ESBD_362177_1721428158159_Exhibit M Construction Documents.pdf

PDF 2 MB Posted

Attached to
THC Palmito Ranch Platform Construction Services
Solicitation number
808-24-242165
Issued by
Cameron County, Brownsville City, Texas

About this file

This document is a Request for Proposals (RFP) issued by the State of Texas, through the Texas Historical Commission (THC), to establish a contract for General Construction Services for a Viewing Platform at the Palmito Ranch Battlefield State Historic Site located in Cameron County, Texas. The RFP outlines the specifications and requirements for the construction of the viewing platform, including structural, architectural, and site work details. The RFP requires bidders to provide sealed proposals by a specified due date, and the contract will be awarded to the successful bidder. The contract term is not explicitly stated, but may include renewal options.

The RFP provides details on the required pricing, including any set-asides or preferences. It does not mention any incumbent contractors or the current environment. The funding source and amounts are not specified, but the RFP indicates the services are for the Texas Historical Commission and the Palmito Ranch Battlefield State Historic Site. Bidders must comply with all applicable state and local requirements for the project.

View the file

Other files

Show all 16

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

V I C I N I T Y M A P N. T. S.

PALMITO RANCH BATTLEFIELD STATE

HISTORIC SITE VIEWING PLATFORM

Brownsville, TX

CS

STRUCTURAL ENGINEER

Brownsville, Texas

400 Nolana, Suite H2

FAX: (956) 687-3211

www.chaninengineering.com

TBPE FIRM REG. NUMBER F-9369

PH: (956) 687-9421

McAllen, Texas 78504

DRAWINGS

D R A W I N G I N D E X

CS-1 COVER SHEET

S1.0 GENERAL NOTES

S1.1 GENERAL NOTES

S1.2 ROOF UPLIFT PLAN

S1.3 OVERALL SITE PLAN

S2.0 PIER LAYOUT/RAMP FRAMING PLAN

S3.0 PIER BRACING/ROOF FRAMING PLAN

S4.0 FRAMING DETAILS

S4.1 SECTIONS

S5.0 ELEVATIONS

S5.1 ELEVATIONS

OWNER

THE PALMITO RANCH BATTLEFIELD HISTORIC SITE IS

OWNED, OPERATED, STAFFED AND MAINTAINED BY THE

TEXAS HISTORICAL COMMISSION, AN AGENCY OF THE

STATE OF TEXAS. THIS SITE FEATURES ARCHEOLOGICAL

FEATURES AND DRIVEWAYS FOR USE BY VISITORS AND

STAFF. THE SITE WILL REMAIN OPEN TO THE PUBLIC

DURING THE COURSE OF THE WORK.

N

PROJECT

SITE

LOCATION

MAP

BROWNSVILLE, TEXAS

PROJECT

SITE

1. THE CONTRACT STRUCTURAL DRAWINGS AND SPECIFICATIONS REPRESENT THE FINISHED

STRUCTURE. UNLESS OTHERWISE INDICATED, THEY DO NOT INDICATE THE METHOD OF

CONSTRUCTION. THE CONTRACTOR SHALL PROVIDE ALL MEASURES NECESSARY TO

PROTECT THE STRUCTURE, WORKMEN, AND OTHER PERSONS DURING CONSTRUCTION.

SUCH MEASURES SHALL INCLUDE, BUT NOT BE LIMITED TO BRACING, SHORING FOR

CONSTRUCTION EQUIPMENT, SHORING FOR THE BUILDING, SHORING FOR THE EARTH

BANKS, FORMS, SCAFFOLDING, PLANNING, SAFETY NETS, SUPPORT AND BRACING FOR

CRANES, GIN POLES, ETC. THE CONTRACTOR SHALL SUPERVISE AND DIRECT THE WORK,

AND HE SHALL BE SOLELY RESPONSIBLE FOR ALL CONSTRUCTION MEANS, METHODS,

TECHNIQUES, SEQUENCES, AND PROCEDURES. OBSERVATION VISITS TO THE SITE BY THE

ARCHITECT OR THE ENGINEER SHALL NOT INCLUDE INSPECTION OF THE ABOVE ITEMS.

2. IT IS SOLELY THE CONTRACTOR'S RESPONSIBILITY TO FOLLOW ALL APPLICABLE SAFETY

CODES AND REGULATIONS DURING ALL PHASES OF CONSTRUCTION.

3. EQUIPMENT FRAMING LOADS, OPENINGS AND STRUCTURE IN ANY WAY RELATED TO HVAC,

PLUMBING, OR ELECTRICAL REQUIREMENTS ARE SHOWN FOR BIDDING PURPOSES ONLY.

EXACT WEIGHTS AND LOCATIONS OF MECHANICAL EQUIPMENT SHALL BE COORDINATED BY

CONTRACTOR. IF THE FINAL LOCATION VARIES FROM THAT SHOWN ON THE PLANS,

CONTRACTOR TO NOTIFY ENGINEER FOR APPROVAL BEFORE INSTALLATION.

4. SHOULD ANY OF THE DETAILED INSTRUCTIONS SHOWN ON THE PLANS CONFLICT WITH

THESE STRUCTURAL NOTES, THE SPECIFICATIONS, OR WITH EACH OTHER, THE STRICTEST

PROVISION SHALL GOVERN.

5. THE GENERAL CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND CONDITIONS AT THE JOB

SITE AND SHALL BE RESPONSIBLE FOR CONDITIONS OF ALL WORK AND MATERIALS.

6. THE CONTRACTOR SHALL REVIEW AND VERIFY ALL DIMENSIONS AND ELEVATIONS.

CONTRACTOR SHALL REPORT ANY DISCREPANCIES IN WRITING TO THE ENGINEER. ANY

CONFLICT BETWEEN THE DRAWING AND SPECIFICATIONS OF THE VARIOUS TRADES

INVOLVED SHALL BE REPORTED TO THE ENGINEER.

7. DETAILS SHOWN ON DRAWINGS APPLY AT SIMILAR CONDITIONS.

8. ALL WORK SHALL BE DONE IN ACCORDANCE WITH LOCAL STANDARDS AND TO ALL

APPLICABLE PROVISIONS OF THE GOVERNING BUILDING CODE.

9. THE ENGINEER SHALL BE NOTIFIED IN WRITING WHEN WORK COMMENCES.

10. CONTRACTOR SUBSTITUTIONS: ANY MATERIALS OR PRODUCTS THAT ARE SUBMITTED FOR

APPROVAL THAT ARE DIFFERENT FROM THE MATERIALS OR PRODUCTS SPECIFIED IN THE

CONTRACT DOCUMENTS WILL ONLY BE CONSIDERED IF THE FOLLOWING CRITERIA ARE

SATISFIED.

A) A COST SAVING TO THE OWNER IS DOCUMENTED AND SUBMITTED WITH THE

REQUEST

B) THE MATERIAL OR PRODUCT HAS BEEN APPROVED BY THE INTERNATIONAL

CONFERENCE OF BUILDING OFFICIALS (ICBO) AND THE ICBO REPORT IS

SUBMITTED WITH THE REQUEST.

GENERAL

STRUCTURAL OBSERVATION

SHOP DRAWINGS & SUBMITTALS

DESIGN CRITERIA

CONTRACTOR NOTE

© COPYRIGHT 2024 - ALL RIGHTS RESERVED

1. THE PROFESSIONAL ENGINEER OR HIS/HER AUTHORIZED REPRESENTATIVE SHALL

CONDUCT ALL STRUCTURAL OBSERVATIONS. STRUCTURAL OBSERVATIONS SHALL BE FOR

THE PURPOSE OF ASCERTAINING GENERAL COMPLIANCE WITH THE CONSTRUCTION

DOCUMENTS. HOWEVER, SUCH OBSERVATION VISITS SHALL NOT RELIEVE THE

CONTRACTOR FROM HIS OBLIGATIONS AND RESPONSIBILITIES TO THE CONSTRUCTION

DOCUMENTS.

2. ITEMS THAT REQUIRE A STRUCTURAL OBSERVATION ARE AS FOLLOWS:

A. STEEL REINFORCEMENT IN SLAB OR FOUNDATION

B. FRAMING OF SECOND FLOOR BEFORE DECKING IS INSTALLED

C. SECOND FLOOR DECKING

D. FRAMING OF ROOF STRUCTURE BEFORE METAL PANELS ARE INSTALLED

E. EXTERIOR METAL PANEL INSTALLATION

F. WINDSTORM BUILDING COMPONENTS

3. NOTIFY ENGINEER 24 HOURS IN ADVANCE WHEN A STRUCTURAL OBSERVATION IS

REQUIRED.

4. WORK SHALL NOT CONTINUE AT THESE AREAS UNTIL OBSERVATION AND APPROVAL BY

ENGINEER. FAILURE BY THE CONTRACTOR TO PROVIDE PROPER NOTICE FOR AN

OBSERVATION VISIT AT THE REQUIRED TIME OR ADDITIONAL WORK PERFORMED WITHOUT

AN OBSERVATION VISIT WILL BE DONE AT CONTRACTOR'S RISK AND MAY BE SUBJECT TO

COMPLETE OR PARTIAL REMOVAL TO VERIFY COMPLIANCE OF PREVIOUS WORK.

1. DESIGN LOADS, STRUCTURAL ANALYSIS AND PREPARATION OF STRUCTURAL MEMBERS ARE

BASED ON THE FOLLOWING CRITERIA:

2. CODE: ........................................................................................... IBC 2018

3. VERTICAL LOADS

A. ROOF DEAD LOAD (CANOPIES): .......................................... 15 PSF

B. ROOF LIVE LOAD( REDUCIBLE) : ........................................ 20 PSF

C. FLOOR DEAD LOAD: ........................................................... 15 PSF D. FLOOR LIVE LOAD: ............................................................. 100 PSF E. UPLIFT LOAD ...................................................................... SEE ROOF UPLIFT PLAN

K. MECHANICAL LOAD:

THE GENERAL CONTRACTOR SHALL SUBMIT ACTUAL WEIGHTS AND LOCATIONS OF

EQUIPMENT TO BE USED IN THE PROJECT TO THE STRUCTURAL ENGINEER FOR

VERIFICATION OF LOADS USED IN THE DESIGN AT LEAST TWO WEEKS PRIOR TO

FABRICATION AND CONSTRUCTION OF THE SUPPORTING STRUCTURE.

