This document appears to be an appendix from a Catalyst 6500 Series Switch Installation Guide that provides detailed specifications for various power supply models, including the 3000W AC-input power supply. The appendix covers information such as power supply compatibility, specifications (AC input voltage, current, frequency, output capacity, connectors, LED indicators, and power cords), and heat dissipation details. It also includes information on the APC Symmetra RM 4kVA and Smart-UPS RT 5000VA uninterruptible power supplies, as well as the APC SURT003 step-down transformer. This document appears to be informational in nature and does not directly address a specific federal contract opportunity.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FDA OIM IT CLOSET ‐ Cooling Requirements
MAIN CLOSET (MPoP) ‐ OIM's typical design includes:
Each Total Reference
Manufacturer Model QTY W QTY Cisco 6500 2 3000 2 12046 48184 Cisco 3000W Power Supply Cisco 4500 1 3000 2 12046 24092 Cisco 3000W Power Supply APC Symmetra 4K6 3 1181 3543 APC Symmetra Data Sheet
APC
SURT003 Step Down Transformer 3 0 0 APC SURT003 Data Sheet
75819
6.31825 TONS
The switches have a wide flavor of power supplies but we base the design on ‐ 3000W power supplies.
Typical IT Closet (per floor) ‐ OIM's typical design includes:
Each Total Manufacturer Model QTY W QTY
Cisco 6500 0 3000 2 12046 0 Cisco 3000W Power Supply Cisco 4500 1 3000 2 12046 24092 Cisco 3000W Power Supply APC Smart UPS 5000 1 1150 1150 APC Smart‐UPS Data Sheet
APC
SURT003 Step Down Transformer 1 0 0 APC SURT003 Data Sheet
25242
2.1035 TONS
The switches have a wide flavor of power supplies but we base the design on ‐ 3000W power supplies.
Power Supply BTU/h
Heat Dissipation
@ 12000BTU/h per ton
Power Supply Heat Dissipation
BTU/h
@ 12000BTU/h per ton
NOTE ‐ While the calculations are based on the MAX heat dissipation, it will be extremely imprudent to discount them in case of network equipment.
The calculations are based on a snapshot of current optimal design. Please note that within the Cisco links provided you will find that there are larger power supplies (4000W, 6000W) also available. The switches are specifically designed for plug and play power supplies and it is certainly in the realm of possibility that network needs within next 5 years could require a power supply upgrade to a larger sized power supply.
EXHIBIT B-3
A-1 Catalyst 6500 Series Switches Installation Guide
OL-5781-07
A P P E N D I X A Power Supply Specifications
This appendix describes the Catalyst 6500 series power supplies and provides their specifications. This appendix contains the following sections:
• Power Supply Compatibility Matrix, page A-2
• 950 W AC-Input and DC-Input Power Supplies, page A-5
• 1000 W AC-Input Power Supply, page A-10
• 1300 W AC-Input and DC-Input Power Supplies, page A-13
• 1400 W AC-Input Power Supply, page A-18
• 2500 W AC-Input and DC-Input Power Supplies, page A-23
• 2700 W AC-Input and DC-Input Power Supplies, page A-29
• 3000 W AC-Input Power Supply, page A-36
• 4000 W AC-Input and DC-Input Power Supplies, page A-41
• 6000 W AC-Input and DC-Input Power Supplies, page A-46
• 8700 W AC-Input Power Supply, page A-54
• AC Power Cord Illustrations, page A-63
• Power Supply Redundancy, page A-73
Table A-1 lists the currently available Catalyst 6500 series switch power supplies and the power supply description location.
Table A-1 Catalyst 6500 Series Power Supplies
Power Supply Rating
AC-Input Model Product Number
DC-Input Model Product Number
950 W1 PWR-950-AC PWR-950-DC
1000 W WS-CAC-1000W Not Available
1300 W WS-CAC-1300W WS-CDC-1300W
1400 W1 PWR-1400-AC Not Available
2500 W WS-CAC-2500W WS-CDC-2500W
2700 W2 PWR-2700-AC/4 PWR-2700-DC/4
3000 W WS-CAC-3000W Not Available
A-36
OL-5781-07
Appendix A Power Supply Specifications 3000 W AC-Input Power Supply
3000 W AC-Input Power Supply The 3000 W AC-input power supply (WS-CAC-3000W) is supported in the following Catalyst 6500 series switches:
• Catalyst 6506
• Catalyst 6506-E
• Catalyst 6509
• Catalyst 6509-E
• Catalyst 6509-NEB
• Catalyst 6509-NEB-A
• Catalyst 6509-V-E
• Catalyst 6513
The 3000 W power supply (see Figure A-13) shares the same form factor as the 1000 W, 1300 W, 2500 W, 4000 W, and 6000 W AC-input power supplies.
