The hi-low inspection booth is used to conduct primary inspections of vehicles in the Primary Inspection Area of the Port. The split level inspection booth is a pre-fabricated metal enclosure on a concrete platform with a wide-angle view and bullet resistant enclosure, typically located under the primary inspection canopy. Booth exterior walls and glazing shall be constructed to meet or exceed UL-752-95 Level 3 for bullet resistance and ASTM F1233 Class 3 Level lll for forced entry resistance. This booth type is able to service noncommercial vehicles in the at-grade portion of the booth and commercial traffic in the upper level of the booth. Northern Border: May be attached to Main Building . Standard details for the booth can be found in Appendix C. One per input (This also implies that one LPR and one truck/bus RPM will be added per lane).

2.2 PRIMARY INSPECTION - BOOTHS & CANOPIES

Sprinkler Head Type:

N/A

Door Type: SL-01 Sliding (integral with Inspection Booth)

Door Frame: HM-5 HM as included with pre-fabricated building

Exterior Windows:

Exterior Window / Door Glazing:

GL-03 Bullet Resistant Glazing, UL–752-95 Level 3 & ASTM F1233 Class 3 Level lll

Special Requirements:

C-1 Lockset and BMAS for rear door. See Appendix for prefabricated booth requirements.

Fire Special Requirements:

Portable fire extinguisher installed in accordance with the requirements in the ICC-IFC.

Fixtures and Fittings 1:

NA

Fixtures and Fittings 2:

Fixtures and FIttings 3:

Fixtures and Fittings 4:

Fixtures and Fittings 5:

Fixtures and Fittings 6:

Fixtures and Fittings 7:

Plumbing Special

Acoustic Separation:

N/A

Floor Finish: FF-14 Rubber Mat

Base: N/A

Wall Construction:

Wall-13 Insulated metal panels with steel roll frames, Level 3 bullet resistant

Wall Finish: WF-11 Prefinished Metal Panels

Ceiling Remark:

Ceiling Const. / Finish:

CF-11 Prefinished Metal Panels

Ceiling Height: 9'-0" Min

Alternate Construction:

Ceiling 5/8" gyp board

Const Special Requirements:

Slope floor of booth 1/8”/1’-0" to door. See Appendix for specific security requirements.

Supply Register: S-2: Square Ceiling Diffuser Return Register: RR-2: Return Grille Temp Summer 85° (max) Temp Winter 55° (min) Temp Control: Room: Dedicated Room Temperature control Humidity Range: N/A Special Security:

Mech Special Requirements:

Locate air intake above canopy. Ruggedized thermostat: temp only control. NB: Provide radiant floor heating, over door unit & heated floor mat.

Fixed Equipment 1:

Fixed Equipment 2:

Receptacles: R-6: Receptacle, Standard GFCI

Electrical Special

(4) duplex GFCI receptacles per position (hi and low) Provide local UPS plugin module for computer.

Lighting Fixture: L-1: Lighting Fixture, Direct/Indirect, Recessed 2x2 or 2x4, 80+ CRI Lamp

Fixture Types Optional/Special:

L-15: Lighting Fixture, Surface Mounted Task Light

Lighting Control: LC-5: Combination Wall Switch with Occupancy Sensor & Dimmer

Lighting Special Provide 50 FC at working surface. Task light shall have three settings: white/red/off.

DIV 08 - DOORS AND WINDOWS Chapter 14

ROOM OCCUPANCY

1 or 2 Officers

ROOM SIZE:

131 SF

DIV 22 - PLUMBING Chapter 17

DIV 23 - MECHANICAL Chapter 18DIV 09 - CONSTRUCTION AND FINISHES Chapter 14

DIV 10 - FIXED EQUIPMENT Chapter 14

DIV 27 - LIGHTING

DIV 26 - ELECTRICAL

Door Lockset Group:

F Deadbolt / Deadlatch

Door Hardware Cylinder:

A-1: Cylinder, keyed individually under a CBP Master

Door Hardware Group:

W Full weatherstriping

Interior Window: N/A

Other Electrical Receptacles:

Cruise

Express

Cargo

Airport

LPOE

Fixed Equipment 3:

40" high X 30" deep stainless steel counter with 2 grommet holes at high and low position

Mail

Office

Room Code:

PRI-010

Chapter 19

Chapter 19

DIV 21 - FIRE SUPPRESSION Chapter 16

[Booth #]

ROOM SIGN 10/2/2014

12:14 PM

High-Low Inspection Booth

ROOM FUNCTION

COMMON DESIGN STANDARD ROOM DATA SHEETS

WARNING: This document is FOR OFFICIAL USE ONLY (FOUO). It contains information that may be exempt from public release under the Freedom of Information Act (5 U.S.C.522). It is to be controlled, stored, handled, transmitted, distributed, and disposed of in accordance with DHS policy relating to FOUO information and is not to be released to the public or other personnel who do not have a valid “need-to-know” without prior approval of an authorized DHS official.

22 - 169

For Official Use Only

Security Special Requirements:

Number and location of cameras to be determined by CBP. Cameras and microphones shall capture full interaction of Officer and Driver.

CBP Equipment

Computer(s), RFID card reader, Telephone

CBP Equipment

OBIM equipment, document reader, black light, and fingerprint/biometric systems

CBP Equipment

POV and Cargo technology equipment

Phone Outlets: Phone 02: Double RJ-11 phone port

Data Outlets: Data 03: Quad data port

Communications Special

Intercom system required. Double phone port and quad data port per position (hi and low)

CCTV Camera: Fixed CCTV wide-angle lens camera and microphone, monitored/recorded at the CCC.

IDS: IDS included if Booth is part of building perimeter

Access Control: N/A

Duress System Duress button on Booth interior and exterior

Mech: No through-the-wall units. Roof-mounted package direct expansion (DX) or split system heat pump incorporated with booth (allow efficient switch-out if equipment fails). Provide Air blowers (cont 200 CFM) outside the booth to provide untreated positive air pressure to mitigate pathogen transmission.

Electrical: Locate Controls for lane equipment, canopy lighting and traffic control devices within Booth. Provide two 240/120V, single phase, 100A, and 24 pole panelboards with main circuit breaker. One panel board shall be located inside and one outside the Booth in a NEMA-3R box.

Protection: Provide bollards at each exposed corner of booth. Provide a 3’ high concrete vehicle barrier at the front of the booth. Provide 1 bollard to the side of the sliding door. Electrical: Controls for lane equipment.

Provide one (min) spare 2" conduit to booth for each type of conduit required.

Provide Mechoshade or similar for shading.

DIV 10 - CBP PROVIDED EQUIPMENT Chapter 14

OTHER REQUIREMENTS DIV 28 - SECURITY Chapter 21

DIV 27 - COMMUNICATIONS Chapter 20

SCHEMATIC PLAN High-Low Inspection Booth PRI-010

COMMON DESIGN STANDARD ROOM DATA SHEETS

WARNING: This document is FOR OFFICIAL USE ONLY (FOUO). It contains information that may be exempt from public release under the Freedom of Information Act (5 U.S.C.522). It is to be controlled, stored, handled, transmitted, distributed, and disposed of in accordance with DHS policy relating to FOUO information and is not to be released to the public or other personnel who do not have a valid “need-to-know” without prior approval of an authorized DHS official.