Exhibit_A-1_-_SFM_Approved_Drawings_JCCA__21791-4.pdf

PDF 6 MB Posted

Attached to
23-30641-000 - N Building Cooling Tower Installation and Site Improvement Services
Solicitation number
0000031721
Issued by
California

About this file

This document contains the approved drawings for a cooling tower installation and site improvement project for the Department of State Hospitals (DSH) in Patton, California. The project involves providing all materials, supplies, tools, equipment, transportation, licenses, permits, prevailing wages, insurance, bonds, and personnel to install a new cooling tower and make site improvements for Building N on the DSH campus. The project is required to be completed by February 8, 2024, with a resubmittal to the State Fire Marshal scheduled for April 23, 2024. The project has received approval from the Division of the State Architect (DSA) and the Office of the State Fire Marshal (OSFM).

The contract opportunity states the selected contractor must meet all prevailing wage requirements and provide necessary insurance and bonds. Pricing terms, funding sources, and other financial details are not provided. The contract opportunity does not mention any set-asides or incumbent contractors.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

X

X X X X X X X X X X X X X X X X X X X X X X X X X X X

X

X X

X

X

X

X

X

X

X X

X

X

X

X

X

X

X

X

X

X

X

X

X X

X

X

X

XX

X

X

X

X

X

X

X XX

X X X

X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X

X

X

X

X

X

X

X

X

X

X X

X X

X X

X X

X X

X X

X X

X

X

X X

X X

X

X

X X

X X

X

X

X X

X X

X

X

X

X X

X

X

X

X

X

X

X

X

X X

X

X

X

X

X

X

X X X X

X X X

X

XXXX

XX

X

X

X X

X

X

X

X

X

X

X

X

X

X

X X

X X

X X

X X

X

X

X

X

X

X X

X

X X X X X X X X X

X X X X X X X X X

X X X X X

X

X

X

X

X

X

X

X

X

X X

X X

X

X

X X

X X

X

X

X X

X X

X X

X X X X X X

X

X

X

X X

X X

X

X

X

X

X

X X

X X

X X

X X

X X

X X

X

X

X X

X

X

X

XX

X

XX X X

X

X

X

X

X

X

X

X X

X

X X X

X

X

X

X

X

X X X

X X

X X X X

X

X

X X

X

X

X

X X

X X

X

X X

X

X

X

X

X

X

X

X

X

X X

X

X

CS-77-CS-79

WEBSTER DRIVE

MILLER

GB-14

M B- P

HIGHLAND

GB-16

S-13

U

GB-15

G-259

C

IR

C L E D

R

G-258

J

S-1

RILEY ST

S-6

GB-10

CS-8

R

CS-5

P A T T O N A

V E

O L

IV

E S

T

O L

IV

E S

T

S-7

CS-70

S-2 S-3

CS-72

S-5

CS-44 -

CS-54 -

CS-71

PATTON

CEMETARY

DATE STREET

MB-30D

G2

R-2

GB-7

GB-18

MB-70A

SBCFD

STATION

#228

294 272

MB-30A

518516 524 525

R-10

R-6

GB-17

R-1

CD

CS-73

MB-ND

G-15

R-15

R-14 G-13

R-13

R-8 G-8

G-19

R-19

G-17 R-18

MB-70F

MB-70B

MB-70C

GB-4

GB-1

GB-13

GB-9

565564

R-11

521 519

R-12

MB-NC

MB-NA

MB-EBB

MB-OA

MB-U

MB-70E

MB-70D

CORP YARD

S-

PUMALO AVE.

