Drawings~1.pdf
PDF 31 MB Posted
- Solicitation number
- S-58100-00010183
- Issued by
- Marion County, Oregon
About this file
This is a comprehensive set of construction drawings and project documentation for the City of Pendleton Well 11-11B project, prepared by civil engineer CONSOR and surveyor the City of Pendleton Department of Public Works. The project involves the construction of two potable water wells (Well 11 and Well 11B) with associated infrastructure including pump stations, flow meter vaults, piping systems, and support buildings. The drawing index contains 65 sheets encompassing general notes, symbols, abbreviations, erosion and sediment control plans, civil site layouts, architectural designs, structural details, HVAC specifications, plumbing and drainage plans, mechanical systems, electrical designs, and instrumentation diagrams. The project is located on SW Houtama Road in Pendleton, Oregon, near the Wastewater Treatment Resource Recovery Facility. Key infrastructure includes potable water lines ranging from 1 inch to 16 inches in diameter, pump-to-waste discharge systems, chlorine treatment facilities, and approximately 200 feet of replacement fencing. The project requires coordination with existing utilities including overhead power lines, irrigation systems, communication lines, sanitary sewer, and storm drains, with the Oregon Utility Notification Center contact number provided as 503-246-6699.
The project specifications mandate potholing and verification of all existing utilities prior to construction, with a minimum 24-hour notice requirement to the Owner's Representative for completion of potholing activities. All buried ductile iron piping requires mechanical joints and polyethylene encasement when within 10 feet of existing gas lines. Hydrostatic testing is required under specified pressure conditions, and all materials contacting potable water must be NSF-approved. Waterline connections to City facilities require a minimum 72-hour advance notice and temporary shutdowns must be coordinated with City personnel. The project includes erosion and sediment control measures in accordance with Oregon Department of Environmental Quality 1200-C permit requirements, with contractors responsible for maintaining sediment fencing, construction entrances, dust control, and vegetation establishment. Trench restoration utilizes imported structural fill Type A1 with 4-inch minimum thickness, and all disturbed property must be restored to existing or better condition. The project owner's representative is Bob Patterson, P.E., and the project superintendent is Tim Smith, both reachable through the City of Pendleton Department of Public Works.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Bid S-58100-00010183 RFI AttB.pdf | ||
| Bid S-58100-00010183 RFI AttA.pdf | ||
| Bid S-58100-00010183 RFI Document.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CITY OF PENDLETON
WELL 11-11B
INDEX OF DRAWINGS
21-3133
MARCH 2024
ATTENTION: OREGON LAW REQUIRES THE CONTRACTOR TO FOLLOW THE RULES
ADOPTED BY THE OREGON UTILITY NOTIFICATION CENTER. THOSE RULES ARE SET
FORTH IN OAR 952-001-0010 THROUGH OAR 952-001-0090. THE CONTRACTOR MAY
OBTAIN COPIES OF THE RULES BY CALLING THE UTILITY NOTIFICATION CENTER.
(NOTE: THE TELEPHONE NUMBER FOR THE OREGON UTILITY NOTIFICATION CENTER
IS 503-246-6699.)Know what'sbelow.
Callbefore you dig.
VICINITY MAP
SCALE: NTS
PROJECT
LOCATION
LOCATION MAP
SCALE: 1"=600'
CITY OF
PENDLETON
PROJECT
LOCATION
WESTGATE
MURIETTA RD
MCKAY CREEK
S W
H O
U
TA
M A R
D
SW HOUTAMA RD
UMAT
ILL
A R
IV
ER
SW RIVERVIEWDR
ONE SW COLUMBIA STREET, SUITE 1700
PORTLAND, OREGON 97204
P 503.225.9010
I:
\B
O I_
Pr oj ec ts
\2 1\
P en dl et on
W el l 1
1\ C A D
\S he et s\
-3
3-
O R -G
.d w g G
-1
/1 4/
:3
PM
J
EF
FR
Y.
O R
LA
N D
O
4.
1s
LM
S T ec h)