4. LATERAL LOADS

A. WIND SPEED (V-ULT): ............................................................ 152 MPH

WIND SPEED (V-ASD) ............................................................. 118 MPH B. EXPOSURE CATEGORY: ......................................................... C

C. IMPORTANCE FACTOR:

D. BUILDING CATEGORY: .......................................................... II

5. GEOTECHNICAL ENGINEERING REPORT:

PROVIDED BY: TERRACON

PROJECT NUMBER: 88215071

DATED: 09/02/21

FOUNDATION DESIGN BASED ON THE FOLLOWING PARAMETERS

A. MIN. EMBEDMENT BELOW EXISTING GRADE: .................... 15 FT.

B. MAX. EMBEDMENT BELOW EXISTING GRADE: .................... 25 FT.

C. NET ALLOWABLE BEARING PRESSURES (TOTAL LOAD):

a. BETWEEN 15 AND 25 FT. BELOW EXISTING GRADE: ... 7500 PSF

D. NET ALLOWABLE SIDE-SHEAR:

a. 5 TO 15 FT. BELOW EXISTING GRADE: ........................ 550 PSF

b. 15 TO 25 FT. BELOW EXISTING GRADE: ...................... 400 PSF

E. APPROXIMATE TOTAL SETTLEMENT: ................................... 1 IN.

F. ESTIMATED DIFFERENTIAL SETTLEMENT: .......................... 1/2

G. ALLOWABLE PASSIVE PRESSURE:

a. 5 TO 15 FT. BELOW EXISTING GRADE: ........................ 1000 PSF

b. 15 TO 25 FT. BELOW EXISTING GRADE: ...................... 750 PSF

H. ESTIMATED UPLIFT PRESSURE (KIPS): ................................ 16 D

These drawings, as instruments of professional service, are the property of Chanin Engineering LLC for use solely with respect to this Project and shall not be reproduced for other purposes.

The Professional Engineer whose seal appears on the structural construction documents is the project Structural Engineer-of-Record (SER) who bears legal responsibility for the performance of the structural framing relating to the public health, safety and welfare. No other party, whether or not a Professional Engineer, may complete, correct, revise, delete or add to these construction documents or perform inspections of the work without the written permission of the SER.

IT IS INTENDED THAT CONSTRUCTION PROCEED BY

UTILIZING ALL OF THE INFORMATION CONTAINED IN THE ENTIRE SET OF CONSTRUCTION

DOCUMENTS TAKEN AS A WHOLE; FAILURE TO DO SO WILL RESULT IN ERRORS WHICH SHALL

BE CORRECTED AT THE CONTRACTOR'S EXPENSE.

1. SUBMITTAL THAT WILL BE REQUIRED FOR APPROVAL INCLUDE:

A. CONCRETE MIX DESIGN

B. CURING COMPOUND FOR CONCRETE

C. REINFORCING STEEL

D. STRUCTURAL STEEL

2. DEFERRED SUBMITTALS THAT WILL REQUIRE APPROVAL INCLUDE:

A. LIGHTNING PROTECTION

B. PARKING DETAILS (INCLUDING BUT NOT LIMITED TO PAVEMENT DESIGN,

VAN ACCESSIBILITY, SIGNAGE, PARKING STRIPPING, HANDICAP RAMP, AND DIMENSIONS)

3. DEFERRED SUBMITTALS SHALL BE DESIGNED BY A TEXAS REGISTERED PROFESSIONAL

ENGINEER ACCORDING TO THE DESIGN CRITERIA STATED IN THE PLANS AND

SPECIFICATIONS, AND AS REQUIRED BY THE RESPECTIVE BUILDING CODE, WHICHEVER IS

GREATER. THE SUBMITTAL SHALL INCLUDE SIGNED AND SEALED CALCULATIONS.

4. ALLOW (2) WEEKS MINIMUM FOR REVIEW OF SHOP DRAWINGS.

5. PRIOR TO ISSUING THE SUBMITTALS TO THE ENGINEER, THE CONTRACTOR SHALL REVIEW

THE SHOP DRAWINGS. CONTRACTOR MUST VERIFY ALL DIMENSION WITH STRUCTURAL

PLANS.

6. REVIEW OF SHOP DRAWINGS BY THE ENGINEER IS FOR GENERAL CONFORMANCE TO THE

STRUCTURAL DRAWINGS. APPROVAL OF THE SHOP DRAWINGS BY THE ENGINEER DOES NOT

RELIEVE THE CONTRACTOR FOR ANY ERRORS IN DIMENSIONS OR MATERIAL INDICATED ON

THE SHOP DRAWINGS.

GENERAL NOTES

STRUCTURAL STEEL

1. STRUCTURAL STEEL SHALL BE DETAILED, FABRICATED, AND ERECTED IN ACCORDANCE TO

AISC SPECIFICATIONS.

2. MATERIALS USED SHALL BE AS FOLLOWS=

A. STRUCTURAL W-SHAPES - ASTM A992 GRADE 50

B. STRUCTURAL M-SHAPES AND S-SHAPES - ASTM A36

C. STRUCTURAL T-SHAPES - CUT FROM W-SHAPES

D. CHANNELS AND ANGLES - ASTM A36

E. ROUND HOLLOW STRUCTURAL SECTIONS - ASTM A500 GRADE B

F. SQUARE AND RECTANGULAR HOLLOW

STRUCTURAL SECTIONS - ASTM A500 GRADE B

G. STRUCTURAL PLATES - ASTM A36

H. STRUCTURAL BARS - ASTM A36

I. HIGH STRENGTH BOLTS - ASTM A325

J. ELECTRODES - SERIES E70

3. ALL WELDING SHALL BE DONE BY CERTIFIED WELDERS IN ACCORDANCE WITH THE LATEST

EDITION OF THE AMERICAN WELDING SOCIETY SPECIFICATIONS.

4. CONNECTIONS NOT DETAILED AND/OR SCHEDULED ON STRUCTURAL DRAWINGS SHALL BE

DETAILED BY FABRICATOR AND MARKED FOR ENGINEERS APPROVAL. CONNECTIONS TO BE

DESIGNED TO AISC SPECIFICATIONS AND SHALL BE CAPABLE OF SUPPORTING 55% OF THE

MAXIMUM UNIFORM LOAD CAPACITY FOR THE SPAN SPECIFIED, SHOWN IN THE TABLES OF

UNIFORM CONSTANTS OF THE AISC MANUAL OF STEEL CONSTRUCTION.

5. REFER TO ARCHITECTURAL PLANS FOR ANY MISCELLANEOUS STEEL NOT SHOWN ON

STRUCTURE DRAWING. MISCELLANEOUS STEEL AND CONNECTIONS SHALL BE DESIGNED

BY STEEL FABRICATOR.

6. HOT DIP GALVANIZE, IN ACCORDANCE WITH ASTM A123 AND ASTM A153, STRUCTURAL

STEEL AND FASTENERS PERMANENTLY EXPOSED TO THE WEATHER. REPAIR DAMAGED

AREAS AND WELDS MADE AFTER GALVANIZING IN ACCORDANCE WITH ASTM A780 WITH

ORGANIC ZINC RICH PAINT COMPLYING WITH DOD-P-21035 OR MIL-P-26915, MULTIPLE

COATS TO DRY FILM THICKNESS OF 4 MILS.

7. STEEL SUPPORTING OR CONNECTED TO HVAC AND OTHER EQUIPMENT AS SHOWN ON THE

DRAWINGS IS SHOWN FOR BIDDING PURPOSES ONLY CONTRACTOR SHALL COORDINATE

EXACT LOCATION AND SIZE BEFORE COMMENCING WORK.

8. STRUCTURAL DRAWINGS SHALL NOT BE REPRODUCED IN WHOLE OR IN PART FOR SHOP

DRAWING SUBMITTALS.

9. PROVIDE 2 TONS OF RED IRON ALLOWANCE TO BE USED AS DIRECTED BY STRUCTURAL

ENGINEER. INCLUDE LABOR COSTS IN THE ALLOWANCE. ANY UNUSED ALLOWANCE SHALL

BE CREDITED BACK TO OWNER AT A COST OF $6,000 PER TON.

10. ALL WELDED CONNECTION SHALL BE MADE WITH A 1/4" FILLET WELD U.N.O.

11. PROVIDE 1/2" GAP AT ALL PENETRATIONS THROUGH CMU WALL AND INFILL WITH

ELASTOMERIC MATERIAL.

12. STEEL FABRICATOR SHALL BE CERTIFIED BY ONE OF THE FOLLOWING: AISC/ IBC/ IAS-ICC

CONCRETE

STEEL REINFORCING

1. ALL CONCRETE WORK SHALL BE EXECUTED IN ACCORDANCE WITH ACI 318 AND ACI 301

LATEST EDITION.

2. CEMENT SHALL CONFORM TO ASTM CI50 TYPE I AGGREGATE SHALL CONFORM TO ASTM C33.

3. CONCRETE SHALL HAVE A MINIMUM 28 DAYS COMPRESSIVE STRENGTH AS FOLLOWS:

MEMBER TYPE STRENGTH SLUMP MAX AGG.

FOUNDATION 3000 PSI 4"-6" 1.25 IN.

AND SLAB

PIERS 4000 PSI 4"-6" 1.25 IN.

COLUMNS 4000 PSI 4"-6" I.25 IN.

4. INSTALL 10 MIL VAPOR RETARDER UNDER SLABS ON GRADE AND ALONG SIDE OF TRENCHES

IN ACCORDANCE WITH ASTM E1643. LAP JOINTS MINIMUM OF 12 INCHES.

5. PLACE CONCRETE CONTINUOUSLY BETWEEN PRE-DETERMINED EXPANSION AND

CONSTRUCTION JOINTS.

6. ALL CONSTRUCTION JOINT LOCATIONS TO BE APPROVED BY ARCHITECT AND STRUCTURAL

ENGINEER.

7. HORIZONTAL CONSTRUCTION JOINTS SHALL NOT BE PERMITTED.

8. CURE CONCRETE IN ACCORDANCE WITH ACI 308.1

9. REFER TO ARCHITECTURAL AND MECHANICAL PLANS FOR LOCATIONS OF ALL DEPRESSIONS,

OPENINGS, ACCESSORIES, ETC.

10. CONDUIT AND PLUMBING LINES SHALL BE PLACED BELOW SLAB REINFORCING AND SHALL

BE NO BIGGER THAN 1 INCH.

11. FLYASH MAY BE USED TO REPLACE A PORTION OF THE PORTLAND CEMENT. THE RATIO OF

FLYASH TO THE TOTAL OF THE FLYASH AND CEMENT IN A MIX SHALL NOT EXCEED 20%.

FLYASH SHALL CONFORM TO ASTM C618, TYPE C OR F.

