Edinburg_Aquatics_Blueprints_PDF_(1).pdf
PDF 3 MB Posted
- Attached to
- Fountain Pool Pump House Renovation
- Solicitation number
- 2026-06
- Issued by
- Hidalgo County, Texas
About this file
This is a set of architectural blueprints for the Fountain Pool Pump House renovation project located at 1227 E McIntyre Street, Edinburg, Texas 78541, prepared by Christopher Builder & Designer. The project encompasses a one-story structure with a total building area of 3,440 square feet, including a new addition of 2,672 square feet and a covered patio of 186 square feet. The structure will be constructed on Lot 28 with front, side, and rear setbacks of 20 feet, 5 feet, and 10 feet respectively. Construction is classified as occupancy type R2 and will include exterior elements such as stucco and tile finish with composition shingle roofing at a 5:12 pitch. The existing structure currently has electrical and plumbing systems, with the renovation requiring new roofing, expansion of the structure, and some demolition work. Interested parties should contact Nicholus Villarreal, Aquatics Manager, at 956-607-2828 or nicvillarreal@cityofedinburg.com to schedule an on-site meeting.
The blueprints specify construction details including a concrete slab-on-grade foundation reinforced with #3 rebar at 12-inch spacing, exterior beams measuring 36 inches deep, and interior beams measuring 24 inches deep. The design incorporates 2-inch by 4-inch wood studs for exterior and interior walls with 2-inch by 6-inch wood rafters for the roof. All work must comply with the 2018 International Building Code, 2017 National Electrical Code, and related codes adopted by the City of Pharr. The plans include comprehensive electrical, mechanical, and plumbing details, with electrical elements including 10 GFCI receptacles, 2 three-way switches, 4 fluorescent grow lights, 2 electrical panels, and 1 electric meter. All contractors must verify dimensions and field conditions prior to commencing work, coordinate with utility companies regarding existing underground utilities, obtain necessary permits and inspections, and ensure compliance with all applicable local building codes and regulations. The designer assumes no liability for structures constructed from these plans, placing responsibility on the purchaser and contractor to verify all specifications and site conditions before construction.
View the file
Other files
Show all 35
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CHRISTOPHER BUILDER & DESIGNER ASSUMES NO LIABILITY FOR ANY STRUCTURE CONSTRUCTED FROM THIS PLAN. IT IS THE RESPONSIBILITY OF THE PURCHASER OF THIS PLAN, TO PERFORM THE FOLLOWING, BEFORE ACTUAL CONSTRUCTION COMMENCES. 1. BUILDER OR CONTRACTOR MUST VERIFY ALL DIMENSIONS PRIOR TO PROCEEDING WITH CONSTRUCTION. 2. BUILDER OR CONTRACTOR MUST VERIFY AND COMPLY WITH ALL LOCAL BUILDING CODES OF THE AREA WHERE THE STRUCTURE IS TO BE CONSTRUCTED AND LOCATED.3. PLANS INDICATE LOCATIONS ONLY. ENGINEER ASPECTS SHOULD BE INCORPORATED TO ACTUAL SITE CONDITIONS.
S H E E T
S C A
LE
D A T E
/5 /2
A -3
A R
E A
T A
B U
LA
TI
O N
1, 8.
T O
T A
L A
R E
A 2, 2.
0'
N E
W A
D D
IT
IO
N
6.
0'
C O
V E
R E
D P
A
TI
O
D R
A W
IN
G
S P
R O
V
ID
E D
B Y
B
U
IL
D E
R
C hr is to ph er
B ui ld nD es ig n@ gm ai l.c om Te le ph on e:
.9
.7
B A
Y
8.
0'
EDINBURG AQUATICS
1227 E MCINTYRE ST, EDINBURG, TX, 78541
CONSTRUCTION ANALYSIS
CONSTRUCTION TYPE
NUMBER OF LEVELS
ONE STORY APARTMENT
FRAME TYPE (EXT. WALLS)
FRAME TYPE (INT. WALLS)
FRAME TYPE (ROOF)
2" X 4" WOOD STUDS
2" X 4" WOOD STUDS
2" X 6" WOOD RAFTERS
EXTERIOR FINISH
FOUNDATION TYPE
ROOF TYPE
STUCCO & TILE
SLAB ON GRADE
COMPOSITION SHINGLES
ROOF PITCH
PLATE HEIGHT (MIN.)
5:12
9'-0"
PLATE HEIGHT (MAX.) 9'-0"
INDEX OF DRAWINGS
DIMENSION PLAN
MECHANICAL PLAN
RCP- ELECTRICAL PLAN
FOUNDATION PLAN
FRAMING PLAN
COVER SHEET
A-4
A-6
A-7
A-5
A-3
A-8
EXTERIOR ELEVATION
A-9
SITE PLAN
A-10
INTERIOR ELEVATIONS
A-13
A-11
DOORS & WINDOWS
A-12
A-14
ROOF PLAN
PLUMBING & FIREWALL PLAN
PROJECT NOTES
1. THE CONTRACTOR SHALL VERIFY THE LOCATION OF ALL
EXISTING UTILITIES BELOW GRADE AND RELATED SERVICE
CONNECTIONS WITH THE RESPECTIVE UTILITY COMPANIES.
PRIOR TO ANY TRENCHING.