GENERAL
1 G-1 COVER SHEET, INDEX OF DRAWINGS, VICINITY
AND LOCATION MAPS
2 G-2 SYMBOLS AND LEGEND
3 G-3 ABBREVIATIONS
4 G-4 GENERAL NOTES
EROSION AND SEDIMENT CONTROL
5 ESC-1 OVERVIEW
6 ESC-2 SITE PLAN
7 ESC-3 DETAILS
CIVIL
8 C-1 SITE MAPPING AND GENERAL PROJECT OVERVIEW
9 C-2 SITE LAYOUT AND HORIZONTAL CONTROL PLAN
10 C-3 SITE GRADING PLAN
11 C-4 SITE PIPING PLAN
12 C-5 SITE PIPING PLAN CONT.
13 C-6 CITY OF PENDLETON STANDARD DETAILS
14 C-7 MISCELLANEOUS CIVIL DETAILS
ARCHITECTURAL
15 A-101 WELL 11B COVER SHEET
16 A-102 WELL 11B FLOOR PLAN
17 A-103 WELL 11B EXTERIOR ELEVATIONS
18 A-201 WELL 11 COVER SHEET
19 A-202 WELL 11 FLOOR PLAN
20 A-203 WELL 11 EXTERIOR ELEVATIONS
21 AD-001 TYPICAL DETAILS
22 AD-002 MISCELLANEOUS ARCHITECTURAL DETAILS
STRUCTURAL
23 S-001 GENERAL STRUCTURAL NOTES
24 S-002 QUALITY ASSURANCE PLAN (1)
25 S-003 QUALITY ASSURANCE PLAN (2)
26 S-101 WELL 11B FOUNDATION & FLOOR PLANS
27 S-102 WELL 11B ROOF PLAN, CEILING PLAN & BUILDING
SECTION
28 S-103 WELL 11B BUILDING SECTION & STRUCTURAL
DETAILS
29 S-104 WELL 11-11B STRUCTURAL DETAILS
30 S-201 WELL 11 FOUNDATION, FLOOR & ROOF FRAMING
PLAN
31 S-202 WELL 11 BUILDING SECTIONS
32 SD-001 CMU DETAILS
HVAC
33 H-101 WELL 11B FLOOR PLAN, SCHEDULES, AND
DETAILS
34 H-202 WELL 11 FLOOR PLAN, SCHEDULES, AND DETAILS
PLUMBING
35 P-101 WELL 11B DRAIN PLAN
36 P-202 WELL 11 DRAIN PLAN
MECHANICAL
37 M-001 MECHANICAL SCHEDULES
38 M-101 WELL 11B PERSPECTIVE
39 M-102 WELL 11B FLOOR PLAN
40 M-103 WELL 11B SECTIONS
41 M-104 WELL 11B FLOW METER VAULT PLAN AND
SECTION
42 M-105 WELL 11B CHLORINE AND WATER QUALITY
DETAILS
43 M-106 WELL 11B PUMP PEDESTAL DETAILS
44 M-107 WELL 11B FUTURE ASR FLOOR PLAN
45 M-201 WELL 11 PERSPECTIVE
46 M-202 WELL 11 FLOOR PLAN
47 M-203 WELL 11 SECTIONS
48 M-204 WELL 11 FLOW METER VAULT PLAN AND SECTION
49 M-205 WELL 11 PUMP PEDESTAL DETAILS
50 MD-001 TYPICAL DETAILS
ELECTRICAL
51 E-001 GENERAL NOTES AND ABBREVIATIONS
52 E-002 SYMBOLS
53 E-003 SITE PLAN - WELL 11 & 11B
54 E-004 ONE-LINE DIAGRAM AND LOAD SUMMARY - WELL
11 & 11B
55 E-005 CIRCUIT SCHEDULE
56 E-005A PANELBOARD SCHEDULES
57 E-006 POWER AND CONTROLS PLAN - WELL 11 & 11B
58 E-007 LIGHTING AND HVAC PLAN - WELL 11 & 11B
59 E-008 GROUNDING PLAN - WELL 11 & 11B
60 ED-001 DETAILS
61 ED-002 DETAILS - TYPICAL VFD WIRING DIAGRAM
INSTRUMENTATION
62 I-001 LEGEND, SYMBOLS AND ABBREVIATIONS 1
63 I-002 LEGEND, SYMBOLS AND ABBREVIATIONS 2
64 I-101 P&ID WELL 11B SYSTEM
65 I-201 P&ID WELL 11 SYSTEM
VALVE
CHAIN LINK FENCE
SCHEMATIC
FLEXIBLE COUPLING
FITTING (45°)
LONG SLEEVE
BLIND FLANGE
CAP
PIPE & FITTING SYMBOLS
PLANT SCHEMATIC
TEE UP
ECCENTRIC REDUCER
CONCENTRIC REDUCER
UNION
LATERAL DOWN
LATERAL UP
TEE DOWN
FLANGED COUPLING ADAPTER
90° BEND DOWN
90° BEND UP
MECHANICAL JOINT
GROOVED END JOINT
FLANGED JOINT
WELDED JOINT
PLANT
VALVE SYMBOLS
SURFACE ELEVATION
SIDEWALK
176.63 176.63
BLOW-OFF ASSEMBLY
AIR RELEASE ASSEMBLY
TREE DECIDUOUS
FIRE HYDRANT ASSEMBLY
PULL BOX/JUNCTION BOX
CATCH BASIN/FIELD INLET
LIGHT POST
BENCHMARK
SIGN
WATER METER
CLEAN-OUT
GUY WIRE
THRUST BLOCK
UTILITY POLE
MANHOLE
PROPOSED
STRUCTURE OR FACILITY
EDGE OF PAVEMENT/AC
CONTOUR MINOR
TREE/BUSH LINE
SANITARY SEWER LINE
DRAINAGE DITCH
SANITARY SEWER FORCE MAIN
EASEMENT/PROPERTY LINE
ROCK WALL
CONTOUR MAJOR
CURB
GUARDRAIL
CULVERT
BARBWIRE FENCE
CENTERLINE
STORM DRAIN
CABLE TELEVISION
TELEPHONE/TELEMETRY
TOPOGRAPHIC LEGEND
ELECTRICITY
GAS
WATERLINE
EXISTING
S/W
TREE TO BE REMOVED X
MAILBOX
AIR INJECTION ASSEMBLY
ABANDON PIPE
EDGE OF GRAVEL
TREE CONIFEROUS
RIGHT-OF-WAY
TEMPORARY SILT FENCE
SHEET FROM WHICH
DETAIL IS TAKEN *
SHEET WHERE SECTION
IS SHOWN *
SECTION AND DETAIL DESIGNATIONS
SECTION DESIGNATIONS DETAIL DESIGNATIONS
SCALE:
DETAIL
A
SCALE:
SECTION
A
* NOTE: IF PLAN AND SECTION FOR DETAIL CALL-OUT AND DETAIL ARE SHOWN
ON THE SAME DRAWING, DRAWING NUMBER IS REPLACED WITH A DASH.
** NOTE: STANDARD DETAILS ARE ON DETAIL SHEETS.
SECTION LETTER
DESIGNATION
SHEET FROM WHICH
SECTION IS TAKEN *
SECTION LETTER
DESIGNATION
DETAIL
NUMBER
12"DI W10"W
E
4"G
T
CATV
8"SS
6"FM
8"SD
E
4"G
T
CATV
8"SS
6"FM
8"SD
18"D
DETAIL CALL OUT
STANDARD DETAIL CALL OUT
C010
DETAIL
NUMBER
DOUBLE BALL FLEXIBLE
EXTENSION COUPLING
FLEXIBLE COUPLING W/
THRUST RING
VALVE NUMBER
PUSH-ON JOINT
(RUBBER GASKET)
PREVENTER W/ GATE VALVES
REDUCED PRESSURE BACKFLOW
HOSE BIBB
HOSE VALVE
RELIEF VALVE
NEEDLE VALVE
PRESSURE REDUCING VALVE
SOLENOID VALVE
BALL CHECK
PLUG VALVE (SIDE)
PLUG VALVE (TOP)
BALL VALVE
GATE VALVE
GLOBE VALVE
BUTTERFLY VALVE
SWING CHECK VALVE
S
V-100
V-500
V-700
V-200
V-300
V-300
V-400
V-401
V-1100
V-1200
V-800
V-600
V-1000
V-900
KNIFE GATE VALVE V-501
K
21-3133 MARCH 2024
CITY OF PENDLETON
WELL 11-11B
AS SHOWN of 65
G-2
SHEET
DG
BB
WRK
SYMBOLS AND LEGEND
GENERAL
NO. DATE BY REVISION
NOT TO SCALE
THEN DRAWING IS
NOT MEASURE 1"
IF THIS BAR DOES
NOTICE
CHECKED
DRAWN
DESIGNED
PROJECT NO.: SCALE: DATE:I:
\B
O I_
Pr oj ec ts
\2 1\
P en dl et on
W el l 1
1\ C A D
\S he et s\
-3
3-
O R -G
.d w g G
-2
/1 4/
:3
PM
J
EF
FR
Y.
