ESBD_File_353715_AHU-K6 Sched and details Garza West MWR 09522005 021524.pdf
PDF 3 MB Posted
- Solicitation number
- IW176581
- Issued by
- Bee County, Beaumont City, Texas
About this file
This document contains the equipment schedule, specifications, and scope of work for the replacement of air handling unit (AHU) K-6 at the Garza West Unit in Beeville, Texas. The Texas Department of Criminal Justice (TDCJ) is requesting bids to procure and install a replacement AHU-K6, including new supply and return fans, gas heating, and associated electrical and control components. The existing AHU-K6 is approximately 40 feet long, 8.3 feet wide, and 8.1 feet high, sitting on a 24-inch curb. The required replacement unit shall match the original unit's performance specifications and physical dimensions. TDCJ has provided detailed design information, including sequence of operations, for the replacement AHU-K6.
The bid documents do not include specific pricing terms, set-asides, incumbent information, or funding details. The contract will be awarded to the successful bidder who can provide the required replacement AHU-K6 and associated services per TDCJ's specifications. The replacement AHU-K6 is part of the HVAC system serving the Garza West Unit, a state correctional facility operated by TDCJ in Bee County, Texas.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
HP VOLTS/PH
AHU-K6
SF-K6
AF-1, AF-2
GB-K6
MCQUAY RAH077CYA CV 2 speed KITCHEN 35570 5 975 25350 50 460/3 1250 1560 23 105 69 74 100 3 460
AHU-K6
Alternative
TBD TBD VAV KITCHEN 33250 4 4200 TBD 460/3
Notes:
Provide Gas Regulator to reduce line pressure from 12 psig to 7" WC minimum or per manufacturer's recommendations Burners shall be selected based on site elevation of 190 ft. AMSL Electrical Disconnect Yes Electrical Disconnect for lights Yes Elevation 190 ft AMSL Service Electrical Outlet 120/60/1 15 amps Furnace Model 150SRA 1 Replacement unit includes new 24"H insulated curb for return air duct Return Air CFM is 19,015 Gas Burner Minimum CFM is 13700 New Air filters shall include a washable prefilter and minimum MERV 8 final filter.
Original Unit Serial# is 3ZBO1184-01 See attached for more details
This schedule and notes below are based on the original 1993 specifcations. Replacement selection capacity shall be no greater than the original. Preferred replacement capacity is detailed as alternative basis of design. Supply Fan motor HP to be based on alternative design cfm and ESP.
PACKAGED AIR HANDLING UNITS (Garza West MWR# 09522005)
TAG
BASIS OF DESIGN
TYPE SERVES
FAN DATA GAS HEAT ELECTRICAL DATA
MANUF. MODEL
TOTAL AIR
(CFM)
ESP IN.
WC
RPM MIN. O.A.
(CFM)
FAN MOTOR MOP PHASE VOLTFILTERS
MBH
OUTPUT
MBH
INPUT
EAT
DB
DEG
LAT
DB
DEG
FLA MCA
FK00057
Text Box Vendor shall furnish and install all equipment and associated parts necessary to complete the installation per equipment schedules, other details provided, and manufacturer's recommendations.
Startup equipment per manufacturer's recommendations.
Vendor is responsible for final integrity, functionality, and operability of the new AHU installation and all installed components.
Awarded Vendor shall contact TDCJ Facilities Engineering to review scope and schedule.
Drawings and other details provided are diagrammatic. Carefully coordinate installation requirements with existing and/or planned structural, architectural, electrical, mechanical and other applicable conditions and field adjust to avoid conflict.
Unless otherwise noted, the locations of both existing and planned elements are approximate and are not intended to convey the exact details and installation. Field determine exact locations by actual measurements and conditions before installation commences.
D. CONSTANT VOLUME UNITS (AHU-K5, 1«ii. KS, K9, K10 and)(
Refer to Page 15970-13, Paragraph D, Constant Volume Units, delete: air damper, return air
1. (AHU-X2).
PSA 4043.00
Al':> z.. fY\ '1. '+ .,f0£Jt2_
a. Normal Mode:
•r.
1) Outside air damper shall be at minimum position. Return air damper shall be fully open.
2) Outside air and return air damper shall be modulated in sequence per economizer cycle of operation. Upon a call for cooling, the enthalpy of the outside air and return air shall be compared. If the enthalpy of the outside air is
-less than the enthalpy of the return air, the dampers-sh-all be modulated upon demand to use up to 100 % outside air to maintain mixed air temperature setpoint. The mixed air temperature setpoint shall be reset based upon return air temperature. Dampers shall provide a low limit mixed air temperature of 55 deg F, as measured from the discharge air temperature sensor. If the enthalpy of the outside air is higher than the enthalpy of the return air, the dampers shall be modulated to minimum outside air position.
3) (AHU-K6 only): Outside air damper shall be modulated to maintain 0.1 IN WC positive pressure in the space, when compared with the outdoors.
15970 - 13 22 April, 1993 TDCJ Alberti/Beeville, TX
FK00057
Text Box Sequence of Operation for AHU-K6 MWR 09522005 (from original specs)
b. Panel shall indicate "FAN FAILURE", "HEATING FAILURE', "DIRTY FILTER #1", and "DIRTY FILTER #2' with a red pilot light which comes on for each condition.
c. Provide a control switch for both supply and return fans, with positions 'OFF', "AUTO', LOW SPEED', and 'HIGH SPEED'.
d. Provide a label for each panel indicating respective AHU, and labels for each pilot light and switch.
e. Provide a time switch or mircoprocessor based programmable controller for scheduled operating periods of the AHU, inside the panel.
f. AHU manufacturer shall furnish the remote status panel, to be field installed and field wired.
PSA 4043.00 15970 - 15 22 April, 1993 TDCJ Alberti/Beeville, TX
FK00057
Text Box AHU-K6 Scope of work - MWR 09522005
FK00057
Rectangle
FK00057
Line
FK00057
AHU-K6 Details - MWR 09522005
Existing AHU-K6 is on 24” curb on a 39’x 14’ pad. AHU is approx. 40’ L x 8.3’ W and 8.1’ H
Inserted Text E
FK00057
Inserted Text E
AHU-K6
FK00057
Text Box
RA
FK00057
Text Box
SA
FK00057
Text Box
OSA
FK00057
Text Box
AHU-K5
FK00057
Text Box
AHU-K7
FK00057
Rectangle
FK00057
Text Box Replace AHU-K6 scope
Line
| AHU Sched AHU-K6 Garza MWR 09522005 021524 |
| Pages 13 to 15 AHU K6 Seq of Ops Garza West |
| M208 M501 AHU-K6 |
| GE image AHU-K6 |
| Untitled |