal guards provided for the lightning arresters. The document notes this is Revision 3 (October 2025) and emphasizes that any specification deviations required to accommodate lead times or other circumstances must receive prior approval from FKEC engineering. All drawings must be approved by FKEC engineering before production commences. The revision history indicates previous updates correcting spelling, changing bushing covers, removing a potential transformer component, adding spacing requirements, and adding equivalent lightning arrester options.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
RECLOSER SPECIFICATIONS FLORIDA KEYS ELECTRIC COOPERATIVE
Rev 3 October 2025
Control SEL 0651R22D1GAXAE1112B4XX System Voltage and Interruption requirements
Rated Max Design Voltage (kV rms 27 Nominal Voltage (kV rms) 24.9 Max Symmetrical Interrupting at Max Design Voltage 12.5kA Rated Continuous Current minimum 800A Impulse Voltage Withstand (kV) Crest 150 Low Frequency Withstand, Dry, 1 minute (kV rms) 60 Low Frequency Withstand, Wet, 10 second (kV rms) 50 Ambient Operating Temperature -30C-40C
Cables Control Cable Length 40ft Connection from Junction Box: Connectorized Connection at Controller Connectorized Interface 32 Pin
Potential Transformer Cable Length 40ft Interface 3 pin
Customer Interface
Silicone Shed Insulators
(Y) side 38KV min 30 inches creepage
(X) side 38KV min 30 inches creepage
Aerial Lugs
(Y) side 4-Hole NEMA, Copper Tinned
(X) side 4-Hole NEMA, Copper Tinned
Minimum spacing for poles and connections:
Phase to Phase 19.5 inches Phase to ground 15 inches
Parameter Sensing
Voltage Sensing
(Y) Side Type LOW Energy Analog (LEA)
(Y) Side Output 10VAC maximum, 10000:1 ratio
(Y) Side Accuracy 2 percent or better
(X) Side Type LOW Energy Analog (LEA)
(X) Side Output 10VAC maximum, 10000:1 ratio
(X) Side Accuracy 2 percent or better
Current Sensing Type Three internal Ratio 1000:1
All Poles must include animal guards. Bid must specify type and drawing include animal guard.
RECLOSER SPECIFICATIONS FLORIDA KEYS ELECTRIC COOPERATIVE
Rev 3 October 2025
Lighting Arrester Lightening Arresters Quantity Total (7) Recloser One for each bushing, 6 total Manufacture Siemens 3EK7 210-4AF4-P12 P31 M83 or Equivalent
Animal guards shall be provided with the LAs *If specification deviations are required to accommodate lead times or other circumstances, all deviations must be approved by FKEC engineering *Drawings must be approved by FKEC engineering prior to production.
Record of Revisions
Rev 0 Original Rev 1 Corrected spelling and changed CCI XS bushing cover to flip Rev 2 Removed PT. Added spacing requirements. Add equivalent LA.