O R
LA
N D
O
4.
1s
LM
S T ec h)
SHEET
20 1 of2 03/13/2024WRK BID SET
@ AT
AASHTO AMERICAN ASSOCIATION OF STATE
HIGHWAY & TRANSPORTATION OFFICIALS
AB ANCHOR BOLT
ABAN(D) ABANDON(ED)
ABS ACRYLONITRILE BUTADIENE STYRENE
ABV ABOVE / ALCOHOL BY VOLUME
AC ASPHALTIC CONCRETE
ACP ASPHALTIC CONCRETE PAVING
ADJ ADJUSTABLE
ADJC ADJACENT
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHR ANCHOR
AL ALUMINUM
ALT ALTERNATE
AMP AMPERE
ANSI AMERICAN NATIONAL STANDARDS
INSTITUTE
APPROX APPROXIMATE
APPVD APPROVED
APWA AMERICAN PUBLIC WORKS ASSOCIATION
ARCH ARCHITECTURAL
ARV AIR RELEASE VALVE
ASCE AMERICAN SOCIETY OF CIVIL
ENGINEERS
ASSN ASSOCIATION
ASSY ASSEMBLY
ASTM AMERICAN SOCIETY FOR TESTING
& MATERIALS
ATM ATMOSPHERE
AUTO AUTOMATIC
AUX AUXILIARY
AVE AVENUE
AVG AVERAGE
AWWA AMERICAN WATER WORKS ASSOCIATION
B&S BELL & SPIGOT
BC BOLT CIRCLE
BD BOARD
BETW BETWEEN
BF BOTH FACE
BFD BACKFLOW PREVENTION DEVICE
BFILL BACKFILL
BFV BUTTERFLY VALVE
BHP BRAKE HORSEPOWER
BKGD BACKGROUND
BLDG BUILDING
BLK BLOCK
BLVD BOULEVARD
BM BENCHMARK / BEAM
BMP BEST MANAGEMENT PRACTICES
BO BLOW-OFF
BOC BACK OF CURB
BS BOTH SIDES
BSMT BASEMENT
BTF BOTTOM FACE
BTU BRITISH THERMAL UNIT
BV BALL VALVE
BW BOTH WAYS
C CELSIUS
C TO C CENTER TO CENTER
CARV COMBINATION AIR RELEASE VALVE
CATV CABLE TELEVISION
CB CATCH BASIN
CCP CONCRETE CYLINDER PIPE
CCW COUNTER CLOCKWISE
CFM CUBIC FEET PER MINUTE
CFS CUBIC FEET PER SECOND
CHAN CHANNEL
CHEM CHEMICAL
CHFR CHAMFER
CHKV CHECK VALVE
CI CAST IRON
CIP CAST IRON PIPE
CIPC CAST IN PLACE CONCRETE
CISP CAST IRON SOIL PIPE
CJ CONSTRUCTION JOINT
CJP COMPLETE JOINT PENETRATION
CL OR C/L CENTER LINE
CL2 CHLORINE
CLG CEILING
CLJ CONTROL JOINT
CLR CLEAR
CLSM CONTROLLED LOW STRENGTH MATERIAL
CMP CORRUGATED METAL PIPE
CMU CONCRETE MASONRY UNIT
CND CONDUIT
CO CLEANOUT
COL COLUMN
COMB COMBINATION
CONC CONCRETE
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUOUS / CONTINUATION
CONTR CONTRACT(OR)
COORD COORDINATE
COP COPPER
CORP CORPORATION
CORR CORRUGATED
CP CONTROL POINT
CPLG COUPLING
CPVC CHLORINATED POLYVINYL CHLORIDE
CR CRUSHED ROCK
CS COMBINED SEWER
CSP CONCRETE SEWER PIPE
CT COURT
CTR CENTER
CU CUBIC
CULV CULVERT
CV CONTROL VALVE
CW CLOCKWISE / COLD WATER
CY CUBIC YARDS
CYL CYLINDER LOCK
D DRAIN
DC DIRECT CURRENT
DEFL DEFLECTION
DET DETAIL
DI DUCTILE IRON
DIA DIAMETER
DIM DIMENSION
DIR DIRECTION
DIST DISTANCE
DN DOWN
DR DRIVE
DS DOWNSPOUT
DWG DRAWING
DWL DOWEL
DWV DRAIN WASTE AND VENT
DWY DRIVEWAY
E OR ELEC ELECTRICAL
EA EACH
ECC ECCENTRIC
EF EACH FACE
EL ELEVATION
ELB ELBOW
ENCL ENCLOSURE
EOP EDGE OF PAVEMENT
EQ EQUAL
EQL SP EQUALLY SPACED
EQUIP EQUIPMENT
ESMT EASEMENT
EW EACH WAY
EXC EXCAVATE/EXCAVATION
EXIST EXISTING
EXP EXPANSION
EXP BT EXPANSION BOLT
EXP JT EXPANSION JOINT
EXT EXTERIOR
F FAHRENHEIT
F TO F FACE TO FACE
FAB FABRICATE
FB FLAT BAR
FCA FLANGED COUPLING ADAPTER
FCO FLOOR CLEANOUT
FD FLOOR DRAIN
FDN FOUNDATION
FEXT FIRE EXTINGUISHER
FF FAR FACE
FGL FIBERGLASS
FH FIRE HYDRANT
FIN FINISH(ED)
FIN GR FINISHED GRADE
FIPT FEMALE IRON PIPE THREAD
FITG FITTING
FL FLOOR LINE
FLEX FLEXIBLE
FLG FLANGE
FLL FLOW LINE
FLR FLOOR
FM FORCE MAIN
FO FIBER OPTIC
FOC FACE OF CONCRETE
FOF FACE OF FINISH
FOM FACE OF MASONRY
FOS FACE OF STUDS
FPM FEET PER MINUTE
FPS FEET PER SECOND
FRP FIBERGLASS REINFORCED PLASTIC
FT FEET / FOOT
FTG FOOTING
FUT FUTURE
FXTR FIXTURE
G GAS
GA GAUGE
GAL GALLON
GALV GALVANIZED
GC GROOVED COUPLING
GEN GENERATOR / GENERAL
GFA GROOVED FLANGE ADAPTER
GI GALVANIZED IRON
GIP GALVANIZED IRON PIPE
GJ GRIP JOINT
GL GLASS
GLV GLOBE VALVE
GND GROUND
GPD GALLONS PER DAY
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GPS GALLONS PER SECOND
GR GRADE
GR LN GRADE LINE
GRTG GRATING
GV GATE VALVE
GRVL GRAVEL
GYP GYPSUM
HB HOSE BIBB
HC HOLLOW CORE
HDPE HIGH DENSITY POLYETHYLENE
HDR HEADER
HDWE HARDWARE
HGR HANGER
HGT HEIGHT
HH HANDHOLD
HM HOLLOW METAL
HMAC HOT MIX ASPHALT CONCRETE
HNDRL HANDRAIL
HOA HAND-OFF-AUTO
HOR HAND-OFF-REMOTE
HORIZ HORIZONTAL
HP HIGH PRESSURE / HORSEPOWER
HPG HIGH PRESSURE GAS
HPT HIGH POINT
HR HOUR
HSB HIGH STRENGTH BOLT
HV HOSE VALVE
HVAC HEATING, VENTILATION, AIR
CONDITIONING
HWL HIGH WATER LINE
HWY HIGHWAY
HYD HYDRANT
HYDR HYDRAULIC
I&C INSTRUMENTATION & CONTROL
IAW IN ACCORDANCE WITH
ID INSIDE DIAMETER
IE INVERT ELEVATION
IF INSIDE FACE
IMPVT IMPROVEMENT
IN INCH
INCC INCLUDE(D)(ING)
INFL INFLUENT
INJ INJECTION
INSTL INSTALLATION / INSTALL
INSUL INSULATION
INTER INTERCEPTOR
INTR INTERIOR
INV INVERT
IP IRON PIPE
IPT IRON PIPE THREAD
IR IRON ROD
IRRIG IRRIGATION
JT JOINT
JUNC JUNCTION
KPL KICK PLATE
KVA KILOVOLT AMPERE
KW KILOWATT
KWY KEYWAY
L LENGTH
LAB LABORATORY
LAV LAVATORY
LB POUND
LF LINEAR FOOT
LIN LINEAL
LN LANE
LOC LOCATION
LONG LONGITUDINAL
LP LOW PRESSURE
LPT LOW POINT
LRG LARGE
LS LONG SLEEVE / LUMP SUM
LT LEFT
LVL LEVEL
LWL LOW WATER LINE
MAN MANUAL
MAT MATERIAL
MAX MAXIMUM
MCC MOTOR CONTROL CENTER
MCP MASTER CONTROL PANEL
MECH MECHANICAL
MET METAL
MFR MANUFACTURER
MGD MILLION GALLONS PER DAY
MH MANHOLE
MIN MINIMUM
MIPT MALE IRON PIPE THREAD
MISC MISCELLANEOUS
MJ MECHANICAL JOINT
MON MONUMENT / MONOLITHIC
MOT MOTOR
MP MILEPOST
MSL MEAN SEAL LEVEL
MTD MOUNTED
NA NOT APPLICABLE
NC NORMALLY CLOSED
NF NEAR FACE
NIC NOT IN CONTRACT
NO / NO. NORMALLY OPEN / NUMBER
NOM NOMINAL
NORM NORMAL
NRS NON-RISING STEM
NTS NOT TO SCALE
O TO O OUT TO OUT
OC ON CENTER
OD OUTSIDE DIAMETER
ODOT OREGON DEPARTMENT OF
TRANSPORTATION
OF OVERFLOW / OUTSIDE FACE
OPNG OPENING
OPP OPPOSITE
ORIG ORIGINAL
OVHD OVERHEAD
P&ID PROCESS & INSTRUMENTATION
DIAGRAM
PC POINT OF CURVE
PCC POINT OF COMPOUND CURVE
PCVC POINT OF CURVATURE ON
VERTICAL CURVE
PE PLAIN END
PERF PERFORATED
PERM PERMANENT
PERP PERPENDICULAR
PG PRESSURE GAUGE
PH PIPE HANGER
PI POINT OF INTERSECTION
PIVC POINT OF INTERSECTION ON
VERTICAL CURVE
PL OR P/L PROPERTY LINE / PLATE / PLASTIC
PLBG PLUMBING
PNL PANEL
POC POINT OF CURVATURE
POLY POLYETHYLENE
PP POWER POLE
PRC POINT OF REVERSE CURVATURE
PRCST PRECAST
PREP PREPARATION
PRESS PRESSURE
PRKG PARKING
PROP PROPOSED
PRV PRESSURE REDUCING VALVE
PS PUMP STATION
PSIG POUNDS PER SQUARE INCH GAUGE
PSL PIPE SLEEVE
PSPT PIPE SUPPORT
PT POINT OF TANGENCY
PTVC POINT OF TANGENCY ON VERTICAL
CURVE
PTW PUMP TO WASTE
PV PLUG VALVE
PVC POLYVINYL CHLORIDE
PVMT PAVEMENT
PW POTABLE WATER
PWR POWER
QTY QUANTITY
RAD RADIUS
RC REINFORCED CONCRETE
RCP REINFORCED CONCRETE PIPE
RD ROAD / ROOF DRAIN
RDCR REDUCER
RECIRC RECIRCULATION
REF REFERENCE
REINF REINFORCE(D)(ING)(MENT)
REQ'D REQUIRED
RES RESERVOIR
RESTR RESTRAINED
RFCA RESTRAINED FLANGE COUPLING
ADAPTER
RM ROOM
RND ROUND
RO ROUGH OPENING
R/W RIGHT-OF-WAY
RPBPD REDUCED PRESSURE BACKFLOW
PREVENTION DEVICE
RPM REVOLUTIONS PER MINUTE
RR RAILROAD
RST REINFORCED STEEL
RT RIGHT
SALV SALVAGE
SAN SANITARY
SC SOLID CORE
SCHED SCHEDULE
SD STORM DRAIN
SDL SADDLE
SDR STANDARD DIMENSION RATIO
