ENGINEER
Basis of Design:
FAA BCT HVAC EQUIPMENT
REPLACEMENT
16-0125
Direct Digital Control (DDC) for HVAC Project:
16-0125
FAA BCT HVAC EQUIPMENT REPLACEMENT
MERRIMACK, NH
Controls Designer:
Future Controls, Inc.
5719 Zip Drive, Suite-1
Fort Myers, FL 33905
Submittal / Dated:
As-Built / Dated:
Reference only
DESIGN ONLY
TSSC 4
Drawing Index:
SYMBOL PAGE Page 1 AHU 284 - 284A FLOW DIAGRAM Page 28
REQUIREMENTS / CLARIFICATIONS Page 2 AHU 284 - 284A BILL OF MATERIAL Page 29
Minimum Graphic Properties Page 3 AHU 284 - 284A CONTROLLERS Page 30
WIRING GUIDES Page 4 AHU 284-A CONTROLLERS Page 31
COMPUTERS & SOFTWARE Page 5 SEQUENCE OF OPS - AHU 284 & 284A Page 32
NETWORK ROUTING SCHEDULE Page 6 AHU 284B FLOW DIAGRAM Page 33
NETWORK CONNECTED DEVICE SUMMARY Page 7 AHU 284-B CONTROLLERS Page 34
CONTROLLER DETAILS - CENTRAL PLANT Page 8 SEQUENCE OF OPS - AHU 284 B Page 35
CONTROLLER DETAILS - CRAC UNITS Page 9 AHU P02 FLOW DIAGRAM Page 36
CONTROLLER DETAILS - AHU PG. 2 Page 10 AHU P02 CONTROLLERS Page 37
CONTROLLER DETAILS - AHU PG. 1 Page 11 SEQUENCE OF OPS - P02 & P02A Page 38
CONTROLLER DETAILS - GENERATOR ROOM Page 12 AHU P02A FLOW DIAGRAM Page 39
CHILLED WATER - DRY COOLERS Page 13 AHU P02A CONTROLLERS Page 40
CHILLED WATER -CHILLERS Page 14 SEQUENCE OF OPS - P02A Page 41
CHILLED WATER - PUMPS Page 15 BASE-VAV CONTROLLER Page 42
CHILLED WATER SYSTEM CONTROLLERS PG.1 Page 16 BASE BUILDING VAV SCHEDULE PG. 1 Page 43
CHILLED WATER SYSTEM CONTROLLERS PG.2 Page 17 BASE BUILDING VAV SCHEDULE PG. 2 Page 44
SEQUENCE OF OPS - CHILLERS Page 18 VAV SEQUENCE OF OPERATIONS Page 45
HOT WATER SYSTEM FLOW Page 19 AHU HNV-192 FLOW DIAGRAM Page 46
HOT WATER SYSTEM CONTROLLERS Page 20 GENERATOR 2 & EF 190B Page 47
SEQUENCE OF OPS - HOT WATER SYSTEM Page 21 GENERATOR 1 & EF 190A Page 48
CRAC UNITS - OPERATIONS RM 152 Page 22 GENERATOR & HNV-192 CONTROLLERS Page 49
CRAC UNITS - OPERATIONS RM 252 Page 23 TYPICAL EXISTING PANEL RETROFIT Page 50
AHU 01 - 02 FLOW DIAGRAM Page 24 CHW and HWS - PANEL LAYOUT Page 51
AHU 01 CONTROLLERS Page 25 AHU ENERGY CONTROL VALVE SCHEDULE Page 52
AHU 02 CONTROLLERS Page 26 CHILLER PLANT VALVE SCHEDULE Page 53
SEQUENCE OF OPS - AHU 1 & 2 Page 27 VAV & RADIATOR VALVE SCHEDULE Page 54
FAA BCT HVAC EQUIPMENT REPLACEMENT
TSSC4
A rc h it e c t:
B K S
L e g e n d P a g e .v s d
P A R S O N S
F A A B C T H V A C E Q U
IP
M E N T
R E P L A C E M E N T
S Y M B O L P A G E
J O B N U M B E R
-0
S H E E T N O
O F
R e v is io n s
2 4
C h a n g e
D a te
1 5 D a te
/2 /2
F
IL
E N A M E
D a te
D a te
E n g in e e r:
C o n tr a c to r:
D e s ig n e d b y
S o ft w a re b y
C h e c k e d b y
S tr e e t A d d re s s Z ip D ri v e S u it e -1
F o rt M y e rs F L
P o s t O ff ic e B o x
F o rt M y e rs F L
P H .6 .1 F a x .6 .5
DESCRIPTION
PANEL
PNT
GND
DESIGNATED
CONTROLLER
POINT
DESCRIPTION
TERMINAL
TYP. GROUND
POINT TYPE/
IO NUMBER
CURRENT SENSOR
TAG
ACTUATOR PART NUMBER
TYPICAL DAMPER MOTOR
TYPICAL FILTER SENSOR
DP
DIFFERENTIAL PRESS.
FILTER
TYPICAL HW COIL DETAIL
HWS
HWR
A AB
CV1
See Valve Schedule
N/C
TYPICAL CHW COIL
CHWR
CHWS
A AB
CV1 See Valve Schedule
N/O DaSp
PNL
PNT GND V+
OUT
PD1
COM POWER
GND
24H
XFMR
HIGH
EPP102-LCD
PANEL MOUNT DIFFERENTIAL PRESS
TYPICAL STATIC PRESSURE
HUMIDIFIER W/AIR FLOW SWITCH
RESET
L H
HSP-1
CLV-AFS-460-D-SS
Fan Interlock
TYPICAL HI STATIC CUT OUT
EBTRON
AFMS
GTx
AIR FLOW STATION
DUCT SEPARATER
EruEF-S
PNL
PNT PNT
CURRENT SENSOR
CURRENT SENSOR
CT1
STR200 NO SP SENSOR
ENERGY WHEEL
TYPICAL FAN SYMBOL
WATER DP SENSOR
120/ 277 VAC
POWER
TRANSFORMER
Line voltage (power) provided by others.
TRANSFORMER - CONTROLLER
TRANSFORMER – GENERAL DUTY
N L
G
N L
G
FUSE SWITCH
X F M R -2
G e n e ra l P u rp o s e T ra n s fo rm e r
M O D E L N U M B E R
V A C :2 V A C
G rn d v a c v a c
G rn d v a c v a c
AO EXPANDER CARD
ANALOG EXPANDER CARD – INET ONLY
Duct Detector
SD
By others
TRANSFORMER ID
XFR
24H
24G
Transformer ID
POLARITY ID
ZONE SENSOR
LOCATE AS DIRECTED
STR250 ROOM SENSOR WITH LCD
ZoneSensor
STR250
SMART WALL SENSOR (VAV)
0.76 x 0.12
PANEL PARTS
1.50 x 0.26
WW
WIRE WAY W/COVER
Size Varies
B L A C K
R E D
G R E E N
TYPICAL TERMAL
BLOCK
C02 WALL MTD.
TYPICAL FREEZE PROTECTION
Fan Interlock
FZ1
A/FS-6
POWER CONNECTION
TYPICAL TEMP/HUM SENSOR
TYPICAL POINT MARKER
TAG
PANEL
PNT/PINOUT GND
Yel
BOM
Yel
MODEL #
If energy valve, see valve schedule for further details
CO2
VER-CWLSXX
LCD DISPLAY
700 PPM
RM. 116
PLAIN WALL VAV SENSOR
WS
STR200
ZONE SENSOR - LOCATE PER PLANS
RELAY IN A BOX (RIB)
C02 DUCT MTD.
FLOW METER / IMMERSION SENSOR
RH WALL SENSOR
If energy valve, see valve schedule for further details
RH%
EHR110
ChwsT
BK
TS-I
BK
ETI100-2
PUMP
TYPICAL PUMP SYMBOL DUCT W/ DIRECTION ARROW
AVG.
