USDA Forest Service Agency Specific Design Requirements.
MALHEUR S.O. LEASE AGENCY SPECIFIC REQUIREMENTS
8/11/2022 LESSOR ________________ GOVERNMENT:____________ PAGE - 1/57
EXHBIT B
MALHEUR NATIONAL FOREST LEASE
Agency Specific Requirements
USDA Forest Service John Day
Malheur National Forest SO/BMRD
The Agency Specific Requirements (ASRs) do not reduce the minimum requirements contained within the Lease. These ASRs provide specific agency requirements, which may be complementary, more specific, or more stringent than those of the Lease minimum requirements.
GSA Public Buildings Service GSA Public Buildings Service
8/11/2022 LESSOR ________________ GOVERNMENT:____________ PAGE - 2/57
MALHEUR S.O. AGENCY SPECIFIC REQUIREMENTS (ASR)
TABLE OF CONTENTS
1. SECTION 1 - ROOM SCHEDULE AND DETAILS
1.01 INTRODUCTION
1.02 ROOM SCHEDULE
1.03 GENERAL OFFICE
1.04 PRINTER / PLOTTER AREAS
1.05 RECEPTION AREA
1.06 EMPLOYEE RESTROOMS
1.07 MAIN CONFERENCE ROOM
1.08 SMALL CONFERENCE ROOMS
1.09 PRIVATE OFFICES
1.10 FIRE RADIO CONSOLE/DISPATCH AREA
1.11 LEO/EVIDENCE ROOM
1.12 MAIL ROOM
1.13 COPY CENTER/SUPPLY ROOM
1.14 BREAK ROOM
1.15 SHOWERS
1.16 IT ROOM
1.17 SECURE ROOMS
1.18 BUSINESS MANAGEMENT ROOM
1.19 SMART CARD SERVICE ROOM
1.20 HERITAGE ROOM:
1.21 WORKING PARENT ROOM
1.22 UNION ROOM
1.23 HALLWAYS
1.24 WAREHOUSE SPACE
2. SECTION 2 - ADJACENCIES
2.01 ADJACENCIES
2.02 ADJACENCY BUBBLE DIAGRAM
3. SECTION 3 - GENERAL ARCHITECTURAL REQUIREMENTS
3.01 ARCHITECTURAL THEME
3.02 ACCESSIBILITY
3.03 ACOUSTICS
3.04 CABINETRY
3.05 DOOR HARDWARE/SYSTEMS
3.06 MASTER KEYS
3.07 GLAZING
3.08 BENEFICIAL OCCUPANCY (VACATING SPACE)
4. SECTION 4 - GENERAL MECHANICAL REQUIREMENTS
4.01 PLUMBING
4.02 HEATING, VENTILATING, AIR CONDITIONING (HVAC)
5. SECTION 5 - GENERAL FIRE PROTECTION SYSTEM REQUIREMENTS
5.01 GENERAL
6. SECTION 6 - GENERAL SECURITY REQUIREMENTS
6.01 GENERAL
6.02 INTRUSION DETECTION SYSTEMS
6.03 DURESS ALARM
6.04 ACCESS CONTROL SYSTEMS
8/11/2022 LESSOR ________________ GOVERNMENT:____________ PAGE - 3/57
6.05 VIDEO SURVEILLANCE SYSTEM
6.06 ROOM LOCKING SCHEDULE
6.07 LOCKS
6.08 KEYS
6.09 PUBLIC ADDRESS SYSTEM
7. GENERAL ELECTRICAL REQUIREMENTS
7.01 GENERAL ELECTRICAL
7.02 GROUNDING
7.03 WSI (WORKSTATION INTERFACE) DEFINITION
7.04 POWER AND DATA OUTLETS FOR TENANT EQUIPMENT
7.05 SPECIAL PURPOSE OUTLETS
7.06 SURGE SUPPRESSION DEVICES (SPD)
7.07 EMERGENCY LIGHTING
7.08 LIGHTING
7.09 EMERGENCY GENERATOR
8. GENERAL IT AND IT ROOM REQUIREMENTS
8.01 GENERAL IT REQUIREMENTS
8.02 TELECOMMUNICATIONS REQUIREMENTS
8.03 GENERAL IT ROOM REQUIREMENTS
8.04 IT ROOM CONTENTS
8.05 LESSOR FURNISHED EQUIPMENT AND WIRING
8.06 GOVERNMENT FURNISHED AND INSTALLED EQUIPMENT
8.07 IT ELECTRICAL
8.08 UPS
8.09 EMERGENCY POWER OFF SYSTEM (EPO)
8.10 IT FIRE PROTECTION
8.11 IT MECHANICAL
8.12 IT SECURITY
9. SECTION 9 - SITE REQUIREMENTS
9.01 GENERAL SITE REQUIREMENTS
9.02 ARRIVAL SEQUENCE
9.03 VEHICLE CIRCULATION
9.04 PEDESTRIAN CONNECTIONS AND OUTDOOR
9.05 EXTERIOR LIGHTING
9.06 ANTENNA TOWER
9.07 DROP BOX PAD
9.08 LANDSCAPING
10. SECTION 10 – SF81 AND SPACE ALLOCATIONS
10.01 SF81 AND SPACE ALLOCATIONS FORMS
11. SECTION 11 – EQUIPMENT LOAD LIST
8/11/2022 LESSOR ________________ GOVERNMENT:____________ PAGE - 4/57
1. SECTION 1 - ROOM SCHEDULE AND DETAILS
1.01 INTRODUCTION
A. Please refer to the Lease document for the construction standards applicable to the interior tenant area build-out. These standards provide a general outline of the interior build-out requirements.
B. The following spaces will be provided within an approximate 28,831square feet of office space and 2,376 square feet of warehouse space.
1.02 ROOM SCHEDULE
Space # Size Flooring
Add HVAC
Reqts. (See
Details)
Reception Area (which serves both
District and SO).
