This is a specification sheet for an industrial spark-ignited generator set provided by Generac and reviewed for compliance by the City of Houston. The document details the SG400 model, a 400 kW, 500 kVA generator rated for 60 Hz operations in both standby and demand response applications. The generator is EPA certified for stationary emergency and non-emergency use and is assembled in the USA using domestic and foreign parts. The specification sheet outlines the generator's standard features, configurable options, and detailed engine specifications rather than procurement timelines, quantities, bidding deadlines, or contract terms.

The specification sheet emphasizes the generator's advanced engineering and manufacturing capabilities, including Generac's proprietary spark-ignited engine design, integrated control systems, and comprehensive protective functions. Standard features include a Power Zone Pro Sync Controller with NFPA 110 Level 1 compliance, a 7-inch color touch screen display, closed coolant recovery system, UL2200 certified alternator with Class H insulation, and internal vibration isolation. Configurable options are available for enclosure types (weather protected, sound attenuated levels 1-3, steel or aluminum), circuit breakers, extended factory testing, and warranty extensions ranging from 2 to 10 years for standby units. The document provides extensive technical specifications for the V12 turbocharged engine with electronic frequency regulation and detailed alternator specifications but contains no pricing information, set-asides, incumbent contractor details, or funding source documentation.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SG400 | 21.9L | 400 kW

INDUSTRIAL SPARK-IGNITED GENERATOR SET

EPA Certified Stationary Emergency and Non-Emergency

S P E C S

H

EE

T

DEMAND RESPONSE READY

Powering Ahead

Generac ensures superior quality by designing and manufacturing most of its generator components, such as alternators, enclosures, control systems and communications software. Generac also makes its own spark-ignited engines, and you�ll find them on every Generac gaseous-fueled generator. We engineer and manufacture them from the block up � all at our facilities throughout Wisconsin. Applying natural gas and LP-fueled engines to generators requires advanced engineering expertise to ensure reliability, durability and necessary performance. By designing specifically for these dry, hotter-burning fuels, the engines last longer and require less maintenance. Building our own engines also means we control every step of the supply chain and delivery process, so you benefit from single-source responsibility.

Plus, Generac Industrial Power�s distribution network provides all parts and service so you don�t have to deal with third-party suppliers. It all leads to a positive owner experience and higher confidence level. Generac spark-ignited engines give you more options in commercial and industrial generator applications as well as extended run time from utility-supplied natural gas.

Codes and Standards Not all codes and standards apply to all configurations. Contact factory for details.

UL2200, UL6200, UL1236, UL489

CSA C22.2, B149

BS5514 and DIN 6271

SAE J1349

NFPA 37, 70, 99, 110

NEC700, 701, 702, 708

ISO 3046, 7637, 8528, 9001

NEMA ICS10, MG1, 250, ICS6, AB1

ANSI C62.41

IBC 2009, CBC 2010, IBC 2012,

ASCE 7-05, ASCE 7-10,

ICC-ES AC-156 (2012)

TM

Image used for illustration purposes only

Standby Power Rating

400 kW, 500 kVA, 60 Hz

Demand Response Rating

400 kW, 500 kVA, 60 Hz

Prime Power Rating

360 kW, 450 kVA, 60 Hz

*Assembled in the USA using domestic and foreign parts

City of Houston

23085826

REVIEWED FOR COMPLIANCE

Performance of this review does not relieve the applicant from full responsibility to comply with all applicable code and regulations.

01/28/26

EPA Certified Stationary Emergency and Non-Emergency

S P E C S

H

EE

T

DEMAND RESPONSE READY

CONTROL SYSTEM

Power Zone® Pro Sync Controller

Program Functions

� NFPA 110 Level 1 Compliant

� Engine Protective Functions

� Alternator Protective Functions

� Digital Engine Governor Control

� Digital Voltage Regulator

� Multiple Programmable Inputs and Outputs

� Remote Display Capability

� Remote Communication via Modbus® RTU, Modbus TCP/IP, and Ethernet 10/100

� Alarm and Event Logging with Real Time Stamping

� Expandable Analog and Digital Inputs and Outputs

� Remote Wireless Software Update Capable

� Wi-Fi, Bluetooth, BMS and Remote Telemetry

� Built-In Programmable Logic Eliminates the Need for

External Controllers Under Most Conditions

� Ethernet Based Communications

Between Generators

� Programmable I/O Channel Properties

� Built-In Diagnostics

Protections

� Low Oil Pressure

� Low Coolant Level

� High/Low Coolant Temperature

� Sensor Failure

� Oil Temperature

� Over/Under Speed

� Over/Under Voltage

� Over/Under Frequency

� Over/Under Current

� Over Load

� High/Low Battery Voltage

� Battery Charger Current

� Phase to Phase and Phase to Neutral Short Circuits

(I2T Algorithm)