TAG
PANEL
PNT/PINOUT GND
Yel
BOM
Yel
MODEL #
XXX
XXX
“XXX” = XFMR ID
RESET
L
TWR-CHW_ChwsDp
CP_M03
UI8 RET
WTR-DP
KEL-M230-025PD-C
COPPER FOR
DP SENSOR BY
OTHERS
RELAY ENC SPDT 10-30VAC/DC 120
R1
KEL-RIBU1C
WHT/BLU
WHT/YEL
BLU (N/C)
YEL (C)
ORG (N/O)
RJ45
RJ 45 JACK REFERENCE
X
C02
VER-CDLSXX
C02
C02_RM116
MR88R-TYP
UI6GNDXFR2
Humidity
MR88R-TYP
UI6GNDXFR2
h it e c t:
B K S
L e g e n d P a g e .v s d
P A R S O N S
F A A B C T H V A C E Q U
IP
M E
P L A C E M E N T
R E Q U
IR
E M E N T S
C L A R
IF
IC
A T
IO
N S
J O B N U M B E R
-0
S H E E T N O
O F
R e v is io n s
2 4
C h a n g e
D a te
1 5 D a te
/2 /2
F
IL
E N A M E
D a te
D a te
E n g in e e r:
C o n tr a c to r:
D e s ig n e d b y
S o ft w a re b y
C h e c k e d b y
S tr e e t A d d re s s Z ip D ri v e S u it e -1
F o rt M y e rs F L
P o s t O ff ic e B o x
F o rt M y e rs F L
P H .6 .1 F a x .6 .5
PROJECT INTENT: This project is a retrofit of the existing INET control system - to a Smart Struxure (SBO) solution, manufactured by Schneider Electric. This project consist, but not limited to, the following points of interest:
1. GENERAL CONDITIONS:
a. The project requires a100% INET Controls replacement, no INET hardware, software, etc.. shall remain present upon completion of project. All INET hardware is property of the FAA and shall be turned over to the FAA COR. Each controller shall be carefully removed and “Bubble wrapped” to help preserve the integrity of the hardware.
b. The newly installed Smart Struxure (SBO) system shall be consistent with the hardware shown on these drawings – any deviation must be pre-approved by the FAA COR.
c. The intent of this project is to replace all Controllers, Peripheral devices, Control valves (Isolation & modulation), Damper actuators, etc. EXCEPT, where indicated on drawings.
d. Each system within the drawing has a “Bill of Materials” associated with that system – The BOM represents hardware and devices that are known to be acceptable to the FAA – any deviations must be pre-approved by the FAA COR.
e. Control Transformers may be re-used as per drawings indicate, however, if additional transformers are required, it is the responsibility of this contract to provide a turn key solution, which means transformers, relays and other such control devices/hardware to make the system 100% operational is the responsibility of this contractor.
f. This project includes numerous equipment to be integrated via BacNet into the SBO control system. This wiring is not existing and shall be newly installed as directed by within these drawings.
2. AHU:
a. The control valves are currently 3-way with isolation valves. These valves will be replaced with 2-way ENERGY VALVES (Manufactured by Belimo, see valve schedule for approved valves and details)
b. Temperature sensors for supply and return shall come with ENERGY VALVE assembly
c. The currently installed isolation valves will be removed and not replaced.
d. Controls Contractor to provide complete valve assembly
e. The valves shall be INSTALLED BY MECHANICAL CONTRACTOR, as per detail on document set of drawings and detail on Valve Schedule page of this drawing set.
f. All Pneumatic controlled devices (Fan Vanes) are to remain
g. All Dampers shall be tested for proper operation –The new actuator shall control the damper to its fullest open & closed position - If a damper is found to be faulty, this contractor must report the issue, in writing, to the FAA COR for direction.
h. All existing enclosures shall be re-used and shall house the new Smart Struxure Hardware.
2A. VAV:
a. Each VAV shall have a new Xenta 102ax (Lon) controller installed with new approved LON wiring installed as indicated within this drawing set.
b. Each VAV shall have a new HW Floating control valve – provided by this contractor and INSTALLED BY THE MECHANICAL CONTRACTOR.
c. Each “Radiator” valve shall be replace with a two position control valve – provided by this contractor and INSTALLED BY THE MECHANICAL CONTRACTOR.
3. CRAC (Computer Room Air Conditioning):
a. The AS-B controller shall be mounted in a newly provided enclosure – 1 per room.
b. Each unit shall be integrated as shown on the drawings.
4. CENTRAL PLANT:
a. New Onicon flow meters are to be provided, as indicated on drawings, by this contractor – INSTALLED BY THE MECHANICAL CONTRACTOR
b. Existing Isolation Valves shall be replaced with new Isolation Valves – INSTALLED BY THE MECHANICAL CONTRACTOR
c. Provide new control By-Pass valve in place of the existing manual operated By-Pass valve – new by-pass valve provided by this contractor - INSTALLED BY THE MECHANICAL CONTRACTOR.
d. Self sensing pumps (Chilled water only) are to be integrated as shown on the drawings.
5. SOFTWARE and WORKSTATIONS:
a. There is an existing Enterprise software license for the fuel system that will be used to bring all the systems together – See network drawing for additional license requirements.
b. The 4 new workstations shall be of the latest technology available with a minimum of 24" wide monitors. Each workstation shall be capable of running Workstation Software without any processor or storage issues.
c. All TCP/IP backbone cabling shall be installed by this contractor and as per described within the documents. The drawings refer to this network as “BMS Network”
d. A secure Sonic Wall Router with an air card is required for this project. The air card shall come with 1 year of air time, min 6GB per month of allowable data. This connection will be used for first responder warranty and support for the 1 year period. There needs to be a written option for subsequent years of support via the air card provided to the FAA upon completion.
6. REDUNDANT SYSTEMS
a. Each redundant system shall have a mode to enable any unit to be placed in a “Maintenance” mode. When a unit is placed in this mode, it shall be clearly visible from the graphic pages (Home & system) that a unit has been disabled. In addition, a message shall also be recorded.
h it e c t:
B K S
L e g e n d P a g e .v s d
P A R S O N S
F A A B C T H V A C E Q U
IP
M E
P L A C E M E N T
M in im u m G ra p h ic P ro p e rt ie s
J O B N U M B E R
-0
S H E E T N O
O F
R e v is io n s
2 4
C h a n g e
D a te
1 5 D a te
/2 /2
F
IL
E N A M E
D a te
D a te
E n g in e e r:
C o n tr a c to r:
D e s ig n e d b y
S o ft w a re b y
C h e c k e d b y
S tr e e t A d d re s s Z ip D ri v e S u it e -1
F o rt M y e rs F L
P o s t O ff ic e B o x
F o rt M y e rs F L
P H .6 .1 F a x .6 .5
a) Pump Status
i) Graphic of all pumps arraigned by their Pri/Sec roles
ii) Quick status of
(1) Running
(2) Start/Stop status
(3) Fault
(4) VFD fault
(5) Hours of operation each motor, next lube time
(6) Hours of operation each pump, next lube time
(7) Indicator of Lubrication needed
iii) Controls to:
(1) Reset pumps
(2) Reset VFDs
(3) Switches/Buttons to “fail” any unit for maintenance
b) Chiller Dry /Cooler Status
i) Graphic of Chiller and Dry coolers
ii) Quick status of:
(1) Which Chiller is running
(2) Which Pump is running
(3) Water Supply temperature
(4) Water Return temperature
(5) Chiller KW
(6) Each Chiller’s compressor KW
(7) Chiller percent of Full load
(8) Each Chiller’s compressor percent of Full load
(9) Pump Frequency
(10) Pump percent Full load
iii) Controls to:
(1) Change Primary, Secondary and Standby of chillers
(2) Change Primary, Secondary of Pumps
(3) Change Primary, Secondary of Dry coolers
(4) Switches/Buttons to “fail” any unit for maintenance
c) VAV/CAVs
i) Spreadsheet style information from each VAV/CAV
(1) Box number
(2) Room number
(3) Each VAV Occupied or Unoccupied set from time schedule, with the ability to force by clicking on the displayed point.
(4) Room temperature Setpoint, with the ability to change within limits by clicking on the setpoint
(5) Room temperature
(6) Supply Temperature
(7) Reheat Valve Percent Open, with the ability to force percentage by clicking on the displayed point.
(8) Radiator Valve Percent Open/Closed, with the ability to force by clicking on the displayed point.
(9) CFM flow
(10) Minimum CFM
(11) Maximum CFM
(12) Percent Box Load
d) System Status (Quick View)
i) Each AHU
(1) Hours of Operation, next lube time
(2) Fan Status
(3) Select which is Pri/Sec
(4) Preheat valve percent open
(5) Chilled Water valve percent open
(6) Reheat valve percent open
(7) Economizer Damper percent open
(8) Humidifier percent on
(9) Humidifier hours of operation
(10) Return Relative humidity
ii) Chiller Status
(1) Which is Primary, Secondary and Standby
(2) Supply Temperature
(3) Return Temperature
(4) Dry Cooler Status
(5) Dry Cooler Stage/ Motor Frequency
(6) Hours of operation
iii) Boilers B179 & B179A
(1) Primary/Secondary, (indication and selector)
(2) On/Off Status
(3) Hours of operation
(4) Valve status
(5) Supply temperature
(6) Return temperature
iv) Miscellaneous
(1) Hot Water Pressure Alarm, (actual pressure?)
(2) Chilled Water Pressure Alarm, (actual pressure?)
(3) Exhaust Fans EF190 and EF190A
(a) Primary/Secondary, (indication and selector)
(b) Enabled/Disabled
(c) On/Off Status
(d) Hours of operation each, next lube time
e) Several Graphic Screens copied from Building drawings for component location information
PAGE NOTE:
GRAPHIC SUGGESTIONS – AS REQUESTED BY THE FAA ENVIROMENTAL GROUP – THESE “SUGGESTIONS” ARE A MINIMUM
AND ARE NOT LIMITED TO THE GRAPHIC PACKAGE AND CAPABILITIES WITHIN A SMART STRUXURE GRAPHICAL PACKAGE.