336 sf Carpet Tile No
Offices (10x10) 3 300 sf (100 sf ea.) Carpet Tile No
Open Office Space 1 8,616 SF Carpet Tile No
FS Law Enforcement Office 1 100 sf Carpet Tile No
Fire Dispatch 1 850 sf Carpet Tile No
Conference Room (detail in Sec. 1.02) 11 3160 sf Carpet Tile Yes
Collaboration Space (detail in Sec. 1.02) 23 2551 sf Carpet Tile
Break Room 2 600 sf Tile Yes
Mail Room 1 200 sf Carpet Tile No
Copy/Print Room 4 400 sf (100sf ea.) Carpet Tile Yes
Heritage Room 2 300 sf (150 sf ea.) Tile No
Aerial Photo/GIS/File Bar 1 200 sf Carpet Tile No
Special Purpose Room (ie. Nursing) 2 400 sf (200 sf ea.) Carpet Tile No
Designated Storage Room (Forest
Sup/Timber/Employee Assoc.)
300 sf (100 sf ea.)
Carpet Tile No
Designated Storage Room (Fire) 1 200 sf Carpet Tile No
SMART card room 1 80 sf Carpet Tile No
Warehouse Storage 1 2160 Sealed
Concrete Yes
Employee Restrooms sets
Per code and accessibility standards
Tile Yes
Unisex Restroom (by Reception) 1 75 sf Tile
Mud Room 1 488 sf Tile
Showers 2 400 sf (200 sf ea.) Tile Yes
IT Room 2 400 sf (200 sf ea.)
Nonconductiv e Tile Yes
Note: Space sizes are shown in the attached SF81 and space allocations. Circulation factors are in addition to space sizes, as shown in the attachment.
8/11/2022 LESSOR ________________ GOVERNMENT:____________ PAGE - 5/57
Workstation/Lateral Storage Space # Size Flooring
Add HVAC
Reqts. (See
Details)
Regular Work Station (6x8) 145 6960 sf (48 sf ea.) Carpet Tile No
Touchdown Work Station (4x6) 11 264 sf (24 sf ea.) Carpet Tile No
Field Crew Space (SO) 1 400 sf Carpet Tile No
Field Crew Space (BMRD) 1 300 sf Carpet Tile No
Lateral Storage 9 270 sf (30 sf ea.) Carpet Tile No
Conference Room Space # Size Flooring
Reqts. (See
Details)
Huddle Meeting Room (10x10) 4 400 sf (100 sf ea.) Carpet Tile No
Small Meeting Room (12x15) 2 360 sf (180 sf ea.) Carpet Tile No
Medium Meeting Room (20x15) 2 600 sf (300 sf ea.) Carpet Tile No
Large Meeting Room (20x30) 3 1800 sf (600 sf ea.) Carpet Tile No
Collaboration Space # Size Flooring
Reqts. (See
Details)
Focus Room (5x10) 6 300 sf (50 sf ea.) Carpet Tile No
Focus Room (10x10) 5 375 sf (75 sf ea.) Carpet Tile No
Train Cars (5x20) 2 200 sf (100 sf ea.) Carpet Tile No
Tall Work Counters (10x15) 2 300 sf (150 sf ea.) Carpet Tile No
Landings (10x20) 4 800 sf (200 sf ea.) Carpet Tile No
Team Lounges (12x12) 2 288 sf (144 sf ea.) Carpet Tile No
Team Tables (12x12) 2 288 sf (144 sf ea.) Carpet Tile No
1.03 GENERAL OFFICE
A. The lessor shall route telephone/data/radio cable throughout the space as required by the Forest Service to meet the needs of the systems.
B. See section 4, 5, 6, 7 & 8 below for electrical and electronic systems requirement for details.
C. Workstations shall be located on the perimeter of the building as much as possible to maximize exposure to windows and natural lighting. Touchdown Stations may be designed as a combination of individual spaces or collective (bullpen) areas. Each work station shall include a work station interface WSI as follows:
8/11/2022 LESSOR ________________ GOVERNMENT:____________ PAGE - 6/57
D. Each Work Station Interface (WSI) shall consist of power and data outlets at each user workstation and all other locations where a WSI is specified. Each WSI shall include:
1. One 20A duplex computer receptacle, 6A loading. Two workstations per 20A circuit, to computer power panel
2. One 20A duplex normal power receptacle, 4A loading. Four workstations per
20A circuit to normal power panel.
3. 2 – CAT6 data jacks home run to IT room patch panel.
E. Provide wiring and data ports for Wireless Access Points (WAP) that will provide full building coverage. Each WAP location shall have two CAT6A data jacks and CAT6A data cable for both FS WAP and open internet WAP home run to IT room patch panels.
Provide 20 dt of coiled extra cable to allow WAP placement. The Government will provide WAP placement locations. These need to be identified in DID phase.
F. If lease includes use of existing buildings, it will provide new carpet and paint on walls.
G. Water to the site must meet Public Drinking Water Standards as regulated by the state of Oregon.
H. Space provided must be ground floor or above.
I. Provide at least 2 frost free hose bib/cocks with vacuum breakers at locations to be determined by government.
J. Roof shall be designed to prevent snow from sliding into foot traffic areas.
K. Floor covering shall be carpet unless otherwise stated. Floors shall provide a noise reduction coefficient (NRC) of 0.15
L. Final design for building shall be approved by the government.
M. Lessor shall provide to the government results of asbestos survey in building and abatement procedures.
N. All doors shall have hinge pins and hasps to be installed to prevent unauthorized removal by using spot welds or pinned mounting bolts. Hinges on the secure side of the enclosed space do not need this requirement.
O. Lockable doors shall have separate keyed locks operable with master key, except LEO
Offices and LEO Storage areas, and Heritage Storage Areas.
P. A fire sprinkler system that meets current City Building code and NFPA standards is required in this building, see section 5 for details on alarm system requirements.
Sprinkler system and alarm audible tests which interfere with employee work shall be coordinated with the LCO. When possible, tests should be run during business hours when a Point of Contact (POC) is needed. Under no circumstances shall POCs be required to attend testing on holidays.
