The project, designated BMH-EXC-B0519-6P, requires comprehensive repairs and modifications to doors and associated infrastructure to achieve NFPA 101 Life Safety Code compliance. Key scope items include: (1) modification of approximately 36 numbered escape and emergency exit doors to eliminate lockable mechanisms that currently violate fire safety codes; (2) installation of a new gate with integrated pedestrian door (Schlupftür) at the north delivery entrance to replace an existing non-compliant gate; (3) construction of walkways and trench covers on the north side with proper pavement heights to eliminate steps at emergency exits; (4) replacement of a deteriorated exterior stair structure at door #12 with a temporary modular stair system requiring structural calculations; (5) closure of a large opening (approximately 3.0m x 2.2m) in the Human Resources office with masonry; (6) enhancement of the fire alarm detection system with additional smoke detectors for complete room coverage; (7) installation of fire-rated drywall with a door enclosure around the fire alarm system location; (8) sealing of cable and utility penetrations through stairwell and fire-rated walls, with replacement of damaged ceiling tiles; (9) modification of door #29 locking hardware to provide fire department emergency access; (10) plaster and paint repairs at multiple locations; and (11) closure of ceiling openings to the attic space. A certified designer is required to prepare construction documents. All work must comply with NFPA 101 requirements and federal building safety standards. Site documentation includes floor plans with marked penetration locations and photographic evidence of current conditions requiring remediation.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Project-No.: BMH- EXC-B0519-6P, Repair Doors PX Bldg. 8401
Typical escape door currently installed (photo shows door #1):
Currently the doors can be locked, this does not meet NFPA 101 requirements.
Photo shows door #12 from the storage to the outside
#36 subway
Stair room number 201, toilet doors #15 and #16. Escape door in the middle #13
Existing gate at delivery entrance on north side:
Sample photo for new gate with integrated door:
Integrated door/ Schlupftür
Sample photo of partial plaster and paint repair around a new door:
Walkway and trench cover must be made on north side (doors #2 and #3):
East side store emergency exit, correct the pavement height (door #1):
Step is not allowed according to NFPA 101.
East side walkway, exit from subway and mechanical room. Pavement must be raised and widened (door # 34 and #35):
Photos of current stair that shall be replaced (door #12 1st floor):
Material is in a very bad condition.
Sample photo of a temporary stair made of individual elements with structural calculation for the system (Systemstatik) (doors # 14 and #25)
Windows and panels that shall be removed and closed with masonry. Size opening appr.
3,00m x 2,20m:
Fire Alarm System, current scope of detectors. Add sufficient number of detectors to every room for full coverage.
Certified designer must do the design described in the contract.
Add fire rated drywall with door in corner where fire alarm system is located:
Prepare wall, remove loose plaster, move outlets, move or remove cable ducts.
Door #29 is currently not accessible from outside. Change half cylinder to a standard cylinder so that fire department can open that door in case of an emergency. Change/ replace covers if needed. Cylinder shall be part of the locking system.
Door #29, detailed view from inside.
Plaster at south side of façade (opposite side of Telekom shop) needs repair of plaster.
Penetrations in stairwell wall and fire rated walls according to marking in floor plan
There are some single cable penetrations and some single small holes in the walls that are not shown on the photos.
For the bid it can be assumed that almost all ceiling tiles along the staircase walls must be removed to get access to the wall penetrations.
Replace all dirty or broken ceiling tiles.
Wall penetrations in the 1st floor storage and mechanical rooms can be seen on site during the pre-bid site visit, no photos are provided.
1st floor
2nd floor
Close ceiling opening to attic
Close penetration/ hole in ceiling.
Replace broken ceiling tiles