12. ALL FLOORS SHALL BE CONSTRUCTED WITH A MINIMUM FLATNESS FF = 35 AND A MINIMUM

LEVELNESS OF FL = 25

13. CONTRACTION JOINTS TO BE INSTALLED WITHIN 12 HOURS OF POURING FOUNDATION.

14. TESTING OF CONCRETE SHALL BE DONE AS FOLLOWS:

1) SETS SHALL CONSIST OF 3 CYLINDERS

ONE TESTED AT 7 DAYS

TWO TESTED AT 28 DAYS

2) ONE SET SHALL BE TAKEN FOR EACH 150 CY AND FOR EVERY 5000 SF OF SURFACE

AREA AND AT LEAST ONCE PER DAY OF POURING

3) A MINIMUM OF 3 SETS SHALL BE TAKEN FOR EACH CLASS OF CONCRETE

15. NO WATER SHALL BE ADDED TO THE CONCRETE AT THE JOBSITE. IT SHALL BE THE

RESPONSIBILITY OF THE CONTRACTOR TO COORDINATE WITH THE CONCRETE SUPPLIER TO

ENSURE A PUMPABLE AND WORKABLE MIX WITHOUT THE ADDITION OF WATER AT THE

JOBSITE. THE USE OF PLASTICIZERS, RETARDANTS AND OTHER ADDITIVES SHALL BE AT THE

OPTION OF THE CONTRACTOR SUBJECT TO THE APPROVAL OF THE STRUCTURAL ENGINEER.

FOLLOW THE RECOMMENDATIONS OF THE MANUFACTURER FOR THE PROPER USE OF

ADDITIVES. THE USE OF CALCIUM CHLORIDE OR OTHER CHLORIDE BEARING SALTS SHALL

NOT BE PERMITTED.

16. PLACE CONCRETE IN A MANNER SO AS TO PREVENT SEGREGATION OF THE MIX. DELAY

FLOATING AND TROWELING OPERATIONS UNTIL CONCRETE HAS LOST SURFACE WATER

SHEEN OR ALL FREE WATER. DO NOT SPRINKLE FREE CEMENT ON THE SLAB SURFACE.

FINISHING OF SLAB SURFACES SHALL COMPLY WITH THE RECOMMENDATIONS OF AC1 302.1

AND 304.

17. UNLESS SPECIFIED, CONCRETE MUST REACH THE FOLLOWING PERCENTAGES OF ITS 28-DAY COMPRESSIVE STRENGTH (F'c), BEFORE FORMS MAY BE REMOVED.

WALL, COLUMNS, & BEAM SIDES..............................................................40% JOIST PANS & BEAM BOTTOMS (IF RESHORED)........................................70%

SHORING FOR FLOOR SYSTEMS (IF NOT RESHORED)...............................85%

18. NO CONCRETE SHALL BE PLACED OUTSIDE OF THESE SPECIFICATIONS WITHOUT THE

OWNER'S PRIOR APPROVAL. ANY ITEMS NOT IN COMPLIANCE WITH THE OUTLINED

SPECIFICATION SHALL BE REPORTED TO THE OWNER AND STRUCTURAL ENGINEER WITHIN

24 HOURS.

19. CONSTRUCTION VEHICLE LOADS SHALL NOT BE PERMITTED ON ELEVATED SLABS AT ANY

TIME.

20. ALL RETAINING WALLS TO BE SHORED UNTIL UPPER SLAB IS IN PLACE AND HAS REACHED

70% OF ITS DESIGN STRENGTH OR THE RETAINING WALL HAS REACHED 100% OF ITS

DESIGN STRENGTH. PROVIDE GRANULAR BACKFILL AND PERFORATED DRAIN PIPE

CONNECTED TO SITE DRAINAGE, RE: CIVIL PLAN.

1. ALL REINFORCEMENT SHALL BE NEW BILLET STEEL CONFORMING TO ASTM A-615 GRADE 60.

2. REINFORCING STEEL SHALL BE DESIGNED, DETAILED, FABRICATED AND PLACED IN

ACCORDANCE WITH THE LATEST ACI DETAILING MANUAL (SP-66) AND CSRI MANUAL OF

STANDARD PRACTICE FOR DETAILING REINFORCED CONCRETE, (ACI #315) LATEST EDITIONS.

3. BARS SCHEDULED OR DETAILED "CONT" SHALL BE SPLICED ONLY WHEN UNAVOIDABLE AT

POINTS OF MINIMUM STRESS AND WITH A MINIMUM LAP AS FOLLOWS:

A. HORIZONTAL BARS w/ MORE THAN 12" OF FRESH CONCRETE CAST BELOW LAPS.

#6 BARS AND SMALLER - 57 BAR DIAMETERS

#7 BARS AND BIGGER - 72 BAR DIAMETERS

B. OTHER BARS

#6 BARS AND SMALLER - 44 BAR DIAMETERS

#7 BARS AND BIGGER - 55 BAR DIAMETERS

C. ALL SPLICES TO BE STAGGERED A MINIMUM OF 4'-0". TOP BAR AND BOTTOM BAR SPLICES

TO BE LOCATED AT MID-SPAN AND WITHIN 1/3 SPAN RESPECTIVELY.

4. CORNER REINFORCING BARS SHALL BE USED AT ALL CORNERS AND INTERSECTIONS.

5. EXTEND THE SLAB REINFORCING STEEL PERPENDICULAR TO EXTERIOR GRADE BEAM TO

THE TOP OUT SIDE REINFORCING BAR OF BEAM.

6. SPACE REINFORCING BARS WITH MINIMUM CLEAR SPACING IN ACCORDANCE WITH ACI 318

OF ONE BAR DIAMETER, BUT NOT LESS THAN 1 INCH. FOR COMPRESSION MEMBERS, SPACE

AT A MINIMUM OF 1.5 INCHES OR 1.5 BAR DIAMETERS, WHICHEVER IS GREATER.

7. WHERE REINFORCING BARS ARE PLACED IN MULTIPLE LAYERS, PLACE UPPER BARS

DIRECTLY ABOVE LOWER BARS.

8. MAINTAIN CONCRETE COVER AROUND REINFORCEMENT IN ACCORDANCE WITH ACI 318 AND

AS FOLLOWS:

A. FOOTING AND CONCRETE CAST AGAINST EARTH - 3 INCHES

B. EXPOSED TO EARTH OR WEATHER

#6 BARS AND BIGGER - 2 INCHES

#5 BARS AND SMALLER - 1.5 INCHES

C. BEAMS AND COLUMNS - 1.5 INCHES

D. SLABS AND WALLS - 1 INCH

9. REPAIR ANY DAMAGE TO VAPOR RETARDER PER MANUFACTURER SPECIFICATIONS.

10. ADDITIONAL REINFORCING TO BE PROVIDED ON SITE FOR USE AS DIRECTED BY

STRUCTURAL ENGINEER.

#4 BARS - 100 FT.

#5 BARS - 100 FT.

#6 BARS - 100 FT.

EXCAVATION NOTES

1. CONSTRUCTION AREAS REMOVE AT LEAST 6 INCHES OF TOP SOIL, VEGETATION, DEBRIS,

ETC., FROM THE PROPOSED BUILDING AREA TO A DISTANCE OF 5'-0" OUTSIDE THE

BUILDING LINE FROM THE PROPOSED.

2. EXPOSED SUBGRADE SHOULD BE THOROUGHLY PROOF ROLLED IN ORDER TO LOCATE AND

DENSITY ANY WEAK, COMPRESSIBLE ZONE. WEAK OR SOFT AREAS IDENTIFIED DURING

PROOF ROLLING SHOULD BE REMOVED AND REPLACED WITH A SUITABLE, COMPACTED

SELECT FILL IN ACCORDANCE WITH THE REQUIREMENTS BELOW. PRIOR TO FILL

PLACEMENT, THE EXPOSED SUBGRADE SHOULD BE MOISTURE CONDITIONED BY

SCARIFYING TO A MINIMUM DEPTH OF 8" AND RECOMPACTING TO A MINIMUM OF 98% OF

THE MAXIMUM DRY DENSITY AS DETERMINED FROM THE ASTM D698 COMPACTION TEST.

THE MOISTURE CONTENT SHOULD BE MAINTAINED WITHIN THE OPTIMUM TO 3% ABOVE.

3. FILL BACK TO REQUIRED GRADE (A MINIMUM OF 12" OF SELECT FILL IS REQUIRED. REFER

TO CIVIL PLANS FOR FINISHED FLOOR ELEVATION TO DETERMINE ADDITIONAL AMOUNT OF

SELECT FILL NEEDED) WITH MATERIAL SELECTED AND COMPACTED IN ACCORDANCE WITH

THE REQUIREMENTS BELOW.

4. SELECT FILL, WHEN PROPERLY SLAKED AND TESTED BY STANDARD LABORATORY

METHODS, SHALL MEET THE FOLLOWING REQUIREMENTS:

A. LIQUID LIMIT SHALL BE LESS THAN OR EQUAL TO 40%.

B. PLASTICITY INDEX SHALL BE LESS THAN 20 AND GREATER THAN 7.

C. SHALL CONTAIN NO ORGANIC MATERIAL.

D. SHALL CONTAIN NO STONES LARGER THAN 2 INCHES.

5. SAMPLES OF PROPOSED SELECT FILL SHALL BE FURNISHED TO THE TESTING LABORATORY

7 DAYS PRIOR TO INSTALLATION TO PERMIT TIME FOR SPECIFICATION COMPLIANCE

INSPECTION AND APPROVAL.

6. SELECT FILL UNDER ALL FLOORS AND WALKS SHALL BE COMPACTED IN THE FIELD IN LIFTS

NOT TO EXCEED 8" TO 95% OF THE MAXIMUM DENSITY, OR ABOVE OF THE OPTIMUM

MOISTURE CONTENT, AS DETERMINED BY TEST METHOD ASTM D-698

7. SITE PREPARATION TESTING SHALL BE AS FOLLOWS:

A. ATTERBERG LIMITS OF SELECT FILL MATERIAL:

(1) ONE TEST PER 5,000 CY

B. COMPACTION TEST:

TO BE PERFORMED PER LIFT ON TEST PER 3,000 SF MINIMUM

OF (4) FOUR TEST PER LIFT

8. GEOTECHNICAL REPORT SHALL BE CONSIDERED A PART OF THE CONSTRUCTION

DOCUMENTS. CONTRACTOR TO REVIEW AND COMPLY WITH ALL EARTHWORK AND GRADING

REQUIREMENT IN GEOTECHNICAL REPORT.

9. FINAL SITE GRADING TO SLOPE AWAY FROM THE STRUCTURE AND SHALL PREVENT WATER

FROM PONDING IN THE AREAS ADJACENT TO THE STRUCTURE FOR A MINIMUM DISTANCE

OF 10'-0". ANY PONDING CLOSE TO THE STRUCTURE MAY CREATE VOLUMETRIC CHANGES IN

THE SOIL AND MAY LEAD TO LESS THAN OPTIMUM PERFORMANCE OF THE BUILDING

FOUNDATION.

10. IT IS ALSO IMPORTANT TO MINIMIZE CHANGES IN MOISTURE CONTENT CREATED BY ROOF

DRAINAGE, PLUMBING LEAKS, LANDSCAPING / IRRIGATION, AND DOWNSPOUT OUTFALLS.