S-

LA

KE

VIE

W CI

RC

LE

S-

R E A R S E R V

IC

E R

O A D

CIR

CL

E D

RIV

E

M Y R T L E D

R

EMERALD LANE

C E N T R A L A

V E

TA

LL

M

AN

R

OAD

V

IC

T O R

IA

A V E

GERICKE

FIELD

GB-12

GB-11

TENNIS COURT

R-17

M B-

OB

REC

FIELD

GB-6

O R A N G E S

T R E E T

GB-5

GB-3

GB-8

GB-10

R-16

G-16

MB-30C

MB-30B

M

IR

T L E D

R

G-260

O

N 235

T

P

297H

CS-9

CS-10

CS-6

CS-7

S-8

MB-EBC

CS-1 -

MB-NB

CS-4

S-4

CS-11-CS-43

CS-47 - CS-53

GB-2

CS-75

CS-74

MB-EBA

G

CS-46

CS-3

M

ED BERNATH 243

CS-76

S-9

LANE

S-14

SOLAR

ARRAY

TITLE SHEET,

DRAWING INDEX,

APPLICABLE CODES

AND SCOPE OF WORK

T0.1

PROJECT INFORMATION VICINITY MAP

COOLING TOWER, BUILDING N

3102 HIGHLAND AVENUE, PATTON, CALIFORNIA 92369

DEPARTMENT OF STATE HOSPITALS - D.S.H.

SHEET INDEX

PROJECT

LOCATION

LOCATION MAP

SCOPE OF WORK

APPLICABLE CODES AND STANDARDS

HCAI DEFERRED APPROVALS

DSA NOTES

HCAI NOTES

RN RF RNRF

JCCA

385 VAN NESS AVENUE, SUITE 208

ASSOCIATES, INC.

J.C. CHANG &

ARCHITECTS PLANNERSENGINEERS

TORRANCE, CALIFORNIA 90501

PH (310) 212-7644

FAX (310) 212-5272

JCCA #21791-4

00000000000XXXX

DEPARTMENT OF STATE

HOSPITALS, PATTON

DEPARTMENT OF

STATE HOSPITALS

(DSH)

AS SHOWN

DSA STAMP

COOLING TOWER,

BUILDING N

DSH

2/08/2024

DEPARTMENT OF STATE HOSPITALS

3/16/2022

1ST SFM & SAN BERNARDINO

FIRE SUBMITTAL

2/08/2024 RESUBMITTAL TO SFM

4/23/2024 SFM PC CORRECTION

OSFM FILE NO. = 19-36-44-0090-00022

OSFM PERMIT NO. = 24-0574

V2

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

05/02/24

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

24-0574

OSFM TRIAGE LIST

AND SEISMIC

PROTECTION NOTES

1. GENERAL

RN RF RN

SEISMIC PROTECTION NOTES SEISMIC PROTECTION NOTES

TEMPORARY AIR COOLED CHILLER NOTES

FIRE SAFETY DURING CONSTRUCTION

FIRE APPARATUS ACCESS

BUILDING

NAME

CONSTRUCTION

TYPE

NUMBER OF

STORIES

ACTUAL

BUILDING

HEIGHT

BUILDING

AREA IN

SQ. FT.

AREA OF

PROJECT

USE

SPRINKLER

COVERAGE

FIRE ALARM

OTHER

PROTECTION

SYSTEM

SMOKE

CONTROL

SYSTEM

OCCUPANT

LOAD

(TOTAL)

YEAR

BUILDING

CONSTRUCTED

HIGH FIRE

HAZARD

SEVERITY ZONE

SEISMIC

JOINT

EMERGENCY

RESPONDER RADIO

COVERAGE

OCCUPANCY

CLASS

ALLOWABLE

AREA

(NOTE 1)

ALLOWABLE

STOREY

(NOTE 1)

AREA

INCREASE

HEIGHT

INCREASE

OCCUPANT

LOAD

(1ST FLR)

OCCUPANT

LOAD

(2ND FLR)

OCCUPANT

LOAD

(3RD FLR)

OCCUPANT

LOAD

(BASEMENT)

ADJACENT BUILDING N BUILDING ANALYSIS

T0.2

COOLING TOWER PHOTO - BUILDING N

RF

JCCA

385 VAN NESS AVENUE, SUITE 208

ASSOCIATES, INC.

J.C. CHANG &

ARCHITECTS PLANNERSENGINEERS

TORRANCE, CALIFORNIA 90501

PH (310) 212-7644

FAX (310) 212-5272

JCCA #21791-4

00000000000XXXX

DEPARTMENT OF STATE

HOSPITALS, PATTON

DEPARTMENT OF

STATE HOSPITALS

(DSH)

AS SHOWN

DSA STAMP

COOLING TOWER,

BUILDING N

DSH

2/08/2024

DEPARTMENT OF STATE HOSPITALS

3/16/2022

1ST SFM & SAN BERNARDINO

FIRE SUBMITTAL

2/08/2024 RESUBMITTAL TO SFM

4/23/2024 SFM PC CORRECTION

V2

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

05/02/24

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject

4/23/2024 SFM PC CORRECTION

V2

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

05/02/24

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject

4/23/2024 SFM PC CORRECTION

V2

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

05/02/24

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject

M0.1

MECHANICAL

COVER SHEET

PROJECT NOTES GENERAL NOTES

RN RF RNRF

JCCA

385 VAN NESS AVENUE, SUITE 208

ASSOCIATES, INC.

J.C. CHANG &

ARCHITECTS PLANNERSENGINEERS

TORRANCE, CALIFORNIA 90501

PH (310) 212-7644

FAX (310) 212-5272

JCCA #21791-4

00000000000XXXX

DEPARTMENT OF STATE

HOSPITALS, PATTON

DEPARTMENT OF

STATE HOSPITALS

(DSH)

AS SHOWN

DSA STAMP

COOLING TOWER,

BUILDING N

DSH

2/08/2024

DEPARTMENT OF STATE HOSPITALS

3/16/2022

1ST SFM & SAN BERNARDINO

FIRE SUBMITTAL

2/08/2024 RESUBMITTAL TO SFM

4/23/2024 SFM PC CORRECTION

MECHANICAL SYMBOLS

MECHANICAL PIPING LEGEND

MECHANICAL PIPING SYMBOLS

MECHANICAL ABBREVIATIONS

HCAI

V2

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

05/02/24

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject

M0.2

EQUIPMENT

SCHEDULE

COOLING TOWER SCHEDULE

FILTER SYSTEM

EXPANSION TANK

EXISTING PUMP SCHEDULE (FOR REFERENCE ONLY)

PIPING ACCESSORIES SCHEDULE

CONSTRUCTION PHASING & TEMPORARY

HVAC EQUIPMENT REQUIREMENTS

6.

1.

4.

2.

5.

3.

START UP AND CERTIFICATE

RN RF RNRF

JCCA

385 VAN NESS AVENUE, SUITE 208

ASSOCIATES, INC.

J.C. CHANG &

ARCHITECTS PLANNERSENGINEERS

TORRANCE, CALIFORNIA 90501

PH (310) 212-7644

FAX (310) 212-5272

JCCA #21791-4

00000000000XXXX

DEPARTMENT OF STATE

HOSPITALS, PATTON

DEPARTMENT OF

STATE HOSPITALS

(DSH)

AS SHOWN

DSA STAMP

COOLING TOWER,

BUILDING N

DSH

2/08/2024

DEPARTMENT OF STATE HOSPITALS

3/16/2022

1ST SFM & SAN BERNARDINO

FIRE SUBMITTAL

2/08/2024 RESUBMITTAL TO SFM

4/23/2024 SFM PC CORRECTION

V2

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

05/02/24

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject

M1.0

SITE PLAN

RN RF RNRF

JCCA

385 VAN NESS AVENUE, SUITE 208

ASSOCIATES, INC.