GRAPHIC PAGES SHALL BE CLOSELY COORDINATED WITH THE FAA AS TO INSURE THAT THE GRAPHIC PAGES / LAYOUT
ARE SATISFACTORY TO THE END USER.
h it e c t:
B K S
L e g e n d P a g e .v s d
P A R S O N S
F A A B C T H V A C E Q U
IP
M E
P L A C E M E N T
W
IR
IN
G G U
ID
E S
J O B N U M B E R
-0
S H E E T N O
O F
R e v is io n s
2 4
C h a n g e
D a te
1 5 D a te
/2 /2
P A G E A D D E D
/9 /1
F
IL
E N A M E
D a te
D a te
E n g in e e r:
C o n tr a c to r:
D e s ig n e d b y
S o ft w a re b y
C h e c k e d b y
S tr e e t A d d re s s Z ip D ri v e S u it e -1
F o rt M y e rs F L
P o s t O ff ic e B o x
F o rt M y e rs F L
P H .6 .1 F a x .6 .5
ALL DATA IS 40% FILL BASED ON NEC
ALL CONDIT UNDER 24" MAY BE FILLED TO 60%
CONDUIT FILL CAPACITIES – LOW VOLTAGE WIRING
DESCRIPTION COLOR P/N
18/4 NON SHIELDED WHITE 002380
22/4 SHIELDED WHITE / BLUE STRIPE 004342
24/2 SHIELDED BLUE 042000
24/2 SHIELDED ORANGE 042002
22/2 SHIELDED PURPLE 0043250
22/2 NON SHIELDED YELLOW 105500
22/6 SHIELDED WHITE / YELLOW STRIPE 444351-03S
24/2 SHIELDED GRAY 042001-S BacNet Cable
FT/10 LON COMMUNICATION
Access Controls - Bulk inputs wiring (T-stat)
WINDY CITY PRODUCT NUMBERS
NOTES - Typical Cable Application
Outputs & 24 v Power Wiring
Inputs (signal wire and up to 10vdc)
RS485 INET BLDG. LAN ONLY! (Low Cap)
INET SUB LAN ONLY! (Low Cap)
RS232 COMMUNICATION (Typically used for ModBus)
18/4 NON SHIELDED (.184
INCHES cable o.d.)
22/4 SHIELDED
(.145 cable o.d.)
24/2 SHIELDED ORANGE,
BLUE & GRAY (.172 cable o.d.)
22/2 SHIELDED PURPLE
(.126 INCHES cable o.d.)
22/6 SHIELDED WHITE W/YELLOW STRIPE
(.163 cable OD)
AREA = .02688 AREA = .01651 AREA = .02329 AREA = .01327 AREA = .0211
1/2" 0.622 0.12154 4 7 5 9 6
3/4" 0.824 0.21331 8 13 9 17 10
1" 1.049 0.3457 13 21 15 27 0.16
1 1/4" 1.38 0.59828 22 36 25 48 28
1 1/2" 1.61 0.81433 30 49 35 65 39
2" 2.067 1.34224 50 81 57 107 64
EMT CONDUIT SIZE CALCULATED AREA @ 40%INNER DIAMETER
1. All controls conduit shall be “Blue” in color – Except where Rigid is required.
2. Wiring above accessible ceilings shall be run parallel and perpendicular to building lines and adequately supported with “J-Hooks” or “Bridal Rings”
(Plenum rated cable only)
3. Conduit attaching to cable tray, must be attached with the following approved attachment strap (or equal):B-LINE 9ZN-1150-¾ (¾” EMT/RIGID)
4. All voltage wiring above 77 volts are not included within this scope
5. Typical color coding for inputs & outputs
Red = power
Black = ground
White = Primary Signal
Green = Secondary Signal / Spare Wire
LON CARD
BY OTHERS
LON
P NLL
LON
IN
OUT
COM+
COM-
SHLD
TB xx
LAN
SHIELD PASSES THROUGH –
CONNECT TO CONTROLLER
AT ONE END ONLY!
Orange = SubLan
Blue = Controller Lan
TYPICAL NETWORK WIRING – DAISY CHAIN METHOD
18/2 NON SHIELDED CABLE
(YELLOW)
ModBus CARD BY OTHERS
P N
MB
Modbus
22/2 SHIELDED CABLE
(PURPLE)
MB
Modbus
BacNet CARD BY OTHERS
P N B
BacNet
22/2 SHIELDED CABLE (GRAY)
B
BacNet
INET / RS232
5 PORT INDUSTRIAL SWITCH
E-SWITCH
LNX-500AG
8 PORT INDUSTRIAL SWITCH
E-SWITCH
LNX-800AG
BMS NETWORK
A rc h it e c t:
B K S
B M S N E T W O R K .v s d
P A R S O N S
F A A B C T H V A C E Q U
IP
M E
P L A C E M E N T
C O M P U T E R
O F T W A R E
J O B N U M B E R
-0
S H E E T N O
O F
R e v is io n s
2 4
C h a n g e
D a te
1 5 D a te
/2 /2
F
IL
E N A M E
D a te
D a te
E n g in e e r:
C o n tr a c to r:
D e s ig n e d b y
S o ft w a re b y
C h e c k e d b y
S tr e e t A d d re ss
Z ip D ri v e S u it e -1
F o rt M ye rs
F
L
P o st O ff ic e B o x
F o rt M ye rs
F
L
P H
.6
.1
F a x
.6
.5
SECURE SONIC WALL
SONICWALLRTR
8 PORT INDUSTRIAL SWITCH
E-SWITCH
LNX-800AG
5 PORT INDUSTRIAL SWITCH
E-SWITCH
LNX-500AG
NETWORK SWITCHES – SEE “NETWORK ROUTING SCHEDULE” FOR
DETAILS OF SWITCH ROUTING
BMS NETWORK BMS NETWORK
To help eliminate network degradation - No single Cat 6e cable shall be more than 300'
DELL COMPUTER SYSTEM - TO BE DETERMINED
FECS1
DELL - TBD
RM 174
DELL COMPUTER SYSTEM - TO BE DETERMINED
FECS2
DELL - TBD
RM 284
DELL COMPUTER SYSTEM - TO BE DETERMINED
FECS3
DELL - TBD
RM P02
DELL COMPUTER SYSTEM - TO BE DETERMINED
FECS4
DELL - TBD
RM 160
DELL LAPTOP COMPUTER SYSTEM
LAPTOP1
DELL LPTP
AT&T WI-FI AIR CARD
AIRCARD
AT&T AIR CARD
SONIC WALL ROUTER W/ AIR CARD – INCLUDE 1 YEAR
SUBSCRIPTION SERVICE FOR MIN. 5GB PER MONTH AIR
TIME FOR REMOTE SUPPORT
SOFTWARE
ENTERPRISE SERVER MAINTENANCE
ES-1
SXWSWESXX00001
ENTERPRISE SERVER – EXISTING
(PART OF FUEL SYSTEM)
SOFTWARE
WORKSTATION PROFESSIONAL SOFT
SOFT-1
SXWSWWORK00002
SOFTWARE
WORKSTATION STD1 USER MAINTE
SOFT-2
SXWSWWORK00001
Device Qty Part Number Description Vendor
AIRCARD 1 AT&T AIR CARD AT&T WI-FI AIR CARD FUTURE CONTROLS
E-SWITCH 5 LNX-500AG 5 PORT INDUSTRIAL SWITCH ANTARIA
E-SWITCH 5 LNX-800AG 8 PORT INDUSTRIAL SWITCH ANTARIA
FECS1-4 4 DELL - TBD DELL COMPUTER SYSTEM - TO BE D DELL
LAPTOP1 1 DELL LPTP DELL LAPTOP COMPUTER SYSTEM DELL
PRNT1 1 PRINTER PRINTER - TO BE DETERMINED TBD
SOFT-1 2 SXWSWWORK00002 WORKSTATION PROFESSIONAL SOFT Schneider Electric
SOFT-2 3 SXWSWWORK00001 WORKSTATION STD1 USER MAINTE Schneider Electric
SONICWALLRTR 1 NETWORK-ROUTER SECURE SONIC WALL FUTURE CONTROLS, INC.