Q. Garbage is considered a utility in the lease and is the responsibility of the lessor.
R. WSI shall be provided for wireless in small conference, large conference, and warehouse.
1.04 PRINTER / PLOTTER AREAS
A. See Equipment Load List, Section 11, for power and data requirements.
8/11/2022 LESSOR ________________ GOVERNMENT:____________ PAGE - 7/57
B. 10 printer/plotter areas will be located throughout the open office space with one in the main conference room.
C. Each area will require one 20 amp 120 volt dedicated fourplex electrical outlet adjacent to one data outlet with four drops. Locations to be determined in DID.
D. Electrical and data outlets shall be placed at 42” above floor.
1.05 RECEPTION AREA
A. See Equipment Load List, Section 11, for details.
B. The architectural design will achieve an open, warm feeling with rustic elements composed of natural materials consistent with the Rocky Mountain Province themes found in the Built Environment Image Guide. Provide large areas of natural light.
Provide elements of local natural materials and an option for vaulted ceilings.
C. Provide lock out switch for front reception area to lockout external doors (panic button).
D. The separation of public and private space is a key organizing element for the building.
While there are a large number of visitors to the building, relatively few interact with staff beyond the front desk. In cases where such interaction does occur, staff will proceed to the reception area where meetings can be held or escorted to meeting room or conference room.
E. The building lobby shall be designed to divide public and employee spaces, secure and non-secure areas. The receptionists shall have an emergency egress (escape) door located behind the desk that exits into a non-public corridor. If escape door is activated, access to secure office area shall automatically lock. Visitors shall have only one access point to the facility and shall make contact with a receptionist prior to being allowed within the facility.
F. Access to secure office area shall be by a locked door controlled by a push button at the reception desk connected to access control system. Also provide the ability to unlock the door by key in case the electronic system is compromised.
G. Duress alarm shall be tied into IDS local bell/strobe and remote callout per general security requirements. See Electronic systems below for additional detail.
H. Provide a mix of lighting in the Reception Area to create an inviting atmosphere and highlight various displays and products for sale. Use track lighting for the walls and displays; use indirect lighting in the public area; and use direct lighting as needed behind the desk. Use energy efficient fixtures and lamps (LED Preferred).
I. Information Counter: Provide a bi-level reception counter or two ABA compliant counters, large enough to place a full map (that is placed to one side rather than face-
on) with computer and telephone connections (List Details) for 2 Information Clerks.
Counter shall be designed to store maps, visitor information, cash drawers, miscellaneous literature and permits. Coordinate material finishes with reception area.
The lower level of the bi-level shall meet ABA requirements. Security façade will be provided on counters to inhibit easily accessible entry over counters.
J. Workspace behind Information Counter: shall accommodate two work stations with computer and telephone connections, space for 2 safes hidden within building cabinetry, supply cabinet, 2 drawer locking file cabinets, and a 6 shelf book shelf.
Exact layout and dimensions will be determined during DID. Provide the following
8/11/2022 LESSOR ________________ GOVERNMENT:____________ PAGE - 8/57
equipment power and data connections, see Equipment Load List, Section 11, for details:
1. 2 POSS computers with all required components,
2. 1 - Copy machine,
3. 1 - Printer
4. 1 - Fax machine
5. Video Surveillance System monitor and operator controls (see section 6 for details).
K. Displays: Provide space in the reception area for displays and books which are available for sale at the information counter. A glass display case with shelves and a tack-able surface shall be designed to match the information counter. This will be placed against one wall. Provide space for 3 wall mounted display cases, one built in map cabinet. Provide space for TV touch screen display with printer.
1. Provide as needed WSI telecommunications/electrical outlet in reception area for computer connections.
2. Waiting Area: The public waiting area should allow for 5 to 10 people to stand.
Additional space for seating shall be provided. Cushioned chairs, couch, or bench, end tables and plants will be provided by the Government. Provide 2
WSI telecommunications/electrical outlet in waiting area for computer connections.
L. The main lobby should accommodate visitors by providing information facilities, waiting areas and access to non-public areas. Space will be provided for public seating within this area.
M. Provide a WSI telecommunications/electrical outlet for public phone in reception area.
1.06 EMPLOYEE RESTROOMS
A. Arrange bathroom entrance door to provide privacy to someone in the restroom.
B. Provide a minimum of 1 GFCI outlet at wash basin locations for each restroom.
C. Provide at least 1 GFCI outlet per 4 feet of counter length, equally distributed above the counter.
D. Urinals shall have privacy partitions.
E. Provide a privacy door lock that shows “Occupied” when in use and keyed to master lock set.
F. Provide foot operated door openers
G. See Mechanical Section for Plumbing and HVAC requirements. Provide exhaust from restrooms in compliance with the Oregon State Mechanical code. Exhaust shall be continuous during occupancy hours and shall be interfaced with the building automation system for scheduling.
H. Arrange bathroom entrance door to provide privacy for occupants.
1.07 MAIN CONFERENCE ROOM
A. The conference room shall be capable of being divided with movable partitions into 3 spaces. Final dimensions to be coordinated during DID. Conference room shall have a width to length ratio not to exceed 1:1.5. The divider shall provide an STC of 50.
8/11/2022 LESSOR ________________ GOVERNMENT:____________ PAGE - 9/57
B. Provide a separate entry for each section of the room. Each door shall have a window lite for visibility through the door.
C. Provide separately zoned regulated HVAC unit for each of three conference rooms and.
Ceiling exhaust fan capable of exchanging air as required by code and must be without objectionable noise. There shall be a separate wall mounted thermostat which allows manual control of temperatures in the conference rooms.
D. Provide a minimum 100 sf storage area adjacent to and accessible from the conference room for storage of tables, chairs, and AV equipment. Use double doors to access storage.
E. Dimmer switches shall be two or three way as required to meet operation specifications. Lighting shall be controlled so that each section of the three divided conference room is switched independently. Controls for each section shall be located in that area.
F. Design conference room lighting to various uses from computer training sessions to workshops to lectures and presentations. Use combinations of direct, indirect, valance and track lighting. Dimming required.