2. CONTRACTOR SHALL VERIFY AND COORDINATE ALL NEW AND
EXISTING CONDITIONS AND DIMENSIONS AT JOB SITE FOR
COMPARISON WITH DRAWINGS AND SPECIFICATIONS PRIOR TO
BIDDING AND START OF AND DURING CONSTRUCTION. IF ANY
DISCREPANCIES, INCONSISTENCIES OR OMISSIONS ARE FOUND,
THE DESIGNER SHALL BE NOTIFIED, IN WRITING FOR
CLARIFICATION PRIOR TO PROCEEDING WITH WORK.
3. DO NOT SCALE DRAWINGS. CONTRACTOR SHALL RELY ON
WRITTEN DIMENSIONS AS GIVEN. THE CONTRACTOR SHALL
NOTIFY THE DESIGNER FOR CLARIFICATIONS. ALL DIMENSIONS
SHALL BE FIELD VERIFIED BY CONTRACTOR AND COORDINATED
WITH ALL OF THE WORK OF ALL TRADES. IF DISCREPANCIES ARE
FOUND, THE CONTRACTOR SHALL NOTIFY THE DESIGNER IN
WRITING FOR CLARIFICATION BEFORE THE COMMENCEMENT OR
RESUMPTION OF WORK.
4. IN THE CASE OF A CONFLICT BETWEEN THE DRAWINGS AND THE
SPECIFICATIONS, SPECIFICATIONS SHALL TAKE PRECEDENCE.
CONTRACTOR SHALL NOTIFY THE CONSTRUCTION MANAGER OF
ANY CONFLICT BEFORE PROCEEDING WITH THE WORK.
5. THE CONTRACTOR SHALL FURNISH ALL MATERIALS, LABOR,
EQUIPMENT, TRANSPORTATION AND SERVICES NECESSARY FOR
THE SATISFACTORY COMPLETION OF WORK UNLESS
DESIGNATED (N.I.C.) OR (O.F.O.I.). ALL EQUIPMENT, WORK AND
MATERIALS SHALL COMPLY WITH ALL CURRENT AND LOCAL
APPLICABLE CODES AND GOVERNING REGULATIONS, AND THE
CONTRACT DOCUMENTS.
6. CITY OF PHARR DEVELOPMENT AND MAINTENANCE CODES
ADOPTED ARE AS FOLLOW;
2018 INTERNATIONAL BUILDING CODE, EXCLUDING E,L,M
2018 INTERNATIONAL ENERGY CONSERVATION CODE, EXCLUDING
APPENDICES RA AND RB
2017 NATIONAL ELECTRICAL CODE
2018 INTERNATIONAL RESIDENTIAL CODE, EXCLUDING L AND I
2018 INTERNATIONAL PLUMBING CODE, EXCLUDING A
2018 INTERNATIONAL SWIMMING POOL AND SPA CODE
2018 INTERNATIONAL FUEL GAS CODE
2018 INTERNATIONAL EXISTING BUILDING CODE
2018 INTERNATIONAL PROPERTY MAINTENANCE CODE
2018 INTERNATIONAL FIRE CODE
7. THE CONTRACTOR SHALL PROVIDE ALL NECESSARY PERMITS
AND INSPECTIONS.
8. THE CONTRACTOR SHALL PERFORM ALL WORK WITHIN PUBLIC
RIGHTS-OF-WAY ACCORDING TO THE CITY'S STANDARD PLANS
AND SPECIFICATIONS. CONTRACTOR SHALL OBTAIN PERMITS
FROM APPROPRIATE AGENCIES.
9. THE CONTRACTOR SHALL COORDINATE WITH REPRESENTATIVES
OF WATER, ELECTRICAL, GAS TELEPHONE AND TELEVISION
COMPANIES TO VERIFY AVAILABLE FACILITIES AND, IF
APPLICABLE, TO ESTABLISH TEMPORARY FACILITIES.
10. OCCUPANCY CLASSIFICATION - R2
CHRISTOPHER BUILDER & DESIGNER ASSUMES NO LIABILITY FOR ANY STRUCTURE CONSTRUCTED FROM THIS PLAN. IT IS THE RESPONSIBILITY OF THE PURCHASER OF THIS PLAN, TO PERFORM THE FOLLOWING, BEFORE ACTUAL CONSTRUCTION COMMENCES. 1. BUILDER OR CONTRACTOR MUST VERIFY ALL DIMENSIONS PRIOR TO PROCEEDING WITH CONSTRUCTION. 2. BUILDER OR CONTRACTOR MUST VERIFY AND COMPLY WITH ALL LOCAL BUILDING CODES OF THE AREA WHERE THE STRUCTURE IS TO BE CONSTRUCTED AND LOCATED.3. PLANS INDICATE LOCATIONS ONLY. ENGINEER ASPECTS SHOULD BE INCORPORATED TO ACTUAL SITE CONDITIONS.
S H E E T
S C A
LE
D A T E
/5 /2
A -4
A R
E A
T A
B U
LA
TI
O N
1, 8.
T O
T A
L A
R E
A 2, 2.
0'
N E
W A
D D
IT
IO
N
6.
0'
C O
V E
R E
D P
A
TI
O
D R
A W
IN
G
S P
R O
V
ID
E D
B Y
B
U
IL
D E
R
Te le ph on e:
.9
.7
B A
Y
8.
0'
SITE PLAN NOTES:
1. CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS &
CONDITIONS PRIOR TO COMMENCING ANY WORK.
2. FINAL SITE GRADING TO SLOPE AWAY FROM THE
STRUCTURE AND SHALL PREVENT WATER FROM
PONDING IN THE AREAS ADJACENT TO THE STRUCTURE.