PRINTER - TO BE DETERMINED
PRNT1
PRINTER
8 PORT INDUSTRIAL SWITCH
E-SWITCH
LNX-800AG
BMS NETWORK BMS NETWORK
5 PORT INDUSTRIAL SWITCH
E-SWITCH
LNX-500AG
BMS NETWORK
RTR-01 RTR-04 RTR-05 RTR-06 RTR-08
RTR-HR
8 PORT INDUSTRIAL SWITCH
E-SWITCH
LNX-800AG
BMS NETWORK
RTR-02
8 PORT INDUSTRIAL SWITCH
E-SWITCH
LNX-800AG
BMS NETWORK
RTR-03
5 PORT INDUSTRIAL SWITCH
E-SWITCH
LNX-500AG
BMS NETWORK
RTR-07
5 PORT INDUSTRIAL SWITCH
E-SWITCH
LNX-500AG
BMS NETWORK
RTR-09
EXIST RM 174
FUEL SYSTEM
h it e c t:
B K S
B M S N E T W O R K .v s d
P A R S O N S
F A A B C T H V A C E Q U
IP
M E
P L A C E M E N T
N E T W O R K R O U T
IN
G
H E D U
J
B N U M B E R
-0
S H E E T N O
O F
R e v is io n s
2 4
C h a n g e
D a te
1 5 D a te
/2 /2
F
IL
E N A M E
D a te
D a te
E n g in e e r:
C o n tr a c to r:
D e s ig n e d b y
S o ft w a re b y
C h e c k e d b y
S tr e e t A d d re ss
Z ip D ri v e S u it e -1
F o rt M ye rs
F
L
P o st O ff ic e B o x
F o rt M ye rs
F
L
P H
.6
.1
F a x
.6
.5
ROUTER NAME PORT 1 PORT 2 PORT 3 PORT 4 PORT 5 PORT 6 PORT 7 PORT 8 PORTS USED DEVICE REQUIRED
RTR-01 AS AHU01 AS AHU02 EV-AHU-1 HW EV-AHU-2 HW EV-AHU-1 CHW EV-AHU-2 CHW RTR-HR RTR-02 8 8 PORT
RTR-02 AS AHU284 AS AHU284A EV-AHU-284 CHW EV-AHU-284 HW EV-AHU-284A CHW EV-AHU-284A HW RTR-01 RTR-03 8 8 PORT
RTR-03 AS AHU284B EV-AS AHU-284B CHW EV-AHU-284B HWp EV-AHU-284B HWr RTR-03 FECS RM 284 6 8 PORT
RTR-04 AS CH01-02-DC01 AS CH03-DC02 AS HWS RTR-HR 4 5 PORT
RTR-05 AS GEN-HNV192 RTR-HR EXISTING FUEL SYS 3 5 PORT
RTR-06 AS AHUP02 EV-AHU-PO2 CHW EV-AHU-PO2 HWp EV-AHU-PO2 HWr RTR-HR RTR-07 6 8 PORT
RTR-07 AS AHUP02A EV-AHU-PO2A CHW EV-AHU-PO2A HW FECS - RM P02 RTR-06 5 5 PORT
RTR-08 AS CRU-RM152 RTR-08 RTR-HR 3 5 PORT
RTR-09 AS CRU-RM252 RTR-07 2 5 PORT
RTR-HR (RM 174) RTR-01 RTR-04 RTR-05 RTR-06A RTR-07 SPARE SPARE 7 8 PORT
SONICWALL (RM 174) FECS RM 174 FECS RM 160 RTR-HR 2 INCLUDED
TOTAL 5 PORT 5
TOTAL 8 PORT 5AS = AUTOMATION SERVER
EV = ENERGY VALVE
RTR-0x= ROUTER
FECS = FRONT END COMPUTER SYSTEM
RTR-HR = ROUTER @ SONICWALL
h it e c t:
B K S
B M S N E T W O R K .v s d
P A R S O N S
F A A B C T H V A C E Q U
IP
M E
P L A C E M E N T
N E T W O R K C O N N E C T
D
V
IC
E S U M M A R Y
J O B N U M B E R
-0
S H E E T N O
O F
R e v is io n s
2 4
C h a n g e
D a te
1 5 D a te
/2 /2
F
IL
E N A M E
D a te
D a te
E n g in e e r:
C o n tr a c to r:
D e s ig n e d b y
S o ft w a re b y
C h e c k e d b y
S tr e e t A d d re ss
Z ip D ri v e S u it e -1
F o rt M ye rs
F
L
P o st O ff ic e B o x
F o rt M ye rs
F
L
P H
.6
.1
F a x
.6
.5
RTR-04
AS CH01-02-DC01
Schneider
Electric
AS CH03-DC02
Schneider
Electric
AS HWS
Schneider
Electric
ASB CRU-RM152
SXW-AS-B-24
Schneider
Electric
ASB CRU-RM252
SXW-AS-B-24
Schneider
Electric
AS AHU01
Schneider
Electric
AS AHU02
Schneider
Electric
AS AHU284
Schneider
Electric
AS AHU284A
Schneider
Electric
AS AHU284B
Schneider
Electric
AS AHUP02
Schneider
Electric
AS AHUP02A
Schneider
Electric
AS GEN-HNV192
Schneider
Electric
EV-AHU-1 HW
BAC Inst #: 0
EV-AHU-2 HW
BAC Inst #: 0
EV-AHU-1 CHW
BAC Inst #: 0
EV-AHU-2 CHW
BAC Inst #: 0
EV-AHU-284 HW
BAC Inst #: 0
EV-AHU-284A HW
BAC Inst #: 0
EV-AHU-284 CHW
BAC Inst #: 0
EV-AHU-284A CHW
BAC Inst #: 0
EV-AHU-284B HWp
BAC Inst #: 0
EV-AHU-284B HWr
BAC Inst #: 0
EV-AHU-284B CHW
BAC Inst #: 0
EV-AHU-PO2 HWp
BAC Inst #: 0
EV-AHU-PO2 HWr
BAC Inst #: 0
EV-AHU-PO2 CHW
BAC Inst #: 0
EV-AHU-PO2A HW
BAC Inst #: 0
EV-AHU-PO2A CHW
BAC Inst #: 0
To help eliminate network degradation - No single Cat 6e cable shall be more than 300'
RTR-05
RTR-09
RTR-01 RTR-02
RTR-03
RTR-06 RTR-08RTR-07
EXISTING FUEL SYSTEM
Schneider
Electric
BACnet MS-TPBACnet MS-TP BACnet MS-TP (COM A)
SmartStruxure I/O ModulesSmartStruxure I/O Modules SmartStruxure IO Modules
BACnet MS-TPBACnet MS-TPBACnet MS-TP BACnet MS-TP (COM A)
SmartStruxure I/O ModulesSmartStruxure I/O ModulesSmartStruxure I/O Modules SmartStruxure IO Modules
AS CH01-02-DC01
Schneider
Electric
CH01-02-DC01_M01
SXW-DO-FA-12
Schneider
Electric
Slot #3
CH01-02-DC01_M02
SXW-UI8-AO-V-4
Schneider
Electric
Slot #4
CH01-02-DC01_M03
SXW-UI-16
Schneider
Electric
Slot #5
CH01-02-DC01_M04
SXW-UI-8-DO-FC-4
Schneider
Electric
Slot #6
C-PMP 178B
BAC Inst #: 0
C-PMP 17D
BAC Inst #: 0
CH01
BAC Inst #: 0
CH02
BAC Inst #: 0AS CH03-DC02
Schneider
Electric
CH03-DC02_M01
SXW-DO-FA-12
Schneider
Electric
Slot #3
CH03-DC02_M02
SXW-UI8-AO-V-4
Schneider
Electric
Slot #4
CH03-DC02_M03
SXW-UI-16
Schneider
Electric
Slot #5
C-PMP 178A
BAC Inst #: 0
C-PMP 178C
BAC Inst #: 0
CH03
BAC Inst #: 0
SmartStruxure I/O ModulesSmartStruxure I/O ModulesSmartStruxure I/O Modules SmartStruxure IO Modules
AS HWS
Schneider
Electric
HWS_M01
SXW-DO-FA-12
Schneider
Electric
Slot #3
HWS_M02
SXW-UI8-AO-V-4
Schneider
Electric
Slot #4
HWS_M03
SXW-UI8-AO-V-4
Schneider
Electric
Slot #5
HWS_M04
SXW-UI-16
Schneider
Electric
Slot #6
A rc h it e c t:
B K S
B M S N
E T W O R K .v s d
P A R S O N S
F A A B C T H
V A C E Q U
IP
M E
P L A C E M E N T
C O N T R O L L E R D
E T A
IL
S
C E N T R A L P L A N T
J O B N
U M B E R
-0
S H E E T N
O
O F
R e v is io n s
2 4
C h a n g e
D a te
1 5 D a te
/2 /2
F
IL
E N
A M E
D a te
D a te
E n g in e e r:
C o n tr a c to r:
D e s ig n e d b y
S o ft w a re b y
C h e c k e d b y
S tr e e t A d d re ss
Z ip D ri v e S u it e -1
F o rt M ye rs
F
L
P o st O ff ic e B o x
F o rt M ye rs
F
L
P H
.6
.1
F a x
.6
.5
BACnet MS-TP (RS-485)
BACnet MS-TPBACnet MS-TPBACnet MS-TP BACnet MS-TP (RS-485)
ASB CRU-RM152
SXW-AS-B-24
Schneider
Electric
CRU 152
BAC Inst #: 0
CRU 152A
BAC Inst #: 0
CRU 152B
BAC Inst #: 0
CRU 152C
BAC Inst #: 0ASB CRU-RM252
SXW-AS-B-24
Schneider
Electric
CRU 252
BAC Inst #: 0
CRU 252A
BAC Inst #: 0
CRU 252B
BAC Inst #: 0
A rc h it e c t:
B K S
B M S N
E T W O R K .v s d
P A R S O N S
F A A B C T H
V A C E Q U
IP
M E
P L A C E M E N T
C O N T R O L L E R D
E T A
IL
S
C R A C U
N
IT
S
J O B N
U M B E R
-0
S H E E T N
O
O F
R e v is io n s
2 4
C h a n g e
D a te
1 5 D a te
/2 /2
F
IL
E N
A M E
D a te
D a te
E n g in e e r:
C o n tr a c to r:
D e s ig n e d b y
S o ft w a re b y
C h e c k e d b y
S tr e e t A d d re ss
Z ip D ri v e S u it e -1
F o rt M ye rs
F
L
P o st O ff ic e B o x
F o rt M ye rs
F
L
P H
.6
.1
F a x
.6
.5
SmartStruxure I/O ModulesSmartStruxure I/O Modules SmartStruxure IO Modules
LonWorksLonWorksLonWorksLonWorksLonWorksLonWorks
LonWorks LonWorks LonWorks LonWorks LonWorks LonWorks LonWorks LonWorks LonWorks LonWorks LonWorks LonWorks
LonWorksLonWorksLonWorksLonWorksLonWorksLonWorksLonWorksLonWorksLonWorksLonWorksLonWorksLonWorks LonWorks
SmartStruxure I/O ModulesSmartStruxure I/O Modules SmartStruxure IO Modules
AS AHUP02
Schneider
Electric
AHUP02_M01
SXW-UI8-AO-V-4
Schneider
Electric
Slot #3
AHUP02_M02
SXW-UI8-AO-V-4
Schneider
Electric
Slot #4
AHUP02_M03
SXW-UI-8-DO-FC-4
Schneider
Electric
Slot #5
CAV 104
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
CAV 116
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
CAV 126
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
CAV 128
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
CAV 208
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
CAV 212
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
CAV 216
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
FMPB-PL7
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
FMPB-PL8
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
FPMB-PL5
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
FPMB-PL6
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
VAV 102
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
VAV 102A
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
VAV 104A
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
VAV 106
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
VAV 108
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
VAV 110
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