G. Provide separate lighting dimmer controls at front of each divided area from rest of lighting in that space.
H. Provide an 8-foot x 8-foot floor grid layout for the telecommunications/electrical shall be required for this room.
1. Provide recessed floor power/data outlet boxes with cast metal 400# load rated covers. Provide for each box a WSI consisting of 4 CAT6 RJ-45 data jacks in each floor outlet box and two 20 A duplex outlets fed from computer power panels.
I. A/V SYSTEM FOR MAIN CONFERENCE ROOM
1. See attached GSA document for detailed 4K A/V system design elements for large conference room and small conference rooms. This GSA attachment needs to be modified for three inputs and three outputs for large conference room. All
Projectors, TV’s, controllers, cables and HDMI jacks shall be rated for 4K video transmission for all devices. Attach this GSA document also as supplemental to these requirements.
2. The intent of the A/V system is to allow the large 3000 SF conference room to be subdivided into three spaces. Three spaces shall be used as single meeting room or larger spaces by opening wall portions and have separate A/V meetings with up to four independent HDMI sources to a central A/V controller.
3. Provide an audio / visual system for large conference room in each third of the room with three separate inputs and three separate outputs from a rack mounted controller independently controlled.
4. A/V system will have a 4K controller in a rack mount which will allow any input from wall mounted HDMI jacks in each of the three spaces to connect to any of three outputs, one ceiling projector or (2) wall mounted GFP TV’s.
5. A/V rack will be located in room and contain both video controller, audio controller and audio amplifiers. Provide a dedicated circuit from computer power panel for this A/V rack equipment. Provide a cooling fan in rack.
8/11/2022 LESSOR ________________ GOVERNMENT:____________ PAGE - 10/57
6. Provide wall mounted A/V touch screen control panels in each of the three main conference room spaces to control all inputs and outputs via main A/V controller.
Each space shall have a wall mounted controller to allow any HDMI input with audio and video signal from a Government laptop to output a combined wall mounted A/V HDMI jack for each of the three video devices. Any of the three wall mounted controllers can control entire system and select any input(s) to go to any output or combination of outputs.
7. CEILING PROJECTOR Provide a 4K ceiling mounted projector and mounting hardware with projector beam throw size to cover area for motorized drop down screen. Limit lower portion of video to about +36” AFF to prevent persons in front row from obstructing projector beam throw. Power projector from computer power panel. Provide adequate lumen output to cover wall screen.
8. AUDIO SYSTEM Each third of large conference room shall have a separate stereo ceiling mounted speaker systems connected to triplex audio amplifiers in each third of the room. The audio system shall be controlled by the main A/V controller and shall route audio portion of HDMI signal inputs to each output for audio so audio for selected video output devices is connected to that selected device ceiling mounted speakers. Audio shall follow video signal to selected projector or wall mounted TVs.
9. A/V CONTROLLER INPUT JACKS: Provide in each of the three spaces a wall mounted HDMI jack and HDMI cable +18” AFF connected to A/V controller for connection of government laptop for an input device or other HDMI device such as a video player.
a. Provide a spare HDMI input jack for a CATV box and a RG-6 coax cable jack at A/V controller for a future CATV box connection provide power outlet at A/V controller for CATV box. Coax cable to terminate in IT room CATV coax patch panel.
10. OUTPUT DEVICES: Provide in the large conference room the following video output devices in three spaces:
a. 1 - Ceiling mounted projector 4k resolution to project to wall mounted in largest portion of room. Provide a motorized screen to cover overheard ceiling projector field of view, see below for screen details.
b. 2 - Wall mounted 4K TV’s Govt Furnished Property (GFP) with wall blocking and a mounting system for TV’s up to 72”, with 3 HDMI inputs in each of two spaces in main conference room.
c. At each wall mounted TV provide 1 wall mounted direct connect under
TV, an HDMI input jack and one RG-6. Each TV shall have a minimum of
3 HDMI inputs, one from main A/V controller, and one local HDMI input cable routed to a wall box under TV with HDMI female jack for local use only from a laptop or other HDMI device. Third HDMI input jack on TV is spare.
d. Provide 120VAC power from computer panel for projectors and wall mount TV’s
J. Provide a WSI telecommunications/electrical outlet every 8 linear feet along the wall consisting of 2 CAT 6 data jacks and one 20A computer power outlet and one 20A normal power outlet.
8/11/2022 LESSOR ________________ GOVERNMENT:____________ PAGE - 11/57
K. Provide additional two WSI outlets by each side of a white board or screen location on the walls.
L. Provide 4 CAT6A data jacks – two in each dividable room – placed either high on the wall or in the ceiling for wireless access points (WAP). Further discussion to be had at
DID.
1. Each divisible room shall have power and satellite connection on one wall in each section to accommodate government furnished video screen VTC capable which may be broadcasted simultaneously, individually. Walls shall be structurally designed to allow mounting of 52” flat screens.
M. Three white marker boards shall be located at one end of the conference room – one in each partitionable section. Approximate size of the board shall be 48 inches high by 96 inches wide.
N. Provide a projector screen with automated operation controls in each of the three divisible room sections. Screen shall be contained above suspended ceiling when not in use. Screen should be run with a remote, key operated, three-position control switch mounted in the wall next to the screen. Provide support structure and video/data and power wiring to ceiling space in the center of the room section with the projection screen.
O. An extruded aluminum and cork tack strip shall run around the room at 4’ and 6’ above the finished floor. A chair rail shall run continuous around the room at 30” above the finished floor.
P. Shall have no columns or other support structures within them.
Q. Any conference room with a window shall be provided with black out blinds.
R. Conference room will be in close proximity to reception area, break room and restrooms.
S. Minimum ceiling height is 10’.
1.08 SMALL CONFERENCE ROOMS
A. Shall have power and Ethernet connection on one wall for Wall mouned GFP TV
B. Provide a WSI telecommunications/electrical outlet every 8 linear feet along the walls.
C. An 8-foot floor grid layout for the telecommunications/electrical shall be required for this room.
1. Provide a combination outlet box with power supply and telecommunications outlet/connector that will allow the use of 2-4 computers, or 2 phones and 2 computers from each box. See IT and Electrical design guidelines for details
2. Provide recessed floor power/data outlet boxes. Provide 2 WSI consisting of 4
CAT6 RJ-45 data jacks in each floor outlet box and two 20 A duplex outlets fed from computer power panels.