3. CONSTRUCTION AREAS REMOVE ALL VEGETATION,
TOPSOIL, ROOTS AND OTHER DELETERIOUS MATERIALS
TYPICALLY 6 TO 12 INCHES IN DEPTH, SHALL BE
REMOVED TO DISTANCE OF 5'-0" OUTSIDE FROM THE
PROPOSED BUILDING LINE.
4. THERE SHALL BE 6" DROP FROM THE SLAB FINISH
FLOOR ELEVATION TO FINISH GRADE. THEN A 5% SLOPE
FOR THE FIRST 10' AND A 1% SLOPE TO THE STREET OR
REAR YARD.
5. LANDSCAPE SHOWN IS ONLY FOR ILLUSTRATION
PURPOSES. CONTRACTORS OPTION TO PROVIDE
LANDSCAPE.
6. DRIVEWAYS SHALL BE 4" THICK FOR SINGLE FAMILY USE
AND 6" THICK FOR ALL OTHERS (I.E. COMMERCIAL
INDUSTRIAL, ETC.)
7. DRIVEWAYS AND SIDEWALKS SHALL BE CONSTRUCTED
WITH PORTLAND CEMENT CONCRETE AND INCLUDE
5-1/2" SACKS OF CEMENT PER CUBIC YARD OF
CONCRETE.
8. 6x6-W 2.9 WELDED WIRE FABRIC MAY BE USED IN LIEU
OF THE REINFORCING STEEL.
9. OWNER, BUILDER, AND SURVEYOR TO APPROVE
LOCATION OF HOUSE ON LOT, AND TO VERIFY ALL
EASEMENTS AND BUILDING LINES PRIOR TO
COMMENCING ANY CONSTRUCTION. DESIGNER SHALL
BE NOTIFIED OF ANY DEVIATION FROM THIS SITE PLAN
10. DRAINAGE DESIGN IS BEYOND THE SCOPE OF THIS
DESIGN. GREAT CARE SHOULD BE TAKEN IN
EVALUATING THE DRAINAGE REQUIREMENTS.
SITE PLAN
LOT 28 SETBACKS
FRONT: 20'
SIDE: 5"
REAR: 10'
SQUARE FOOTAGE
BUILDING: 3,440.0'
SIDE WALK: 462.0'
PARKING: 2,160.0'
LANDSCAPING: 3,298'
CMU BLOCK FOUNDATION DIAGRAM
E1 A-5 E1 A-5
E3 A-5 E3 A-5
46'
13'12'21'
46'
21' 12' 13'
3'
EXISTING MAN HOLE
1 FOUNDATION PLAN
1/4 IN = 1 FT1 FOUNDATION PLAN
1/4 IN = 1 FT
4" 6"
1'
4" 6"
4" 6"
1'
2' 1'
-6
2'
1/
2"
4" 6"
1'
2'
4" 6"
1'
4" 6"
4" 6"
1'
2' 1'
-6
2'
4" 6"
1'
2'
3 1/2"
1/
2"
1/
2"
2"
4" CONCRETE SLAB
REINFORCED W/ #3
BARS AT 12" O.C. TYP.
COMPACTED
FILL DIRT
6 MIL POLY
VAPOR BARRIER
(2) #5 BARS TOP
& BOTTOM
EXTERIOR BEAM
SCALE: 1/2" = 1'-0"
#3 STIRRUPS
@ 24" O.C.
4" CONCRETE SLAB
REINFORCED W/ #3
BARS AT 12" O.C. TYP.
COMPACTED
FILL DIRT
6 MIL POLY
VAPOR BARRIER
(2) #5 BARS TOP
& BOTTOM
INTERIOR BEAM
SCALE: 1/2" = 1'-0"
#3 STIRRUPS
@ 24" O.C.
4" CONCRETE SLAB
REINFORCED W/ #3
BARS AT 12" O.C. TYP.
COMPACTED
FILL DIRT
6 MIL POLY
VAPOR BARRIER
(2) #5 BARS TOP
& BOTTOM
ELEVATION TRANSITION BEAM
SCALE: 1/2" = 1'-0"
#3 STIRRUPS
@ 24" O.C.
MIN. 1/8" SLP.
PER FT.
4" CONCRETE SLAB
REINFORCED W/ #3
BARS AT 12" O.C. TYP.
COMPACTED
FILL DIRT
6 MIL POLY
VAPOR BARRIER
(2) #5 BARS TOP
& BOTTOM
EXT. PORCH & PATIO BEAM
SCALE: 1/2" = 1'-0"
#3 STIRRUPS
@ 24" O.C.
MIN. 1/8" SLP.
PER FT.
4" CONCRETE SLAB
REINFORCED W/ #3
BARS AT 12" O.C. TYP.
COMPACTED
FILL DIRT
6 MIL POLY
VAPOR BARRIER
(2) #5 BARS TOP
& BOTTOM
EXT. CARPORT BEAM
SCALE: 1/2" = 1'-0"
#3 STIRRUPS
@ 24" O.C.
4" CONCRETE SLAB
REINFORCED W/ #3
BARS AT 12" O.C. TYP.
COMPACTED
FILL DIRT
6 MIL POLY
VAPOR BARRIER
(2) #5 BARS TOP
& BOTTOM
INT. SLOPE BEAM
SCALE: 1/2" = 1'-0"
#3 STIRRUPS
@ 24" O.C.
4" CONCRETE SLAB
REINFORCED W/ #3
BARS AT 12" O.C. TYP.