ANY PLUMBING LEAKS SHALL BE REPAIRED AS SOON AS POSSIBLE AND PROPER DRAINAGE

PROVIDED AWAY FROM THE BUILDING. LARGE BUSHES AND TREES SHALL NOT BE PLACED

IN AREAS DIRECTLY ADJACENT TO THE FOUNDATION AS THEIR ROOT SYSTEM MAY CREATE

SUBSTANTIAL MOISTURE DIFFERENTIALS THAT MAY LEAD TO VOLUME CHANGES IN THE

SOIL. LARGE BUSHES AND TREES SHOULD BE LOCATED AT A REASONABLE DISTANCE FROM

THE FOUNDATION.

DATE: 4/19/24

DRAWING NO:

JOB NO. 21178

SEAL:

DRAWN BY: EC,VDV

CHECKED BY:HR

REVISION:

PR

OJ

EC

T:

Pa lm ito R an ch

B at tle fie ld S ta te

H is to ric

S ite

400 Nolana, Suite H2

FAX: (956) 687-3211

www.chaninengineering.com

TBPE FIRM REG. NUMBER F-9369

PH: (956) 687-9421

McAllen, Texas 78504

Vi ew in g

Pl at fo rm

Br ow ns vi lle , T ex as

S1.0

AutoCAD SHX Text

COPYRIGHT 2024 - ALL RIGHTS RESERVED

AutoCAD SHX Text

HECTOR RAMIREZ

AutoCAD SHX Text F

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text P

AutoCAD SHX Text O

AutoCAD SHX Text S

AutoCAD SHX Text 103720

AutoCAD SHX Text G

AutoCAD SHX Text O

AutoCAD SHX Text I

AutoCAD SHX Text E

AutoCAD SHX Text L

AutoCAD SHX Text N

AutoCAD SHX Text A

AutoCAD SHX Text E

AutoCAD SHX Text C

AutoCAD SHX Text I

AutoCAD SHX Text L

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text N

AutoCAD SHX Text N

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text I

AutoCAD SHX Text N

AutoCAD SHX Text X

AutoCAD SHX Text O

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text S

REQUIRED VERIFICATION AND INSPECTION OF STEEL CONSTRUCTION

TYPE CONTINUOUS PERIODIC REFERENCED

STANDARD IBC REFERENCEa

TABLE N5.4-1 INSPECTION TASKS PRIOR TO WELDING

SECTIONS

1705.5, 2205, 2206, 2207, 2208, 2210, AISC SECT. N5

INSPECTION TASKS PRIOR TO WELDING QC QA

WELDING PROCEDURE SPECIFICATIONS (WPSs) AVAILABLE P P

MANUFACTURER CERTIFICATIONS FOR WELDING

CONSUMABLES AVAILABLE P P

MATERIAL IDENTIFICATION (TYPE/GRADE) P P

WELDING IDENTIFICATION SYSTEM P P1

FIT-UP GROOVE WELDS (INCLUDING JOINT GEOMETRY)

· JOINT PREPARATION

· DIMENSIONS (ALIGNMENT, ROOT OPENING, ROOT FACE, BEVEL

· CLEANLINESS (CONDITION OF STEEL SURFACES)

· TACKING (TACK WELD QUALITY AND LOCATION)

· BACKING TYPE AND FIT (IF APPLICABLE)

O O

FIT-UP OF FILLET WELDS

· DIMENSIONS (ALIGNMENT, GAPS OF ROOT

· CLEANLINESS (CONDITION OF STEEL SURFACES)

· TACKING (TACK WELD QUALITY AND LOCATION)

O O

CONFIGURATION AND FINISH OF ACCESS HOLES O O

CHECK WELDING EQUIPMENT O

TABLE N5.4-2 INSPECTION TASKS DURING WELDING

INSPECTION TASKS DURING WELDING QC QA

USE OF QUALIFIED WELDERS O O

CONTROL AND HANDLING OF WELDING CONSUMABLES

· PACKAGING

· EXPOSURE CONTROL

O O

NO WELDING OVER CRACKED TACK WELDS O O

CONTROL AND HANDLING OF WELDING CONSUMABLES

· WIND SPEED WITHIN LIMITS

· PRECIPITATION AND TEMPERATURE

O O

WPS FOLLOWED

· SETTING ON WELDING EQUIPMENT

· TRAVEL SPEED

· SELECTED WELDING MATERIALS

· PREHEAT APPLIED

· INTERPASS TEMPERATURE MAINTAINED (MIN./MAX.)

· PROPER POSITION (F,V,H,OH.)

O O

WELDING TECHNIQUES

· INTERPASS AND FINAL CLEANING

· EACH PASS WITHIN PROFILE LIMITATIONS

· EACH PASS MEETS QUALITY REQUIREMENTS

O O

TABLE N5.4-3 INSPECTION TASKS AFTER WELDING

SECTIONS

1705.5, 2205, 2206, 2207, 2208, 2210, AISC SECT. N5

INSPECTION TASKS AFTER WELDING QC QA

WELDS CLEANED O O

SIZE, LENGTH ANA LOCATION OF WELDS P P

WELDS MEET VISUAL ACCEPTANCE CRITERIA

· CRACK PROHIBITION

· WELD/BASE-METAL FUSION

· CRATER CROSS SECTION

· WELD PROFILES

· WELD SIZE

· UNDERCUT

· POROSITY

P P

ARC STRIKES P P

K-AREA P P1

BACKING REMOVAL AND WELD TABS REMOVED (IF REQUIRED) P P

REPAIR ACTIVITIES P P

DOCUMENT ACCEPTANCE OR REJECTION OF WELDED

JOINT OR MEMBER P P

SECTIONS

1705.5, 2205, 2206, 2207, 2208, 2210, AISC SECT. N5

TABLE N5.6-1 INSPECTION TASKS PRIOR TO BOLTING

INSPECTION TASKS PRIOR TO BOLTING QC QA

MANUFACTURER'S CERTIFICATION AVAILABLE FOR

FASTENER MATERIALS O P

FASTENER MARKED IN ACCORDANCE WITH ASTM REQUIREMENTS O O

PROPER FASTENERS SELECTED FOR THE JOINT DETAIL (GRADE,

TYPE, BOLT LENGTH IF THREADS ARE TO BE EXCLUDED FROM

SHEAR PLANE)

O O

PROPER BOLTING PROCEDURE SELECTED FOR JOINT DETAIL O O

CONNECTING ELEMENTS, INCLUDING THE APPROPRIATE FAYING

SURFACE CONDITION AND HOLE PREPARATION, IF SPECIFIED,

MEET APPLICABLE REQUIREMENTS

O O

PRE-INSTALLATION VERIFICATION TESTING BY INSTALLATION

PERSONNEL OBSERVED AND DOCUMENTED FOR FASTENER

ASSEMBLIES AND METHODS USED

P O

PROPER STORAGE PROVIDED FOR BOLTS, NUTS, WASHERS AND

OTHER FASTENER COMPONENTS O O

SECTIONS

1705.5, 2205, 2206, 2207, 2208, 2210, AISC SECT. N5

TABLE N5.6-2 INSPECTION TASKS DURING BOLTING

INSPECTION TASKS DURING BOLTING QC QA

FASTENER ASSEMBLES, OF SUITABLE CONDITION, PLACED IN

ALL HOLES AND WASHERS (IF REQUIRED) ARE POSITIONED

AS REQUIRED

O O

JOINT BROUGHT TO THE SNUG-TIGHT CONDITION PRIOR TO THE

PRETENSIONING OPERATION O O

FASTENER COMPONENT NOT TURNED BY THE WRENCH

PREVENTED FROM ROTATING O O

FASTENER ARE PRETENSIONED IN ACCORDANCE WITH THE RCSC

SPECIFICATION, PROGRESSING SYSTEMATICALLY FROM THE MOST

RIGID POINT TOWARD THE FREE EDGES

O O

TABLE N5.6-3 INSPECTION TASKS AFTER BOLTING

INSPECTION TASKS AFTER BOLTING QC QA

DOCUMENT ACCEPTANCE OR REJECTION OF

BOLTED CONNECTIONS

P P

TABLE N6.1 INSPECTION OF STEEL ELEMENTS OF COMPOSITE CONSTRUCTION PRIOR TO CONCRETE PLACEMENT

INSPECTION OF STEEL ELEMENTS OF COMPOSITE

CONSTRUCTION PRIOR TO CONCRETE PLACEMENT QC QA

PLACEMENT AND INSTALLATION OF STEEL DECK P P

SECTIONS

1705.5, 2205, 2206, 2207, 2208, 2210, AISC SECT. N5

SECTIONS

1705.2, 2205, 2206, 2207,2208, 2210, 2211

AISC SECT. N5

PLACEMENT AND INSTALLATION OF STEEL

HEADED STUD ANCHORS P P

DOCUMENT ACCEPTANCE OR REJECTION OF STEEL ELEMENTS P P

SECTIONS

1705.5, 2205, 2206, 2207, 2208, 2210, AISC SECT. N5

1. THE FABRICATOR OR ERECTOR AS APPLICABLE, SHALL MAINTAIN A SYSTEM BY WHICH A WELDER WHO HAS WELDED A JOINT

OR MEMBER CAN BE IDENTIFIED. STAMPS IF USED, SHALL BE THE LOW-STRESS TYPE.

2. WHEN WELDING OF DOUBLE PLATES, CONTINUITY PLATES OR STIFFENERS HAS BEEN PREFORMED IN THE K-AREA , VISUALLY INSPECT THE WEB K-AREA FOR WITHIN 3 IN. (75m) OF THE WELD.

3. QC = QUALITY CONTROL

4. QA = QUALITY ASSURANCE

5. O = OBSERVE THESE ON A RANDOM BASIS. OPERATIONS NEED NOT TO DELAYED PENDING THESE INSPECTIONS.

6. P = PREFORM THESE TASKS FOR EACH WELD JOINT OR MEMBER.

GENERAL NOTES

1. THE OWNER SHALL EMPLOY A SPECIAL INSPECTOR TO PROVIDE

INSPECTIONS DURING CONSTRUCTION ON THE TYPES OF WORK LISTED

IN THIS SECTION.

2. THE FOLLOWING TERMS AND PHRASES SHALL HAVE THE MEANINGS

SHOWN BELOW AS IT PERTAINS TO THIS SECTION,

A. APPROVED AGENCY - AN ESTABLISHED AND RECOGNIZED AGENCY

REGULARLY ENGAGED IN CONDUCTING AND FURNISHING SPECIAL

INSPECTION SERVICES.

B. APPROVED FABRICATOR - AN ESTABLISHED AND QUALIFIED FIRM

APPROVED BY BUILDING OFFICIAL. SPECIAL INSPECTIONS ARE NOT

REQUIRED WHEN WORK IS PERFORMED ON THE PREMISES OF AN

APPROVED FABRICATOR.