Note The 3000 W AC-input power supply needs 220 VAC to deliver 3000 W of power. When operating with 110 VAC, it delivers only 1400 W. In addition, the power supply needs 16 A, regardless of whether it is plugged into 110 VAC or 220 VAC.
Figure A-13 3000 W AC-Input Power Supply
INPUT
OK
FAN
OK
OUTPUT
FAIL
OUTPUT 42V /17A
42V /17A
OK
I
INSTALL
RUN
O
110-120V - 15A 200-240V - 15A
60/50HZ
Power switch
Cable retention device
AC power connection
Captive installation screw
Status LEDs (3) External power connector cover
A-37
OL-5781-07
Appendix A Power Supply Specifications 3000 W AC-Input Power Supply
3000 W Power Supply Specifications Table A-25 lists the specifications for the 3000 W AC-input power supply.
Table A-25 3000 W Power Supply Specifications
Specification Description
AC-input type Autoranging input with power factor correction (PFC).
Note Power factor correction is a standard feature on all Catalyst 6500 series AC-input power supplies. PFC reduces the reactive component in the source AC current allowing higher power factors (typically 99 percent or better) and lower harmonic current components.
AC-input voltage • Low-line (120 VAC nominal)—90 VAC (min) to 132 VAC (max)
• High-line (230 VAC nominal)—170 VAC (min) to 264 VAC (max)
AC-input current • 16 A @ 200 VAC (3000 W output)
• 16 A @ 100 VAC (1400 W output)
AC-input frequency 50/60 Hz (nominal) (±3% for full range)
Branch circuit requirement Each chassis power supply should have its own dedicated, fused-branch circuit:
• For North America—20 A
• For International—Circuits sized to local and national codes
• All AC power supply inputs are fully isolated.
– Source AC can be out of phase between multiple power supplies in the same chassis, which means that PS1 can be operating from phase A and PS2 can be operating from phase B.
– For high-line operation, the power supply operates with the hot conductor wired to a source AC phase and the neutral conductor wired either to ground or to another source AC phase as long as the net input voltage is in the range of 170 to 264 VAC.
– Source AC can be out of phase between AC inputs on power supplies that are equipped with multiple AC inputs, which means that power cord 1 can be plugged into phase A and power cord 2 can be plugged into phase B.
Power supply output capacity
• 1400 W maximum (100–120 VAC)
• 3000 W maximum (200–240 VAC)
A-38
OL-5781-07
Appendix A Power Supply Specifications 3000 W AC-Input Power Supply
Table A-26 lists the power supply LEDs and their meanings.
Power supply output • 100/120 VAC operation
– 25.0 A @ +3.3 V
– 5 A @ +5 V
– 12 A @ +12 V
– 27.89 A @ +42 V
• 200/240 VAC operation
– 25.0 A @ +3.3 V
– 5 A @ +5 V
– 12 A @ +12 V
– 65.98 A @ +42 V
Front panel power connector
A two-pin male Molex connector is located in the lower right corner of the power supply front panel. The connector provides 42 VDC at a maximum of 17 A. This connector provides power to the WS-6509-NEB-UPGRD kit fan assembly through a power harness also provided in the kit. A hinged protective flap secured by a captive screw covers the connector when it is not in use.
Output holdup time 20 ms minimum kVA rating1 3520 W (total input power) or 3.6 KVA (high-line operation)
Heat dissipation 12,046 BTU/hour (approx.)
Weight 15.8 lb (7.2 kg)
1. The kVA rating listed for the power supply should be used as the sizing criteria for both UPS outputs as well as standard circuits and transformers to power a switch.
Table A-25 3000 W Power Supply Specifications (continued)
Specification Description
A-39
OL-5781-07
Appendix A Power Supply Specifications 3000 W AC-Input Power Supply
Table A-26 3000 W AC-Input Power Supply LEDs
LED Meaning
INPUT OK • Green—Source AC voltage is OK. (Input voltage is 85 VAC or greater.)
