ESBD_File_355131_HHS0014504-2 Exhibit F Drawing 2.pdf
PDF 113 KB Posted
- Attached to
- HHS0014504-2 Reverse Osmosis Control Panel
- Solicitation number
- HHS0014504-2
- Issued by
- Travis County, Austin City, Texas
About this file
The document is an engineering drawing and specifications for a Reverse Osmosis (RO) system model XL-3L-4H that is part of a state and local contract opportunity issued by the Texas Department of State Health Services (DSHS) for Travis County and the City of Austin. The contract involves the design, programming, and installation of a replacement control panel for the RO/Deionization Water Purification system. The drawing provides detailed schematics and technical specifications for the RO system components, including the structural frame, hydraulic panel, electrical requirements, pump motors, and piping.
The contract opportunity covers jurisdictions within Travis County and the City of Austin. No specific pricing terms, set asides, incumbent information, or funding details are provided in the document. The contract appears to be for the replacement of an existing RO control panel, but the full scope and requirements are not detailed in the drawing.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
D
C
B
A
8 7 6 5 4 3 2 1
STANDARD STAINLESS STEEL FEATURES AND SPECIFICATIONS
1. Structural Frame
2. Structural Frame Finish
304SS Structural Tubing, ASTM A554 Buff Finish
-------- 48" -------+---------------------- 148"
---------------------i------ 48" ---------1•-1
3. Cantrel Panel
4. Hydraulic Panel
304SS, NEMA 4X
304SS Plate, ASTM A240, Buff Finish
304SS, 150# RF, ASTM A182
CLEARANCE REQ'D
FOR ELEMENT REMOVAL
TP 1
...----i
ELECTRICAL
480 V / 3PH / 60 HZ
(SEE CHART FOR FLA)
RO HOUSING, FRP(TYP)
RATED 300 PSI
DISCONNECT 1STARTER
PANEL �181
CONTROL
PANEL
NEMA 4X
304 S5
74•
ANCHOR BOLTS
Pl Pl
HYDRAULIC
PANEL
c:::D:J c:::D:J
RECIRC WASTE
V/>J..VE V/>J..VE
PLAN VIEW
TP
INLET
FILTER
HOUSING
'-----------11------------�prz> sv
RO
PUMP
�----------- 83"'---------------
NOTES:
1. MODEL XL-3L-4H SHOWN.
2. ALL PUMP MOTORS ARE 480 VAC / 3 PH / 60 HZ.
3. INLET FLANGES ARE 150# RF 304 SS
4. PRODUCT AND WASTE FLANGES ARE 150# RF SCH80 PVC.
5. SY= SAMPLE VALVE 1/4" PVC.
6. Pl= PRESSURE GAUGE
7. RO FRAME MUST BE LEVELED AND ANCHORED PROPERLY BEFORE OPERATING.
8. HMI= ALLEN-BRADLEY COLOR TOUCH SCREEN CONTROL.
9. DO NOT SCALE DRAWING.
10. ALL DIMENSIONS ±2".
7 6
ELEVATION VIEW
CLEARANCE REQ'D
FOR ELEMENT REMOVAL
32"
ANCHOR BOLTS
1 /2",0'HOLE FOR 3/8".0 AB
(4) PLACES
ALL STAINLESS STEEL STRUCTURAL
FRAME-304 SS
WELD TYPE: GTAW (TIG)
ER 308/308L FILLER
RO MODEL
XL-3L-4H
TP101
INLET
2"
5. Inlet Flange
6. Inlet Piping
7. Filter Housing
8. RO Booster Pump
9. Booster Pump Motor
10. Pump Control Valve
11. Waste Control Valve
304SS, SCH10, ASTM A182
304SS, Multi-Cartridge Type, 100 PSI 316SS, Grundfos Model CRN
480VAC/3PH/60HZ, TEFC
316SS, Needle Valve 316SS, Needle Valve
12. Recirculatian Control Valve 316SS, Needle Valve
13. High Pressure Piping
14. Victaulic Clamps
15. Pipe Clamps
16. Air Bleed Valves
17. Pressure Gauges
18. Bolting Hardware
19. Inlet Valve
TP102 TP103 TP104
WASTE PRODUCT Cleaning
Connection
1" 2· 1.5" VIC
6 "77"
316SS Tubing x .065" Wall, ASTM A269 316SS, 600 PSI Rated 304SS w/Polypropylene Insert 316SS Needle Valve 316SS, 2.5" Dial, Liquid Filled
304SS, ANSI 818.2.1
316SS 2" Diaphragm Type
RO HOUSING PUMP FULL LOAD
FEED PORTS HP AMPS@
480V
2" VIC 15 21
SHIPPING
WT. (lbs)
PUMP
CONTROL
VALVE
------- 41"--------1
RIGHT SIDE VIEW
TITLE:
XL RO SERIES
™ REVERSE OSMOSIS
MODEL XL-3L-4H
_. COMPANY: CUSTOMER /I:
(,,� _CROSSLINK ULTRA PURE & INDUSTRIAL
Nanul'adullng DRAWN BY: APPROVED BY: DRAWING
ENGINEERED SYSTEMS TEP CEN 7-45GA_R(O)
DATE: 9/12/07 DATE: 9/12/07
GLENWOOD, ILLINOIS
Tel: 708-756-2417 Fax: 708-754-9897 www.crosslink-manufacturing.com
# OF SHEETS: SHEET #: