This document appears to be an appendix from a Catalyst 6500 Series Switch Installation Guide that provides detailed specifications for various power supply models, including the 3000W AC-input power supply. The appendix covers information such as power supply compatibility, specifications (AC input voltage, current, frequency, output capacity, connectors, LED indicators, and power cords), and heat dissipation details. It also includes information on the APC Symmetra RM 4kVA and Smart-UPS RT 5000VA uninterruptible power supplies, as well as the APC SURT003 step-down transformer. This document appears to be informational in nature and does not directly address a specific federal contract opportunity.

View the file

Other files

Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FDA OIM IT CLOSET ‐ Cooling Requirements

MAIN CLOSET (MPoP) ‐ OIM's typical design includes:

Each Total Reference

Manufacturer Model QTY W QTY Cisco 6500 2 3000 2 12046 48184 Cisco 3000W Power Supply Cisco 4500 1 3000 2 12046 24092 Cisco 3000W Power Supply APC Symmetra 4K6 3 1181 3543 APC Symmetra Data Sheet

APC

SURT003 Step Down Transformer 3 0 0 APC SURT003 Data Sheet

75819

6.31825 TONS

The switches have a wide flavor of power supplies but we base the design on ‐ 3000W power supplies.

Typical IT Closet (per floor) ‐ OIM's typical design includes:

Each Total Manufacturer Model QTY W QTY

Cisco 6500 0 3000 2 12046 0 Cisco 3000W Power Supply Cisco 4500 1 3000 2 12046 24092 Cisco 3000W Power Supply APC Smart UPS 5000 1 1150 1150 APC Smart‐UPS Data Sheet

APC

SURT003 Step Down Transformer 1 0 0 APC SURT003 Data Sheet

25242

2.1035 TONS

The switches have a wide flavor of power supplies but we base the design on ‐ 3000W power supplies.

Power Supply BTU/h

Heat Dissipation

@ 12000BTU/h per ton

Power Supply Heat Dissipation

BTU/h

@ 12000BTU/h per ton

NOTE ‐ While the calculations are based on the MAX heat dissipation, it will be extremely imprudent to discount them in case of network equipment.

The calculations are based on a snapshot of current optimal design. Please note that within the Cisco links provided you will find that there are larger power supplies (4000W, 6000W) also available. The switches are specifically designed for plug and play power supplies and it is certainly in the realm of possibility that network needs within next 5 years could require a power supply upgrade to a larger sized power supply.

EXHIBIT B-3

A-1 Catalyst 6500 Series Switches Installation Guide

OL-5781-07

A P P E N D I X A Power Supply Specifications

This appendix describes the Catalyst 6500 series power supplies and provides their specifications. This appendix contains the following sections:

• Power Supply Compatibility Matrix, page A-2

• 950 W AC-Input and DC-Input Power Supplies, page A-5

• 1000 W AC-Input Power Supply, page A-10

• 1300 W AC-Input and DC-Input Power Supplies, page A-13

• 1400 W AC-Input Power Supply, page A-18

• 2500 W AC-Input and DC-Input Power Supplies, page A-23

• 2700 W AC-Input and DC-Input Power Supplies, page A-29

• 3000 W AC-Input Power Supply, page A-36

• 4000 W AC-Input and DC-Input Power Supplies, page A-41

• 6000 W AC-Input and DC-Input Power Supplies, page A-46

• 8700 W AC-Input Power Supply, page A-54

• AC Power Cord Illustrations, page A-63

• Power Supply Redundancy, page A-73

Table A-1 lists the currently available Catalyst 6500 series switch power supplies and the power supply description location.

Table A-1 Catalyst 6500 Series Power Supplies

Power Supply Rating

AC-Input Model Product Number

DC-Input Model Product Number

950 W1 PWR-950-AC PWR-950-DC

1000 W WS-CAC-1000W Not Available

1300 W WS-CAC-1300W WS-CDC-1300W

1400 W1 PWR-1400-AC Not Available

2500 W WS-CAC-2500W WS-CDC-2500W

2700 W2 PWR-2700-AC/4 PWR-2700-DC/4

3000 W WS-CAC-3000W Not Available

A-36

OL-5781-07

Appendix A Power Supply Specifications 3000 W AC-Input Power Supply

3000 W AC-Input Power Supply The 3000 W AC-input power supply (WS-CAC-3000W) is supported in the following Catalyst 6500 series switches:

• Catalyst 6506

• Catalyst 6506-E

• Catalyst 6509

• Catalyst 6509-E

• Catalyst 6509-NEB

• Catalyst 6509-NEB-A

• Catalyst 6509-V-E

• Catalyst 6513

The 3000 W power supply (see Figure A-13) shares the same form factor as the 1000 W, 1300 W, 2500 W, 4000 W, and 6000 W AC-input power supplies.