• Off—Source AC voltage falls below 70 VAC, is not present, or the power supply is turned off.
FAN OK • Green—Power supply fan is operating properly.
• Off—Power supply fan failure is detected.
OUTPUT FAIL • Red—Problem with one or more of the DC-output voltages of the power supply.
• Off—DC-output voltages within acceptable margins.
Note For proper operation of the OUTPUT FAIL LED, systems with single power supplies must be configured with a minimum of one fan tray and one supervisor engine. Systems with dual power supplies must have a minimum configuration of one fan tray, one supervisor engine, and one additional module. Failure to meet these minimum configuration requirements can cause a false power supply output fail signal.
42V OK • Green—42 VDC is present at the fan power connector.
• Off—42 VDC is not present at the fan power connector.
A-40
OL-5781-07
Appendix A Power Supply Specifications 3000 W AC-Input Power Supply
3000 W Power Supply AC Power Cords Table A-27 lists the specifications for the AC power cords that are available for the 3000 W AC-input power supply. The table includes references to power cord illustrations.
Note All 3000 W power supply power cords are 14 feet (4.3 meters) in length.
Note All 3000 W power supply power cords have an IEC60320/C19 appliance connector at one end.
Table A-27 3000 W Power Supply AC Power Cords
Locale Power Cord Part Number
AC Source Plug Type Cordset Rating Power Cord Reference Illustration
Argentina CAB-7513ACR= or
CAB-IR2073-C19-AR=
IRAM 2073 16 A, 250 VAC Figure A-31
Australia, New Zealand CAB-AC-16A-AUS= AU20S3 16 A, 250 VAC Figure A-46
People’s Republic of China CAB-AC16A-CH= GB16C 16 A, 250 VAC Figure A-37
Continental Europe CAB-AC-2500W-EU= CEE 7/7 16 A, 250 VAC Figure A-41
International CAB-AC-2500W-INT= IEC 309 16 A, 250 VAC Figure A-42
Israel CAB-AC-2500W-ISRL= SI16S3 16 A, 250 VAC Figure A-34
Italy CAB-7513ACI= CEI 23-16/7 16 A, 250 VAC Figure A-35
Japan, North America (nonlocking plug) 200–240 VAC operation
CAB-AC-2500W-US1= NEMA 6-20 16 A, 250 VAC Figure A-43
Japan, North America (locking plug) 200–240 VAC operation
CAB-AC-C6K-TWLK= NEMA L6-20 16 A, 250 VAC Figure A-44
Japan, North America 100–120 VAC operation1
1. The 3000 W power supply operating on 110 VAC delivers 1400 W.
CAB-7513AC= NEMA 5-20 20 A, 125 VAC Figure A-36
Power Distribution Unit
(PDU)2
2. The PDU power cable is designed for users who power their switch from a PDU. The end of the cable that plugs into the chassis power supply has a C19 connector; the other end of the cable that connects to the PDU has a C20 connector.
CAB-C19-CBN= IEC 60320 C19
IEC 60320 C20
16 A, 250 VAC Figure A-47
Switzerland CAB-ACS-16= SEV 5934-2 Type 23 16 A, 250 VAC Figure A-45
Home Products Uninterruptible Power Supply (UPS) Network and Server Product Family
APC Symmetra RM 4kVA Scalable to 6kVA N+1 208/240V
Part Number: SYH4K6RMT
Output Power Capacity 2800 Watts / 4000 VA
Max Configurable Power 4200 Watts / 6000 VA
Nominal Output Voltage 208V
Output Voltage Note Configurable for 208 or 240 nominal output voltage
Efficiency at Full Load 89%
Output Voltage Distortion Less than 5% at full load
Output Frequency (sync to mains)
57 - 63 Hz for 60 Hz nominal
Crest Factor up to 5 : 1
Waveform Type Sine wave
Output Connections (2) NEMA L6-20R
(1) NEMA L6-30R
Bypass Internal Bypass (Automatic and Manual)
Nominal Input Voltage 208V
Input Frequency 50/60 Hz +/- 5 Hz (auto sensing)
Input Connections Hard Wire 3-wire (2PH + G) NEMA L6-30P (30A Twist-Lock)
Cord Length 6 feet (1.83 meters)
Input voltage range for main operations
155 - 276V
Battery Type
Output
Input
Batteries & Runtime
1 of 3 7/27/2010 7:46 PM
Maintenance-free sealed Lead-Acid battery with suspended electrolyte :
leakproof
4 hour(s)
SYBT2
note UPS accepts 1-2 additional battery packs
APC Symmetra RM 4kVA Scalable to 6kVA N+1 208/240V
Curve Part Number(s)
A SYH4K6RMT
B SYH4K6RMT
+ (1)SYBT2
C SYH4K6RMT
+ (2)SYBT2
D SYH4K6RMT
+ (1)SYRMXR4B4
E SYH4K6RMT
+ (2)SYRMXR4B4
View Enlarged Graph View Runtime Chart
Hover over the line on the graph above to view the runtime at any desired load
Curve fit to measured runtime data. All measurements taken with new, fully charged batteries, at typical environmental conditions, with no electrical input and balanced resistive load (PF = 1.0) output.