C. SPECIAL INSPECTION, CONTINUOUS - THE FULL TIME OBSERVATION

OF WORK REQUIRING SPECIAL INSPECTION.

D. SPECIAL INSPECTION, PERIODIC - THE PART TIME OR INTERMITTENT

OBSERVATION OF WORK REQUIRING SPECIAL INSPECTION.

3. SPECIAL INSPECTORS SHALL KEEP RECORDS OF ALL INSPECTIONS AND

SHALL FURNISH REPORTS TO THE BUILDING OFFICIAL AND TO THE

REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE.

DISCREPANCIES SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION

OF THE CONTRACTOR FOR CORRECTION. IF THE DISCREPANCIES ARE

NOT CORRECTED THEY SHALL BE BROUGHT TO THE ATTENTION OF THE

REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE.

4. THE FOLLOWING ITEMS REQUIRE SPECIAL INSPECTION.

5. SPECIAL INSPECTION FOR STRUCTURAL STEEL SHALL BE IN ACCORDANCE

WITH THE QUALITY ASSURANCE INSPECTION REQUIREMENTS OF AISC 360.

STRUCTURAL TESTS AND SPECIAL INSPECTION

TABLE 1705.3

REQUIRED VERIFICATION AND INSPECTION OF CONCRETE CONSTRUCTION

1. INSPECTION OF REINFORCING STEEL, INCLUDING

PRESTRESSING TENDONS, AND PLACEMENT.

VERIFICATION AND INSPECTION CONTINUOUS PERIODIC

X

2. INSPECTION OF REINFORCING STEEL WELDING IN

ACCORDANCE WITH TABLE 1705.2.2, ITEM 2b.

3. INSPECTION OF ANCHORS CAST IN CONCRETE WHERE

ALLOWABLE LOADS HAVE BEEN INCREASED OR WHERE

STRENGTH DESIGN IS USED.

5. VERIFYING USE OF REQUIRED DESIGN MIX. X

7. INSPECTION OF CONCRETE AND SHOTCRETE PLACEMENT

FOR PROPER APPLICATION TECHNIQUES.

8. INSPECTION FOR MAINTENANCE OF SPECIFIED CURING

TEMPERATURE AND TECHNIQUES.

9. INSPECTION OF PRESTRESSED CONCRETE:

a. APPLICATION OF PRESTRESSING FORCES.

b. GROUTING OF BONDED PRESTRESSING TENDONS IN

THE SEISMIC-FORCE-RESISTING SYSTEM.

REFERENCED

STANDARD IBC REFERENCEa

ACI 318: 3.5,

7.1-7.7 1910.4

AWS D1.4

ACI 318: 3.5.2

1908.5, 1909.1

ACI 318: Ch. 4, 5.2-5.4

1904.2, 1910.2, 1910.3

6. AT THE TIME FRESH CONCRETE IS SAMPLED TO FABRICATE

SPECIMENS FOR STRENGTH TESTS, PERFORM SLUMP AND

AIR CONTENT TESTS, AND DETERMINE THE TEMPERATURE

OF THE CONCRETE.

X

ASTM C 172

ASTM C 31

ACI 318: 5.6, 5.8

1910.10

X ACI 318: 5.9, 5.10 1910.6, 1910.7,

1910.8

X ACI 318: 5.11-5.13 1910.9

X X

ACI 318: 18.20

ACI 318: 18.18.4

10. ERECTION OF PRECAST CONCRETE MEMBERS. X ACI 318: Ch.16

11. VERIFICATION OF IN-SITU CONCRETE STRENGTH, PRIOR TO

STRESSING OF TENDONS IN POSTTENSIONED CONCRETE AND

PRIOR TO REMOVAL OF SHORES AND FORMS FROM BEAMS

AND STRUCTURAL SLABS.

X ACI 318: 6.2

12. INSPECT FORMWORK FOR SHAPE, LOCATION AND

DIMENSIONS OF THE CONCRETE MEMBER BEING FORMED. X ACI 318: 6.1.1

TABLE 1705.6

REQUIRED VERIFICATION AND INSPECTION OF SOILS

1. VERIFY MATERIALS BELOW FOOTINGS ARE ADEQUATE TO ACHIEVE THE

DESIGN BEARING CAPACITY.

VERIFICATION AND INSPECTION TASK CONTINUOUS DURING

TASK LISTED

PERIODICALLY DURING

TASK LISTED

X

2. VERIFY EXCAVATIONS ARE EXTENDED TO PROPER DEPTH AND HAVE

REACHED PROPER MATERIAL. X

3. PERFORM CLASSIFICATION AND TESTING OF COMPACTED

FILL MATERIALS.

4. VERIFY USE OF PROPER MATERIALS, DENSITIES AND LIFT THICKNESSES

DURING PLACEMENT AND COMPACTION OF COMPACTED FILL.

5. PRIOR TO PLACEMENT OF COMPACTED FILL, OBSERVE SUBGRADE AND

VERIFY THAT SITE HAS BEEN PREPARED PROPERLY.

X

X

X

X

ACI 318:

8.1.3, 21.2.8

4. INSPECTION OF ANCHORS POST-INSTALLED IN HARDENED

CONCRETE MEMBERS.

ACI 318.

3.86, 8.1.3, 21.2.8X 1909.1

TABLE 1705.8

REQUIRED VERIFICATION OF CAST-IN-PLACE DEEP FOUNDATION ELEMENTS

1. OBSERVE DRILLING OPERATIONS AND MAINTAIN COMPLETE AND

ACCURATE RECORDS FOR EACH ELEMENT.

VERIFICATION AND INSPECTION TASK CONTINUOUS DURING

TASK LISTED

PERIODICALLY DURING

TASK LISTED

2. VERIFY PLACEMENT LOCATIONS AND PLUMBNESS CONFIRM ELEMENT

DIAMETERS, BELL DIAMETERS (IF APPLICABLE), LENGTHS, EMBEDMENT

INTO BEDROCK (IF APPLICABLE) AND ADEQUATE END-BEARING STRATA

CAPACITY. RECORD CONCRETE OR GROUT VOLUMES.

3. VERIFY USE OF PROPER MATERIALS, DENSITIES AND LIFT THICKNESSES

DURING PLACEMENT AND COMPACTION OF COMPACTED FILL.

X

X

DATE: 4/19/24

DRAWING NO:

JOB NO. 21178

SEAL:

DRAWN BY: EC,VDV

CHECKED BY:HR

REVISION:

PR

OJ

EC

T:

Pa lm ito R an ch

B at tle fie ld S ta te

H is to ric

S ite

400 Nolana, Suite H2

FAX: (956) 687-3211

www.chaninengineering.com

TBPE FIRM REG. NUMBER F-9369

PH: (956) 687-9421

McAllen, Texas 78504

Vi ew in g

Pl at fo rm

Br ow ns vi lle , T ex as

S1.1

AutoCAD SHX Text

HECTOR RAMIREZ

AutoCAD SHX Text F

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text P

AutoCAD SHX Text O

AutoCAD SHX Text S

AutoCAD SHX Text 103720

AutoCAD SHX Text G

AutoCAD SHX Text O

AutoCAD SHX Text I

AutoCAD SHX Text E

AutoCAD SHX Text L

AutoCAD SHX Text N

AutoCAD SHX Text A

AutoCAD SHX Text E

AutoCAD SHX Text C

AutoCAD SHX Text I

AutoCAD SHX Text L

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text N

AutoCAD SHX Text N

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text I

AutoCAD SHX Text N

AutoCAD SHX Text X

AutoCAD SHX Text O

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text F

AutoCAD SHX Text A

ROOF UPLIFT PLAN

SCALE: NTSPLAN NORTH

N

WINDSTORM NOTES

1. THIS PROJECT IS LOCATED IN A STATE OF TEXAS COASTAL COUNTY, AS SUCH, IT MUST MEET

TEXAS DEPARTMENT OF INSURANCE (TDI) WINDSTORM REQUIREMENTS.

2. CONTRACTOR SHALL PROVIDE SUBMITTALS FOR ALL EXTERIOR CLADDING COMPONENTS.

THE SUBMITTALS SHALL INCLUDE:

A. MANUFACTURER SPECIFICATIONS

B. TEXAS DEPARTMENT OF INSURANCE APPROVAL CERTIFICATE

C. PRODUCT TEST DATA

D. PLAN DRAWING OF PROJECT INDICATING THE LOCATION OF PRODUCT USE

3. CONTRACTOR SHALL NOTIFY ENGINEER OF THE INTENDED SCHEDULE OF INSTALLATION FOR

SITE OBSERVATION VISITS.

TDI WINDSTORM COMPLIANCE

CONTRACTOR RESPONSIBILITY

1. CONTRACTOR TO PROVIDE REQUIRED SUBMITTALS WITH REQUESTED DOCUMENTATION TO

ENGINEER FOR APPROVAL.

2. CONTRACTOR TO HOLD WINDSTORM PRE-CONSTRUCTION MEETING WITH ENGINEER AND

SPECIAL INSPECTOR.

3. CONTRACTOR TO PROVIDE ENGINEER AND SPECIAL INSPECTOR WITH 48 HR. NOTICE OF

INSTALLATION SCHEDULING.

4. INSTALLATION OF APPROVED WINDSTORM COMPNENTS SHALL BE DOCUMENTED BY SPECIAL

INSPECTOR AS SHOWN IN WINDSTORM SPECIAL INSPECTION REQUIREMENTS.

5. INSTALLATION OF WINDSTORM COMPONENTS SHALL BE APPROVED BY ENGINEER BEFORE

WORK CONTINUES IN THAT AREA.

ROOFING

1. ROOF SYSTEMS SHALL COMPLY WITH IBC SECTION 1504 REQUIREMENTS.

2. UPLIFT DESIGN PRESSURES SHALL BE AS INDICATED ON STRUCTURAL ROOF UPLIFT PLAN.

3. CONTRACTOR TO PROVIDE TEXAS DEPARTMENT OF INSURANCE APPROVAL CERTIFICATE OR

MIAMI DADE COUNTY NOTICE OF ACCEPTANCE.

4. CONTRACTOR TO PROVIDE PRODUCT TEST DATA SUPPORTING WIND LOAD RATING OF

ASSEMBLY.

5. PROPOSED ASSEMBLY SHALL MATCH ASSEMBLY INSTRUCTIONS SHOWN ON APPROVAL

CERTIFICATES, TESTING DATA, AND MANUFACTURER SPECIFICATIONS. NO SUBSTITUTIONS

SHALL BE ALLOWED.

6. SUBMITTALS SHALL INCLUDE REQUIRED ATTACHMENT PATTERNS FOR CORNER, END ZONES

AND INTERIOR ROOF ZONES SHOWN ON THE WIND UPLIFT DRAWINGS.