COMPACTED
FILL DIRT
6 MIL POLY
VAPOR BARRIER
(2) #5 BARS TOP
& BOTTOM
GARAGE DOOR OPENING BEAM
SCALE: 1/2" = 1'-0"
#3 STIRRUPS
@ 24" O.C.
MIN. 1/8" SLP.
PER FT.
4" CONCRETE SLAB
REINFORCED W/ #3
BARS AT 12" O.C. TYP.
COMPACTED
FILL DIRT
6 MIL POLY
VAPOR BARRIER
(2) #5 BARS TOP
& BOTTOM
EXTERIOR BEAM W LEDGE
SCALE: 1/2" = 1'-0"
#3 STIRRUPS
@ 24" O.C.
MIN. 1/8" SLP.
PER FT.
GARAGE TIRE STOP
SCALE: 1/2" = 1'-0"
D. 2" 3" 4" 5" 6" E. 2'-0" 3'-0" 3'-6" 4'-0" 4'-6"
NOTE: WIDTH: 12" DEPTH: 24"
FOUNDATION FOOTING DETAILS
NOTES:
1. 4" CONCRETE SLAB @ 3,000 PSI W/ #3 REBAR 12" O.C.
2. 36" DEEP EXTERIOR & 24" DEEP INTERIOR BEAMS.
3. CONCRETE SLUMP PER NOTES
24 INCH EXT. FOOTINGS
18 INCH INT. FOOTINGS
4" CONCRETE SLAB ON
6 MIL POLY W/ #3 REBAR
@ 12" O.C. BOTH WAYS
ON COMPACT SELECT FILL
CHRISTOPHER BUILDER & DESIGNER ASSUMES NO LIABILITY FOR ANY STRUCTURE CONSTRUCTED FROM THIS PLAN. IT IS THE RESPONSIBILITY OF THE PURCHASER OF THIS PLAN, TO PERFORM THE FOLLOWING, BEFORE ACTUAL CONSTRUCTION COMMENCES. 1. BUILDER OR CONTRACTOR MUST VERIFY ALL DIMENSIONS PRIOR TO PROCEEDING WITH CONSTRUCTION. 2. BUILDER OR CONTRACTOR MUST VERIFY AND COMPLY WITH ALL LOCAL BUILDING CODES OF THE AREA WHERE THE STRUCTURE IS TO BE CONSTRUCTED AND LOCATED.3. PLANS INDICATE LOCATIONS ONLY. ENGINEER ASPECTS SHOULD BE INCORPORATED TO ACTUAL SITE CONDITIONS.
S H E E T
S C A
LE
D A T E
/5 /2
A -5
A R
E A
T A
B U
LA
TI
O N
1, 8.
T O
T A
L A
R E
A 2, 2.
0'
N E
W A
D D
IT
IO
N
6.
0'
C O
V E
R E
D P
A
TI
O
D R
A W
IN
G
S P
R O
V
ID
E D
B Y
B
U
IL
D E
R
Te le ph on e:
.9
.7
B A
Y
8.
0'
FOUNDATION NOTES
1 ALL CONCRETE WORK SHALL CONFORM TO THE AMERICAN CONCRETE
INSTITUTE SPECIFICATION, A.C.I. #301 AND BUILDING CODE
REQUIREMENTS. A.C.I. #318, LATEST EDITION.
2 ALL DETAILING, FABRICATION AND ERECTION OF REINFORCING BARS,
UNLESS OTHERWISE NOTED MUST FOLLOW THE A.C.I. MANUAL OF
STANDARD PRACTICE FOR DETAILING REINFORCED CONCRETE, A.C.I.
#315 LATEST EDITION.
3 CONCRETE SHALL HAVE A MINIMUM COMPRESSION STRENGTH AT 28
DAYS AS FOLLOWS:
* 3000 PSI FOR ALL CONCRETE FOUNDATION COMPONENTS A
MAXIMUM OF 25% FLASH MAY BE USED AS A CEMENT
SUBSTITUTE AND SHALL CONFORM TO ASTM C618. THE WATER/
CEMENT RATIO SHALL NOT EXCEED 0.58 AND SLUMPS SHALL BE BETWEEN
4 AND 5 INCHES. COORDINATE WITH OWNERS TESTING LABORATORY (IF
ONE SELECTED) TO PROVIDE TESTING AS PER A.C.I.
4 REINFORCING BARS SHALL BE NEW BILLET STEEL CONFORMING TO
ASTM A-615, GRADE 60.
5 STANDARD PROTECTIVE COVER OF REINFORCING BARS UNLESS
OTHERWISE NOTED SHALL BE USED:
* WHERE CAST AGAINST DIRT OR FILL..... 3 IN.
* EXPOSED TO EARTH OR WEATHER....... 2 IN.
* COLUMNS.................................................... 1 1/2 IN.
* SLABS AND WALLS.................................... 1 IN.
* OTHER......................................................... 1 1/2 IN.
6 ALL ACCESSORIES SHALL BE IN ACCORDANCE WITH THE A.C.I.
"MANUAL OF STANDARD PRACTICE FOR DETAILING REINFORCED
CONCRETE", A.C.I. #315 LATEST EDITION. ACCESSORIES FOR EXPOSED
CONCRETE SHALL PLASTIC COATED FEET.
7 VERTICAL CONSTRUCTION JOINTS IN FLOOR OR ROOF SLABS ARE TO
BE AS SHOWN ON PLANS. NO HORIZONTAL JOINTS WILL BE PERMITTED
ON SLABS OR BEAMS UNLESS OTHERWISE NOTED.