SECT SECTION
SHLDR SHOULDER
SHT SHEET
SIM SIMILAR
SLP SLOPE
SLV SLEEVE
SOLN SOLUTION
SP SOIL PIPE / SEWER PIPE
SPCL SPECIAL
SPEC(S) SPECIFICATION(S)
SPG SPACING
SPL SPOOL
SPRT SUPPORT
SQ SQUARE
SQ FT SQUARE FOOT
SQ IN SQUARE INCH
SQ YD SQUARE YARD
SS SANITARY SEWER
SST STAINLESS STEEL
ST STREET
STA STATION
STD STANDARD
STL STEEL
STOR STORAGE
STR STRAIGHT
STRUCT STRUCTURE / STRUCTURAL
SUBMG SUBMERGED
SUCT SUCTION
SV SOLENOID VALVE
S/W SIDEWALK
SWD SIDEWATER DEPTH
SWGR SWITCH GEAR
SYMM SYMMETRICAL
SYS SYSTEM
T OR TEL TELEPHONE
T&B TOP & BOTTOM
TAN TANGENCY
TB THRUST BLOCK
TBM TEMPORARY BENCHMARK
TC TOP OF CONCRETE / TOP OF CURB
TCE TEMPORARY CONSTRUCTION EASEMENT
TDH TOTAL DYNAMIC HEAD
TEMP TEMPERATURE / TEMPORARY
T&G TONGUE & GROOVE
THK THICK / THICKNESS
THRD THREAD (ED)
THRU THROUGH
TP TEST PIT / TOP OF PAVEMENT /
TURNING POINT
TRANS TRANSITION
TSP TRI-SODIUM PHOSPHATE
TST TOP OF STEEL
TW TOP OF WALL
TYP TYPICAL
UG UNDERGROUND
UH UNIT HEATER
UN UNION
UON UNLESS OTHERWISE NOTED
USGS UNITED STATES GEOLOGIC SURVEY
V VENT / VOLT
VAC VACUUM
VB VACUUM BREAKER
VBOX VALVE BOX
VC VERTICAL CURVE
VERT VERTICAL
VFD VARIABLE FREQUENCY DRIVE
VOL VOLUME
VCP VITRIFIED CLAY PIPE
VTR VENT THROUGH ROOF
W WATER
W/ WITH
W/IN WITHIN
W/O WITHOUT
W/W WALL TO WALL
WD WOOD
WF WIDE FLANGE
WH WATER HEATER
WI WROUGHT IRON
WM WATER METER
WP WORKING POINT / WATERPROOFING
WS WATER SERVICE
WSDOT WASHINGTON STATE DEPARTMENT
OF TRANSPORTATION
WT WEIGHT
WTP WATER TREATMENT PLANT
WTRT WATERTIGHT
WWF WELDED WIRE FABRIC
WWTF WASTEWATER TREATMENT FACILITY
WWTP WASTEWATER TREATMENT PLANT
X SECT CROSS SECTION
XFMR TRANSFORMER
YD YARD DRAIN / YARD
YH YARD HYDRANT
YR YEAR
ZN ZINC
21-3133 MARCH 2024
CITY OF PENDLETON
WELL 11-11B
AS SHOWN of 65
G-3
SHEET
DG
BB
WRK
ABBREVIATIONS
GENERAL
NO. DATE BY REVISION
NOT TO SCALE
THEN DRAWING IS
NOT MEASURE 1"
IF THIS BAR DOES
NOTICE
CHECKED
DRAWN
DESIGNED
PROJECT NO.: SCALE: DATE:I:
\B
O I_
Pr oj ec ts
\2 1\
P en dl et on
W el l 1
1\ C A D
\S he et s\
-3
3-
O R -G
.d w g G
-3
/1 4/
:3
PM
J
EF
FR
Y.
O R
LA
N D
O
4.
1s
LM
S T ec h)
SHEET
GENERAL NOTES:
1. THE CONTRACTOR SHALL POTHOLE AND VERIFY LOCATIONS, ELEVATIONS, TYPES AND SIZES OF ALL EXISTING UTILITIES PRIOR TO CONSTRUCTING NEW PIPING FAR ENOUGH IN ADVANCE TO ALLOW NECESSARY ADJUSTMENTS IN GRADE AND SHALL NOTIFY OWNER'S REPRESENTATIVE OF NEED TO ADJUST PIPING INSTALLATION ACCORDINGLY. POTHOLING SHALL SUFFICIENTLY PRECEDE LAYING OF PIPE TO ALLOW REQUIRED ELEVATION ADJUSTMENTS TO BE ACCOMPLISHED WITHOUT REWORK. ELEVATION ADJUSTMENTS SHALL BE EXPECTED AND ARE INCIDENTAL TO THE WORK. DEFLECT PIPE AS REQUIRED AND WITHIN SPECIFIED
TOLERANCES TO AVOID EXISTING UTILITIES AND COMPLETE TIE-INS.
2. LOCATIONS OF EXISTING UTILITIES ARE BASED ON INFORMATION SUPPLIED BY THE UTILITIES AND CONSIDERED APPROXIMATE ONLY. AS REQUIRED BY STATE LAW, THE CONTRACTOR SHALL OBTAIN UTILITY
LOCATES PRIOR TO COMMENCING CONSTRUCTION.
3. CONTRACTOR SHALL PROVIDE OWNER'S REPRESENTATIVE WITH MINIMUM 24 HOURS NOTICE WHEN POTHOLING WILL BE COMPLETE. COORDINATE WITH OWNER'S REPRESENTATIVE TO REVIEW UTILITY INVESTIGATIONS AND TO MAKE APPROPRIATE ADJUSTMENTS FOR ANY ALIGNMENT CONFLICTS WHERE
CONNECTING TO EXISTING UTILITIES.
4. OREGON LAW REQUIRES THE CONTRACTOR TO FOLLOW THE RULES ADOPTED BY THE OREGON UTILITY NOTIFICATION CENTER. THOSE RULES ARE SET FORTH IN OAR 952-001-0010 THROUGH OAR 952-001-0090.