VAV 112
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
VAV 114
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
VAV 118
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
VAV 120
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
VAV 122
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
VAV 125
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
VAV 200
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
VAV 202
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
VAV 202A
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
VAV 206
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
VAV 206A
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
VAV 210
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
VAV 210A
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
VAV 211
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
AS AHUP02A
Schneider
Electric
AHUP02A_M01
SXW-UI8-AO-V-4
Schneider
Electric
Slot #3
AHUP02A_M02
SXW-UI8-AO-V-4
Schneider
Electric
Slot #4
AHUP02A_M03
SXW-UI-8-DO-FC-4
Schneider
Electric
Slot #5
SmartStruxure I/O Modules SmartStruxure IO Modules
SmartStruxure I/O Modules SmartStruxure IO Modules
AS AHU01
Schneider
Electric
AHU01_M01
SXW-UI8-AO-V-4
Schneider
Electric
Slot #3
AHU01_M02
SXW-UI-8-DO-FC-4
Schneider
Electric
Slot #4
AS AHU02
Schneider
Electric
AHU02_M01
SXW-UI8-AO-V-4
Schneider
Electric
Slot #3
AHU02_M02
SXW-UI-8-DO-FC-4
Schneider
Electric
Slot #4
A rc h it e c t:
B K
S B
M S
N E
T W
O R
K .v s d
P A
R S
O N
S
F A
A B
C T
H V
A C
E Q
U
IP
M E
P L
A C
E M
E N
T
C O
N T
R O
L L E
R D
E T
A
IL
S
A H
U P
G
J O
B N
U M
B E
R -0
S H
E E
T N
O
O F
R e v is io n s
2 4
C h a n g e
D a te
1 5
D a te
/2
/2
F
IL
E
N A
M E
D a te
D a te
E n g in e e r:
C o n tr a c to r:
D e s ig n e d b y
S o ft w a re b y
C h e c k e d b y
S tr e e t A d d re ss
Z ip D ri v e S u it e -1
F o rt M ye rs
F
L
P o st O ff ic e B o x
F o rt M ye rs
F
L
P H
.6
.1
F a x
.6
.5
LonWorksLonWorksLonWorksLonWorksLonWorksLonWorksLonWorks
LonWorks LonWorks LonWorks LonWorks LonWorks LonWorks LonWorks LonWorks LonWorks LonWorks LonWorks LonWorks
LonWorksLonWorksLonWorksLonWorksLonWorksLonWorksLonWorksLonWorksLonWorksLonWorksLonWorksLonWorks LonWorks
SmartStruxure I/O ModulesSmartStruxure I/O Modules SmartStruxure IO Modules
SmartStruxure I/O ModulesSmartStruxure I/O Modules SmartStruxure IO Modules
AS AHU284A
Schneider
Electric
AHU284A_M01
SXW-UI8-AO-V-4
Schneider
Electric
Slot #3
AHU284A_M02
SXW-UI8-AO-V-4
Schneider
Electric
Slot #4
AHU284A_M03
SXW-UI-8-DO-FC-4
Schneider
Electric
Slot #5AS AHU284B
Schneider
Electric
AHU284B_M01
SXW-UI8-AO-V-4
Schneider
Electric
Slot #3
AHU284B_M02
SXW-UI8-AO-V-4
Schneider
Electric
Slot #4
AHU284B_M03
SXW-UI-8-DO-FC-4
Schneider
Electric
Slot #5
CAV 162
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
CAV 164
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
CAV 166
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
CAV 169
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
CAV 250
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
CAV 250B
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
CAV 278
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
CAV 282
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
CAV 288
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
CAV 288A
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
FMPB-PL2
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
FMPB-PLI
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
FPMP-PL3
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
FPMP-PL4
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
FPMP-PL9
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
VAV 154
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
VAV 157
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
VAV 158
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
VAV 160
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
VAV 174
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
VAV 250A
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
VAV 250C
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
VAV 261
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
VAV 261A
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
VAV 261B
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
VAV 261C
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
VAV 261D
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
VAV 261E
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
VAV 261F
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
VAV 261G
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
VAV 265
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
VAV 276
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
LonWorksLonWorksLonWorksLonWorksLonWorksLonWorks LonWorks
SmartStruxure I/O ModulesSmartStruxure I/O Modules SmartStruxure IO Modules
AS AHU284
Schneider
Electric
AHU284_M01
SXW-UI8-AO-V-4
Schneider
Electric
Slot #3
AHU284_M02
SXW-UI8-AO-V-4
Schneider
Electric
Slot #4
AHU284_M03
SXW-UI-8-DO-FC-4
Schneider
Electric
Slot #5
CAV 150
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
CAV 251
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
CAV 251A
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
CAV 251B
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
CAV 251C
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
VAV 251A
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
VAV 290
Xenta 102-AX
Schneider
Electric
LON Subnet/Node: 0:0
A rc h it e c t:
B K
S B
M S
N E
T W
O R
K .v s d
P A
R S
O N
S
F A
A B
C T
H V
A C
E Q
U
IP
M E
P L
A C
E M
E N
T
C O
N T
R O
L L E
R D
E T
A
IL
S
A H
U P
G
J O
B N
U M
B E
R -0
S H
E E
T N
O
O F
R e v is io n s
2 4
C h a n g e
D a te
1 5
D a te
/2
/2
F
IL
E
N A
M E
D a te
D a te
E n g in e e r:
C o n tr a c to r:
D e s ig n e d b y
S o ft w a re b y
C h e c k e d b y
S tr e e t A d d re ss
Z ip D ri v e S u it e -1
F o rt M ye rs
F
L
P o st O ff ic e B o x
F o rt M ye rs
F
L
P H
.6
.1
F a x
.6
.5
SmartStruxure I/O ModulesSmartStruxure I/O Modules SmartStruxure IO Modules
LonWorks
AS GEN-HNV192
Schneider
Electric
EF 190A
STR350
Schneider
Electric
LON Subnet/Node: 0:0
GEN-HNV192_M01
SXW-UI8-AO-V-4
Schneider
Electric
Slot #3
GEN-HNV192_M02
SXW-UI-8-DO-FC-4
Schneider
Electric
Slot #4
GEN-HNV192_M03
SXW-UI-8-DO-FC-4
Schneider
Electric
Slot #5
A rc h it e c t:
B K S
B M S N
E T W O R K .v s d
P A R S O N S
F A A B C T H
V A C E Q U
IP
M E
P L A C E M E N T
C O N T R O L L E R D
E T A
IL
S
G E N E R A T O R R
O O M
J O B N
U M B E R
-0
S H E E T N
O
O F
R e v is io n s
2 4
C h a n g e
D a te
1 5 D a te
/2 /2
F
IL
E N
A M E
D a te
D a te
E n g in e e r:
C o n tr a c to r:
D e s ig n e d b y
S o ft w a re b y
C h e c k e d b y
S tr e e t A d d re ss
Z ip D ri v e S u it e -1
F o rt M ye rs
F
L
P o st O ff ic e B o x
F o rt M ye rs
F
L
P H
.6
.1
F a x
.6
.5 h it e c t:
B K S
C E N T R A L P L A N T .v s d
P A R S O N S
F A A B C T H V A C E Q U
IP
M E
P L A C E M E N T
C H
IL
L E D W A T E R D
Y
O L E R S
J O B N U M B E R
-0
S H E E T N O
O F
R e v is io n s
2 4
C h a n g e
D a te
1 5 D a te
/2 /2
F
IL
E N A M E
D a te
D a te
E n g in e e r:
C o n tr a c to r:
D e s ig n e d b y
S o ft w a re b y
C h e c k e d b y
S tr e e t A d d re s s Z ip D ri v e S u it e -1
F o rt M y e rs F L
P o s t O ff ic e B o x
F o rt M y e rs F L
P H .6 .1 F a x .6 .5
/4 " R
IG
ID
CHILLER
AB A
ISO
See Valve Schedule
CHILLER
AB A
ISO
See Valve Schedule
1 2
DC 01_ChwrFlo
CH01-02-DC01_M03
UI13 RET
FM
ONI-F-1210
FLOW METER, DUAL TURBINE
ROOF
MECH ROOM
DC 02_ChwrFlo
CH03-DC02_M02
UI7 RET
FM
ONI-F-1210
FLOW METER, DUAL TURBINE
3/4" RIGID3/4" RIGID
T-CONDULET
ANCHOR
¼” MIN THREADED ROD
Approved strap (Mineralac or
Unistrut)
CONTROL CONDUIT TO C-PMPS – INTENT ONLY
TYP.
