APPENDIX B: GOVERNMENT ELECTRICAL AND ENVIRONMENTAL REQUIREMENTS
2020 Census – Area Census Office (ACO)
NETWORK ELECTRICAL REQUIREMENTS
Network Equipment Volts Amps Watts BTUs Quantity Total Amps Total BTUs
Edge Router 120 4.0 480 1638 2 4.0 1,638
UPS 120 12.5 1499 5111 1
12.5 5111 ACO LAN Switch 120 3.8 450 1,536 2 7.5 3,072
NETWORK EQUIPMENT SUBTOTAL: 24 9821
Analog Telephone Adapter 120 0.5 60 205 2 1.0 410 Security IDS Panel (Lessor Provided)
120 1.2 144 492 1 1.2 492
TOTAL: 26.2 10723
NETWORK EQUIPMENT ENVIRONMENTAL REQUIREMENTS
Temperature - 50 - 95 degrees F (10 - 35 degrees C); Temperature Gradient 4 degrees C hour; Relative Humidity 20% to 80% (non-condensing). A minimum 75 CFM air circulation is required.
2020 ACO - OFFICE EQUIPMENT
Equipment Volts Amps Watts BTUs Quantity Total Amps Total BTUs
PC & Monitor 120 5.4 325 1109 51 275 56,559 B&W Multi-Function Printer
(MFP)
120 10 1200 3750 4 40 15,000
Fax 120 4.0 480 1639 1 4 1,639
HSPD-12 Badge Printer 120 4.0 480 1639 1-2 8 3,278
ACO SPACE - SUBTOTAL: 327 76,476
GRAND TOTAL: 353.2 87199
CIRCUIT / RECEPTACLE REQUIREMENTS
Network Equipment
One (1) dedicated 120 volt, 30-amp circuit to L5-30R receptacle.
One (1) dedicated 120 volt 20-amp circuit to one NEMA 5-20R receptacle.
NOTE: The router and switch will plug into the UPS. Also include two (2) convenience outlets.
Security IDS Panel (Lessor Provided)
One (1) dedicated 120 volt, 20-amp circuit to one (1) Quad NEMA 5-20R receptacle.
HSPD-12 Badge Printer One (1) dedicated 120 volt, 20 amp circuit to one (1) NEMA 5-20R receptacle.
Copier (B/W) One (1) dedicated 120 volt, 20 amp circuit to one (1) NEMA 5-20R receptacle.
PCs & Monitors One (1) 120 volt, 20 amp circuit to no more than three (3) NEMA 5-20R receptacles for three (3) PCs & Monitors
B&W Multi-Function Printer
(MFP)
A minimum of one (1) dedicated 120 volt, 20-amp circuit to support each of the multi-function printers that have print copy and fax capability.
Convenience Outlets Install in accordance with provided plan. These shall not be included in count of outlets dedicated to PCs.