Interface Port(s) DB-9 RS-232,RJ-45 10 Base-T ethernet for web/ SNMP/ Telnet management
Available SmartSlot™ Interface Quantity
Pre-Installed SmartSlot™ Cards
Communications & Management
2 of 3 7/27/2010 7:46 PM
Copyright © American Power Conversion Corp., all rights reserved
Maximum Height 14.00 inches (356 mm)
Maximum Width 19.00 inches (483 mm)
Maximum Depth 28.75 inches (730 mm)
Rack Height 8U
Net Weight 229.00 lbs. (104.09 kg)
Shipping Weight 256.00 lbs. (116.36 kg)
Shipping Height 20.00 inches (508 mm)
Shipping Width 23.00 inches (584 mm)
Shipping Depth 31.00 inches (787 mm)
Color Black
Operating Environment 32 - 104 °F (0 - 40 °C)
Operating Relative Humidity 0 - 95%
Operating Elevation 0-10000 feet (0-3000 meters)
Storage Temperature 5 - 113 °F (-15 - 45 °C)
Storage Relative Humidity 0 - 95%
Storage Elevation 0-50000 feet (0-15000 meters)
Audible noise at 1 meter from surface of unit
60.00 dBA
Online Thermal Dissipation 1181.00 BTU/hr
Regulatory Approvals CSA,FCC Part 15 Class A,UL 1778
Standard Warranty 2 years repair or replace,optional on-site warranties available,optional extended warranties available
Physical
Environmental
Conformance
*Except where noted, all prices are Estimated Resale Price (ERP) - Without Tax/VAT. Pricing in other locations and sites may vary.
**The time to recharge to 90% of full battery capacity following a discharge to shutdown using a load rated for 1/2 the full load rating of the UPS.
3 of 3 7/27/2010 7:46 PM
Home Products Uninterruptible Power Supply (UPS) Network and Server Product Family
APC Smart-UPS RT 5000VA Rack Tower 208V
Part Number: SURTD5000RMXLT3U
Output Power Capacity 3500 Watts / 5000 VA
Max Configurable Power 3500 Watts / 5000 VA
Nominal Output Voltage 208V
Output Voltage Note Configurable for 208 or 240 nominal output voltage
Efficiency at Full Load 91%
Output Voltage Distortion Less than 3%
Output Frequency (sync to mains)
50/60 Hz +/- 3 Hz user adjustable +/- 0.1
Crest Factor 3 : 1
Waveform Type Sine wave
Output Connections (2) NEMA L6-20R
(2) NEMA L6-30R
Bypass Internal Bypass (Automatic and Manual)
Nominal Input Voltage 208V
Input Frequency 50/60 Hz +/- 5 Hz (auto sensing)
Input Connections
Output
Input
1 of 4 7/27/2010 7:47 PM
Battery Type Maintenance-free sealed Lead-Acid battery with suspended electrolyte :
leakproof
Included Battery Modules 2
Typical recharge time 2.50 hour(s)
Replacement Battery RBC44
RBC™ Quantity 1
Extended Run Options APC Smart-UPS RT 5000VA Rack Tower 208V
Runtime Graph
Curve Part Number(s)
A SURTD5000RMXLT3U
B
SURTD5000RMXLT3U
(1)SURT192RMXLBP3U
C
SURTD5000RMXLT3U
(2)SURT192RMXLBP3U
D
SURTD5000RMXLT3U
(3)SURT192RMXLBP3U
E
SURTD5000RMXLT3U
(4)SURT192RMXLBP3U
View Enlarged Graph View Runtime Chart
Hover over the line on the graph above to view the runtime at any desired load
Curve fit to measured runtime data. All measurements taken with new, fully charged batteries, at typical environmental conditions, with no electrical input and balanced resistive load (PF = 1.0) output.