CONDUIT MUST MEET NEC
CODE REQUIREMENTS
DRY COOLER DRY COOLER
TYPICAL RELAY FOR ENABLE POINTS
RELAY ENC SPDT 10-30VAC/DC 120
R1
KEL-RIBU1C
WHT/BLU
WHT/YEL
BLU (N/C)
YEL (C)
ORG (N/O)
x x
Motor Starter or Equip enable contacts
Device Qty Part Number Description Vendor
FM 2 ONI-F-1210 FLOW METER, DUAL TURBINE INSER Schneider Electric
R1 4 KEL-RIBU1C RELAY ENC SPDT 10-30VAC/DC 120 Schneider Electric
ENABLE POINT
DC 02_Stg2Enable
CH03-DC02_M01
DO5
COM
DC 01_Stg2Enable
CH01-02-DC01_M01
DO8
COM
DC 02_IsoVlvSts
CH03-DC02_M02
UI15
RET
DC 02_IsoValve
CH03-DC02_M01
DO6
COM
DC 02_IsoVlvSts
CH01-02-DC01_M03
UI14
RET
DC 02_IsoValve
CH01-02-DC01_M01
DO9
COM
DEV
EXIST
DEV
EXIST
DC 01_Stg1Enable
CH01-02-DC01_M01
DO7
COM
DC 02_Stg1Enable
CH03-DC02_M01
DO4
COM
/4 " R
IG
ID
A rc h it e c t:
B K S
C E N T R A L P L A N T .v s d
P A R S O N S
F A A B C T H V A C E Q U
IP
M E
P L A C E M E N T
C H
IL
L E D W A T E R
C H
IL
L E R S
J O B N U M B E R
-0
S H E E T N O
O F
R e v is io n s
2 4
C h a n g e
D a te
1 5 D a te
/2 /2
F
IL
E N A M E
D a te
D a te
E n g in e e r:
C o n tr a c to r:
D e s ig n e d b y
S o ft w a re b y
C h e c k e d b y
S tr e e t A d d re s s Z ip D ri v e S u it e -1
F o rt M y e rs F L
P o s t O ff ic e B o x
F o rt M y e rs F L
P H .6 .1 F a x .6 .5
CHILLER
AB A
ISO
See Valve Schedule
CHILLER
AB A
ISO
See Valve Schedule
CHILLER
AB A
ISO
See Valve Schedule
1 2 3
NEXTTo AS-P CH01-02-DC01 PREVIOUS To AS-P CH03-DC02
MS/TP BACNET WIRING (TYP.)
CHILLER 01_ChwrFlo
CH01-02-DC01_M03
UI3 RET
FM
ONI-F-1210
FLOW METER, DUAL TURBINE
CHILLER 01_Amps
CH01-02-DC01_M03
UI1 RET
X
CH01
X
VER-H321
ROOF
MECH ROOM
CHILLER 01_IsoVlvSts
CH01-02-DC01_M03
UI4
RET
CHILLER 01_IsoValve
CH01-02-DC01_M01
DO2
COM
CHILLER 01_ChillerAlrm
CH01-02-DC01_M03
UI2
RET
CHILLER 01_ChillerEnable
CH01-02-DC01_M01
DO1
COM
CHILLER 02_ChwrFlo
CH01-02-DC01_M03
UI9 RET
FM
ONI-F-1210
FLOW METER, DUAL TURBINE
CHILLER 02_Amps
CH01-02-DC01_M03
UI7 RET
X
CH01
X
VER-H321
CHILLER 02_IsoVlvSts
CH01-02-DC01_M03
UI10
RET
CHILLER 02_IsoValve
CH01-02-DC01_M01
DO6
COM
CHILLER 02_ChillerAlrm
CH01-02-DC01_M03
UI8
RET
CHILLER 02_ChillerEnable
CH01-02-DC01_M01
DO5
COM
CHILLER 03_ChwrFlo
CH03-DC02_M02
UI3 RET
FM
ONI-F-1210
FLOW METER, DUAL TURBINE
CHILLER 03_Amps
CH03-DC02_M02
UI1 RET
X
CH01
X
VER-H321
CHILLER 03_IsoVlvSts
CH03-DC02_M02
UI4
RET
CHILLER 03_IsoValve
CH03-DC02_M01
DO2
COM
CHILLER 03_ChillerAlrm
CH03-DC02_M02
UI2
RET
CHILLER 03_ChillerEnable
CH03-DC02_M01
DO1
COM
3/4" RIGID3/4" RIGID
T-CONDULET
ANCHOR
¼” MIN THREADED ROD
Approved strap (Mineralac or
Unistrut)
CONTROL CONDUIT TO C-PMPS – INTENT ONLY
TYP.
CONDUIT MUST MEET NEC
CODE REQUIREMENTS
TYPICAL RELAY FOR ENABLE POINTS
RELAY ENC SPDT 10-30VAC/DC 120
R1
KEL-RIBU1C
WHT/BLU
WHT/YEL
BLU (N/C)
YEL (C)
ORG (N/O)
x x
Motor Starter or Equip enable contacts
Device Qty Part Number Description Vendor
CH01 3 VER-H321 CURRENT TRANSDUCER SPLIT CORE Schneider Electric
FM 3 ONI-F-1210 FLOW METER, DUAL TURBINE INSER Schneider Electric R1 9 KEL-RIBU1C RELAY ENC SPDT 10-30VAC/DC 120 Schneider Electric
ENABLE POINT
DEV
EXIST
DEV
EXIST
DEV
EXIST
h it e c t:
B K S
C E N T R A L P L A N T .v s d
P A R S O N S
F A A B C T H V A C E Q U
IP
M E
P L A C E M E N T
C H
IL
L E D W A T E R P U M P S
J O B N U M B E R
-0
S H E E T N O
O F
R e v is io n s
2 4
C h a n g e
D a te
1 5 D a te
/2 /2
F
IL
E N A M E
D a te
D a te
E n g in e e r:
C o n tr a c to r:
D e s ig n e d b y
S o ft w a re b y
C h e c k e d b y
S tr e e t A d d re s s Z ip D ri v e S u it e -1
F o rt M y e rs F L
P o s t O ff ic e B o x
F o rt M y e rs F L
P H .6 .1 F a x .6 .5
/4 " R
IG
ID
C-PMP 178BC-PMP 178A
C-Pump178A_PmpAlarm
CH01-02-DC01_M03
UI5
RET
C-Pump178A_PmpEnable
CH01-02-DC01_M01
DO11
COM
C-Pump178B_PmpAlarm
CH03-DC02_M02
UI5
RET
C-Pump178B_PmpEnable
CH03-DC02_M01
DO8
COM
3/4" RIGID3/4" RIGID
T-CONDULET
ANCHOR
¼” MIN THREADED ROD
Approved strap (Mineralac or
Unistrut)
CONTROL CONDUIT TO C-PMPS – INTENT ONLY
TYP.
CONDUIT MUST MEET NEC
CODE REQUIREMENTS
To AS-P CH03-DC02
TYPICAL RELAY FOR ENABLE POINTS
RELAY ENC SPDT 10-30VAC/DC 120
R1
KEL-RIBU1C
WHT/BLU
WHT/YEL
BLU (N/C)
YEL (C)
ORG (N/O)
x x
Motor Starter or Equip enable contacts
Device Qty Part Number Description Vendor
R1 4 KEL-RIBU1C RELAY ENC SPDT 10-30VAC/DC 120 Schneider Electric
TS-I 4 ETI100-4 TEMP SENSOR IMRSN 1.8K 4" Schneider Electric TS-I_1 4 ETI-WELL-4S 4" 2-PART STAINLESS WELL Schneider Electric
WTR-DP 2 KEL-M230-025PD-C DP XMTR 25 PSI Schneider ElectricENABLE POINT
C-PMP 178C
C-Pump178C_PmpAlarm
CH01-02-DC01_M03
UI6
RET
C-Pump178C_PmpEnable
CH01-02-DC01_M01
DO12
COM
TRACON
ADMIN
TRACON
ADMIN
A B
A
C V
S e e V a lv e S c h e d u le
TRACON-LOOP_ChwrT
CH03-DC02_M02
UI11 RET
RED
TS-I
YEL
ETI100-4
ADMIN-LOOP_ChwrT
CH03-DC02_M02
UI9 RET
RED
TS-I
YEL
ETI100-4
TRACON-LOOP_ChwsT
CH03-DC02_M02
UI12 RET
RED
TS-I
YEL
ETI100-4
ADMIN-LOOP_ChwsT
CH03-DC02_M02
UI10 RET
RED
TS-I
YEL
ETI100-4
CP_ByPassFdbck
CH01-02-DC01_M02
UI1
RET
CP_ByPassControl
CH01-02-DC01_M02
VO1
RET
A D M
IN
-L O O P C h w s D p
C H -D C M
U I1
R E T
W T R -D
P KEL-M230-025PD-C
ROOM P02
T R A C O N -L O O P C h w s D p
C H -D C M
U I1
R E T
W T R -D
P KEL-M230-025PD-C
ROOM 284
MECH. RM. BUILDING
DEV
EXIST
DEV
EXIST
DEV
EXIST
To AS-P CH01-02-DC01
T E M P C H W M A N V A L V E
T E M P C H W M A N V A L V E
During construction, there will be temporary chilled water serving the facility. The DDC contractor shall provide all necessary control wiring and programmable controller for the purpose to control temporary equipment during this time period.