J.C. CHANG &

ARCHITECTS PLANNERSENGINEERS

TORRANCE, CALIFORNIA 90501

PH (310) 212-7644

FAX (310) 212-5272

JCCA #21791-4

00000000000XXXX

DEPARTMENT OF STATE

HOSPITALS, PATTON

DEPARTMENT OF

STATE HOSPITALS

(DSH)

AS SHOWN

DSA STAMP

COOLING TOWER,

BUILDING N

DSH

2/08/2024

DEPARTMENT OF STATE HOSPITALS

3/16/2022

1ST SFM & SAN BERNARDINO

FIRE SUBMITTAL

2/08/2024 RESUBMITTAL TO SFM

4/23/2024 SFM PC CORRECTION

SITE PLAN

V2

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

05/02/24

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject

M1.1

DEMOLITION

FLOOR PLAN

MECHANICAL DEMOLITION FLOOR PLAN

DEMOLITION KEYNOTES:

GENERAL NOTES:

RN RF RNRF

JCCA

385 VAN NESS AVENUE, SUITE 208

ASSOCIATES, INC.

J.C. CHANG &

ARCHITECTS PLANNERSENGINEERS

TORRANCE, CALIFORNIA 90501

PH (310) 212-7644

FAX (310) 212-5272

JCCA #21791-4

00000000000XXXX

DEPARTMENT OF STATE

HOSPITALS, PATTON

DEPARTMENT OF

STATE HOSPITALS

(DSH)

AS SHOWN

DSA STAMP

COOLING TOWER,

BUILDING N

DSH

2/08/2024

DEPARTMENT OF STATE HOSPITALS

3/16/2022

1ST SFM & SAN BERNARDINO

FIRE SUBMITTAL

2/08/2024 RESUBMITTAL TO SFM

4/23/2024 SFM PC CORRECTION

V2

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

05/02/24

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject

M2.1

NEW WORK

FLOOR PLAN

MECHANICAL NEW WORK FLOOR PLAN

RN RF RNRF

JCCA

385 VAN NESS AVENUE, SUITE 208

ASSOCIATES, INC.

J.C. CHANG &

ARCHITECTS PLANNERSENGINEERS

TORRANCE, CALIFORNIA 90501

PH (310) 212-7644

FAX (310) 212-5272

JCCA #21791-4

00000000000XXXX

DEPARTMENT OF STATE

HOSPITALS, PATTON

DEPARTMENT OF

STATE HOSPITALS

(DSH)

AS SHOWN

DSA STAMP

COOLING TOWER,

BUILDING N

DSH

2/08/2024

DEPARTMENT OF STATE HOSPITALS

3/16/2022

1ST SFM & SAN BERNARDINO

FIRE SUBMITTAL

2/08/2024 RESUBMITTAL TO SFM

4/23/2024 SFM PC CORRECTION

NEW WORK KEYNOTES:

EXISTING SEQUENCE OF OPERATION (FOR INFO.)

GENERAL NOTES:

V2

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

05/02/24

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject

M3.1

DETAILS

COOLING TOWER PIPING

RN RF RNRF

JCCA

385 VAN NESS AVENUE, SUITE 208

ASSOCIATES, INC.

J.C. CHANG &

ARCHITECTS PLANNERSENGINEERS

TORRANCE, CALIFORNIA 90501

PH (310) 212-7644

FAX (310) 212-5272

JCCA #21791-4

00000000000XXXX

DEPARTMENT OF STATE

HOSPITALS, PATTON

DEPARTMENT OF

STATE HOSPITALS

(DSH)

AS SHOWN

DSA STAMP

COOLING TOWER,

BUILDING N

DSH

2/08/2024

DEPARTMENT OF STATE HOSPITALS

3/16/2022

1ST SFM & SAN BERNARDINO

FIRE SUBMITTAL

2/08/2024 RESUBMITTAL TO SFM

4/23/2024 SFM PC CORRECTION

COOLING TOWER DETAIL

CHILLED WATER & CONDENSER WATER PIPING SCHEMATIC

TOP VIEW

SIDE VIEW

FRONT VIEW

V2

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

05/02/24

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject

M3.2

DETAILS

FILTRATION SYSTEM DETAIL

COMPONENT LIST:

NOTES:

FRONT VIEW ROTATED STRAINER

FRONT VIEW PUMP & STRAINER

TOP VIEW

FRONT VIEW W/O STRAINER

RN RF RNRF

JCCA

385 VAN NESS AVENUE, SUITE 208

ASSOCIATES, INC.

