About this file

This document is a response to bidder questions for Solicitation No. 696-FD-23-B014-B, the Ferguson Water Treatment Plant project in Texas. The project involves constructing two new 150,000-gallon potable water storage tanks and a new 1.5 MGD potable water plant, including new foundations, cathodic protection, and all new piping and valves. Jacobs Engineering Group is the designer. The solicitation has a bid due date of September 15, 2023 at 3:00 PM. Responses address questions related to instrumentation details, control panels, MCC equipment, material storage, scheduling software, staffing requirements, stockpiling of earth, and American Iron and Steel requirements. An addendum was issued modifying specification 40 90 02.05 for the magnetic level indicator.

The solicitation is open to out-of-state bidders. The performance period is 600 calendar days, though bidders can propose an alternative duration. Weather days are calculated based on working days, not calendar days. Existing equipment and materials from the demolition must be salvaged for the owner. Material substitutions, such as metal wall panels for masonry, are generally not allowed. Reuse of existing soil is permitted with testing and approval.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Memorandum

Memorandum

Response to Bidders Questions, Solicitation No. 696-FD-23-B014-B, Ferguson Water Treatment Plant

Date:
August 15, 2023
Jacobs Engineering Group Inc.

2705 Bee Cave Road Suite 300 Austin, TX 78746-5688 United States T +1.512.314.3100 F +1.512.314.3135 www.jacobs.com

Project name:
Ferguson Unit – Construct Water Treatment Plant
Project no:
WFXP7300
Attention:
Brian Carney PE, Aaron Martinez, Rob Love, & Contracts Engineering
Company:
TDCJ
Prepared by:
Rick Villalobos

The following questions and responses are provided to bidder questions.

No.
Question
Answer
1
FI-1100, FI-1402 & FI-4231 are shown on the contract drawings but are not included in the Instrument List in Specification 40 90 01 (starting on page 51). Please confirm the PIC contractor to provide as part of Instr. Detail 4091-043? Please provide the Comp Code and applicable specification?
Yes, the PIC contractor shall provide the rotameters as part of the Instrument Detail 4091-043. The rotameter flows are highly dependent on the analyzer flow requirements and are expected to be sized appropriately by the analyzer panel builder. Refer to analyzer panel example sheets added as an addendum to specification 40 90 01.
2
Please advise the Inst. Detail for FI-4211 & FI-4213?
Refer to Specification 40 91 02.03 Section 2.4 – F16 Flow Element, Rotameter for instrument detail. Refer to Detail 4097-002 added to new sheet 99-N-504.
3
Please confirm the Instr. Detail for the level switches on page 52 of Specification 40 90 01 is 4091-248? If not please provide.
The level switches are not the same type as shown on detail 4091-248. Refer to the component code descriptors (e.g. L112, and L115) on specification 40 91 02.05 for the type of level switch required. Refer to Details 4091-027 and 4091-250AG added to new sheet 99-N-504.
4
LCP4210 on 09-N-006 is not included in specification 40 90 01. Please confirm if the PIC contractor is to provide this under this specification section?
Refer to specification 44 42 56.02 Section 2.2.E for the requirements of LCP4210. It is currently assumed that this may be provided by pump vendor, but the general contractor has ultimate decision on who supplies each item on this project.
5
MCC120 on 09-N-000 is not included in specification 40 90 01. Please confirm if the PIC contractor is to provide this under this specification section?
The general contractor has ultimate decision on who supplies each item on this project. The MCC120 shall be provided under specification 40 90 01 since the existing pump is currently controlled out of the existing control house which will be demolished.
6
Is the PIC contractor responsible for furnishing and installation of the level indicator LI 2001 on 09-N-009? Or will it be provided with the tank?
The general contractor has ultimate decision on who supplies each item on this project. Refer to the specification modification listed below regarding the magnetic level indicator. Refer to Detail 4091-025 added to new sheet 99-N-504.
7
LCP-X on 09-N-009 is not included in specification 40 90 01. Please confirm if the PIC contractor is to provide this under this specification section?
LCP-X on Sheet 09-N-009 is in error. This has been corrected to read LCP-2001 and has been added to the control panel schedule attached.
8
It states that “payment for Materials stored on & offsite must be scheduled for installation within 60 days of arrival on the job-site and is properly stored and protected”. Due to the current market conditions, can this be voided so that full payment for materials is accepted without having to fall within any number of days of installation? This mitigates a large amount of risk for both the Contractor & Owner on schedule delays.
Follow the terms of the contract solicitation.
9
Is Primavera (P6) scheduling software required? Can Microsoft Project be utilized instead?
Yes, Microsoft Project may be utilized.
10
Can the QC Manager be a Project Manager or Superintendent?
No
11
Can some dirt be stockpiled for later facility use?
Yes, please refer to specification 31 22 00 Section 3.3.J for further details on stockpiling earth.
12
Can we hold material on site for over 60 days?
Follow the terms of the contract solicitation.
13
Does American Iron and Steel Use (Section I, Subpart 14.11 ‘Required Use of American Iron and Steel Products) per Texas Government Code, Section 2252.202 apply to all materials and equipment on the project? Section 33 16 13.12 species glass-fused, bolted-steel tanks. There is only one US located glass- tank manufacturing facility, CST Industries Aquastore facility in Dekalb, IL. CST Industries distributes to Texas through one entity only: Texas Aquastore. If American Iron & Steel applies to this product, only one supplier/subcontractor will be compliant.
Yes, the American Iron and Steel Use applies to all materials and equipment.