-Controller is temporary and will be returned to contractor upon completion. Used controller is acceptable.
-Wiring is temporary and shall be protected from physical damage. It is acceptable to run wiring without conduit as long it can be protected from reasonable damage.
Programming shall include:
1. Enable/disable & Status for temporary pumps.
2. Pump Lead/Standby control logic. Standby pump shall run in the case of the lead pump failure
*Chillers shall be enabled manually and are self controlling to temperature set point.
Temporary controls shall have GUI for facility use – Temporary use of a laptop is acceptable.
h it e c t:
B K S
C E N T R A L P L A N T .v s d
P A R S O N S
F A A B C T H V A C E Q U
IP
M E
P L A C E M E N T
C H
IL
L E D W A T E R S Y S T
M
N T R O L L E R S P G .1
J O B N U M B E R
-0
S H E E T N O
O F
R e v is io n s
2 4
C h a n g e
D a te
1 5 D a te
/2 /2
F
IL
E N A M E
D a te
D a te
E n g in e e r:
C o n tr a c to r:
D e s ig n e d b y
S o ft w a re b y
C h e c k e d b y
S tr e e t A d d re s s Z ip D ri v e S u it e -1
F o rt M y e rs F L
P o s t O ff ic e B o x
F o rt M y e rs F L
P H .6 .1 F a x .6 .5
1EXISTING POWER SUPPIES – FIELD VERIFY
1. POWER TRANSFORMERS ARE EXISTING AND SHALL BE RE-USED.
2. CONTROLLER POWER SHALL BE MINIMUM 40VA HALF WAVE (GROUNDED)
3. GENERAL PURPOSE TRANSFORMERS SHALL BE MINIMUM 96VA HALF WAVE (GROUNDED)
4. ALL TRANSFORMERS SHALL BE RELOCATED FROM WIREWAY (GUTTER) TO RESPECTIVE
CONTROLLER PANEL.
120 VAC
POWER
TRANSFORMER
Line voltage (power) provided by others.
VAC
X F R
N
H
GND
DEV
EXIST Power connections – field verify locations required.
PS-24V POWER SUPPLY 24 VAC/VDC
PS CH03-DC02
SXWPS24VX10001
L
L
G N D
24HEXIST
24NXFR
Schneider Electric
SXW PS-24V
T o :A S C H -D C
01:PS CH03-DC02 on AS CH03-DC02
SMARTX CONTROLLER AS-P
AS CH03-DC02
SXWASPXXX10001
T X /R X
T X /R X
R E T
B
IA
S
T X /R X
T X /R X
R E T
T X /R X
T X /R X
R E T
L O N -1
L O N -2
IP Address:
Subnet:
Gateway:
To: NEXT
From: PREV
Schneider Electric
SXW AS-P
F ro m :P S C H -D C o n A S C H -D C
T o :C H -D C M o n A S C H -D C
02:AS CH03-DC02
RS-485 LON
Com A Com B
Device
RS-485
Host
10/100
Ethernet 1
10/100
Ethernet 2
TP/FT
DO-FA-12-H 12 DO FORMA HAND
CH03-DC02_M01
SXWDOA12H10001
C O M
D O
C O M
D O
C O M
D O
C O M
D O
C O M
D O
C O M
D O
C O M
D O
C O M
D O
C O M
D O
C O M
D O
C O M
D O
C O M
D O
DO:CHILLER 03_ChillerEnable
24HEXIST
DO:CHILLER 03_IsoValve
24HEXIST
DO:DC 02_Stg1Enable
24H EXIST
DO:DC 02_Stg2Enable
24H EXIST
DO:DC 02_IsoValve
24H EXIST
DO:C-Pump178B_PmpEnable
24HEXIST
Schneider Electric
SXW DO-FA-12-H
F ro m :A S C H -D C
T o :C H -D C M o n A S C H -D C
03:CH03-DC02_M01 on AS CH03-DC02
Digital Outputs
Digital Outputs
1 2 3 4 5 6
7 8 9 10 11 12
UI-16 16 Universal In
CH03-DC02_M02
SXWUI16XX10001
U I1
R E T
U I2
U I3
R E T
U I4
U I5
R E T
U I6
U I7
R E T
U I8
U I9
R E T
U I1
U I1
R E T
U I1
U I1
R E T
U I1
U I1
R E T
U I1
CH01:CHILLER 03_Amps
DI:CHILLER 03_ChillerAlrm
FM:CHILLER 03_ChwrFlo
DI:CHILLER 03_IsoVlvSts DI:C-Pump178B_PmpAlarm
FM:DC 02_ChwrFlo
TS-I:ADMIN-LOOP_ChwrT
TS-I:ADMIN-LOOP_ChwsT
TS-I:TRACON-LOOP_ChwrT
TS-I:TRACON-LOOP_ChwsT WTR-DP:ADMIN-LOOP_ChwsDp
WTR-DP:TRACON-LOOP_ChwsDp
DI:DC 02_IsoVlvSts
Schneider Electric
SXW UI-16
F ro m :C H -D C M o n A S C H -D C
05:CH03-DC02_M03 on AS CH03-DC02
Universal Inputs
Universal Inputs
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16
Device Qty Part Number Description Vendor
AS CH03-DC02 1 SXWASPXXX10001 SMARTX CONTROLLER AS-P Schneider Electric
AS CH03-DC02_1 1 SXWTBASW110002 TB-ASP-W1 TERM BASE ASP W1 Schneider Electric
CH03-DC02_M01 1 SXWDOA12H10001 DO-FA-12-H 12 DO FORMA HAND Schneider Electric
CH03-DC02_M02 1 SXWUI16XX10001 UI-16 16 UNIVERSAL IN Schneider Electric
CH03-DC02_M01_1 1 SXWTBIOW110001 TB-IO-W1 TERM BASE I/O W1 Schneider Electric
CH03-DC02_M02_1 1 SXWTBIOW110001 TB-IO-W1 TERM BASE I/O W1 Schneider Electric
PS CH03-DC02 1 SXWPS24VX10001 PS-24V POWER SUPPLY 24 VAC/VDC Schneider Electric
PS CH03-DC02_1 1 SXWTBPSW110001 TB-PS-W1 TERM BASE PWR SUP W1 Schneider Electric h it e c t:
B K S
C E N T R A L P L A N T .v s d
P A R S O N S
F A A B C T H V A C E Q U
IP
M E
P L A C E M E N T
C H
IL
L E D W A T E R S Y S T
N T R O L L E R S P G .2
J O B N U M B E R
-0
S H E E T N O
O F
R e v is io n s
2 4
C h a n g e
D a te
1 5 D a te
/2 /2
F
IL
E N A M E
D a te
D a te
E n g in e e r:
C o n tr a c to r:
D e s ig n e d b y
S o ft w a re b y
C h e c k e d b y
S tr e e t A d d re s s Z ip D ri v e S u it e -1
F o rt M y e rs F L
P o s t O ff ic e B o x
F o rt M y e rs F L
P H .6 .1 F a x .6 .5
1EXISTING POWER SUPPIES – FIELD VERIFY
1. POWER TRANSFORMERS ARE EXISTING AND SHALL BE RE-USED.
2. CONTROLLER POWER SHALL BE MINIMUM 40VA HALF WAVE (GROUNDED)
3. GENERAL PURPOSE TRANSFORMERS SHALL BE MINIMUM 96VA HALF WAVE (GROUNDED)
4. ALL TRANSFORMERS SHALL BE RELOCATED FROM WIREWAY (GUTTER) TO RESPECTIVE
CONTROLLER PANEL.
120 VAC
POWER
TRANSFORMER
Line voltage (power) provided by others.
VAC
X F R
N
H
GND
DEV
EXIST Power connections – field verify locations required.