7. SUBMITTAL SHALL ALSO INCLUDE REQUIRED ANCHOR TYPE AND LENGTH REQUIRED TO

ACHIEVE PROPER SUBSTRATE PENETRATION.

WINDSTORM SPECIAL INSPECTION REQUIREMENTS

1. THE FOLLOWING COMPONENTS SHALL BE A PART OF THE SPECIAL INSPECTION PROGRAM OF

THIS PROJECT.

2. CONTRACTOR TO PROVIDE A COPY OF THE REQUIRED PRODUCT SUBMITTALS, INCLUDING

INSTALLATION INSTRUCTIONS TO SPECIAL INSPECTOR.

3. SPECIAL INSPECTOR SHALL VERIFY ON SITE PRODUCTS ARE AS SHOWN ON SUBMITTALS AND

LABELED AS REQUIRED.

4. SPECIAL INSPECTOR SHALL VERIFY INSTALLATION IS AS REQUIRED BY MANUFACTURER AND

APPROVAL CERTIFICATES.

1. ROOFING

A. VERIFICATION OF ROOFING ASSEMBLY

B. VERIFICATION OF ATTACHMENT PATTERN

VERIFICATION AND INSPECTION CONTINUOUS PERIODIC

X

X

TYP.

3'-0"

TY

P.

3' -0

3 3

3 3

2 2

2 2

2 2

1 1

ALLOWABLE STRESS DESIGN

-26.1 psf

EFFECTIVE WIND AREA GROSSZONE

NET

-20.1 psf

-26.1 psf -20.1 psf

-26.1 psf -20.1 psf

-39.2 psf -33.2 psf

-39.2 psf -33.2 psf

-26.1 psf -20.1 psf

-78.4 psf -72.4 psf

-39.2 psf -33.2 psf

-26.1 psf -20.1 psf

DATE: 4/19/24

DRAWING NO:

JOB NO. 21178

SEAL:

DRAWN BY: EC,VDV

CHECKED BY:HR

REVISION:

PR

OJ

EC

T:

Pa lm ito R an ch

B at tle fie ld S ta te

H is to ric

S ite

400 Nolana, Suite H2

FAX: (956) 687-3211

www.chaninengineering.com

TBPE FIRM REG. NUMBER F-9369

PH: (956) 687-9421

McAllen, Texas 78504

Vi ew in g

Pl at fo rm

Br ow ns vi lle , T ex as

S1.2

AutoCAD SHX Text

HECTOR RAMIREZ

AutoCAD SHX Text F

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text P

AutoCAD SHX Text O

AutoCAD SHX Text S

AutoCAD SHX Text 103720

AutoCAD SHX Text G

AutoCAD SHX Text O

AutoCAD SHX Text I

AutoCAD SHX Text E

AutoCAD SHX Text L

AutoCAD SHX Text N

AutoCAD SHX Text A

AutoCAD SHX Text E

AutoCAD SHX Text C

AutoCAD SHX Text I

AutoCAD SHX Text L

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text N

AutoCAD SHX Text N

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text I

AutoCAD SHX Text N

AutoCAD SHX Text X

AutoCAD SHX Text O

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text F

AutoCAD SHX Text A

EXISTING CALICHE

PARKING LOT

WEST PROPERTY LINE

FOR MORE INFORMATION REFER

TO SHEETS S2.0, S3.0, S4.0

32'-0"

'-0

5' -0

PROPOSED

PLATFORM

UP

U P

UP

UP

3'-1"

DELEGATED PARKING LOT DESIGN:

DESIGN TO INCLUDE BUT NOT LIMITED TO

PAVEMENT DESIGN, VAN ACCESSIBILITY,

SIGNAGE, PARKING STRIPPING, HANDICAP

RAMP, AND DIMENSIONS.

DATE: 4/19/24

DRAWING NO:

JOB NO. 21178

SEAL:

DRAWN BY: EC,VDV

CHECKED BY:HR

REVISION:

PR

OJ

EC

T:

Pa lm ito R an ch

B at tle fie ld S ta te

H is to ric

S ite

400 Nolana, Suite H2

FAX: (956) 687-3211

www.chaninengineering.com

TBPE FIRM REG. NUMBER F-9369

PH: (956) 687-9421

McAllen, Texas 78504

Vi ew in g

Pl at fo rm

Br ow ns vi lle , T ex as

OVERALL SITE PLAN

SCALE: 3/32"=1'-0" S1.3PLAN NORTH

N

AutoCAD SHX Text

HECTOR RAMIREZ

AutoCAD SHX Text F

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text P

AutoCAD SHX Text O

AutoCAD SHX Text S

AutoCAD SHX Text 103720

AutoCAD SHX Text G

AutoCAD SHX Text O

AutoCAD SHX Text I

AutoCAD SHX Text E

AutoCAD SHX Text L

AutoCAD SHX Text N

AutoCAD SHX Text A

AutoCAD SHX Text E

AutoCAD SHX Text C

AutoCAD SHX Text I

AutoCAD SHX Text L

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text N

AutoCAD SHX Text N

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text I

AutoCAD SHX Text N

AutoCAD SHX Text X

AutoCAD SHX Text O

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text F

AutoCAD SHX Text A

103'-6"

103'-6"

'-4

'-4

52'-2" 51'-4"

'-2

'-2

5' -0

5" 5'-3" 19'-0" 27'-6"

5" 5'-3" 9'-6" 10'-4" 16'-6" 16'-6" 16'-6" 16'-6" 2'-6"

5'-8" 9'-6" 9'-6"

5" 5'

-3

9' -6

9'

-6

5' -3

5"

OVERALL

BUILDING BREAKS

O

VE

R

AL

L

OVERALL

COLUMNS

O

VE

R

AL

L

BU

IL

D

IN

G B

R

EA

KS

1 3 4 62

1 7 9

A

B

D

H

K

A

E

F

G J

K

5 8 10

5' -0

'-4

5' -0

R

AM

P

BR

EA

KS

C O

LU

M

N S

RAMP BREAKS

COLUMNS

COLUMNS

4" 4'

-8

5" 5'

-2

5' -2

5"

6' -2

4'

-2

C O

LU

M

N S

C O

LU

M

N S

5'-0" 27'-0" 6'-0" 27'-0" 6'-0" 27'-6" 5'-0" RAMP BREAKS

24'-6"6'-0"16'-8"5'-0"

9'-6"

3 42

P12

S4.0

TYP.

5" THK. SLAB ON GRADE

WITH #4 AT 14" O.C.

EACH WAY AT MID-DEPTH

OF SLAB

SLOPE

P12

P12

P12

P12

P12

P18

P12

P12

P12 P12 P12

P12

P12

P12 P12

P12

P12 P12

P12

P12

P12

P12

P12

P12

P18

P18

P18 P18 P18

P18 P18 P18 P12

P12 S4.0

CONTRACTION

JOINT, TYP.

2'-6"

2' -6

TYP.

TY

P.

103'-6"

103'-6"

'-4

'-4

52'-2" 51'-4"

'-2

'-2

5' -0

5" 5'-3" 19'-0" 27'-6"

5" 5'-3" 9'-6" 10'-4" 16'-6" 16'-6" 16'-6" 16'-6" 2'-6"

5'-8" 9'-6" 9'-6"

5" 5'

-3

9' -6

9'

-6

5' -3

5"

OVERALL

BUILDING BREAKS

O

VE

R

AL

L

OVERALL

COLUMNS

O

VE

R

AL

L

BU

IL

D

IN

G B

R

EA

KS

1 3 4 62

1 7 9

A

B

D

H

K

A

E

F

G J

K

5 8 10

5' -0

'-4

5' -0

R

AM

P

BR

EA

KS

C O

LU

M

N S

RAMP BREAKS

COLUMNS

COLUMNS

4" 4'

-8

5" 5'

-2

5' -2

5"

6' -2

4'

-2

C O

LU

M

N S

C O

LU

M

N S

5'-0" 27'-0" 6'-0" 27'-0" 6'-0" 27'-6" 5'-0" RAMP BREAKS

24'-6"6'-0"16'-8"5'-0"

9'-6"

3 42

C10 C10 C10 C10

C10

C10

C10

C10 C10 C10 C10 C10

C10

C10

C10

C10

C10

C10

C10

C10

C10

C10

C10

C10

C10

C10

C12 C12C12

C12 C12 C12

C12C12C12 SLO

PESLOPE

SLOPESLO

PE

DOWNSPOUT

SLOPE TYP.

DATE: 4/19/24

DRAWING NO:

JOB NO. 21178

SEAL:

DRAWN BY: EC,VDV

CHECKED BY:HR

REVISION:

PR

OJ

EC

T:

Pa lm ito R an ch

B at tle fie ld S ta te

H is to ric

S ite

400 Nolana, Suite H2

FAX: (956) 687-3211

www.chaninengineering.com

TBPE FIRM REG. NUMBER F-9369

PH: (956) 687-9421

McAllen, Texas 78504

Vi ew in g

Pl at fo rm

Br ow ns vi lle , T ex as

S2.0

PIER LAYOUT PLAN

SCALE: 1/8"=1'-0"

PIER NOTES:

PX

1. CONTRACTOR TO VERIFY ALL DIMENSIONS BEFORE

COMMENCING WORK

2. CONTRACTOR TO SLOPE SITE AWAY FROM STRUCTURE.

3. INDICATES CONCRETE PIER, SEE DETAIL 9/S4.0

COLUMN LAYOUT PLAN

SCALE: 1/8"=1'-0"

FRAMING NOTES:

1. CONTRACTOR TO VERIFY ALL DIMENSIONS BEFORE

COMMENCING WORK.

2. ALL STEEL MEMBERS AND CONNECTIONS TO BE HOT

DIPPED GALVANIZED.

3. INDICATES COLUMN, SEE DETAIL 12/S4.0 FOR SCHEDULECX

PLAN NORTH

N

PLAN NORTH

N

AutoCAD SHX Text

HECTOR RAMIREZ

AutoCAD SHX Text F

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text P

AutoCAD SHX Text O

AutoCAD SHX Text S

AutoCAD SHX Text 103720

AutoCAD SHX Text G

AutoCAD SHX Text O

AutoCAD SHX Text I

AutoCAD SHX Text E

AutoCAD SHX Text L

AutoCAD SHX Text N

AutoCAD SHX Text A

AutoCAD SHX Text E

AutoCAD SHX Text C

AutoCAD SHX Text I

AutoCAD SHX Text L

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text N

AutoCAD SHX Text N

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text I

AutoCAD SHX Text N

AutoCAD SHX Text X

AutoCAD SHX Text O

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text F

AutoCAD SHX Text A

5'-8" 9'-6" 9'-6"

C8x11.5

AT 2'-0" O.C., MAX.

W8x22

AT 2'-0" O.C., MAX.

T.

O

.B R

G

7'

-0

T.

O

.B R

G

7'

-0

T.