Interface Port(s) Smart-Slot
Pre-Installed SmartSlot™ Cards AP9619
Batteries & Runtime
Communications & Management
2 of 4 7/27/2010 7:47 PM
Surge energy rating 480 Joules
Filtering Full time multi-pole noise filtering : 0.3% IEEE surge let-through : zero clamping response time : meets UL 1449
Maximum Height 5.10 inches (130 mm)
Maximum Width 17.00 inches (432 mm)
Maximum Depth 26.00 inches (660 mm)
Rack Height 3U
Net Weight 128.00 lbs. (58.18 kg)
Shipping Weight 159.00 lbs. (72.27 kg)
Shipping Height 13.68 inches (347 mm)
Shipping Width 23.73 inches (603 mm)
Shipping Depth 38.60 inches (980 mm)
Color Black
Units per Pallet 6.00
Operating Environment 32 - 104 °F (0 - 40 °C)
Operating Relative Humidity 0 - 95%
Operating Elevation 0-10000 feet (0-3000 meters)
Storage Temperature 5 - 113 °F (-15 - 45 °C)
Storage Relative Humidity 0 - 95%
Storage Elevation 0-50000 feet (0-15000 meters)
Audible noise at 1 meter from surface of unit
55.00 dBA
Online Thermal Dissipation 1150.00 BTU/hr
Regulatory Approvals CSA,FCC Part 15 Class A,UL 1778
Standard Warranty 2 years repair or replace
Environmental Compliance RoHS 7b Exemption,China RoHS
Surge Protection and Filtering
Physical
Environmental
Conformance
*Except where noted, all prices are Estimated Resale Price (ERP) - Without Tax/VAT. Pricing in other locations and sites may vary.
**The time to recharge to 90% of full battery capacity following a discharge to shutdown using a load rated for 1/2 the full load rating of the UPS.
3 of 4 7/27/2010 7:47 PM
4 of 4 7/27/2010 7:47 PM
Home Products AV Cables Product Family
APC Smart-UPS RT Tower Isolation/Step-Down Transformer
Part Number: SURT003
Nominal Output Voltage 120V,208V
Maximum Total Current Draw per Phase
30A
Output Connections (8) NEMA 5-20R
(1) NEMA L14-30R
(2) NEMA L6-20R
(1) NEMA L6-30R
Overload Protection Yes
Nominal Input Voltage 208V
Input Frequency 50/60 Hz
Input Connections NEMA L6-30P
Cord Length 3 feet (0.91 meters)
Number of Power Cords 1
Acceptable Input Voltage 180-264 VAC
Output
Input
1 of 2 7/27/2010 7:49 PM
Net Weight 125.00 lbs. (56.82 kg)
Maximum Height 5.10 inches (130 mm)
Maximum Width 17.00 inches (432 mm)
Maximum Depth 26.00 inches (660 mm)
Shipping Weight 140.00 lbs. (63.64 kg)
Shipping Height 13.68 inches (347 mm)
Shipping Width 23.74 inches (603 mm)
Shipping Depth 38.60 inches (980 mm)
Color Black
Units per Pallet 6.00
Operating Environment 32 - 104 °F (0 - 40 °C)
Operating Relative Humidity 0 - 95%
Operating Elevation 0-10000 feet (0-3000 meters)
Storage Temperature -13 - 149 °F (-25 - 65 °C)
Storage Relative Humidity 0 - 95%
Storage Elevation 0-50000 feet (0-15000 meters)
Regulatory Approvals CSA,UL Listed
Standard Warranty 2 years repair or replace
Environmental Compliance RoHS 7b Exemption
Physical
Environmental
Conformance
*Except where noted, all prices are Estimated Resale Price (ERP) - Without Tax/VAT. Pricing in other locations and sites may vary.
2 of 2 7/27/2010 7:49 PM
| FDA Typical IT CLoset Calculations.pdf |
| Cisco 3000W Power Supply Data.pdf |
| Pages from 0apwsply-2.pdf |
| Pages from 0apwsply.pdf |
| APC Symmetra RM 4kVA UPS.pdf |
| APC Smart-UPS RT 5000VA.pdf |
| APC SURT003 Step Down Transformer.pdf |
File details come from the government source that posted it. Updated .