D. Provide mounting hardware for a wall mounted a GFP 4K TV in each small conference room with the following wall mounted connections
1. TV wall mounting bracket for up to a 72” TV
2. Power outlet behind monitor
3. HDMI wall mounted jack +18” AFF routed thru wall up to TV HDMI input jack.
8/11/2022 LESSOR ________________ GOVERNMENT:____________ PAGE - 12/57
E. Design conference room lighting to various uses from computer training sessions to workshops to lectures and presentations. Use combinations of direct, indirect, valance and track lighting. Dimming is required. Dimmer switches shall be two or three way as required to meet operation specifications. Provide separately controlled lighting in front of room for presentations from rest of room.
F. Provide one tack board in each room.
G. One to be located near Forest Supervisors office and one near the District Ranger’s office, as approved by the LCO.
H. Final dimensions will be decided during the DID.
I. All to be located in secure office space.
J. Small conference rooms shall provide an STC of 50 for doors.
1.09 PRIVATE OFFICES
A. Provide a minimum of 4 private offices for the primary Forest line officers and FS
LEO, (100 square feet each). All walls to have data and electrical outlets WSIs at 8’ spacing on walls. Provide one tack board in each office. Offices shall be solid core wood door with side-lite. Offices shall provide an STC of 50 for doors and walls.
Place these offices within the staff spaces.
B. Room configuration shall accommodate a custom 2’ D x 7’ W stand up desk.
C. Provide lockable doors for all private offices.
D. For Law Enforcement Offices, wall partitions shall continue all the way to ceiling joists.
E. Locations will be specified during DID.
F. Rooms shall be secured with a hard key.
G. STC of 45 for doors.
1.10 FIRE RADIO CONSOLE/DISPATCH AREA
A. Dispatch workstations will not follow space policy; they are a specific size to house
Dispatch consoles. In space planning, provide an open office environment to allow personnel to see across the room easily.
B. Twelve workstations and 6 consoles with 2 lead stations shall be provided in this space.
C. Use 64 SF as a planning estimate for each Dispatch workstation. Each workstation is roughly 8’ x 6’ and includes the following:
1. Dual monitors with mount.
2. Additional touchscreen monitor.
3. Portion of desk is adjustable height for standing.
4. Locking personal filing cabinet at each desk.
D. Dispatch center will require a trailer-mounted emergency generator for 24 hour operations in the event of power outage. Provide emergency power connection for lighting, IT room and all IT equipment, and HVAC for IT and dispatch center work area, restrooms, and break room.
E. Provide separate HVAC system for 24 hour operations.
F. This room shall have a minimum of one wall for windows and two walls for display.
Wall maps to be illuminated by lighting on a separate switch.
8/11/2022 LESSOR ________________ GOVERNMENT:____________ PAGE - 13/57
G. Provide 4 dedicated power computer outlets per workstation. Each workstation will require 6 data jacks and #6 ground to Dispatch Room power panel. Dispatch Center power panel shall be fed from IT room power panel.
H. Provide small break room area within the Dispatch Center. Break room to include the following:
1. 20 inch wide double basin stainless steel sink and all associated plumbing.
2. Plastic laminate countertop with integral backsplash/base cabinets and concealed hinges and staple pulls. Wall cabinets shall be provided above base cabinets.
Cabinets to be custom grade.
3. Space for 1 full size refrigerator and 1 full sized microwave.
4. 4 dedicated duplex electrical receptacles outlets for appliances (refrigerator, microwave, coffee maker, and one additional). Provide 2 additional duplex electrical receptacles above the counter (GFI as required by code).
I. Provide structural backing, power and data connections for a Government provided for two 65” flat screen TV’s. Location of flat screen will be determined at DID.
1. Provide a duplex power outlet, CAT 6 data jack and RG-6 coax cable jack behind
TV and cables home run to IT room for connection for internet connection or cable or SAT TV box. Provide an HDMI 4K data cable from back of TV into wall and conduit down to a 4K HDMI recessed jack below TV to plug in computer for display on TV.
J. A ‘blank’ wall 32’ X 8’ with no switches, vents or other appurtenances, for maps, boards etc. It shall have wall outlets every 8 feet or as otherwise located in the DID.
K. Exterior door controlled with key card with hard key back up and shall have a security window in door. Audible Buzzer (similar to doorbell) with lock release located in dispatch. This will allow Dispatch to provide access to crews and fire fighters from dispatch room.
1.11 LEO/EVIDENCE ROOM
A. Include evidence storage and equipment locker attached and accessible from Private
LEO office.
B. The walls, floor and ceiling of the evidence room need to be hardened to reduce unauthorized access. This room shall not be on an outside wall.
C. Provide solid, lockable door with hard key and unique lock set.
D. Provide 1 duplex outlet on each wall.
E. Shall be maintained in negative pressure with no return air to the common HVAC system. Evidence room shall ventilate to the outside per OSHA.
F. Rooms shall provide an STC of 45 for doors.
1.12 MAIL ROOM
A. This space should be easily accessible by all building occupants. Windows are required.
B. Design room for a Government provided high load capacity shelving system for supplies.
C. Provide two WSI outlets on each wall. Provide 1 duplex electrical outlet every 4 feet along walls.
8/11/2022 LESSOR ________________ GOVERNMENT:____________ PAGE - 14/57
D. Provide data outlets for all equipment in this room requiring a telephone or network connection.
E. Accommodate 3 WSI workstations on walls in addition to the requirements listed below. Provide space for route boxes and at a minimum 100 sf of high density storage.
The following equipment will be in this room with power and network connection:
1. Postage Machine
2. Label Maker
3. Printer/Copier
4. Fax Machine
F. Locate the mail room away from the IT room and the LEO offices.
G. Design separate heating, ventilation, and air conditioning (HVAC) units for the mail room in order to prevent the contents of chemically contaminated packages from being distributed throughout the facility. Install an exhaust system containing a purge fan to negatively pressurize the space with minimum of 15 air changes per hour to remove any contaminants that may be diluted in air. Purge fan shall be energized locally with a manual push button.