O

.B R

G

7'

-0

T.O.BRG. = 17'-0"

T.O.BRG. = 17'-0"

T.O.BRG. = 17'-0"

INDICATES FLOOR

FRAMED WITH TREX

COMPOSITE DECKING

B

H

2 43

D

C8x11.5

C8x11.5

C8x11.5

C 8x

.5S4.1

C8x11.5

C8x11.5

S4.0

C 8x

.5

C 8x

.5

C 8x

.5

SIM.

5'-8" 9'-6" 9'-6"

MBCI "PB2"26 GA.

GALVALUME PLUS

ROOF PANEL w/

FASTENERS PER

DETAIL S/5.01, COLOR

SHALL BE MBCI

"BROWNSTONE" OR

EQUAL APPROVED BY

OWNER IF OTHER

MFR IS SELECTED.

HSS6x4x-1/4

S4.1

B

H

2 43

D

5' -8

9'

-6

9' -6

5'

-8

AT 2'-0" O.C., MAX.

HSS6x4x-1/4

AT 2'-0" O.C., MAX.

H

SS

6x 4x

-1 /4

AT

'-0 " O

.C

M

AX

H

SS

6x 4x

-1 /4

AT

'-0 " O

.C

M

AX

HSS6x 6x

-1/ 4 HSS6x6x-1/4

HSS6x6x-1/4 HSS6x 6x

-1/

S4.0

HSS6x6x-1/4

HSS6x6x-1/4

H

SS

6x 6x

-1 /4

H

SS

6x 6x

-1 /4

103'-6"

103'-6"

'-4

'-4

52'-2" 51'-4"

'-2

'-2

5' -0

5" 5'-3" 19'-0" 27'-6"

5" 5'-3" 9'-6" 10'-4" 16'-6" 16'-6" 16'-6" 16'-6" 2'-6"

5" 5'

-3

9' -6

9'

-6

5' -3

5"

OVERALL

BUILDING BREAKS

O

VE

R

AL

L

OVERALL

COLUMNS

O

VE

R

AL

L

BU

IL

D

IN

G B

R

EA

KS

1 7 9

A

D

K

A

F

G J

K

5 8 10

5' -0

'-4

5' -0

R

AM

P

BR

EA

KS

C O

LU

M

N S

RAMP BREAKS

COLUMNS

COLUMNS

4" 4'

-8

5" 5'

-2

5' -2

5"

6' -2

4'

-2

C O

LU

M

N S

C O

LU

M

N S

5'-0" 27'-0" 6'-0" 27'-0" 6'-0" 27'-6" 5'-0" RAMP BREAKS

24'-6"6'-0"16'-8"5'-0"

9'-6"

T.

O

.B R

G

'-1

1"

T.

O

.B R

G

'-3

T.O.BRG. = 3'-3"

T.O.BRG. = 4'-11 7/8"

T.

O

.B R

G

'-1

7/

8"

T.

O

.B R

G

'-2

/8

T.

O

.B R

G

'-5

/8

T.

O

.B R

G

1'

-1

/8

T.

O

.B R

G

1'

-1

/8

T.

O

.B R

G

4'

-1

/8

INDICATES FLOOR

FRAMED WITH TREX

COMPOSITE DECKING

S4.1

S4.1

S4.1

SIM.

T.

O

.B R

G

6'

-4

/8

C8x11.5

C8x11.5

C8x11.5 BENT BEAM

C8x11.5

C8x11.5

C8x11.5

C8x11.5

W8x15

C8x11.5

C 8x

.5

C 8x

.5

C 8x

.5

C 8x

.5

W 8x

W

8x

W 8x

W 8x

C 8x

.5

W 8x

W

8x

C 8x

.5

C 8x

.5

W 8x

W

8x

W 8x

W

8x

W 8x

W

8x

S4.0

SLOPE

SLOPE SLOPE

SLOPESLOPESLOPE

SL

O

PE

W 8x

W

8x

T.O.BRG. = 4'-11 7/8"

T.

O

.B R

G

'-1

7/

8"

T.

O

.B R

G

'-2

/8

T.

O

.B R

G

'-2

/8

T.

O

.B R

G

'-5

/8

T.

O

.B R

G

'-5

/8

T.

O

.B R

G

'-3

T.O.BRG. = 3'-3"

T.

O

.B R

G

'-1

1"

T.

O

.B R

G

'-1

1"

T.

O

.B R

G

1'

-9

/8

T.

O

.B R

G

1'

-9

/8

T.

O

.B R

G

1'

-9

/8

T.

O

.B R

G

1'

-9

/8

T.

O

.B R

G

4'

-1

/8

T.

O

.B R

G

4'

-1

/8

T.

O

.B R

G

6'

-4

/8

T.

O

.B R

G

6'

-4

/8

C8x11.5

C8x11.5 BENT BEAM

S4.1

S4.1

S4.0

C8x11.5 BENT BEAM

C8x11.5

C8x11.5

C8x11.5

C8x11.5

C8x11.5

C 8x

.5

C8x11.5

BENT

BEAM

C8x11.5 BENT BEAM

C8x11.5 BENT BEAM

C8x11.5 BENT BEAM

C8x11.5 BENT BEAM

C8x11.5

BENT BEAM

C8x11.5 C8x11.5

C 8x

.5

C 8x

.5 C8x11.5

C8x11.5

C 8x

.5C 8x

.5

C 8x

.5

C8x11.5 BENT BEAMC8x11.5 BENT BEAM

C8x11.5 BENT BEAMC8x11.5 BENT BEAM

C8x11.5 C8x11.5

C 8x

.5

C 8x

.5

C8x11.5C8x11.5

C8x11.5 BENT BEAM

C8x11.5 BENT BEAM

C8x11.5

BENT

BEAM

C 8x

.5

C 8x

.5

C 8x

.5

W8x15

W8x15C 8x

.5

S5.0

C8x11.5

TYP.

S5.0

C8x11.5

SIM.

W 8x

C 8x

.5

C8x11.5 BENT BEAM

C8x11.5 BENT BEAM

C8x11.5

C8x11.5

C8x11.5 BRACE TYP.

C8x11.5 BRACE TYP.

TYP.

DATE: 4/19/24

DRAWING NO:

JOB NO. 21178

SEAL:

DRAWN BY: EC,VDV

CHECKED BY:HR

REVISION:

PR

OJ

EC

T:

Pa lm ito R an ch

B at tle fie ld S ta te

H is to ric

S ite

400 Nolana, Suite H2

FAX: (956) 687-3211

www.chaninengineering.com

TBPE FIRM REG. NUMBER F-9369

PH: (956) 687-9421

McAllen, Texas 78504

Vi ew in g

Pl at fo rm

Br ow ns vi lle , T ex as

ROOF FRAMING PLAN

SCALE: 1/8"=1'-0" S3.0PLATFORM/STAIRS LAYOUT PLAN

SCALE: 1/8"=1'-0"

RAMP FRAMING PLAN

SCALE: 1/8"=1'-0"

FRAMING NOTES:

1. CONTRACTOR TO VERIFY ALL DIMENSIONS BEFORE

COMMENCING WORK.

2. ALL STEEL MEMBERS AND CONNECTIONS TO BE HOT

DIPPED GALVANIZED.

FRAMING NOTES:

1. CONTRACTOR TO VERIFY ALL DIMENSIONS BEFORE

COMMENCING WORK.

2. ALL STEEL MEMBERS AND CONNECTIONS TO BE HOT

DIPPED GALVANIZED.

PLAN NORTH

N

PLAN NORTH

N

PLAN NORTH

N

FRAMING NOTES:

1. CONTRACTOR TO VERIFY ALL DIMENSIONS BEFORE

COMMENCING WORK.

2. ALL STEEL MEMBERS AND CONNECTIONS TO BE HOT

DIPPED GALVANIZED.

AutoCAD SHX Text

HECTOR RAMIREZ

AutoCAD SHX Text F

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text P

AutoCAD SHX Text O

AutoCAD SHX Text S

AutoCAD SHX Text 103720

AutoCAD SHX Text G

AutoCAD SHX Text O

AutoCAD SHX Text I

AutoCAD SHX Text E

AutoCAD SHX Text L

AutoCAD SHX Text N

AutoCAD SHX Text A

AutoCAD SHX Text E

AutoCAD SHX Text C

AutoCAD SHX Text I

AutoCAD SHX Text L

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text N

AutoCAD SHX Text N

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text I

AutoCAD SHX Text N

AutoCAD SHX Text X

AutoCAD SHX Text O

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text F

AutoCAD SHX Text A

CONTRACTION JOINT DETAIL

T/

T

CONTRACTION JOINT

(GROOVE OR SAW CUT)

1. JOINT PATTERN SHALL BE NEARLY SQUARE

2. JOINT SPACING SHALL NOT EXCEED 15'-0"

TYPE "P" FOOTING

D E

PT

H

A

DIA.

PIER SCHEDULE

NOTE: FOR MORE

INFORMATION SEE DETAILS

4/S4.0

BOTTOM OF PIER

FROM

NOTE: BOTTOM OF PIER

ELEVATION TAKEN FROM

EXISTING NATURAL GRADE

PIER SCHEDULE AT STEEL COLUMNS

TYPE A REBAR REINFORCEMENTDEPTH

OF PIER

P18 18" (6) #6's (V) #3 SPIRAL WITH A 6" PITCH15'-0"

EXISTING

NATURAL

GRADE

P12 12" 15'-0"

3' -0

6"

PE

R

S C

H E

D U

LE

2"

6"

REINFORCING PER

SCHEDULE

C

LR

CONCRETE COLUMN

PER PLAN

S4.0

AA

#6 "U" BARS AT 12"

O.C. EACH WAY

TOP AND BOTTOM

(3) #6 CONT. TOP

AND BOTTOM

PIER PER

SCHEDULE

FOOTING AT CONCRETE COLUMN

2STEEL CHANNEL TO CONCRETE COLUMN

AT RAMP

9 1/2" 1'-0" 1'-0" 2 1/2"

1/

4"

3'-0"3'-0" 1'-0" 1'-0" 1'-0"

2 1/2" 7" 5" 7" 7"5" 2 1/2"

1/

4"

PBR FASTENER SPACING

AT INTERMEDIATE SUPPORT

PBR FASTENER SPACING

AT PANEL ENDS

ROOF PANEL FASTER SPACING

LAP SECTION

LONG LIFE

FASTENER #9 w/

WASHER TYP.

1/4-14x 7/8" LONG- LIFE LAPTEK w/

WASHER AT

20" O.C. TYP.

TAPE SEALER

PBR ROOF PANEL

STEEL BEAM TO STEEL BEAM CONNECTION

SIZE OF BOLTS

NUMBER OF ROWS/

(2) 3/4" DIA. A325C8x11.5

SIZE

BEAM

ANGLE

CLIP

∠∠4x3 1/2 x1/4

1/

2" 3"

1/

2"

1 1/2" 3 1/2"

T.O.S.

