This document is a Computer Rm BTU Loading Worksheet that provides detailed information about the power and cooling requirements for various IT equipment and devices associated with a federal contract opportunity.

The worksheet lists numerous Cisco, Dell, HP, and other equipment including routers, switches, servers, storage systems, and UPS units, along with their corresponding power consumption in BTU/hr and wattage. It provides a total BTU per hour requirement of 73,523 BTU. This information appears to be an attachment or appendix to a larger federal contract solicitation, as evidenced by the reference to "Exhibit B-4" and the related federal contract opportunity details provided. The contract opportunity is a Request for Lease Proposals (Solicitation Number 7CA3301) for the General Services Administration to lease space in El Segundo, CA.

View the file

Other files

Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Computer Rm BTU Loading Worksheet (Ver. 11.26.2012)

Manufacturer Function Model BTU/HR or Wattage Qty BTU/Hr Extended BTU/Hr

Cisco VoIP Switch C3750G-24PS 2440 BTU/hr @ 715W 0 2440 0

Cisco VOIP Switch C3850-48PS 3793 BTU/hr @ 1900W 4 3793 15172

Cisco VoIP Switch 4507R-E 2387 BTU/hr @ 2333W 1 2387 2387

Cisco Network Router 3845 1890 BTU/hr @ 555W 0 1890 0

Cisco Network Router 2851 197 BTU/hr @ 58W 0 197 0

Cisco Network Router ISR4451 1800 BTU/hr @1000W 1 1800 1800

Cisco Network Router ISR4431 1000 BTU/hr @500W 0 0 0

Cisco Analog Device VG-224 204 BTU/hr @ 60W 1 204 204

Cisco Media Delivery System Server MDE 1100 3490 BTU/hr @ 800W 0 3490 0

APC VoIP Switch UPS SUA2200XL 6312 BTU/hr @1850W 0 6312 0

APC VoIP Switch UPS SURTD5000RMXLT-1TF5 11942 BTU/hr @ 3500W 2 11942 23884

Cisco VoIP CRS/TAPS Server N/A 3490 BTU/hr @ 800W 0 3490 0

Cisco VoIP CCM Subscriber N/A 1710 BTU/hr @ 420W 0 1710 0

Cisco VoIP CCM Publisher N/A 1710 BTU/hr @ 420W 0 1710 0

Unknown VoIP IP Celerate (paging) Server N/A 1826 BTU/hr @ 350W 0 1826 0

Dell District Server Poweredge T410 1365 BTU/hr @ 400W 1 1365 1365

Dell LABSAN Server Poweredge T310 1280 BTU/hr @375W 1 1280 1280

Dell LABSAN Server Poweredge T410 1365 BTU/hr @ 400W 1 1365 1365

Dell SCCM Server Poweredge T310 1280 BTU/hr @375W 1 1280 1280

APC SCCM UPS Smart-UPS 1500 3412 BTU/hr @ 1000W 1 3412 3412

Dell Axas|} Dimension 2400 853 BTU/hr 0 853 0

Dell Monitor, TepSys / SMS N/A Minimal 0 0 0

HP SANs, VC ProLiant DL380 3530 BTU/hr @ 850W 1 3530 3530

HP SANs ESX ProLiant DL380 3530 BTU/hr @ 850W 1 3530 3530

HP SANs ESX ProLiant DL380 3530 BTU/hr @ 850W 1 3530 3530

HP Domain Controller ProLiant DL380 3530 BTU/hr @ 850W 1 3530 3530

HP SANs KVM IP Server Console Switch Minimal 1 0 0

HP SANs MSA Controller MSA 2012 fc, 12 HDs 1622 BTU/hr @ 475W 1 1622 1622

HP SANs MSA, Drive Enclosure 1 MSA 30 SB Storage, 12 HDs 1232 BTU/hr 1 1232 1232

HP SANs MSA, Drive Enclosure 2 MSA 30 SB Storage, 12 HDs 1232 BTU/hr 1 1232 1232

HP SANs MSA, Drive Enclosure 3 MSA 30 SB Storage, 12 HDs 1232 BTU/hr 1 1232 1232

HP SANs Backup Tape Library MSL4048 2 Ultrium 960 1065 BTU/hr @312 Watts 1 0 0

HP SANs Fibre Channel Switch HP StorageWorks 4/16 SANs Switch 266 BTU/hr @ 75W 1 266 266

Tripp Lite SMART UPS PRO Smart UPS 198 BTU/hr @2250 0 2250 0

Check Point LIMS Firewall 4800 Series 426 BTU/hr @275W 1 426 0

Cisco SANs Gigabit Switch 2960, 24 port 244 BTU/hr @ 72W 0 244 0

Riverbed WAN Optimizer 6050 Series 310 MPBS 1670@352W 1 1670 1670

Riverbed WAN Optimizer 3500 Series 45 MPBS 1450 BTU/HR @435 0 1450 0

Riverbed WAN Optimizer 1500 Series 4 MPBS 508 BTU/hr @ 149W 0 508 0

Total BTU Per Hour 73,523