8 MAINTAIN A MINIMUM OF ONE BAR DIAMETER (BUT NOT LESS THAN 1"
BETWEEN ALL REINFORCING BARS (INCLUDING LAPS) ON ALL SLABS.
MAINTAIN A MINIMUM 1 1/2" TIMES THE MAXIMUM COARSE AGGREGATE
SIZE IN ALL CASES.
9 BARS SCHEDULED OR DETAILED "CONT." SHALL BE LAPPED 24 BAR
DIAMETERS UNLESS OTHERWISE NOTED.
10 ALLOW FOR THE EQUIVALENT OF 5% OF REINFORCING FOR #4 BARS
TO BE USED AS REQUIRED IN THE FIELD FOR SPECIAL CONDITIONS
(LABOR FOR PLACING SAME TO BE INCLUDED).
11 AT CORNERS AND "I" INTERSECTIONS OF ALL FOUNDATIONS BEAMS.
EXTEND 4 CORNER BARS EQUAL TO THE DETAILED STEEL IN THE
ADJACENT BEAMS 2'-0" EACH WAY, 2 BARS TOP AND 2 BARS BOTTOM.
12 REMOVE AT LEAST 6 INCHES OF TOP SOIL, VEGETATION, DEBRIS, ETC.
FROM THE PROPOSED BUILDING AREA TO A DISTANCE OF 5'-0"
OUTSIDE THE BUILDING LINE.
13 REWORK AND COMPACT THE TOP 6" OF THE EXPOSED SUBGRADE
UNDER ALL FLOORS AND WALKS TO A 95% (+5%) OF THE MAXIMUM
DENSITY AT -2% TO +3% OF THE OPTIMUM MOISTURE CONTENT IN
ACCORDANCE WITH THE TEST METHOD ASTM D-698 PRIOR TO
PLACEMENT OF SELECT FILL.
14 FILL BACK THE REQUIRED GARDE (A MINIMUM OF 12" ABOVE EXISTING
GRADE) WITH MATERIAL SELECTED AND COMPACTED IN ACCORDANCE
WITH THE REQUIREMENT BELOW.
15 SELECT FILL WHEN PROPERLY SLAKED AND TESTED BY STANDARD
LABORATORY METHODS SHALL MEET THE FOLLOWING
REQUIREMENTS:
A. LIQUID LIMIT SHALL BE LESS THAN OR EQUAL TO 37.
B. PLASTICITY INDEX SHALL BE LESS THAN 17 AND GREATER THAN 5.
C. SHALL CONTAIN NO ORGANIC MATERIAL.
D. SHALL CONTAIN NO STONES LARGER THAN 2 IN.
16 SAMPLES OF PROPOSED SELECT FILL SHALL BE FINISHED TO THE
TESTING LABORATORY 7 DAYS PRIOR TO INSTALLATION TO PERMIT
TIME FOR SPECIFICATION COMPLIANCE INSPECTION AND APPROVAL.
17 SELECT FILL UNDER ALL FLOORS AND WALKS SHALL BE COMPACTED
IN THE FIELD IN LIFTS NOT TO 8" TO 95%(+5%) OF THE MAXIMUM
DENSITY AT -2% TO +35 OF THE OPTIMUM MOISTURE CONTENT AS
DETERMINED BY TEXAS HIGHWAY DEPARTMENT SOIL TESTING
PROCEDURE TEX-1 13-E (COMPACTED EFFORT 6.63 FT. -LC./CU. IN.)
FIELD DENSITIES SHALL BE CHECKED IN ACCORDANCE WITH TEX-1 13-
E.
18 CONCRETE PLACED BY PLUMBING SHALL MEET THE FOLLOWING
REQUIREMENTS:
A COARSE AGGREGATE SHALL BE GRADED FROM A MAXIMUM OF 1"
DOWN.
B MAXIMUM ALLOWABLE INCREASE IN CEMENT FACTOR SHALL BE 1/2
SACK PER CUBIC YARD OVER A NORMAL MIX DESIGN.
C MAXIMUM WATER CEMENT RATIO SHALL BE 7 1/2 GALLONS PER SACK
OF CEMENT. IF MORE WORKABILITY IS REQUIRED AN ADMIXTURE MAY
BE USED.
D MAXIMUM WEIGHT RATIO OF FINE AGGREGATES TO COARSE
AGGREGATES SHALL NOT EXCEED 2/3.
E REFER TO A.C.I. #301, LATEST EDITION, SECTION 800, FOR OTHER
PUMPING REQUIREMENTS.
F IN NO CASE SHALL CONCRETE BE PUMPED THROUGH AN ALUMINUM
TUBE.