THE CONTRACTOR MAY OBTAIN COPIES OF THE RULES BY CALLING THE UTILITY NOTIFICATION CENTER. (NOTE:
THE TELEPHONE NUMBER FOR THE OREGON UTILITY NOTIFICATION CENTER IS 503-246-6699.)
5. NUMEROUS EXISTING OVERHEAD POWER LINES OCCUR IN THE VICINITY OF THE PROJECT. CONTRACTOR TO CONFORM TO CONDITIONS IN VICINITY OF OVERHEAD LINES AND COORDINATE ALL CONSTRUCTION
ACTIVITIES WITH PACIFIC LIGHT AND POWER REPRESENTATIVES.
6. PROVIDE "AS CONSTRUCTED" DRAWINGS INDICATING ALL CHANGES IN GRADE, ALIGNMENT, FITTINGS AND MATERIALS INSTALLED AND ANY OTHER UTILITIES OR OBSTACLES NOT SO INDICATED ON THESE PLANS.
7. AT THE END OF EACH WORK DAY, ALL OPEN TRENCHES SHALL BE BACKFILLED AND ALL TRENCHES SHALL EITHER BE TEMPORARILY PAVED OR FILLED TO THE SATISFACTION OF THE OWNER'S REPRESENTATIVE.
8. CONTRACTOR SHALL PROTECT ALL PROPERTY CORNERS, SURVEY MONUMENTS, AND CONTROL SURVEY MONUMENTS. ALL ITEMS DISTURBED DURING CONSTRUCTION SHALL BE REPLACED AT CONTRACTOR'S
EXPENSE, WITH APPROPRIATE SURVEY FILED WITH COUNTY SURVEYOR.
9. CONTRACTOR SHALL SUPPORT AND PROTECT AS NECESSARY ANY PIPE OR CONDUIT EXPOSED AS PART OF THE NEW PIPE TRENCH EXCAVATION. CONTRACTOR SHALL MAINTAIN ALL EXISTING UTILITIES IN SERVICE AT ALL TIMES AND SHALL COORDINATE WITH RESPECTIVE UTILITY COMPANIES TO MAINTAIN AND PROTECT
SERVICES.
10. ALL WORK SHALL BE CONFINED TO RIGHT-OF-WAY OR CITY PROPERTY, AS GENERALLY SHOWN IN THE
DRAWINGS AS AREA OF PROJECT IMPROVEMENTS.
11. ALL EXISTING FEATURES INCLUDING, BUT NOT LIMITED TO, ROADWAYS, STRUCTURES, LOTS, CURBS, SIDEWALKS, FENCES, WALLS, PLANTING, DITCHES, MAILBOXES, SIGNS, PIPING AND UTILITIES DISTURBED DURING CONSTRUCTION SHALL BE RESTORED TO AS GOOD OR BETTER THAN EXISTING CONDITION UNLESS OTHERWISE SPECIFIED. IF A UTILITY IS DAMAGED DURING CONSTRUCTION, THE CONTRACTOR SHALL CONTACT OWNER OF UTILITY FOR INSPECTION OF DAMAGE PRIOR TO REPAIRS. CONTRACTOR SHALL REPAIR ALL UTILITY SERVICES DAMAGED DURING CONSTRUCTION AND SUCH REPAIR SHALL BE CONSIDERED INCIDENTAL.
12. CONTRACTOR TO OBTAIN AND COMPLY WITH APPLICABLE CITY OF PENDLETON PERMITS AND
REQUIREMENTS FOR WORK IN, AND RESTORATION OF CITY ROADWAYS.
13. DO NOT REMOVE TREES UNLESS THEY HAVE BEEN PREVIOUSLY IDENTIFIED IN THE FIELD FOR REMOVAL PER OWNER'S REPRESENTATIVE. CONTRACTOR SHALL COORDINATE REMOVAL OF IMPACTED TREES WITH ADJACENT HOMEOWNER WITH REGARDS TO TREE CUTTING, REMOVAL, FIREWOOD RETENTION AND TREE REPLACEMENT.
OWNER:
CITY OF PENDLETON, DEPT OF PUBLIC WORKS
500 SW DORION AVENUE
PENDLETON, OR 97801
OWNER'S REPRESENTATIVE:
BOB PATTERSON, P.E.
E: BOB.PATTERSON@PENDLETONOR.GOV
P: 541-966-0202 F: 541-966-0251
OWNER'S PROJECT SUPERINTENDENT:
TIM SMITH
E: TIM.SMITH@PENDLETONOR.GOV
P: 541-379-1195 F: 541-966-0251
CIVIL ENGINEER:
CONSOR
345 BOBWHITE COURT, SUITE 230
BOISE, ID 83706
CONTACT: WILL KIRBY, P.E.
E: WILL.KIRBY@CONSORENG.COM
P: 208-947-9033
PROJECT CONTACTS:
TOPOGRAPHIC SURVEY NOTES:
1. SURVEY WAS COMPLETED BY THE CITY OF PENDLETON. ELEVATIONS ARE BASED ON NGVD 1929 DATUM.
HORIZONTAL COORDINATES ARE LOCAL CITY OF PENDLETON GRID SYSTEM.
2. UTILITY INFORMATION SHOWN HEREIN IS COMPILED FROM FIELD OBSERVED SURFACE FEATURES, AND FIELD LOCATED PAINT MARK "LOCATES" PERFORMED BY OTHERS. SURVEYOR MAKES NO GUARANTEE THAT UTILITIES SHOWN HEREIN COMPRISE ALL POSSIBLE UTILITIES IN THE AREA NOR WARRANTS THAT UTILITIES ARE IN THE
EXACT LOCATIONS INDICATED.
3. THIS TOPOGRAPHIC SURVEY WAS PERFORMED WITHOUT THE BENEFIT OF A CURRENT TITLE REPORT, AND THEREFORE DOES NOT PURPORT TO TO SHOW ALL EASEMENTS, ENCUMBRANCES, OR RESTRICTIONS OF
RECORD, IF ANY.