7 Inch Color Touch Screen Display

� Resistive Color Touch Screen

� Sunlight Readable (1400 NITS)

� Easily Identifiable Icons

� Multi-Lingual

� On Screen Editable Parameters

� Key Function Monitoring

� Three Phase Voltage, Amperage, kW, kVA, and kVAR

� Selectable Line to Line or Line to

Neutral Measurements

� Frequency

� Engine Speed

� Engine Coolant Temperature

� Engine Oil Pressure

� Engine Oil Temperature

� Battery Voltage

� Hourmeter

� Warning and Alarm Indication

� Diagnostics

� Maintenance Events/Information

ENGINE SYSTEM

� Oil Drain Extension

� Engine Coolant Heater

� Air Cleaner

� Stainless Steel Flexible Exhaust Connection

� Factory Filled Oil and Coolant

� Radiator Duct Adapter (Open Set Only)

� Critical Silencer

Fuel System

� NPT Fuel Connection on Frame

� Primary and Secondary Fuel Shutoff

Cooling System

� Closed Coolant Recovery System

� UV/Ozone Resistant Hoses

� Factory-Installed Radiator

� 50/50 Ethylene Glycol Antifreeze

� Radiator Drain Extension

Electrical System

� Battery Charging Alternator

� Battery Cables

� Battery Tray

� Rubber-Booted Engine Electrical Connections

� Solenoid Activated Starter Motor

ALTERNATOR SYSTEM

� UL2200 GENprotect�

� Class H Insulation Material

� 2/3 Pitch

� Skewed Stator

� Permanent Magnet Excitation

� Sealed Bearing

� Amortisseur Winding

� Full Load Capacity Alternator

GENERATOR SET

� Internal Genset Vibration Isolation

� Separation of Circuits - High/Low Voltage

� Separation of Circuits - Multiple Breakers

� Wrapped Exhaust Piping

� Standard Factory Testing

� 2 Year Limited Warranty (Standby and Demand

Response Rated Units)

� 1 Year Limited Warranty (Prime Rated Units)

� Silencer Mounted in the Discharge Hood

(Enclosed Units Only)

ENCLOSURE (If Selected)

� Rust-Proof Fasteners with Nylon Washers to

Protect Finish

� High Performance Sound-Absorbing Material

(Sound Attenuated Enclosures)

� Gasketed Doors

� Upward Facing Discharge Hoods (Radiator and Exhaust)

� Stainless Steel Lift Off Door Hinges

� Stainless Steel Lockable Handles

� RhinoCoat� - Textured Polyester Powder Coat Paint

STANDARD FEATURES

City of Houston

23085826

REVIEWED FOR COMPLIANCE

Performance of this review does not relieve the applicant from full responsibility to comply with all

EPA Certified Stationary Emergency and Non-Emergency

S P E C S

H

EE

T

DEMAND RESPONSE READYCONFIGURABLE OPTIONS

ENGINE SYSTEM

○ Baseframe Cover/Rodent Guard

○ Oil Heater

○ Air Filter Restriction Indicator

○ Radiator Stone Guard (Open Set Only)

○ Level 1 Fan and Belt Guards (Enclosed Units Only)

FUEL SYSTEM

○ NPT Flexible Fuel Line

ELECTRICAL SYSTEM

○ 10A UL Listed Battery Charger

○ Battery Warmer

ALTERNATOR SYSTEM

○ Alternator Upsizing

○ Anti-Condensation Heater

○ Tropical Coating

CIRCUIT BREAKER OPTIONS

○ Main Line Circuit Breaker

○ 2nd Main Line Circuit Breaker

○ Shunt Trip and Auxiliary Contact

○ Electronic Trip Breakers

GENERATOR SET

○ Demand Response Rating

○ Extended Factory Testing (3-Phase Only)

○ 12 Position Load Center

ENCLOSURE

○ Weather Protected Enclosure

○ Level 1 Sound Attenuated

○ Level 2 Sound Attenuated

○ Level 2 Sound Attenuated with Motorized Dampers

○ Level 3 Sound Attenuated (Steel Only)

○ Steel Enclosure

○ Aluminum Enclosure

○ Damper Alarm (Motorized Dampers Only)

○ Up to 200 MPH Wind Load Rating (Contact Factory for Availability)

○ AC/DC Enclosure Lighting Kit

○ Enclosure Heaters (Motorized Dampers Only)

○ Door Open Alarm Switch

CONTROL SYSTEM

○ NFPA 110 Compliant 21-Light Remote Annunciator

○ Remote Relay Assembly (8 or 16)

○ Oil Temperature Sender with Indication Alarm

○ Remote E-Stop (Break Glass-Type, Surface Mount)

○ Remote E-Stop (Red Mushroom-Type, Surface Mount)

○ Remote E-Stop (Red Mushroom-Type, Flush Mount)

○ 10A Engine Run Relay

○ Ground Fault Annunciator

○ 100 dB Alarm Horn

○ 120V GFCI and 240V Outlets

WARRANTY (Standby Gensets Only)

○ 2 Year Extended Limited Warranty

○ 5 Year Limited Warranty

○ 5 Year Extended Limited Warranty

○ 7 Year Extended Limited Warranty

○ 10 Year Extended Limited Warranty

ENGINEERED OPTIONS

ENGINE SYSTEM

○ Coolant Heater Ball Valves

○ Fluid Containment Pan

ALTERNATOR SYSTEM

○ 3rd Breaker System

CONTROL SYSTEM

○ Battery Disconnect Switch

GENERATOR SET

○ Special Testing

○ Battery Box

City of Houston

23085826

REVIEWED FOR COMPLIANCE

Performance of this review does not relieve the applicant from full responsibility to comply with all

EPA Certified Stationary Emergency and Non-Emergency

S P E C S

H

EE

T

DEMAND RESPONSE READY

General

Make Generac

Cylinder # 12

Type V12

Displacement - in3 (L) 1,336.4 (21.9)

Bore - in (mm) 5.03 (128)

Stroke - in (mm) 5.6 (142)

Compression Ratio 10.0:1

Intake Air Method Turbocharged/Aftercooled

Number of Main Bearings 7

Connecting Rods Steel Alloy

Cylinder Head Cast Iron

Cylinder Liners Cast Steel Alloy

Ignition Electronic

Piston Type Cast Aluminum Alloy

Crankshaft Type Steel

Lifter Type Solid

Intake Valve Material High Temp Steel Alloy

Exhaust Valve Material High Temp Steel Alloy

Hardened Valve Seats Proprietary Alloy

Engine Governing

Governor Electronic

Frequency Regulation (Steady State) ±0.25%

Lubrication System

Oil Pump Type Gear

Oil Filter Type Full-Flow Spin on Cartridge

Crankcase Capacity - qt (L) 31.7 (30)

Cooling System

Cooling System Type Pressurized Closed Recovery

Fan Type Pusher

Fan Speed - RPM 1,404

Fan Diameter - in (mm) 44 (1,117.6)

Fuel System

Fuel Type Natural Gas

Carburetor Down Draft

Secondary Fuel Regulator Standard

Fuel Shut Off Solenoid Standard

Operating Fuel Pressure - in H2O (kPa) 11 - 14 (2.7 - 3.5)

Optional Operating Fuel Pressure - in H2O (kPa) 7 - 11 (1.7 - 2.7)

Engine Electrical System

System Voltage 24 VDC

Battery Charger Alternator 57 A

Battery Size See Battery Index 0161970SBY

Battery Voltage (2) - 12 VDC

Ground Polarity Negative

APPLICATION AND ENGINEERING DATA

ENGINE SPECIFICATIONS

ALTERNATOR SPECIFICATIONS

Standard Model K0400124Y21

Poles 4

Field Type Revolving

Insulation Class - Rotor H

Insulation Class - Stator H

Total Harmonic Distortion <5% (3-Phase)

Telephone Interference Factor (TIF) <52

Standard Excitation Permanent Magnet

Bearings Sealed Ball

Coupling Direct via Flexible Disc

Prototype Short Circuit Test Yes

Voltage Regulator Type Full Digital

Number of Sensed Phases All

Regulation Accuracy (Steady State) ±0.25%

City of Houston

23085826

REVIEWED FOR COMPLIANCE

Performance of this review does not relieve the applicant from full responsibility to comply with all

EPA Certified Stationary Emergency and Non-Emergency

S P E C S

H

EE

T

DEMAND RESPONSE READY

** Refer to �Emissions Data Sheet� for maximum bHP for EPA and SCAQMD permitting purposes.

Deration � Operational characteristics consider maximum ambient conditions. Derate factors may apply under atypical site conditions.

Please contact a Generac Power Systems Industrial Dealer for additional details. All performance ratings in accordance with ISO3046, BS5514, ISO8528, and DIN6271 standards.

Standby - See Bulletin 0187500SSB Demand Response - See Bulletin 10000018250 Prime - See Bulletin 0187510SSB

POWER RATINGS - NATURAL GAS

Standby/Demand Response Prime

Three-Phase 120/208 VAC @0.8pf 400 kW/500 kVA Amps: 1,390 360 kW/450 kVA Amps: 1,251

Three-Phase 120/240 VAC @0.8pf 400 kW/500 kVA Amps: 1,204 360 kW/450 kVA Amps: 1,084