FOUNDATION PLAN
22'
46'
21'-4"
21'-4"
24'-0" X 14'-0"
341 SQ FT
644 SQ FT
FENCED AREA
LIVING AREA
1 ORGINAL PLAN
1/4 IN = 1 FT1 ORGINAL PLAN
1/4 IN = 1 FT
18" X 18"306818" X 18"306818" X 18"
18" X 18" 9080 18" X 18" 18" X 18"
X
8"
GFCI
GFCI
GFCI
GFCI GFCI
GFCI
GFCI
GFCI
GFCI
GFCI
E1 A-5 E1 A-5
ELEVATION 1
E2 A-5 E2 A-5
E3 A-5 E3 A-5
5 14
6' -3
1'
-6
6' -3
46'
3'-9" 1'-6"
17' 1'-6"
4'-3"9'3'-10" 1'-6"
3'-8"
2' -6
9'
2' -6
46'
3'-7" 1'-6" 4'-4" 3' 9'-10" 1'-6" 9'-10" 3' 4' 1'-6" 3'-11"
644 SQ FT
LIVING AREA
1 RENOVATION PLAN
1/4 IN = 1 FT1 RENOVATION PLAN
1/4 IN = 1 FT
WALL SCHEDULE
2D SYMBOL WALL TYPE
12" CONCRETE STEM WALL
8" CMU (BLOCK) STEM WALL
INTERIOR-4
CHRISTOPHER BUILDER & DESIGNER ASSUMES NO LIABILITY FOR ANY STRUCTURE CONSTRUCTED FROM THIS PLAN. IT IS THE RESPONSIBILITY OF THE PURCHASER OF THIS PLAN, TO PERFORM THE FOLLOWING, BEFORE ACTUAL CONSTRUCTION COMMENCES. 1. BUILDER OR CONTRACTOR MUST VERIFY ALL DIMENSIONS PRIOR TO PROCEEDING WITH CONSTRUCTION. 2. BUILDER OR CONTRACTOR MUST VERIFY AND COMPLY WITH ALL LOCAL BUILDING CODES OF THE AREA WHERE THE STRUCTURE IS TO BE CONSTRUCTED AND LOCATED.3. PLANS INDICATE LOCATIONS ONLY. ENGINEER ASPECTS SHOULD BE INCORPORATED TO ACTUAL SITE CONDITIONS.
S H E E T
S C A
LE
D A T E
/5 /2
A -6
A R
E A
T A
B U
LA
TI
O N
1, 8.
T O
T A
L A
R E
A 2, 2.
0'
N E
W A
D D
IT
IO
N
6.
0'
C O
V E
R E
D P
A
TI
O
D R
A W
IN
G
S P
R O
V
ID
E D
B Y
B
U
IL
D E
R
Te le ph on e:
.9
.7
B A
Y
8.
0'
DIMENSION PLAN
DIMENSION PLAN NOTES:
1. THESE PLANS MUST BE VERIFIED AND CHECKED
COMPLETELY BY BUILDER, AND DISCREPANCY, ERROR,
AND OMISSION,IF FOUND, ARE TO BE BROUGHT UP
IMMEDIATELY TO OWNER BEFORE CONSTRUCTION
WORK OR PURCHASE IS MADE.
2. FEDERAL STATE, COUNTY AND LOCAL CITY ORDINANCE
AND BUILDING CODES TAKE PRECEDENCE OVER ANY
PART OF THESE DRAWINGS. ANY CONFLICT MUST BE
ADHERED TO THE PROJECT BEFORE CONSTRUCTION.
3. GENERAL CONTRACTOR AND TRADE PARTNERS SHALL
VISIT THE SITE AND BECOME FAMILIAR WITH ALL
EXISTING CONDITIONS PRIOR TO COMMENCING WORK.
4. GENERAL CONTRACTOR AND TRADE PARTNERS WILL
ASCERTAIN THAT NO DAMAGE WILL BE CAUSED TO
EXISTING SITE IMPROVEMENTS. IF SUCH DAMAGE
OCCURS, THE RESPONSIBLE PARTY WILL HAVE TO
REPAIR SUCH DAMAGE TO THE SATISFACTION OF THE
OWNER.
5. DESIGNER NOT RESPONSIBLE FOR MATERIALS OR
WORKMANSHIP UNDER CONSTRUCTION, BUILDER TO
VERIFY ALL DIMENSIONS.
6. BUILDER SHALL CHECK ALL MEASUREMENTS AND MAKE
REQUIRED ADJUSTMENTS FOR PROPER
CONSTRUCTION.
7. ALL SPACES WITH FLOOR DRAIN- SLOPE NOT TO
EXCEED 2% (ONE-IN-FIFTY) IN ANY DIRECTION.
8. DO NOT SCALE DRAWINGS. DIMENSIONS ARE ACTUAL,
NOT NOMINAL, AS FOLLOWS:
COLUMNS- FROM CENTERLINE TO CENTERLINE
INTERIOR PARTITIONS- FROM STUD FACE TO STUD FACE
CONCRETE/ MASONRY- FROM FINISH FACE TO FINISH
FACE
EXTERIOR WALLS- FROM EXTERIOR STUD FACE TO
EXTERIOR STUD FACE.
9. ALL INTERIOR DOORS IN STUD WALL ASSEMBLES SHALL
BE SET A MINIMUM OF 4" OFF THE PERPENDICULAR
WALL ON THE HINGE SIDE OF THE DOOR U.N.O.
10. ALL MILLWORK, APPLIANCES, & EQUIPMENT SIZE TO BE
MEASURED ON SITE BEFORE ORDERING.
11. ALL FURR-OUT WALLS TO BE FRAMED WITH 2X4 STUDS,
UNLESS OTHERWISE NOTED ON PLAN.
12. ALL INTERIOR WALLS TO BE 2X4 STUDS AT 16" O.C. W/ 1-
PLY. & 1/2" GYP BOARD AT EACH SIDE UNLESS NOTED
OTHERWISE.
13. ALL PLUMBING WALLS TO BE FRAMED WITH 2X6 STUDS.
14. WINDOWS IN BATHROOMS TO HAVE OPAQUE GLASS.
15. ALL WORK SHOULD BE INSPECTED PRIOR TO COVERING
OF FINISHES.