1.13 COPY CENTER/SUPPLY ROOM
A. See Equipment Load List, Section 11, for all equipment loads
B. Locate the copy center to be easily accessed by all building occupants, but near the mail room. Windows are not required.
C. Provide space for 2 large copiers and a plotter.
D. Provide 4 dedicated 120V receptacles 20A and network connections. Locations to be determined in DID.
E. Variable fan on a 30 minute timer initiated by a push button. Ventilate to outside. Supply air shall not be returned to building HVAC system.
1.14 BREAK ROOM
A. See Equipment Load List, Section 11, for details
B. General:
1. Provide at least one area per floor that serves as a break room for the occupants, dimensions to be determined during DID.
2. Break rooms shall be at least 200 SF. Current breakroom configurations are adequate.
C. Large Break Room near Main Conference Room.
1. Provide an area near the largest conference room that serves as a break room for the occupants, dimensions to be determined during DID.
2. Space shall be equipped with a minimum of 30 linear feet of plastic laminate countertop with integral backsplash/base cabinets and concealed hinges and staple pulls. Include a 20 inch wide double basin stainless steel sink with 8” goose neck faucet, sprayer and instant hot water faucet and all associated plumbing. Include space for four full size refrigerators. Approximately 30 feet of wall cabinets shall be provided above base cabinets. Division of countertops and refrigerators per break room to be identified during DID.
3. Provide three duplex electrical receptacles (determine locations in DID).
8/11/2022 LESSOR ________________ GOVERNMENT:____________ PAGE - 15/57
4. Provide four dedicated duplex electrical receptacles for up to 4 refrigerators and four dedicated duplex electrical receptacles for vending machines. Provide two dedicated electrical receptacles for microwave ovens above the counter. Provide two additional dedicated duplex electrical receptacles above the counter (GFI as required by code). Provide a duplex electrical outlet every 8 linear feet along the walls without cabinets.
5. Provide plumbing for at least one vending machine and refrigerators.
6. 2-4 foot X 4 foot cork tack boards shall be provided and installed in locations to be determined during DID.
7. Layout of space(s) to be determined during DID.
1.15 SHOWERS
A. Provide 2 gender neutral shower stalls.
B. Provide 1 ABA compliant restroom/shower combo.
C. Provide visual privacy between the access door and shower stall, towel hooks, bench and base cabinet with sink and mirror. Design shower rooms as “wet” rooms with necessary waterproof materials and drainage. Avoid use of shower curtains for privacy or delineation.
D. Provide a GFCI outlet next to sink and one on wall in shower rooms and restrooms.
E. Provide low flow shower heads not exceeding 1.3 GPM flow.
F. Provide a minimum 50 SF space for changing in room in addition to the bench and changing area within the shower, themselves.
G. Provide towel hooks or racks to handle 6 towels in each shower room.
H. Exhaust fans shall operate on motion sensors. Fan to turn on with space occupancy followed by a 30 minute delay off. Do not return air from showers to the building air supply.
I. Doors will be solid with privacy “Occupied” locks and hard keyed to master lockset.
1.16 IT ROOM
A. The IT room is defined in its own section. Please see that section for details.
1.17 SECURE ROOMS
A. Doors: Hinges, pivots, and pins shall be installed in a manner which prevents removal when the door is closed and locked. These shall be lockable with each having a separate keyed lock.
1.18 BUSINESS MANAGEMENT ROOM
A. Locked and a minimum of 100 sf.
1.19 SMART CARD SERVICE ROOM
A. Provide 80 SF interior to the building or on an exterior wall without windows.
B. Door shall be solid with ePACs Lock and hard keyed to a unique lockset. Door hinges, pivots, and pins shall be installed in a manner which prevents removal when the door is closed and locked.
C. Wall partitions shall continue all the way to ceiling joists.
D. Space will meet HSPD-12 requirements.
8/11/2022 LESSOR ________________ GOVERNMENT:____________ PAGE - 16/57
E. Provide space for a Touchdown Station and guest chair.
F. Provide 2 wall mounted WSI configurations.
1.20 HERITAGE ROOM:
A. Shall be locked with hard key.
B. Can be located in the warehouse area.
1.21 WORKING PARENT ROOM
A. The location and design of this room will be determined at DID.
B. This room will support a Touchdown station, mini-bar, lounge chair, crib and changing table.
C. Provide a ceiling mounted energy recovery exhaust/make-up air unit with wall mounted on/off switch to relieve odor when needed.
D. Provide one WSI outlet on 2 walls.
E. Door shall have a side lite with privacy film and privacy “Occupied” lock keyed to master.
F. Provide space, dedicated electrical outlets and plumbing for a 36” built in base cabinet with a 15” x 15” single sink, microwave and coffee pot on the counter and a 1.7 CF refrigerator located underneath.
1.22 UNION ROOM
A. This room will be locked with a hard key.
B. Two WSIs and data equally space, located during DID.
1.23 HALLWAYS
A. All hallways shall be approximately 5 feet wide and provide for disabled access throughout office.
1.24 WAREHOUSE SPACE
A. All warehouse space shall be ground level.
B. Floor shall be sealed concrete with a live load capacity of 250 lbs. psf.
C. Ceiling height shall be 10’ to the lowest point of obstruction.
D. Ceiling and walls may remain unfinished.
E. The warehouse shall be insulated and have walls and ceiling.
F. Space in warehouse must be clear span not containing any pillars or supports.
G. Interior lighting (See general lighting required in section 6 for standards).with a minimum lighting level of 30 foot candles measured at floor level is required. Lighting shall be controlled with switches at each door.
H. Warehouse to generally store low hazard materials.
I. Provide as much uncluttered wall space as possible.
J. One truck bed height loading dock with adjustable loading platform shall be provided that accommodates semi-trailers and office supply delivery trucks, K. Shall have an overhead door to the exterior minimum 9 ft. X 9 ft. with automatic operation or manual operation requiring no more than 5 pounds to open and have interior lockable controls. Door shall be constructed of steel of a quality meeting heavy
8/11/2022 LESSOR ________________ GOVERNMENT:____________ PAGE - 17/57
duty commercial standards. Door shall not completely block overhead lighting when open.
