EXHIBIT A TUS FAN SCHEDULE INFORMATION.pdf
PDF 60 KB Posted
- Attached to
- Tacoma Union Station TAB Testing - HVAC Testing Federal contract opportunity
- Solicitation number
- 47PL0220Q0016
About this file
This document contains technical specifications for HVAC systems at Tacoma Union Station and details for a related federal contract opportunity. The specifications provide design airflow capacities, terminal unit counts, motor details, and other technical information for 13 air handling units and 6 cooling refrigeration units that serve the facility.
The related solicitation is seeking a contractor to conduct test and balance (TAB) of the Tacoma Union Station HVAC systems. The General Services Administration Public Buildings Service Region 10 is the contracting agency. The facility is experiencing issues maintaining temperatures in various areas, negatively impacting tenant comfort. The contractor will be responsible for providing all labor, materials, and equipment to conduct TAB testing and balancing of the HVAC systems according to the technical specifications in order to resolve temperature regulation problems at the facility.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| EXHIBIT F April 2020 Airflow Readings.xlsx | XLSX spreadsheet | |
| 47PL0220Q0016.pdf | ||
| EXHIBIT C WAGE DETERMINATION.pdf | ||
| ATTACHMENT A CONTRACTOR INFORMATION WORKSHEET CIW.pdf | ||
| EXHIBIT D TUS TAB DWGS.pdf | ||
| ATTACHMENT B VENDOR FITNESS DETERMINATION TRAINING .pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Tacoma Union Station AHU data obtained from TAB reports
Fan ID
Design Airflow
(CFM)
Max Primary Airflow
(CFM)
Min Primary Airflow
(CFM) % OA
Outside air intake
(CFM)
No of Terminal Units
No of supply registers
Motor
HP
Motor BHP Voltage
Avg Amps
Motor
RPM
AHU-1 40000 43022 9518 22.1236 9518.015192 66 215 60 44.26 460 ( 52.63) 1780 CTV-C AHU-2 40000 39060 6210 15.8986 6209.99316 59 186 60 26.84 460 ( 31.87) 1780 CTV-C
AHU-3 15000 15846 3090 19.5 3089.97 12 61 20 13.05 460 ( 16.13) 1760
AHU-4 40000 38840 5000 12.8733 4999.98972 55 164 50 46.35 460 ( 51.80) 1760
AHU-5 9900 10325 18.52784504 1913 6 10 8.17 460 ( 10.17) 1745
AHU-6 9400 12048 20.02822045 2413 6 10 7.97 460 ( 10.10) 1745
AHU-7 5800 5970 9890 16.4154 979.99938 5 23 7.5 5.81 460 ( 7.67) 1750 CTV-A
AHU-8 6600 6589 1500 22.7652 1499.999028 4 7.5 5.14 460 ( 7.00) 1750
AHU-9 6016 5260 900 17.1103 900.00178 7 26 5 5.18 460 ( 6.23) 1740
AHU-10 4460 5435 840 15.4554 840.00099 5 23 5 3.09 460 ( 4.43) 1740 CTV-A
AHU-11 3800 3599 1300 36.1211 1299.998389 4 5 2.35 460 ( 3.37) 1740
AHU-12 4600 5220 820 15.7088 819.99936 8 25 5 3.16 460 ( 4.53) 1740
AHU-13 2200 2280 200 5 1.5 0.84 460 ( 1.77) 1735
RF-1 38000 5 40 17.83 460 ( 21.03) 1760 CTV-B
RF-2 38000 5 40 30.07 460 ( 35.53) 1760 CTV-B
RF-3 13000 10 5.85 460 ( 7.83) 1745
Service EG EF-1 Toilet? 18
EF-2
EF-3
EF-4
EF-5
EF-6
EF-7
EF-8
EF-9
EF-10
EF-11
EF-12
EF-13
EF-14
Exclude from scope of work
AC-1 5000 9 34
Tacoma Union Station AHU data obtained from TAB reports
Fan ID
Design Airflow
(CFM)
Max Primary Airflow
(CFM)
Min Primary Airflow
(CFM) % OA
Outside air intake
(CFM)
No of Terminal Units
No of supply registers
Motor
HP
Motor BHP Voltage
Avg Amps
Motor
RPM
AC-2 2800
AC-3 1200
AC-4 1200
AC-5 2800
AC-6 1200
CRU #2 2800
CRU #3 1250
CRU #4 Not used
CRU #5 2150
CRU #6 950
File details come from the government source that posted it. Updated .