16. ALL MATERIALS SHOULD BE NEW AND OF THE HIGHEST
QUALITY.
17. PROVIDE 1-PLY 1/2" WATER RESISTANT GYP. BOARD AT
ALL BATHROOM WALLS.
18. PROVIDE 3-1/2" BATT INSULATION AT ALL BATHROOM
WALLS.
19. ALL EXTERIOR WALLS TO BE 2X4 STUDS AT 16" O.C.
REFER TYPICAL WALL SECTION DETAIL.
20. PROVIDE EXTERIOR HOSE BIBS. REFER TO PLUMBING
PLAN FOR QUANTITY AND LOCATION.
21. PROVIDE BALL VALVE RECESSED WALL BOX W/ 3/8"
FLEX TUBING ROUTED TO REFRIGERATOR ICE MAKER
CONNECTION. PROVIDE IN-LINE FILTER.
GFCI
GFCI
GFCI
GFCI GFCI
GFCI
GFCI
GFCI
GFCI
GFCI
1 ELECTRICAL PLAN
1/4 IN = 1/2 FT1 ELECTRICAL PLAN
1/4 IN = 1/2 FT
ELECTRICAL SCHEDULE
2D SYMBOL DESCRIPTION QTY COMMENTS
3-WAY SWITCH 2
4 BULB FLUORESCENT GROW LIGHTS 4
ELECTRICAL PANEL - SURFACE MOUNTED 2
GFCI RECEPTACLE 10
ELECTRIC METER 1
TOTALS: 19
GFCI
CHRISTOPHER BUILDER & DESIGNER ASSUMES NO LIABILITY FOR ANY STRUCTURE CONSTRUCTED FROM THIS PLAN. IT IS THE RESPONSIBILITY OF THE PURCHASER OF THIS PLAN, TO PERFORM THE FOLLOWING, BEFORE ACTUAL CONSTRUCTION COMMENCES. 1. BUILDER OR CONTRACTOR MUST VERIFY ALL DIMENSIONS PRIOR TO PROCEEDING WITH CONSTRUCTION. 2. BUILDER OR CONTRACTOR MUST VERIFY AND COMPLY WITH ALL LOCAL BUILDING CODES OF THE AREA WHERE THE STRUCTURE IS TO BE CONSTRUCTED AND LOCATED.3. PLANS INDICATE LOCATIONS ONLY. ENGINEER ASPECTS SHOULD BE INCORPORATED TO ACTUAL SITE CONDITIONS.
S H E E T
S C A
LE
D A T E
/5 /2
A -7
A R
E A
T A
B U
LA
TI
O N
1, 8.
T O
T A
L A
R E
A 2, 2.
0'
N E
W A
D D
IT
IO
N
6.
0'
C O
V E
R E
D P
A
TI
O
D R
A W
IN
G
S P
R O
V
ID
E D
B Y
B
U
IL
D E
R
Te le ph on e:
.9
.7
B A
Y
8.
0'
RCP- ELECTRICAL PLAN
ELECTRICAL NOTES
1. POWER OUTLETS SET 18" ABOVE FINISHED FLOOR VERIFY
ACTUAL LAYOUT WITH BUILDER AND OWNER.
2. POWER, COMMUNICATION/DATA AND CABLE TV OUTLET
LOCATION. HEIGHT PLACEMENT TO BE VERIFIED AND
COORDINATED BY GC AND OWNER BASED ON AUDIO/VISUAL
EQUIPMENT SPECIFICATIONS.
3. POWER OUTLETS COORDINATE FINAL PLACEMENT WITH
BUILDER AND OWNER.
4. POWER OUTLETS SET AT END OF ISLAND MILLWORK. FINAL
PLACEMENT TO BE COORDINATED WITH BUILDER AND
OWNER.
5. POWER OUTLET AND RECESSED WATER/DRAIN BOX FOR
REFRIGERATOR/FREEZER. VERIFY CIRCUIT AND PLUS
CONFIGURATION REQUIREMENTS WITH BUILDER AND
OWNER BASED ON FINAL APPLICATION SELECTION.
6. POWER OUTLET FOR DISHWASHER. (NOTE: SET OUTLET AT
BACK WALL OF CABINET BOX)
7. HARDWIRE CONNECTION FOR EXHAUST HOOD. (NOTE: SET
HEIGHT MINIMUM 6'-0" A.F.F. VERIFY FINAL SELECTION WITH
BUILDER AND OWNER.
8. CEILINGS MOUNTED OUTLET FOR OVERHEAD GARAGE DOOR
OPENER. (VERIFY AND COORDINATE ACTUAL POWER
REQUIREMENTS WITH BUILDER).
9. LOCATION OF DRYER VENT WALL PENETRATION. (BUILDER
SHALL VERIFY ACTUAL ROUTING OF VENT WITH ROOF LINE).
10. 240-VOLT OUTLET FOR DRYER.
11. OUTLET AND VALVE DRAIN FOR WASHER.
12. 240-VOLT OUTLET FOR A/C UNIT.
13. 240-VOLT OUTLET FOR TANK-LESS WATER HEATER.
14. POWER OUTLET FOR WASHER AND DRYER. FINAL
PLACEMENT TO BE COORDINATED WITH BUILDER AND
OWNER.