With regard to 33 16 13.12, note that this current bid set does not include glass-fused bolted tanks; these were removed and replaced with AWWA D100 welded steel ground storage tanks in this iteration of bidding. Verify that you are using the current plan sets dated November 23, 2022.

14
With the ongoing issues with supply chain availability for products, are the above-ground bolted steel tanks going to be allowed to be used on this project that are made overseas?
With regard to 33 16 13.12, note that this current bid set does not include glass-fused bolted tanks; these were removed and replaced with AWWA D100 welded steel ground storage tanks in this iteration of bidding. Verify that you are using the current plan sets dated November 23, 2022.
15
For the bolted-steel tanks, would a more standard ‘T’ vent or mushroom-shaped gravity vent be acceptable? The shown ‘Gooseneck’ vent is not typical of AWWA D103; both ‘T’ vents and gravity vents have been used on other TCEQ projects and are more standardized to bolted-steel tanks.
With regard to 33 16 13.12, note that this current bid set does not include glass-fused bolted tanks; these were removed and replaced with AWWA D100 welded steel ground storage tanks in this iteration of bidding. Verify that you are using the current plan sets dated November 23, 2022.
16
For the bolted-steel tanks, what is the roof hatch size required? Section 33 16 13.12, Subpart 3.3.C.3.e calls for a 24X15 roof hatch. The drawings (40-D-102) show a 36”x36” roof hatch. A knuckle roof cannot accommodate this hatch dimension so either the smaller hatch or an alternate roof style is required.
With regard to 33 16 13.12, note that this current bid set does not include glass-fused bolted tanks; these were removed and replaced with AWWA D100 welded steel ground storage tanks in this iteration of bidding. Verify that you are using the current plan sets dated November 23, 2022.
17
Is it possible to extend the Questions date past the August 8, 2023 date?
No.
18
Is it possible to extend the Bid Due date past the August 25, 2023 date?
Yes, new bid closing date is September 15, 2023 @ 3:00PM.
19
Can a bidder for this project be an out of state entity?
Yes.
20
Can Offers providing less than one hundred eighty (180) Days for acceptance after the date offers still be considered? Vendors will not provide anything over ninety (90) Days.
No, they will be rejected. The TDCJ needs the time for board approval from the TBCJ.
21
The performance period of this Contract is currently six hundred (600) calendar days. If the bidder identifies that the period of performance is actually closer to seven hundred (700) calendar days, will the bidder be disqualified?
No, the bidder will not be disqualified.
22
The Standard Work week is Mon-Fri, eight (8) hours per day. Do the bidders bid based on this or can the bidders base it of ten (10) hours per day?
TDCJ standard workday is eight (8) hours. The bidder can bid however they choose.
23
The bid documents currently have Average Days lost monthly due to Anticipated Adverse Weather Days equal to 73 days per year.

a. Are these calendar days or working days?

b. 73 days out of 352 calendar days equals 21%. Do bidders utilize the Calendar Days scenario?

c. 73 days out of 260 working days equals 28%. Do bidders utilize the Working Day scenario?

Working days.

24
During demolition of existing WTP facilities, are there any parts required to save and store for Owner?
The existing pumps, pump controller (Devar), emergency generator, chlorine tanks and chlorinators will go to TDCJ maintenance.
25
On the Chemical Control Building, Can the masonry wall be substituted for metal wall panels?
Unfortunately, no. The metal wall panels are not an approved alternative due to the chemical storage requirements.
26
Can the existing soil be excavated and hauled off to a location onsite in close proximity or does it have to be hauled off at a location offsite?
Yes existing soil can be located on site, please refer to specification 31 22 00 Section 3.3.J for further details on stockpiling earth.
27
Can the existing soil be reused to backfill the hole after demolition of the existing WTP facilities?
Due to the proximity of the existing East well and Elevated Water Tower, the backfill required after demolition of the underground tank shall be ‘Select Fill’. Existing soil that meets the requirements of ‘Select Fill’ per Section 31 22 00 Section 3.3.E.8, whether as-is or amended, must be tested for approval for use.

The Specifications shall be modified per the items indicated in the table below:

No.
Specification
Modification
1
40 90 02.05 – Level Measurement Components.
Add as follows to Section 2.2:

N. L245 Magnetic Level Indicator

1. General:

a. Function: Provide level indication with magnetic level indication floats

b. Type:

i. Suitable for sensing tank levels.

ii. Assembly consisting of vertical pipe with float and magnetic indicator devices.

2. Performance:

a. Temperature: 32 degrees F (nonfreezing) to 167 degrees F.

b. Suitable for monitoring sulfuric acid.

3. Features:

a. Vertical assembly with horizontal flanges suited for direct mount to tank.

b. Vertical chamber contains a flange mount on the bottom for float removal/replacement.

c. Chamber size: min. 2”, Sch 40

d. Process connections: 2” flanged

e. Flange class: 150#

f. Materials: TFE Coated carbon steel

g. Scale: 0-100%

4. Manufacturers and Products:

a. Jerguson Magnicator.

b. Emerson Magtech

Attachments:

· Drawing 01-G-002-A

· Drawing 09-N-009-A

· Drawing 10-D-301-A

· Drawing 20-D-101-A

· Drawing 40-D-102-A

· Drawing 40-D-301-A

· Drawing 99-N-504-A

· Specification 40 90 01 Instrument List – Rev A

· Specification 40 90 01 Control Panel Schedule – Rev A

· Specification 40 90 01 Addendum – Analyzer Panel Example Drawings