J.C. CHANG &

ARCHITECTS PLANNERSENGINEERS

TORRANCE, CALIFORNIA 90501

PH (310) 212-7644

FAX (310) 212-5272

JCCA #21791-4

00000000000XXXX

DEPARTMENT OF STATE

HOSPITALS, PATTON

DEPARTMENT OF

STATE HOSPITALS

(DSH)

AS SHOWN

DSA STAMP

COOLING TOWER,

BUILDING N

DSH

2/08/2024

DEPARTMENT OF STATE HOSPITALS

3/16/2022

1ST SFM & SAN BERNARDINO

FIRE SUBMITTAL

2/08/2024 RESUBMITTAL TO SFM

4/23/2024 SFM PC CORRECTION

V2

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

05/02/24

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject

M5.1

TITLE 24 COMPLIANCE

FORM

RN RF RNRF

JCCA

385 VAN NESS AVENUE, SUITE 208

ASSOCIATES, INC.

J.C. CHANG &

ARCHITECTS PLANNERSENGINEERS

TORRANCE, CALIFORNIA 90501

PH (310) 212-7644

FAX (310) 212-5272

JCCA #21791-4

00000000000XXXX

DEPARTMENT OF STATE

HOSPITALS, PATTON

DEPARTMENT OF

STATE HOSPITALS

(DSH)

AS SHOWN

DSA STAMP

COOLING TOWER,

BUILDING N

DSH

2/08/2024

DEPARTMENT OF STATE HOSPITALS

3/16/2022

1ST SFM & SAN BERNARDINO

FIRE SUBMITTAL

2/08/2024 RESUBMITTAL TO SFM

4/23/2024 SFM PC CORRECTION

V2

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

05/02/24

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject

E0.1

ELECTRICAL NOTES,

ABBREVIATIONS,

SYMBOLS & DRAWING

LEGEND

RN RF RNGJN

JCCA

385 VAN NESS AVENUE, SUITE 208

ASSOCIATES, INC.

J.C. CHANG &

ARCHITECTS PLANNERSENGINEERS

TORRANCE, CALIFORNIA 90501

PH (310) 212-7644

FAX (310) 212-5272

JCCA #21791-4

00000000000XXXX

DEPARTMENT OF STATE

HOSPITALS, PATTON

DEPARTMENT OF

STATE HOSPITALS

(DSH)

AS SHOWN

DSA STAMP

COOLING TOWER,

BUILDING N

DSH

2/08/2024

DEPARTMENT OF STATE HOSPITALS

3/16/2022

1ST SFM & SAN BERNARDINO

FIRE SUBMITTAL

2/08/2024 RESUBMITTAL TO SFM

4/23/2024 SFM PC CORRECTION

LINETYPE LEGENDAPPLICABLE CODES & STANDARDS

GENERAL NOTES ABBREVIATIONS SYMBOL LIST

OSHPD SEISMIC NOTES DEFINITION

V2

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

05/02/24

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject

E0.2

SINGLE LINE

DIAGRAM

RN RF RNGJN

JCCA

385 VAN NESS AVENUE, SUITE 208

ASSOCIATES, INC.

J.C. CHANG &

ARCHITECTS PLANNERSENGINEERS

TORRANCE, CALIFORNIA 90501

PH (310) 212-7644

FAX (310) 212-5272

JCCA #21791-4

00000000000XXXX

DEPARTMENT OF STATE

HOSPITALS, PATTON

DEPARTMENT OF

STATE HOSPITALS

(DSH)

AS SHOWN

DSA STAMP

COOLING TOWER,

BUILDING N

DSH

2/08/2024

DEPARTMENT OF STATE HOSPITALS

3/16/2022

1ST SFM & SAN BERNARDINO

FIRE SUBMITTAL

2/08/2024 RESUBMITTAL TO SFM

4/23/2024 SFM PC CORRECTION

SINGLE LINE DIAGRAM

NEW WORK KEYNOTES:

VFD

VFD VFD

V2

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

05/02/24

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject

V F D

V F D

V F D

E1.1

ELECTRICAL

DEMOLITION

FLOOR PLAN

ELECTRICAL DEMOLITION FLOOR PLAN

DEMOLITION KEYNOTES:

GENERAL NOTES:

RN RF RNGJN

JCCA

385 VAN NESS AVENUE, SUITE 208

ASSOCIATES, INC.