SURVEYOR:
CITY OF PENDLETON, DEPT OF PUBLIC WORKS
500 SW DORION AVENUE
PENDLETON, OR 97801
CONTACT: WAYNE GREEN
E: WAYNE.GREEN@PENDLETONOR.GOV
P: 541-966-0243 F: 541-966-0251
1. RESTRAIN ALL VALVES, TEES, BENDS, AND FITTINGS UNLESS OTHERWISE NOTED. ALL BURIED FITTINGS TO
BE MECHANICAL JOINT UNLESS OTHERWISE NOTED.
2. ALL FLANGED CONNECTIONS SHALL CONFORM TO THE REQUIREMENTS OF AWWA C115 AND C207, LATEST
EDITION.
3. PROVIDE POLYETHYLENE ENCASEMENT FOR ALL DUCTILE IRON PIPING ACCORDING TO ANSI/AWWA
C105/A21.5 AND WHEN NEW PIPING IS WITHIN 10' HORIZONTALLY OF EXISTING GAS LINES.
4. ALL COATINGS AND MATERIALS SPECIFIED HEREIN THAT COME IN CONTACT WITH POTABLE WATER SHALL BE
NATIONAL SANITATION FOUNDATION (NSF) APPROVED.
5. ALL PIPING SHALL BE TESTED UNDER A HYDROSTATIC TEST PRESSURE AS STATED IN THE SPECIFICATIONS, MEASURED FROM THE LOWEST POINT ALONG THE TEST SECTION OR AS SHOWN ON THE PLANS. ALL VALVES, FITTINGS, AND PIPING SHALL BE SUITABLE FOR TEST PRESSURES.
6. WHERE VERTICAL BENDS ARE NOT SHOWN, CONTRACTOR IS TO DEFLECT PIPE TO ACHIEVE VERTICAL ADJUSTMENTS AS NEEDED. THE MAXIMUM ALLOWABLE DEFLECTION SHALL NOT EXCEED ONE-HALF OF THE
MAXIMUM INSTALL DEFLECTION SPECIFIED.
7. CONTRACTOR SHALL PROVIDE TEMPORARY TAPS, BLOW-OFFS, AND THRUST BLOCKING AS REQUIRED TO FACILITATE FLUSHING, TESTING, AND DISINFECTION OF WATERLINES. REMOVE TEMPORARY TEST TAPS UPON COMPLETION OF DISINFECTION, AND REPLACE WITH STERILIZED TEMPORARY PLUGS. TEMPORARY PLUGS
SHALL BE REMOVED TO MAKE FINAL CONNECTIONS TO SERVICE LINES.
8. CONNECTIONS TO CITY WATERLINES MAY REQUIRE TEMPORARY SHUTDOWNS OF CITY FACILITIES. THE CONTRACTOR SHALL COORDINATE THIS WORK WITH THE CITY AND PROVIDE A MINIMUM OF 72 HOURS ADVANCE NOTICE PRIOR TO PERFORMING WATERLINE TIE-IN WORK. CONTRACTOR TO VERIFY WITH THE CITY IF CITY WATER LINES ARE TO BE TAKEN OUT OF SERVICE PRIOR TO PERFORMING THIS WORK. OPERATION OF
VALVES SHALL BE BY CITY PERSONNEL ONLY.
9. WHERE A WATERLINE CROSSES A SANITARY SEWER LINE, ONE PIPE LENGTH OF THE WATERLINE MUST BE
CENTERED AT THE CROSSING.
WATER NOTES:
21-3133 MARCH 2024
CITY OF PENDLETON
WELL 11-11B
AS SHOWN of 65
G-4
SHEET
DG
BB
WRK
GENERAL NOTES
GENERAL
NO. DATE BY REVISION
NOT TO SCALE
THEN DRAWING IS
NOT MEASURE 1"
IF THIS BAR DOES
NOTICE
CHECKED
DRAWN
DESIGNED
PROJECT NO.: SCALE: DATE:I:
\B
O I_
Pr oj ec ts
\2 1\
P en dl et on
W el l 1
1\ C A D
\S he et s\
-3
3-
O R -G
.d w g G
-4
/1 4/
:3
PM
J
EF
FR
Y.
O R
LA
N D
O
4.
1s
LM
S T ec h)
SHEET
NO. DATE BY REVISION
NOT TO SCALE
THEN DRAWING IS
NOT MEASURE 1"
IF THIS BAR DOES
NOTICE
CHECKED
DRAWN
DESIGNED
PROJECT NO.: SCALE: DATE:I:
\B
O I_
Pr oj ec ts
\2 1\
P en dl et on
W el l 1
1\ C A D
\S he et s\
-3
3-
O R -E
S C .d w g
ES
C -1
/1
/2
4:
P
M J
EF
FR
Y.
O
R
LA
N D
O
4.
1s
LM
S T ec h)
SHEET
20 1 of2 03/13/2024WRK BID SET
PLAN
SCALE: 1"=20'
HOUTAMA RD
AREA OF PROJECT IMPROVEMENTS
COMMERCIAL CONST ENTRANCE
SEE DET DWG 4-13, SHT ESC-3
CONSTRUCTION STAGING AND STOCKPILING AREA
EROSION AND SEDIMENT CONTROL GENERAL NOTES:
1. CONTRACTOR SHALL PREPARE, SUBMIT, AND ACQUIRE AN OREGON DEPARTMENT OF ENVIRONMENTAL QUALITY (DEQ) 1200-C EROSION CONTROL PLAN AND PERMIT PRIOR TO BEGINNING ANY SITE DISTURBING ACTIVITY. IF DISTURBING GREATER THAN ONE ACRE OF LAND AS PART OF THIS PROJECT, CONTRACTOR SHALL PROVIDE
PAYMENT FOR ALL PERMIT FEES.
2. EMERGENCY EROSION CONTROL MATERIALS MUST BE KEPT ON SITE AT ALL TIMES.
3. INSTALL, INSPECT, CLEAN, AND MAINTAIN SEDIMENT FENCE TO PREVENT SEDIMENT LADEN WATER FROM LEAVING THE SITE THROUGHOUT CONSTRUCTION. SEDIMENT FENCE SHALL BE INSTALLED PARALLEL TO SLOPE CONTOURS. ADDITIONAL SEDIMENT FENCE MAY BE REQUIRED BASED ON SITE CONDITIONS AND MEANS AND METHODS DEVELOPED BY CONTRACTOR. OVERLAY SEDIMENT FENCE 6" MINIMUM AND TURN LAST 6 FEET OF
FENCE UPSLOPE (TYPICAL).