PS-24V POWER SUPPLY 24 VAC/VDC
PS CH01-02-DC01
SXWPS24VX10001
L
L
G N D
24HEXIST
24NXFR
Schneider Electric
SXW PS-24V
T o :A S C H -0 -D C
01:PS CH01-02-DC01 on AS CH01-02-
DC01
SMARTX CONTROLLER AS-P
AS CH01-02-DC01
SXWASPXXX10001
T X /R X
T X /R X
R E T
B
IA
S
T X /R X
T X /R X
R E T
T X /R X
T X /R X
R E T
L O N -1
L O N -2
To: NEXT
From: PREV
Schneider Electric
SXW AS-P
F ro m :P S C H -0 -D C o n A S C H -0 -D C
T o :C H -0 -D C M o n A S C H -0 -D C
02:AS CH01-02-DC01
RS-485 LON
Com A Com B
Device
RS-485
Host
10/100
Ethernet 1
10/100
Ethernet 2
TP/FT
DO-FA-12-H 12 DO FORMA HAND
CH01-02-DC01_M01
SXWDOA12H10001
C O M
D O
C O M
D O
C O M
D O
C O M
D O
C O M
D O
C O M
D O
C O M
D O
C O M
D O
C O M
D O
C O M
D O
C O M
D O
C O M
D O
DO:CHILLER 01_ChillerEnable
24HEXIST
DO:CHILLER 01_IsoValve
24HEXIST DO:CHILLER 02_ChillerEnable
24H EXIST
DO:CHILLER 02_IsoValve
24H EXIST
DO:DC 01_Stg1Enable
24HEXIST
DO:DC 01_Stg2Enable
24HEXIST
DO:DC 02_IsoValve
24HEXIST
DO:C-Pump178A_PmpEnable
24H EXIST
DO:C-Pump178C_PmpEnable
24H EXIST
Schneider Electric
SXW DO-FA-12-H
F ro m :A S C H -0 -D C
T o :C H -0 -D C M o n A S C H -0 -D C
03:CH01-02-DC01_M01 on AS CH01-02-
DC01
Digital Outputs
Digital Outputs
1 2 3 4 5 6
7 8 9 10 11 12
UI-16 16 Universal In
CH01-02-DC01_M03
SXWUI16XX10001
U I1
R E T
U I2
U I3
R E T
U I4
U I5
R E T
U I6
U I7
R E T
U I8
U I9
R E T
U I1
U I1
R E T
U I1
U I1
R E T
U I1
U I1
R E T
U I1
CH01:CHILLER 01_Amps
DI:CHILLER 01_ChillerAlrm
FM:CHILLER 01_ChwrFlo
DI:CHILLER 01_IsoVlvSts DI:C-Pump178A_PmpAlarm
DI:C-Pump178C_PmpAlarm
CH01:CHILLER 02_Amps
DI:CHILLER 02_ChillerAlrm
FM:CHILLER 02_ChwrFlo
DI:CHILLER 02_IsoVlvSts
FM:DC 01_ChwrFlo
DI:DC 02_IsoVlvSts
Schneider Electric
SXW UI-16
F ro m :C H -0 -D C M o n A S C H -0 -D C
T o :C H -0 -D C M o n A S C H -0 -D C
05:CH01-02-DC01_M03 on AS CH01-02-
DC01
Universal Inputs
Universal Inputs
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16
UI-8/AO-V-4-H UI/AO(V) HAND
CH01-02-DC01_M02
SXWUI8V4H10001
V O
R E T
V O
R E T
V O
R E T
V O
R E T
U I1
R E T
U I2
U I3
R E T
U I4
U I5
R E T
U I6
U I7
R E T
U I8
AI:CP_ByPassFdbck
AO:CP_ByPassControl
Schneider Electric
SXW UI-8/AO-V-4-H
F ro m :C H -0 -D C M o n A S C H -0 -D C
T o :C H -0 -D C M o n A S C H -0 -D C
04:CH01-02-DC01_M02 on AS CH01-02-
DC01
Analog Outputs
Universal Inputs
1 2 3 4
1 2 3 4 5 6 7 8
Device Qty Part Number Description Vendor AS CH01-02-DC01 1 SXWASPXXX10001 SMARTX CONTROLLER AS-P Schneider Electric AS CH01-02- 1 SXWTBASW110002 TB-ASP-W1 TERM BASE ASP W1 Schneider Electric
DC01_1
CH01-02-DC01_M01 1 SXWDOA12H10001 DO-FA-12-H 12 DO FORMA HAND Schneider Electric CH01-02-DC01_M02 1 SXWUI8V4H10001 UI-8/AO-V-4-H UI/AO(V) HAND Schneider Electric CH01-02-DC01_M03 1 SXWUI16XX10001 UI-16 16 UNIVERSAL IN Schneider Electric CH01-02- 1 SXWTBIOW110001 TB-IO-W1 TERM BASE I/O W1 Schneider Electric
DC01_M01_1
CH01-02- 1 SXWTBIOW110001 TB-IO-W1 TERM BASE I/O W1 Schneider Electric
DC01_M02_1
CH01-02- 1 SXWTBIOW110001 TB-IO-W1 TERM BASE I/O W1 Schneider Electric
DC01_M03_1
PS CH01-02-DC01 1 SXWPS24VX10001 PS-24V POWER SUPPLY 24 VAC/VDC Schneider Electric PS CH01-02- 1 SXWTBPSW110001 TB-PS-W1 TERM BASE PWR SUP W1 Schneider Electric
DC01_1
h it e c t:
B K
S S E
Q U
E N
C E
F
P E
R A T
IO
N S .v s d
P A
R S
O N
S
F A
A B
C T H
V A
C E
Q U
IP
M
E
P L A
C E
M E
N T
S E
Q U
E N
C E O
F O
P S
C H
IL
L E
R S
J O
B N
U M
B E
R -0
S H
E E
T N
O
O F
R e v is io n s
2 4
C h a n g e
D a te
1 5
D a te
/2
/2
F
IL
E N
A M
E
D a te
D a te
E n g in e e r:
C o n tr a c to r:
D e s ig n e d b y
S o ft w a re b y
C h e c k e d b y
S tr e e t A d d re s s Z ip D ri v e S u it e -1
F o rt M y e rs
F L
P o s t O ff ic e B o x
F o rt M y e rs
F L
P H
.6
.1
F a x
.6
.5
1General:
The chilled water control system shall operate three chillers (CH-1 thru CH-3), and two Dry coolers (DC-1 and DC-2) and 3 Primary pumps (C-Pmp278A-C) as a “Variable-Flow” control sequence. All systems are redundant and shall operate as such. Programming shall permit any combination of chillers, dry coolers (Unit and staging) and loop pumps to be selected and utilized.
Chillers and Pumps operate as Lead/Lag/Standby system: The operator shall have the ability to select lead-lag-standby by placing the equipment in numerical order of operation (Staging).
1 = Lead
2 = Lag
3 = Standby
Redundant equipment shall alternate weekly on Tuesdays @09:30am to help ensure equal runtime on all equipment.
In normal mode, at least one Chiller or one Dry Cooler shall be in operation at all times. Chillers only, each chiller is equipped with onboard controls that will control to a given set point provided by the BMS. Dry coolers are staged as described later in this sequence.
Sequence to start any chiller / Dry cooler:
Open the respective isolation valve;
Upon verification that the valve is in open position (Via end switch);
Start the Lead Primary chilled water pump;
Upon verification of water flow for a minimum of 2 minutes (Adj.);
Enable lead chiller / Dry cooler.
Rotation: All routine rotations shall be programmed in a manner as to not interrupt operation. The rotated chiller, dry cooler or pump shall remain in operation until the new lead system is fully operational. Chillers and pumps shall be delayed by a minimum of 15 minutes.
Chiller staging - ADD
Lead chiller shall run until the control system senses the demand can no longer be satisfied by a single chiller. Lag chiller enables when:
Demand > 95% (adj.) for a time period of no less than 20 minutes (Adj.)
Chiller staging – DEDUCT
Lag chiller shall run until the control system senses the demand no longer requires the lag chiller. Lag chiller disables when:
Demand < 40% (adj.) for a time period of no less than 20 minutes (Adj.)
Demand: The chiller integration shall provide the actual chiller demand - If this data point is not available, demand shall be determined by: Measured amps / Full load rating (amps) * 100 = Demand %
Dry coolers:
When switching the system to Dry Cooler operation, the lead dry cooler shall be enabled and started before the Chiller is disabled. The following conditions are to be sensed by the control system before enabling any dry cooler:
a.Outdoor air temperature (OAT) drops below 38 o F (adj.) for more than 30 minutes (adj.)
b.Return water temperature is below 52 o F (adj.)
Staging: 2 stages of fans shall enable/disable on supply water temperature to maintain 45 o F (Adj.).
Stage 1 – ON = 1 o > set point / OFF = 3 o < set point
Stage 2 – ON = 3 o > set point / OFF = 1 o < set point
Dry cooler to chilled water: The system shall switch back to the chilled water system when the control system senses the following conditions:
a.Outdoor air temperature (OAT) rises above 40 o F (adj.) for more than 30 minutes (adj.)
b.Return water temperature rises above 50 o F (adj.) for more than 15 minutes (adj.)
Chiller / Dry cooler minimum flow control (By pass valve operation)
The chillers require a minimum flow of water, the flow rates are determined by the chiller / Dry cooler manufacture. The by-pass valve shall modulate open/close to maintain the minimum flow rate, as sensed by the flow meters at each active chiller / Dry cooler.
The minimum flow rate is determined by the number of active chillers / dry coolers and their respective minimum flow requirements.
Chilled water pumps: The building control system shall enable/disable as required – see chilled water sequence above. These pumps are self-sensing pumps and have onboard controls where the VFD’s maintain system differential pressure as sensed by the onboard controller.