Note The 3000 W AC-input power supply needs 220 VAC to deliver 3000 W of power. When operating with 110 VAC, it delivers only 1400 W. In addition, the power supply needs 16 A, regardless of whether it is plugged into 110 VAC or 220 VAC.

Figure A-13 3000 W AC-Input Power Supply

INPUT

OK

FAN

OK

OUTPUT

FAIL

OUTPUT 42V /17A

42V /17A

OK

I

INSTALL

RUN

O

110-120V - 15A 200-240V - 15A

60/50HZ

Power switch

Cable retention device

AC power connection

Captive installation screw

Status LEDs (3) External power connector cover

A-37

OL-5781-07

Appendix A Power Supply Specifications 3000 W AC-Input Power Supply

3000 W Power Supply Specifications Table A-25 lists the specifications for the 3000 W AC-input power supply.

Table A-25 3000 W Power Supply Specifications

Specification Description

AC-input type Autoranging input with power factor correction (PFC).

Note Power factor correction is a standard feature on all Catalyst 6500 series AC-input power supplies. PFC reduces the reactive component in the source AC current allowing higher power factors (typically 99 percent or better) and lower harmonic current components.

AC-input voltage • Low-line (120 VAC nominal)—90 VAC (min) to 132 VAC (max)

• High-line (230 VAC nominal)—170 VAC (min) to 264 VAC (max)

AC-input current • 16 A @ 200 VAC (3000 W output)

• 16 A @ 100 VAC (1400 W output)

AC-input frequency 50/60 Hz (nominal) (±3% for full range)

Branch circuit requirement Each chassis power supply should have its own dedicated, fused-branch circuit:

• For North America—20 A

• For International—Circuits sized to local and national codes

• All AC power supply inputs are fully isolated.

– Source AC can be out of phase between multiple power supplies in the same chassis, which means that PS1 can be operating from phase A and PS2 can be operating from phase B.

– For high-line operation, the power supply operates with the hot conductor wired to a source AC phase and the neutral conductor wired either to ground or to another source AC phase as long as the net input voltage is in the range of 170 to 264 VAC.

– Source AC can be out of phase between AC inputs on power supplies that are equipped with multiple AC inputs, which means that power cord 1 can be plugged into phase A and power cord 2 can be plugged into phase B.

Power supply output capacity

• 1400 W maximum (100–120 VAC)

• 3000 W maximum (200–240 VAC)

A-38

OL-5781-07

Appendix A Power Supply Specifications 3000 W AC-Input Power Supply

Table A-26 lists the power supply LEDs and their meanings.

Power supply output • 100/120 VAC operation

– 25.0 A @ +3.3 V

– 5 A @ +5 V

– 12 A @ +12 V

– 27.89 A @ +42 V

• 200/240 VAC operation

– 25.0 A @ +3.3 V

– 5 A @ +5 V

– 12 A @ +12 V

– 65.98 A @ +42 V

Front panel power connector

A two-pin male Molex connector is located in the lower right corner of the power supply front panel. The connector provides 42 VDC at a maximum of 17 A. This connector provides power to the WS-6509-NEB-UPGRD kit fan assembly through a power harness also provided in the kit. A hinged protective flap secured by a captive screw covers the connector when it is not in use.

Output holdup time 20 ms minimum kVA rating1 3520 W (total input power) or 3.6 KVA (high-line operation)

Heat dissipation 12,046 BTU/hour (approx.)

Weight 15.8 lb (7.2 kg)

1. The kVA rating listed for the power supply should be used as the sizing criteria for both UPS outputs as well as standard circuits and transformers to power a switch.

Table A-25 3000 W Power Supply Specifications (continued)

Specification Description

A-39

OL-5781-07

Appendix A Power Supply Specifications 3000 W AC-Input Power Supply

Table A-26 3000 W AC-Input Power Supply LEDs

LED Meaning

INPUT OK • Green—Source AC voltage is OK. (Input voltage is 85 VAC or greater.)

