EXHIBIT A TUS FAN SCHEDULE INFORMATION.pdf

PDF 60 KB Posted

Attached to
Tacoma Union Station TAB Testing - HVAC Testing Federal contract opportunity
Solicitation number
47PL0220Q0016
Issued by
General Services Administration Public Buildings Service Region 10

About this file

This document contains technical specifications for HVAC systems at Tacoma Union Station and details for a related federal contract opportunity. The specifications provide design airflow capacities, terminal unit counts, motor details, and other technical information for 13 air handling units and 6 cooling refrigeration units that serve the facility.

The related solicitation is seeking a contractor to conduct test and balance (TAB) of the Tacoma Union Station HVAC systems. The General Services Administration Public Buildings Service Region 10 is the contracting agency. The facility is experiencing issues maintaining temperatures in various areas, negatively impacting tenant comfort. The contractor will be responsible for providing all labor, materials, and equipment to conduct TAB testing and balancing of the HVAC systems according to the technical specifications in order to resolve temperature regulation problems at the facility.

View the file

Other files for this federal contract opportunity

Other files attached to Tacoma Union Station TAB Testing - HVAC Testing, newest first.
File Type Posted
EXHIBIT F April 2020 Airflow Readings.xlsx XLSX spreadsheet
47PL0220Q0016.pdf PDF
EXHIBIT C WAGE DETERMINATION.pdf PDF
ATTACHMENT A CONTRACTOR INFORMATION WORKSHEET CIW.pdf PDF
EXHIBIT D TUS TAB DWGS.pdf PDF
ATTACHMENT B VENDOR FITNESS DETERMINATION TRAINING .pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Tacoma Union Station AHU data obtained from TAB reports

Fan ID

Design Airflow

(CFM)

Max Primary Airflow

(CFM)

Min Primary Airflow

(CFM) % OA

Outside air intake

(CFM)

No of Terminal Units

No of supply registers

Motor

HP

Motor BHP Voltage

Avg Amps

Motor

RPM

AHU-1 40000 43022 9518 22.1236 9518.015192 66 215 60 44.26 460 ( 52.63) 1780 CTV-C AHU-2 40000 39060 6210 15.8986 6209.99316 59 186 60 26.84 460 ( 31.87) 1780 CTV-C

AHU-3 15000 15846 3090 19.5 3089.97 12 61 20 13.05 460 ( 16.13) 1760

AHU-4 40000 38840 5000 12.8733 4999.98972 55 164 50 46.35 460 ( 51.80) 1760

AHU-5 9900 10325 18.52784504 1913 6 10 8.17 460 ( 10.17) 1745

AHU-6 9400 12048 20.02822045 2413 6 10 7.97 460 ( 10.10) 1745

AHU-7 5800 5970 9890 16.4154 979.99938 5 23 7.5 5.81 460 ( 7.67) 1750 CTV-A

AHU-8 6600 6589 1500 22.7652 1499.999028 4 7.5 5.14 460 ( 7.00) 1750

AHU-9 6016 5260 900 17.1103 900.00178 7 26 5 5.18 460 ( 6.23) 1740

AHU-10 4460 5435 840 15.4554 840.00099 5 23 5 3.09 460 ( 4.43) 1740 CTV-A

AHU-11 3800 3599 1300 36.1211 1299.998389 4 5 2.35 460 ( 3.37) 1740

AHU-12 4600 5220 820 15.7088 819.99936 8 25 5 3.16 460 ( 4.53) 1740

AHU-13 2200 2280 200 5 1.5 0.84 460 ( 1.77) 1735

RF-1 38000 5 40 17.83 460 ( 21.03) 1760 CTV-B

RF-2 38000 5 40 30.07 460 ( 35.53) 1760 CTV-B

RF-3 13000 10 5.85 460 ( 7.83) 1745

Service EG EF-1 Toilet? 18

EF-2

EF-3

EF-4

EF-5

EF-6

EF-7

EF-8

EF-9

EF-10

EF-11

EF-12

EF-13

EF-14

Exclude from scope of work

AC-1 5000 9 34

Tacoma Union Station AHU data obtained from TAB reports

Fan ID

Design Airflow

(CFM)

Max Primary Airflow

(CFM)

Min Primary Airflow

(CFM) % OA

Outside air intake

(CFM)

No of Terminal Units

No of supply registers

Motor

HP

Motor BHP Voltage

Avg Amps

Motor

RPM

AC-2 2800

AC-3 1200

AC-4 1200

AC-5 2800

AC-6 1200

CRU #2 2800

CRU #3 1250

CRU #4 Not used

CRU #5 2150

CRU #6 950