15. SWITCH FOR ALL EXTERIOR FLOOR LIGHTS.
16. PROVIDE WEATHER PROOF RECEPTACLE OUTLETS UNDER
ROOF SOFFIT BETWEEN 8 TO 10 FOOT SEPARATION.
17. SWITCH FOR ALL EXTERIOR SOFFIT OUTLETS.
18. PROVIDE GFI ELECTRICAL OUTLET AT EVERY SINK IN ALL
BATHROOMS.
19. PROVIDE ELECTRICAL OUTLETS FOR A/C IN ROOM.
20. EXTERIOR FOG LIGHTS AND AREA LIGHT TO BE EQUIPPED W/
SENSORS AND AUTOMATIC TIMER.
21. ELECTRICAL METER TO BE LOCATED AS PER ELECTRICIAN
AND CONTRACTOR SPECIFICATIONS.
22. BREAKER PANEL TO BE LOCATED INSIDE GARAGE.
23. LOCATE OUTLET CONNECTION FOR ALARM SYSTEM UNIT, AS
PER CONTRACTOR AND INSTALLER SPECS.
24. ALL KITCHEN COUNTER OUTLETS TO 44" ABV. FFL.
25. ALL KITCHEN OUTLETS MUST BE NO MORE THAN 48" APART.
26. ALL KITCHEN COUNTER OUTLETS WITHIN 6 FEET OF A
WATER SOURCE MUST BE G.F.I. OR PER LOCAL CODES.
METAL ROOF DETAIL
1 FRAMING RAFTER PLAN
1/4 IN = 3/4 FT1 FRAMING RAFTER PLAN
1/4 IN = 3/4 FT
: 1
1 ROOF PLAN
1/4 IN = 3/4 FT1 ROOF PLAN
1/4 IN = 3/4 FT
Roof Eave Detail with Sloped Ceiling
ROOFING
ROOFING MEMBRANE
SIP ROOF
FLASHING
FASCIA
FASTEN PER
MANUFACTURER'S
SPECIFICATIONSBEVELED BLOCKING
INTERIOR FINISH
WALL SIP
WOOD TRIM
FINISH SIDING
CHRISTOPHER BUILDER & DESIGNER ASSUMES NO LIABILITY FOR ANY STRUCTURE CONSTRUCTED FROM THIS PLAN. IT IS THE RESPONSIBILITY OF THE PURCHASER OF THIS PLAN, TO PERFORM THE FOLLOWING, BEFORE ACTUAL CONSTRUCTION COMMENCES. 1. BUILDER OR CONTRACTOR MUST VERIFY ALL DIMENSIONS PRIOR TO PROCEEDING WITH CONSTRUCTION. 2. BUILDER OR CONTRACTOR MUST VERIFY AND COMPLY WITH ALL LOCAL BUILDING CODES OF THE AREA WHERE THE STRUCTURE IS TO BE CONSTRUCTED AND LOCATED.3. PLANS INDICATE LOCATIONS ONLY. ENGINEER ASPECTS SHOULD BE INCORPORATED TO ACTUAL SITE CONDITIONS.
S H E E T
S C A
LE
D A T E
/5 /2
A -8
A R
E A
T A
B U
LA
TI
O N
1, 8.
T O
T A
L A
R E
A 2, 2.
0'
N E
W A
D D
IT
IO
N
6.
0'
C O
V E
R E
D P
A
TI
O
D R
A W
IN
G
S P
R O
V
ID
E D
B Y
B
U
IL
D E
R
Te le ph on e:
.9
.7
B A
Y
8.
0'
ROOF PLAN
HIGHEST RIDGEHIGHEST RIDGE
E1 FRONT VIEW
1/4 IN = 1 FTE1 FRONT VIEW
1/4 IN = 1 FT
HIGHEST RIDGE
E2 RIGHT SIDE VIEW
1/4 IN = 3/4 FTE2 RIGHT SIDE VIEW
1/4 IN = 3/4 FT
HIGHEST RIDGEHIGHEST RIDGE
E3 REAR VIEW
1/4 IN = 1 FTE3 REAR VIEW
1/4 IN = 1 FT
HIGHEST RIDGE
E4 LEFT SIDE VIEW
1/4 IN = 3/4 FTE4 LEFT SIDE VIEW
1/4 IN = 3/4 FT
CHRISTOPHER BUILDER & DESIGNER ASSUMES NO LIABILITY FOR ANY STRUCTURE CONSTRUCTED FROM THIS PLAN. IT IS THE RESPONSIBILITY OF THE PURCHASER OF THIS PLAN, TO PERFORM THE FOLLOWING, BEFORE ACTUAL CONSTRUCTION COMMENCES. 1. BUILDER OR CONTRACTOR MUST VERIFY ALL DIMENSIONS PRIOR TO PROCEEDING WITH CONSTRUCTION. 2. BUILDER OR CONTRACTOR MUST VERIFY AND COMPLY WITH ALL LOCAL BUILDING CODES OF THE AREA WHERE THE STRUCTURE IS TO BE CONSTRUCTED AND LOCATED.3. PLANS INDICATE LOCATIONS ONLY. ENGINEER ASPECTS SHOULD BE INCORPORATED TO ACTUAL SITE CONDITIONS.
S H E E T
S C A
LE
D A T E
/5 /2
A -9
TA
B
U
LA
TI
O
N
2, 2.
0'
6.
0' C
O V
E R
E D
P A
TI
O
D R
A W
IN
G
S P
R
IL
D E
R
Te le ph on e:
ELEVATION PLAN
File details come from the government source that posted it. Updated .