• Off—Source AC voltage falls below 70 VAC, is not present, or the power supply is turned off.

FAN OK • Green—Power supply fan is operating properly.

• Off—Power supply fan failure is detected.

OUTPUT FAIL • Red—Problem with one or more of the DC-output voltages of the power supply.

• Off—DC-output voltages within acceptable margins.

Note For proper operation of the OUTPUT FAIL LED, systems with single power supplies must be configured with a minimum of one fan tray and one supervisor engine. Systems with dual power supplies must have a minimum configuration of one fan tray, one supervisor engine, and one additional module. Failure to meet these minimum configuration requirements can cause a false power supply output fail signal.

42V OK • Green—42 VDC is present at the fan power connector.

• Off—42 VDC is not present at the fan power connector.

A-40

OL-5781-07

Appendix A Power Supply Specifications 3000 W AC-Input Power Supply

3000 W Power Supply AC Power Cords Table A-27 lists the specifications for the AC power cords that are available for the 3000 W AC-input power supply. The table includes references to power cord illustrations.

Note All 3000 W power supply power cords are 14 feet (4.3 meters) in length.

Note All 3000 W power supply power cords have an IEC60320/C19 appliance connector at one end.

Table A-27 3000 W Power Supply AC Power Cords

Locale Power Cord Part Number

AC Source Plug Type Cordset Rating Power Cord Reference Illustration

Argentina CAB-7513ACR= or

CAB-IR2073-C19-AR=

IRAM 2073 16 A, 250 VAC Figure A-31

Australia, New Zealand CAB-AC-16A-AUS= AU20S3 16 A, 250 VAC Figure A-46

People’s Republic of China CAB-AC16A-CH= GB16C 16 A, 250 VAC Figure A-37

Continental Europe CAB-AC-2500W-EU= CEE 7/7 16 A, 250 VAC Figure A-41

International CAB-AC-2500W-INT= IEC 309 16 A, 250 VAC Figure A-42

Israel CAB-AC-2500W-ISRL= SI16S3 16 A, 250 VAC Figure A-34

Italy CAB-7513ACI= CEI 23-16/7 16 A, 250 VAC Figure A-35

Japan, North America (nonlocking plug) 200–240 VAC operation

CAB-AC-2500W-US1= NEMA 6-20 16 A, 250 VAC Figure A-43

Japan, North America (locking plug) 200–240 VAC operation

CAB-AC-C6K-TWLK= NEMA L6-20 16 A, 250 VAC Figure A-44

Japan, North America 100–120 VAC operation1

1. The 3000 W power supply operating on 110 VAC delivers 1400 W.

CAB-7513AC= NEMA 5-20 20 A, 125 VAC Figure A-36

Power Distribution Unit

(PDU)2

2. The PDU power cable is designed for users who power their switch from a PDU. The end of the cable that plugs into the chassis power supply has a C19 connector; the other end of the cable that connects to the PDU has a C20 connector.

CAB-C19-CBN= IEC 60320 C19

IEC 60320 C20

16 A, 250 VAC Figure A-47

Switzerland CAB-ACS-16= SEV 5934-2 Type 23 16 A, 250 VAC Figure A-45

Home Products Uninterruptible Power Supply (UPS) Network and Server Product Family

APC Symmetra RM 4kVA Scalable to 6kVA N+1 208/240V

Part Number: SYH4K6RMT

Output Power Capacity 2800 Watts / 4000 VA

Max Configurable Power 4200 Watts / 6000 VA

Nominal Output Voltage 208V

Output Voltage Note Configurable for 208 or 240 nominal output voltage

Efficiency at Full Load 89%

Output Voltage Distortion Less than 5% at full load

Output Frequency (sync to mains)

57 - 63 Hz for 60 Hz nominal

Crest Factor up to 5 : 1

Waveform Type Sine wave

Output Connections (2) NEMA L6-20R

(1) NEMA L6-30R

Bypass Internal Bypass (Automatic and Manual)

Nominal Input Voltage 208V

Input Frequency 50/60 Hz +/- 5 Hz (auto sensing)

Input Connections Hard Wire 3-wire (2PH + G) NEMA L6-30P (30A Twist-Lock)

Cord Length 6 feet (1.83 meters)

Input voltage range for main operations

155 - 276V

Battery Type

Output

Input

Batteries & Runtime

1 of 3 7/27/2010 7:46 PM

Maintenance-free sealed Lead-Acid battery with suspended electrolyte :

leakproof

4 hour(s)