Three-Phase 277/480 VAC @0.8pf 400 kW/500 kVA Amps: 602 360 kW/450 kVA Amps: 542

Three-Phase 346/600 VAC @0.8pf 400 kW/500 kVA Amps: 482 360 kW/450 kVA Amps: 434

MOTOR STARTING CAPABILITIES (skVA) skVA vs. Voltage Dip

277/480_3PH 30% 208/240 VAC 30%

K0400124Y21 953 K0500124Y23 730

K0500124Y23 1,020 K0600124Y23 1,120

K0600124Y23 1,560

FUEL CONSUMPTION RATES*

Natural Gas � scfh (m3/hr)

Percent Load Standby/Demand Response Prime

25% 1,680 (47.6) 1,620 (45.9)

50% 2,640 (74.8) 2,460 (69.7)

75% 3,600 (101.9) 3,300 (93.4)

100% 4,620 (130.8) 4,200 (118.9)

* Fuel supply installation must accommodate fuel consumption rates at 100% load.

COOLING

Standby/Demand Response Prime

Air Flow (Fan Air Flow Across Radiator) scfm (m3/min) 28,004 (793) 28,004 (793)

Coolant Flow gpm (Lpm) 211 (798.6) 211 (798.6)

Coolant System Capacity gal (L) 15.5 (58.7) 15.5 (58.7)

Max. Operating Ambient Temperature °F (°C) 122 (50) 122 (50)

Maximum Operating Ambient Temperature (Before Derate) See Bulletin No. 0199270SSD

Maximum Radiator Backpressure in H2O (kPa) 0.5 (0.12) 0.5 (0.12)

COMBUSTION AIR REQUIREMENTS

Standby/Demand Response Prime

Flow at Rated Power - scfm (m3/min) 731 (20.7) 666 (18.9)

ENGINE EXHAUST

Standby/Demand

Response Prime

Standby/Demand

Response Prime

Rated Engine Speed RPM 1,800 1,800 Exhaust Flow (Rated Output) scfm (m3/min) 2,378 (67.3) 2,142 (60.7)

Horsepower at Rated kW** hp 589 530 Max. Backpressure (Post Silencer) inHg (kPa) 0.75 (2.54) 0.75 (2.54)

Piston Speed ft/min (m/min) 1,680 (512) 1,680 (512) Exhaust Temp (Rated Output - Post Silencer) °F (°C) 1,297 (702.8) 1,277 (691.7)

BMEP psi (kPa) 194 (1,338) 175 (1,204)

OPERATING DATA

City of Houston

23085826

REVIEWED FOR COMPLIANCE

Performance of this review does not relieve the applicant from full responsibility to comply with all

EPA Certified Stationary Emergency and Non-Emergency

S P E C S

H

EE

T

DEMAND RESPONSE READY

YOUR FACTORY RECOGNIZED GENERAC INDUSTRIAL DEALER

Specification characteristics may change without notice. Dimensions and weights are for preliminary purposes only. Please contact a Generac Power Systems Industrial Dealer for detailed installation drawings.

* All measurements are approximate and for estimation purposes only.

Part No. 10000035560

Rev. B 11/15/19

Generac Power Systems, Inc. | P.O. Box 8 | Waukesha, WI 53189

P: (262) 544-4811 ©2019 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice.

DIMENSIONS AND WEIGHTS*

OPEN SET (Includes Exhaust Flex)

L x W x H - in (mm) 154.4 (3,922) x 71.0 (1,803) x 66.5 (1,689)

Weight - lbs (kg) 7,286 - 8,650 (3,304 - 3,923)

WEATHER PROTECTED ENCLOSURE

L x W x H - in (mm) 207.4 (5,268) x 71.0 (1,803) x 80.0 (2,032)

Weight - lbs (kg) Steel: 9,490 - 10,840 (4,304 - 4,916)

Aluminum: 8,404 - 9,753 (3,811 - 4,423)

LEVEL 1 SOUND ATTENUATED ENCLOSURE

L x W x H - in (mm) 247.5 (6,287) x 71.0 (1,803) x 80.0 (2,032)

Weight - lbs (kg) Steel: 10,498 - 11,847 (4,761 - 5,373)

Aluminum: 8,818 - 10,185 (3,999 - 4,619)

LEVEL 2 SOUND ATTENUATED ENCLOSURE

L x W x H - in (mm) 207.4 (5,268) x 71.0 (1,803) x 114.1 (2,898)

Weight - lbs (kg) Steel: 10,836 - 12,185 (4,914 - 5,526)

Aluminum: 8,963 - 10,330 (4,065 - 4,685)

LEVEL 3 SOUND ATTENUATED ENCLOSURE

L x W x H - in (mm) 232.0 (5,893) x 76.9 (1,953) x 129.2 (3,282)

Weight - lbs (kg) 13,224 - 14,285 (5,997 - 6,478)

L

H

W

L

H

W

L

H

W

L

H

W

City of Houston

23085826

REVIEWED FOR COMPLIANCE

Performance of this review does not relieve the applicant from full responsibility to comply with all