L. A concrete apron with a minimum width 2’ greater than the overhead doors shall extend 12 feet in front of the warehouse overhead door.
M. All personnel doors shall have a 5’ x 5’ concrete slab adjacent to the building and directly in front of the door.
N. Person door linked to building access control and audible buzzer linked to administrative staff area.
O. Door Controlled with key card with hard key back up.
P. Door to have security window.
2. SECTION 2 - ADJACENCIES
2.01 ADJACENCIES
A. The schematic below is representative of the layout required for this Space. The Lessor is responsible for using the room schedule in Section 1.02 and this layout to adapt the
Government’s requirements to the Space. Specific questions regarding the layout should be directed to the Lease Contracting Officer for resolution. The Government shall not be responsible for errors, omissions, or assumptions made by the Lessor in the adaption of the Government’s requirements to the Lessor’s Space.
1. Locate warehouse next to mail room and copy room.
2. Business management secure room within/next to warehouse. (Lockable)
3. 1 small interview room adjacent to or within BMRD area. Provide same power and data as enclosed office space.
4. If 2 story building, at least 1 small interview room on each floor.
5. Locate the main conference room near the break room
6. All private offices should be located next to their respective staff spaces.
8/11/2022 LESSOR ________________ GOVERNMENT:____________ PAGE - 18/57
2.02 ADJACENCY BUBBLE DIAGRAM
8/11/2022 LESSOR ________________ GOVERNMENT:____________ PAGE - 19/57
3. SECTION 3 - GENERAL ARCHITECTURAL REQUIREMENTS
3.01 ARCHITECTURAL THEME
A. It is important that the building fits into the local community context while still presenting the Forest Service as a natural resource agency. Natural materials should be incorporated into the building wherever possible. Allowances to maintain the existing architecture where existing buildings are used, may be allowed as determined by the
LCO.
B. Consider use of the Forest Service Built Environment Guide and specifically the Rocky
Mountain Province.
1. General: Structures of the Rocky Mountain Province should match the impressive scale and texture of their setting. Use materials found in the landscape, and make substantial structural members visible.
2. Sustainability: Use local and indigenous building materials. Emphasize water conservation in fixtures, water harvesting, xeriscaping, and graywater recycling.
3. Materials: Use natural, non-toxic building materials that require little maintenance. Use materials that are energy efficient to produce and transport.
When using synthetic materials, select materials that resemble natural materials and are durable.
a. Material should be appropriately scaled to the size of the building, the surrounding natural environment, and the overall complex.
b. Express the structure by exposing wood beams, trusses, brackets, or framing.
c. Use stone, wood, heavy timber, and other natural materials when they are available and practical to use.
d. Exterior finish materials should be durable and low maintenance, with detailing that protects materials that are vulnerable to deterioration.
4. Color: Dominate the palette with earth tones. Use color schemes that are inspired by rock outcrops, trees, and colors found on the forest floor. Use accent colors drawn from accents of the setting.
3.02 ACCESSIBILITY
A. All exterior and interior design components shall meet Architectural Barriers Act
(ABA) requirements.
3.03 ACOUSTICS
A. Provide soundproofing materials such as mineral fiber acoustic insulation, caulking, and construction techniques specifically made for interior walls. Rooms with acoustic treatment shall extend from floor to ceiling, as well as the ceiling. The minimum
Sound Transmission Class (STC) shall be 45. Room doors shall have a minimum STC of 45.
B. Provide acoustic treatments for walls and ceilings of the following areas:
1. Reception Area
2. Conference and Huddle Rooms
3. Rest Rooms and Showers
8/11/2022 LESSOR ________________ GOVERNMENT:____________ PAGE - 20/57
4. Private Offices
5. Dispatch
6. IT Room
7. Smart Card Room
8. Between Floor and Ceiling Assemblies.
3.04 CABINETRY
A. All cabinets and counters shall have solid wood frames and doors with plywood boxes, light color, heavy duty hardware, and standard size.
B. Cabinets may be prefabricated or site built, as long as they meet standards.
3.05 DOOR HARDWARE/SYSTEMS
A. A minimum of one employee entrance shall have accessible power door operator. Specific doors shall be designated during DID.
B. Employee external doors shall have card key readers, door pushbuttons, magnetic door position sensors, and IDS magnetic switches. Interlock access control system to door operators.
C. The main public entrance shall have at least one door with an accessible power door operator, interlocked with access control system.
D. Operator at employee door shall utilize a separate push button for each door in the vestibule.
E. Interior doors to be equipped with card key readers shall be designated during DID. (IT room, Front lobby door, etc.)
F. All exterior personnel doors to have security windows, hard key and key card access, which will include break room, dispatch and warehouse, with the exception of front vestibule public entrance.
3.06 MASTER KEYS
A. Provide 20 master keys
3.07 GLAZING
A. Glass shall meet performance level 3b on the ground floor of the building, and ‘2’ for the LEO.
B. Window treatments
1. All interior and exterior windows, except those in the bathroom, shall have window blinds.
2. Specific brands, styles, colors, material, etc. shall be determined during DID via samples or catalog data for Government approval.
3.08 BENEFICIAL OCCUPANCY (VACATING SPACE)
A. If the new lease is located in space currently occupied by the Forest Service, relocation of the Forest Service into swing space shall serve as ‘vacation’ of the space for approval purposes.
8/11/2022 LESSOR ________________ GOVERNMENT:____________ PAGE - 21/57
4. SECTION 4 - GENERAL MECHANICAL REQUIREMENTS
4.01 PLUMBING
A. A chilled, filtered drinking fountain shall be located outside of the restrooms, minimum of one on each floor. The fountain near the employee’s restroom shall include a filtered, sensor activated water bottle fill station, with a visual filter sensor, at least one per floor. Filters will be changed per manufacturer’s direction.