J.C. CHANG &

ARCHITECTS PLANNERSENGINEERS

TORRANCE, CALIFORNIA 90501

PH (310) 212-7644

FAX (310) 212-5272

JCCA #21791-4

00000000000XXXX

DEPARTMENT OF STATE

HOSPITALS, PATTON

DEPARTMENT OF

STATE HOSPITALS

(DSH)

AS SHOWN

DSA STAMP

COOLING TOWER,

BUILDING N

DSH

2/08/2024

DEPARTMENT OF STATE HOSPITALS

3/16/2022

1ST SFM & SAN BERNARDINO

FIRE SUBMITTAL

2/08/2024 RESUBMITTAL TO SFM

4/23/2024 SFM PC CORRECTION

V2

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

05/02/24

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject

F

V F D

V F D

V F D

F

NEW WORK KEYNOTES:

GENERAL NOTES:

RN RF RNGJN

JCCA

385 VAN NESS AVENUE, SUITE 208

ASSOCIATES, INC.

J.C. CHANG &

ARCHITECTS PLANNERSENGINEERS

TORRANCE, CALIFORNIA 90501

PH (310) 212-7644

FAX (310) 212-5272

JCCA #21791-4

00000000000XXXX

DEPARTMENT OF STATE

HOSPITALS, PATTON

DEPARTMENT OF

STATE HOSPITALS

(DSH)

AS SHOWN

DSA STAMP

COOLING TOWER,

BUILDING N

DSH

2/08/2024

DEPARTMENT OF STATE HOSPITALS

3/16/2022

1ST SFM & SAN BERNARDINO

FIRE SUBMITTAL

2/08/2024 RESUBMITTAL TO SFM

4/23/2024 SFM PC CORRECTION

E2.1

ELECTRICAL

NEW WORK

FLOOR PLAN

ELECTRICAL NEW WORK FLOOR PLAN

V2

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

05/02/24

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject

0001 T0.1 TITLE SHEET, DRAWING INDEX, APPLICABLE CODES
217914_T01--
0002 T0.2 OSFM TRIAGE LIST AND SEISMIC PROTECTION NOTES
217914_T02--
0003 S0.1 STRUCTURAL COVER SHEET
0004 S2.1 FOUNDATION PLAN & STRUCTURAL DETAILS
0005 M0.1 MECHANICAL COVER SHEET
217914_M01-M0.1
0006 M0.2 MECHANICAL EQUIPMENT SCHEDULE
217914_M02-M0.1
0007 M1.0 SITE PLAN
217914_M10-M10
0008 M1.1 MECHANICAL DEMOLITION FLOOR PLAN
217914_M11-M1.1
0009 M2.1 MECHANICAL NEW WORK FLOOR PLAN
217914_M21-M1.1
0010 M3.1 MECHANICAL DETAILS
217914_M31-M0.1
0011 M3.2 MECHANICAL DETAILS
217914_M32-M0.1
0012 M5.1 TITLE 24 COMPLIANCE FORM
217914_M51-M5.1
0013 E0.1 ELECTRICAL NOTES, ABBREVIATIONS, SYMBOLS
217914_E01-M1.1
0014 E0.2 SINGLE LINE DIAGRAM
217914_E02-M1.1
0015 E1.1 ELECTRICAL DEMOLITION FLOOR PLAN
217914_E11-M1.1
0016 E2.1 ELECTRICAL NEW WORK FLOOR PLAN
217914_E21-M1.1

File details come from the government source that posted it. Updated .