SYBT2

note UPS accepts 1-2 additional battery packs

APC Symmetra RM 4kVA Scalable to 6kVA N+1 208/240V

Curve Part Number(s)

A SYH4K6RMT

B SYH4K6RMT

+ (1)SYBT2

C SYH4K6RMT

+ (2)SYBT2

D SYH4K6RMT

+ (1)SYRMXR4B4

E SYH4K6RMT

+ (2)SYRMXR4B4

View Enlarged Graph View Runtime Chart

Hover over the line on the graph above to view the runtime at any desired load

Curve fit to measured runtime data. All measurements taken with new, fully charged batteries, at typical environmental conditions, with no electrical input and balanced resistive load (PF = 1.0) output.

Interface Port(s) DB-9 RS-232,RJ-45 10 Base-T ethernet for web/ SNMP/ Telnet management

Available SmartSlot™ Interface Quantity

Pre-Installed SmartSlot™ Cards

Communications & Management

2 of 3 7/27/2010 7:46 PM

Copyright © American Power Conversion Corp., all rights reserved

Maximum Height 14.00 inches (356 mm)

Maximum Width 19.00 inches (483 mm)

Maximum Depth 28.75 inches (730 mm)

Rack Height 8U

Net Weight 229.00 lbs. (104.09 kg)

Shipping Weight 256.00 lbs. (116.36 kg)

Shipping Height 20.00 inches (508 mm)

Shipping Width 23.00 inches (584 mm)

Shipping Depth 31.00 inches (787 mm)

Color Black

Operating Environment 32 - 104 °F (0 - 40 °C)

Operating Relative Humidity 0 - 95%

Operating Elevation 0-10000 feet (0-3000 meters)

Storage Temperature 5 - 113 °F (-15 - 45 °C)

Storage Relative Humidity 0 - 95%

Storage Elevation 0-50000 feet (0-15000 meters)

Audible noise at 1 meter from surface of unit

60.00 dBA

Online Thermal Dissipation 1181.00 BTU/hr

Regulatory Approvals CSA,FCC Part 15 Class A,UL 1778

Standard Warranty 2 years repair or replace,optional on-site warranties available,optional extended warranties available

Physical

Environmental

Conformance

*Except where noted, all prices are Estimated Resale Price (ERP) - Without Tax/VAT. Pricing in other locations and sites may vary.

**The time to recharge to 90% of full battery capacity following a discharge to shutdown using a load rated for 1/2 the full load rating of the UPS.

3 of 3 7/27/2010 7:46 PM

Home Products Uninterruptible Power Supply (UPS) Network and Server Product Family

APC Smart-UPS RT 5000VA Rack Tower 208V

Part Number: SURTD5000RMXLT3U

Output Power Capacity 3500 Watts / 5000 VA

Max Configurable Power 3500 Watts / 5000 VA

Nominal Output Voltage 208V

Output Voltage Note Configurable for 208 or 240 nominal output voltage

Efficiency at Full Load 91%

Output Voltage Distortion Less than 3%

Output Frequency (sync to mains)

50/60 Hz +/- 3 Hz user adjustable +/- 0.1

Crest Factor 3 : 1

Waveform Type Sine wave

Output Connections (2) NEMA L6-20R

(2) NEMA L6-30R

Bypass Internal Bypass (Automatic and Manual)

Nominal Input Voltage 208V

Input Frequency 50/60 Hz +/- 5 Hz (auto sensing)

Input Connections

Output

Input

1 of 4 7/27/2010 7:47 PM

Battery Type Maintenance-free sealed Lead-Acid battery with suspended electrolyte :

leakproof

Included Battery Modules 2

Typical recharge time 2.50 hour(s)

Replacement Battery RBC44

RBC™ Quantity 1

Extended Run Options APC Smart-UPS RT 5000VA Rack Tower 208V

Runtime Graph

Curve Part Number(s)

A SURTD5000RMXLT3U

B

SURTD5000RMXLT3U

(1)SURT192RMXLBP3U

C

SURTD5000RMXLT3U

(2)SURT192RMXLBP3U

D

SURTD5000RMXLT3U

(3)SURT192RMXLBP3U

E

SURTD5000RMXLT3U

(4)SURT192RMXLBP3U

View Enlarged Graph View Runtime Chart

Hover over the line on the graph above to view the runtime at any desired load

Curve fit to measured runtime data. All measurements taken with new, fully charged batteries, at typical environmental conditions, with no electrical input and balanced resistive load (PF = 1.0) output.