PER PLAN

STEEL BEAM

PER PLAN

STEEL BEAM

PER PLAN

DOUBLE CLIP ANGLE

PER SCHEDULE

STEEL CHANNEL TO CONCRETE COLUMN

AT RAMP

EXTERIOR FOOTING

GRID

STEEL BEAM PER PLAN

CONCRETE COLUMN

PER PLAN

4"

H E

IG

H

T G

U A

R D

R A

IL

T

YP

H E

IG

H

T H

A N

D R

A

IL

T

YP

TY

P.

GRID

STEEL BEAM PER PLAN

CONCRETE COLUMN

PER PLAN

3/4" THK. PLATE w/

(2) 1/2" DIA. x 1'-0" LONG

J-BOLTS PLUG WELDED TO

STEEL BEAM

4"

H E

IG

H

T G

U A

R D

R A

IL

T

YP

H E

IG

H

T H

A N

D R

A

IL

T

YP

TY

P.

5/16" THK. BENT PLATE w/

5/16" STIFFENER PLATE AT

EACH VERTICAL

WOOD TREAD TO STEEL CHANNELS

6x2 COMPOSITE

DECKING

STEEL CHANNEL

PER PLAN

A

DIA.

CONCRETE COLUMN SCHEDULE

CONCRETE COLUMN SCHEDULE

TYPE A REBAR REINFORCEMENT

C12 12" (6) #6's w/ #3 CLOSED STIRRUPS AT 12" O.C.

C10 10" (6) #5's w/ #3 CLOSED STIRRUPS AT 10" O.C.

2' -0

1'-0"

SLOPE AS OCCURS

2' -0

V

A R

IE

S

1'-0"

EXTERIOR FOOTING

3" SQ. 3" SQ.

7/8" SQ. PIPE

1/4" BENT PLATE

AT EACH STEP

STEEL CHANNEL w/

1/4" BENT PLATE

AT EACH STEP

STEEL CHANNEL w/

FASTENING TO

STRUCTURE PER

SUPPLIER

RECOMMENDATIONS

7/8" SQ. PIPE

15 HSS BEAM TO HSS BEAM

CONNECTION PER

DETAIL 8/S4.0

(2) #6 CONT.

TOP AND BOTTOM

MID DEPTH

#3 STIRRUPS AT

18" O.C.

SLAB AND REINFORCEMENT

PER PLAN

SLAB AND REINFORCEMENT

PER PLAN

(2) #6 CONT.

TOP AND BOTTOM

MID DEPTH

#3 STIRRUPS AT

12" O.C.

ADDITIONAL (2) #6 CONT.

BARS IF GRADE BEAM DEPTH

EXCEEDS 4 FEET DEPTH

3/16 TYP.

SLAB AND REINFORCEMENT

PER PLAN

1'-0"

2' -0

/2

STEEL CHANNEL TO FOUNDATION

STEEL CHANNEL TO CONCRETE COLUMN

AT RAMP

NOTE:

ALL STEEL MEMBERS AND

COMPONENTS TO BE HOT-DIPPED

GALVANIZED

SECTION A-A

STEEL BEAM PER PLAN

DOUBLE CLIP ANGLE

PER SCHEDULE

STEEL BEAM PER PLAN

PER PLAN

C8x11.5 CONT. w/ 1/2" DIA.

THREADED ANCHORS

STAGGERED w/ HILTI

HY200 ADHESIVE AT

12" O.C. MAX.

2' -0

PE

R

S C

H E

D U

LE

2"

REINFORCING PER

SCHEDULE

C

LR

1/4" END CAP

(6) #5's w/ #3 CLOSED STIRRUPS AT 4" O.C.

CONNECTION PER

DETAIL 8/S4.0

5/16" THK. BENT PLATE

w/ 5/16" STIFFENER

PLATE AT EACH VERTICAL

SHIM PLATE

AS NEEDED

SECTION A-A

2" C

LR

S5.0

(4) #3 CLOSED

STIRRUPS AT

ANCHORS w/ A MAX

SPACING OF 3" O.C.

DATE: 4/19/24

DRAWING NO:

JOB NO. 21178

SEAL:

DRAWN BY: EC,VDV

CHECKED BY:HR

REVISION:

PR

OJ

EC

T:

Pa lm ito R an ch

B at tle fie ld S ta te

H is to ric

S ite

400 Nolana, Suite H2

FAX: (956) 687-3211

www.chaninengineering.com

TBPE FIRM REG. NUMBER F-9369

PH: (956) 687-9421

McAllen, Texas 78504

Vi ew in g

Pl at fo rm

Br ow ns vi lle , T ex as

S4.0

AutoCAD SHX Text

HECTOR RAMIREZ

AutoCAD SHX Text F

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text P

AutoCAD SHX Text O

AutoCAD SHX Text S

AutoCAD SHX Text 103720

AutoCAD SHX Text G

AutoCAD SHX Text O

AutoCAD SHX Text I

AutoCAD SHX Text E

AutoCAD SHX Text L

AutoCAD SHX Text N

AutoCAD SHX Text A

AutoCAD SHX Text E

AutoCAD SHX Text C

AutoCAD SHX Text I

AutoCAD SHX Text L

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text N

AutoCAD SHX Text N

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text I

AutoCAD SHX Text N

AutoCAD SHX Text X

AutoCAD SHX Text O

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text F

AutoCAD SHX Text A

CONCRETE POST PILE

PER PLAN

RAMP WALKWAY SECTION

WALKWAY ELEVATION

5'-10" MAX.

6x2 COMPOSITE

DECKING

CONCRETE COLUMN

PER PLAN

SECTION AT GAZEBO

NOTE:

ALL STEEL MEMBERS AND

CONNECTIONS TO BE HOT-DIPPED

GALVANIZED, ALL SIMPSON

CONNECTORS AND FASTENERS TO BE

GALVANIZED

H E

IG

H

T

G

U A

R D

R A

IL

GUARDRAIL

42" MIN. HEIGHT

GRID

GRID

GRID

CONCRETE POST

COLUMN PER PLAN

NOTE:

ALL STEEL MEMBERS AND CONNECTIONS

TO BE HOT-DIPPED GALVANIZED

NOTE:

ALL SIMPSON CONNECTORS TO BE

GALVANIZED

STEEL BEAM PER PLAN

GRID GRID

NOTE: ALL HAND RAILS NOT SHOWN

FOR CLARITY

6x2 COMPOSITE

DECKING

S4.0

TYP.

GRID

0'-0"

T.O.BRG. = 17'-0"

T.O.BRG. = 25'-0"

17STEEL BEAM TO CONCRETE COLUMN

CONCRETE POST PILE

PER PLAN

T.O.BRG.

PER PLAN

NOTE:

ALL STEEL MEMBERS AND CONNECTIONS

TO BE HOT-DIPPED GALVANIZED, ALL

SIMPSON CONNECTORS TO BE

GALVANIZED

H E

IG

H

T

G

U A

R D

R A

IL

GRID

6x2 COMPOSITE

DECKING

S4.0

TYP.

GRID

1'-2"

S4.1

TYP.

RAMP WALKWAY SECTION

T.O.BRG.

PER PLAN

HANDRAIL

33" MIN. HEIGHT

4" M

A X

4"

O.C. MAX. TYP.

T.O.BRG.

PER PLAN

6" GALVANIZED HALF-ROUND

GUTTERS w/ 4" DIA. ROUND

DOWNSPOUTS TO EACH

GRADE. ONE AT EACH CORNER

SPLASH BLOCKS AT EACH

DOWNSPOUT

STEEL BEAM PER PLAN

1/4" THK. BENT

PLATE

METAL ROOF

PANEL PER PLAN

COMPOSITE DECKING

PER PLAN

7/8" SQ. BAR

TYP.

RAMP

RAMP

1"

1" ROOF PANEL

EXTENSION BEYOND

FACE OF STEEL BEAM

PER ROOF PANEL AND

GUTTER SUPPLIER

6" HALF-ROUND

GUTTER

RAMP

4" ROUND

DOWNSPOUT

ALTERNATE #1- DELETE ROOF

STRUCTURE

ALTERNATE #2- REPLACE

COMPOSITE WOOD DECKING

WITH TREATED WOOD PLANKS

4x4x1/4 BENT PLATE w/ (2) 3/4" DIA. BOLTS & (2)

1/2" DIA. THREADED

ANCHORS w/ HILTI HY270

ADHESIVE

STEEL BEAM

PER PLAN

STEEL BEAM

PER PLAN

3/4" THK. PLATE

w/ (4) 1/2" DIA. x

1'-0" LONG

J-BOLT

3/16

3/16

GUTTER

HANGER

PER GUTTER

SUPPLIER

S5.0

S5.0

STEEL BEAM PER PLAN

DOUBLE CLIP ANGLE

PER SCHEDULE

STEEL BEAM PER PLAN

S5.0

3/16

CONTRACTOR TO

ULTRASONICALLY TEST

WELD CONNECTION

DATE: 4/19/24

DRAWING NO:

JOB NO. 21178

SEAL:

DRAWN BY: EC,VDV

CHECKED BY:HR

REVISION:

PR

OJ

EC

T:

Pa lm ito R an ch

B at tle fie ld S ta te

H is to ric

S ite

400 Nolana, Suite H2

FAX: (956) 687-3211

www.chaninengineering.com

TBPE FIRM REG. NUMBER F-9369

PH: (956) 687-9421

McAllen, Texas 78504

Vi ew in g

Pl at fo rm

Br ow ns vi lle , T ex as

S4.1

AutoCAD SHX Text

HECTOR RAMIREZ

AutoCAD SHX Text F

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text P

AutoCAD SHX Text O

AutoCAD SHX Text S

AutoCAD SHX Text 103720

AutoCAD SHX Text G

AutoCAD SHX Text O

AutoCAD SHX Text I

AutoCAD SHX Text E

AutoCAD SHX Text L

AutoCAD SHX Text N

AutoCAD SHX Text A

AutoCAD SHX Text E

AutoCAD SHX Text C

AutoCAD SHX Text I

AutoCAD SHX Text L

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text N

AutoCAD SHX Text N

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text I

AutoCAD SHX Text N

AutoCAD SHX Text X

AutoCAD SHX Text O

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text F

AutoCAD SHX Text A

2EAST ELEVATION 10 WEST ELEVATION

STEEL BEAM TO STEEL BEAM 18

STEEL BEAM TO CONCRETE COLUMN

GUARDRAIL ELEVATION

IZENE RAIL INSTALLATION DETAIL ENLARGED DOWNSPOUT DETAIL

T.O.BRG. = 25'-0"

T.O.BRG. = 17'-0"

T.O.BRG. = 25'-0"

T.O.BRG.