B. Provide low flow plumbing fixtures throughout the facility.
C. Domestic water heaters shall meet current Oregon Energy Efficiency Specialty Code
(OEESC) Table 504.2 as a minimum.
4.02 HEATING, VENTILATING, AIR CONDITIONING (HVAC)
A. Areas requiring only part time occupancy, with conditions being maintained at the unoccupied level the remainder of the time, to be isolated from the full time occupied area. Use either separate equipment or zones to meet the needs of these areas.
B. Areas having excessive heat gain or heat loss, seasonal imbalances, or affected by solar radiation at different times of the day, shall be independently zoned or controlled.
C. AIR DISTRIBUTION DUCTWORK:
1. Fresh air intakes shall be relocated, extended, or secured to prevent easy ground or roof access. Locate intakes on the roof or as high as practical. Locating intakes high on a wall is preferred over a roof location.
D. RESTROOMS, SHOWERS, COPY, SUPPLY, JANITOR AND OTHER SPECIAL
PURPOSE ROOMS
1. Provide exhaust from restrooms in compliance with the Oregon State ventilation code. Exhaust shall be continuous during occupancy hours and shall be interfaced with the building automation system for scheduling. Provide an override switch for manual controls.
2. Address each room, heating, cooling and exhausting fumes in a separately zoned or dedicated HVAC system, as required.
3. Exhaust fans shall be controlled by a countdown timer, on/off switch, or by an appropriate means. Fans to exhaust to the outside.
4. Toilet and shower room exhaust fans to operate on motion sensors. Fan to turn on with space occupancy followed by a 30 minute delay off. Do not return air from toilet rooms into the building air supply.
5. Special Purpose Rooms - Address each room, heating, cooling and exhausting fumes as required. Provide automatic controlled, timer controlled or switch controlled exhaust fans as appropriate. Fans to exhaust to the outside.
8/11/2022 LESSOR ________________ GOVERNMENT:____________ PAGE - 22/57
5. SECTION 5 - GENERAL FIRE PROTECTION SYSTEM
REQUIREMENTS
5.01 GENERAL
A. If required by code, provide and install a Fire Alarm System that provides 100% coverage in office.
B. Install a fire sprinkler system throughout the facility only if required by code. New and existing systems shall meet requirements of each occupancy type and hazard classification and conform to NFPA standards.
C. In new or remodeled construction, to minimize the visual impact of fire protection systems on the building, install a recessed or flush-type sprinkler head with an escutcheon plate in public areas, as allowed by code for the type of system installed. The entire assembly shall be listed.
D. Sprinkler locations:
1. Sprinkler heads shall be located to prevent operating sprinklers from wetting adjacent sprinklers and to prevent skipping of sprinklers.
2. Sprinklers shall be located to minimize obstructions to discharge.
3. The minimum distance permitted between sprinklers shall comply with Code and manufacturers information for each type or style of sprinkler.
E.
Conform to NFPA standard 72, National Fire Alarm Code, including requirements for temporal sound patterns for the alarm signals and should be listed by a recognized testing laboratory.
1. System shall meet requirements of each occupancy type and hazard classification.
F. Provide a fire alarm system in IT room with two cross zoned fire detectors that will interlock with EPO system (emergency power off system) to shut down power and
HVAC fans in IT room. This is required whether or not there is a main building overall fire alarm system.
1. If a building wide fire alarm is provided, the IT room shall be a separate zone of the main building fire alarm system
2. A phone dialer for the IT room fire alarm input to the EPO panel is required for remote alarm to GSA Mega Center for notation of local emergency services.
3. See EPO description below for system details.
G. Location of a remote high-temperature annunciator at main entrance will be determined during DID.
H. Provide an auto dialer to interface with the local emergency services.
I. Locate manual fire alarm pull stations at the following locations:
1. Computer / Telecomm room exit(s).
2. Employee entrances.
3. Stair wells.
4. Warehouse exterior doors.
8/11/2022 LESSOR ________________ GOVERNMENT:____________ PAGE - 23/57
5. As required by code and as designated in DID.
J. Provide two POTS lines for fire alarm panel for remote fire alarm dialer access.
K. Handheld fire extinguishers will be installed in cabinets inserted in the wall throughout the building.
6. SECTION 6 - GENERAL SECURITY REQUIREMENTS
6.01 GENERAL
A. Refer to Building Physical Security Requirements for specific details.
B. Power supplies for building alarm systems should have battery back-up of at least 24 hours.
6.02 INTRUSION DETECTION SYSTEMS
A. Design and install an Intrusion Detection System that meets the criteria shown in the
R6 Building Physical Security Requirements.
B. Alarm to be integrated into security systems with communication for remote dial out to a monitored facility GSA Mega center. Mega Center support a limited number of brands, this needs verifications.
C. Provide POTS lines for the intrusion detection system digital dialer.
D. Intrusion detection system shall cover all employee entrances and the computer room and ground floor rooms with window access.
E. System shall include the following functions
1. Main control panel located in IT room powered by IT room UPS
2. Remote digital alarm and monitoring panel at entrance door location with digital message showing system status and alarm zone area, with a keypad for arming disarming system.
3. Door position magnetic sensors on all exit doors.
4. Motion detectors in rooms with windows on the first floor or on entry areas on the second floor if they have a direct stairway to the outside.
5. Audible alarm horns in office on each floor.
6. Input from Duress alarm as a separate zone for local alarm and remote monitoring.
7. System shall have 24 hour battery backup.
F. See example specification 281600-IntrusionDetectionSystem for general system guidelines
6.03 DURESS ALARM
A. Provide and install a duress alarm system for local and remote alarm notification.
B. Provide three fixed panic buttons. Locations to be determined during DID.
C. Duress alarm system shall be a part of the intrusion detection system as a separate zone and shall have activation buttons at each workstation in the reception area.
1. Each of the three panic buttons will turn on audio and visuals by LEO office area when pressed and will energize a separate duress zone on the intrusion detection system to dial out to the Monitored central station.
8/11/2022 LESSOR ________________ GOVERNMENT:____________ PAGE - 24/57
2. When alarm panic button is pushed it shall…