Interface Port(s) Smart-Slot

Pre-Installed SmartSlot™ Cards AP9619

Batteries & Runtime

Communications & Management

2 of 4 7/27/2010 7:47 PM

Surge energy rating 480 Joules

Filtering Full time multi-pole noise filtering : 0.3% IEEE surge let-through : zero clamping response time : meets UL 1449

Maximum Height 5.10 inches (130 mm)

Maximum Width 17.00 inches (432 mm)

Maximum Depth 26.00 inches (660 mm)

Rack Height 3U

Net Weight 128.00 lbs. (58.18 kg)

Shipping Weight 159.00 lbs. (72.27 kg)

Shipping Height 13.68 inches (347 mm)

Shipping Width 23.73 inches (603 mm)

Shipping Depth 38.60 inches (980 mm)

Color Black

Units per Pallet 6.00

Operating Environment 32 - 104 °F (0 - 40 °C)

Operating Relative Humidity 0 - 95%

Operating Elevation 0-10000 feet (0-3000 meters)

Storage Temperature 5 - 113 °F (-15 - 45 °C)

Storage Relative Humidity 0 - 95%

Storage Elevation 0-50000 feet (0-15000 meters)

Audible noise at 1 meter from surface of unit

55.00 dBA

Online Thermal Dissipation 1150.00 BTU/hr

Regulatory Approvals CSA,FCC Part 15 Class A,UL 1778

Standard Warranty 2 years repair or replace

Environmental Compliance RoHS 7b Exemption,China RoHS

Surge Protection and Filtering

Physical

Environmental

Conformance

*Except where noted, all prices are Estimated Resale Price (ERP) - Without Tax/VAT. Pricing in other locations and sites may vary.

**The time to recharge to 90% of full battery capacity following a discharge to shutdown using a load rated for 1/2 the full load rating of the UPS.

3 of 4 7/27/2010 7:47 PM

4 of 4 7/27/2010 7:47 PM

Home Products AV Cables Product Family

APC Smart-UPS RT Tower Isolation/Step-Down Transformer

Part Number: SURT003

Nominal Output Voltage 120V,208V

Maximum Total Current Draw per Phase

30A

Output Connections (8) NEMA 5-20R

(1) NEMA L14-30R

(2) NEMA L6-20R

(1) NEMA L6-30R

Overload Protection Yes

Nominal Input Voltage 208V

Input Frequency 50/60 Hz

Input Connections NEMA L6-30P

Cord Length 3 feet (0.91 meters)

Number of Power Cords 1

Acceptable Input Voltage 180-264 VAC

Output

Input

1 of 2 7/27/2010 7:49 PM

Net Weight 125.00 lbs. (56.82 kg)

Maximum Height 5.10 inches (130 mm)

Maximum Width 17.00 inches (432 mm)

Maximum Depth 26.00 inches (660 mm)

Shipping Weight 140.00 lbs. (63.64 kg)

Shipping Height 13.68 inches (347 mm)

Shipping Width 23.74 inches (603 mm)

Shipping Depth 38.60 inches (980 mm)

Color Black

Units per Pallet 6.00

Operating Environment 32 - 104 °F (0 - 40 °C)

Operating Relative Humidity 0 - 95%

Operating Elevation 0-10000 feet (0-3000 meters)

Storage Temperature -13 - 149 °F (-25 - 65 °C)

Storage Relative Humidity 0 - 95%

Storage Elevation 0-50000 feet (0-15000 meters)

Regulatory Approvals CSA,UL Listed

Standard Warranty 2 years repair or replace

Environmental Compliance RoHS 7b Exemption

Physical

Environmental

Conformance

*Except where noted, all prices are Estimated Resale Price (ERP) - Without Tax/VAT. Pricing in other locations and sites may vary.

2 of 2 7/27/2010 7:49 PM

FDA Typical IT CLoset Calculations.pdf
Cisco 3000W Power Supply Data.pdf
Pages from 0apwsply-2.pdf
Pages from 0apwsply.pdf
APC Symmetra RM 4kVA UPS.pdf
APC Smart-UPS RT 5000VA.pdf
APC SURT003 Step Down Transformer.pdf

File details come from the government source that posted it. Updated .