4. INSPECT, CLEAN, AND MAINTAIN GRAVEL CONSTRUCTION ENTRANCE TO PREVENT SEDIMENT AND SEDIMENT
LADEN WATER FROM LEAVING THE SITE THROUGHOUT CONSTRUCTION.
5. ADDITIONAL TRACKING CONTROL MEASURES SUCH AS A WHEEL WASH MAY BE NECESSARY IF CONSTRUCTION
ENTRANCE IS NOT SUFFICIENT.
6. ON-SITE RUNOFF ACCUMULATION INTO LOW POINTS SHALL BE PUMPED BY THE CONTRACTOR TO A SUITABLE
LOCATION, IF REQUIRED.
7. CONTRACTOR SHALL INSTALL AND MAINTAIN EROSION/SEDIMENTATION CONTROL DURING CONSTRUCTION (ANY
TIME OF YEAR) IN ACCORDANCE WITH THE DEQ EROSION PREVENTION AND SEDIMENT CONTROL
REQUIREMENTS, THE STANDARD CONSTRUCTION SPECIFICATIONS FOR THIS PROJECT AND THE EROSION CONTROL NOTES INCLUDED BELOW AND WITHIN THESE PLANS. IF DISCREPANCIES BETWEEN STANDARDS
OCCUR, THE MORE STRINGENT REGULATION SHALL APPLY.
8. THE IMPLEMENTATION OF EROSION/SEDIMENTATION CONTROL (ESC) PLANS AND THE CONSTRUCTION, MAINTENANCE, REPLACEMENT, AND UPGRADING OF THESE ESC FACILITIES IS THE RESPONSIBILITY OF THE CONTRACTOR UNTIL ALL CONSTRUCTION IS COMPLETED AND APPROVED AND VEGETATION/LANDSCAPING IS
ESTABLISHED.
9. THE BOUNDARIES OF THE LIMITS OF WORK SHALL BE CLEARLY FLAGGED IN THE FIELD PRIOR TO CONSTRUCTION. DURING THE CONSTRUCTION PERIOD, NO DISTURBANCE BEYOND THE FLAGGED LIMITS OF WORK SHALL BE PERMITTED. THE FLAGGING SHALL BE MAINTAINED BY THE CONTRACTOR FOR THE DURATION
OF CONSTRUCTION.
10. ESC FACILITIES MUST BE CONSTRUCTED IN CONJUNCTION WITH ALL CLEARING AND GRADING ACTIVITIES, AND IN SUCH A MANNER AS TO ENSURE THAT SEDIMENT AND SEDIMENT LADEN WATER DO NOT ENTER THE
DRAINAGE SYSTEM, ROADWAYS, OR VIOLATE APPLICABLE WATER STANDARDS.
11. THE ESC FACILITIES SHALL BE INSPECTED DAILY BY THE CONTRACTOR AND MAINTAINED AS NECESSARY TO
ENSURE THEIR CONTINUED FUNCTIONALITY.
12. THE ESC FACILITIES ON INACTIVE SITES SHALL BE INSPECTED AND MAINTAINED A MINIMUM OF ONCE A MONTH
OR WITHIN 24 HOURS FOLLOWING A STORM EVENT.
13. STABILIZED CONSTRUCTION ENTRANCES SHALL BE INSTALLED AT THE BEGINNING OF CONSTRUCTION AND MAINTAINED FOR THE DURATION OF THE PROJECT. ADDITIONAL MEASURES MAY BE REQUIRED TO ENSURE THAT
ALL PAVED AREAS ARE KEPT CLEAN FOR THE DURATION OF THE PROJECT.
14. CONTRACTOR SHALL PROVIDE DUST CONTROL AS REQUIRED.
15. SEEDING SHALL BE PERFORMED NO LATER THAN SEPTEMBER 1 FOR EACH PHASE OF CONSTRUCTION. ROUGHEN
AND SEED ALL DISTURBED SURFACES OUTSIDE OF CRUSHED ROCK SURFACING TOP DRESSING.
16. IF THERE ARE EXPOSED SOILS OR SOILS NOT FULLY STABILIZED FROM NOVEMBER 1 THROUGH APRIL 30, THE WET WEATHER EROSION CONTROL MEASURES WILL BE IN EFFECT ACCORDING TO THE OREGON DEQ TECHNICAL
GUIDANCE HANDBOOK.
17. ESC MEASURES SHALL BE REMOVED BY THE CONTRACTOR WHEN VEGETATION IS FULLY ESTABLISHED.
18. CONTRACTOR SHALL PREPARE AND SUBMIT A DE-WATERING PLAN FOR PROPER DISPOSAL OF ALL WATER RESULTING FROM EXCAVATION AT THE PROJECT SITE. SEE SPECIFICATION FOR DE-WATERING REQUIREMENTS.
19. COMPLY WITH APPLICABLE OREGON DEQ DUST RULES (DIVISION 208) DURING EXCAVATION AND/OR
DEMOLITION WORK.
https://secure.sos.state.or.us./oard/displayDivisionRules.action?selectedDivision=1533
20. THE OWNER AND OPERATOR OF THE ROCK CRUSHER AND ASPHALT PLANT THAT PROVIDES MATERIAL FOR THE
PROJECT SHALL OPERATE UNDER AN AIR QUALITY PERMIT.
LEGEND
PRESERVE NATURAL VEGETATION AND
TEMPORARY SEEDING AREA
21-3133 MARCH 2024
CITY OF PENDLETON
WELL 11-11B
AS SHOWN of 65
ESC-1
SHEET
WRK
BAW
DG
OVERVIEW
EROSION AND SEDIMENT CONTROL
NO. DATE BY REVISION
NOT TO SCALE
THEN DRAWING IS
NOT MEASURE 1"
IF THIS BAR DOES
NOTICE
CHECKED
DRAWN
DESIGNED
PROJECT NO.: SCALE: DATE:I:
\B
O I_
Pr oj ec ts
\2 1\
P en dl et on
W el l 1
1\ C A D
\S he et s\
-3
3-
O R -E
S C .d w g
ES
C -2
/1
/2
4:
P
M J
EF
FR
Y.
O
R
LA
N D
O
4.
1s
LM
S T ec h)
SHEET
20 1 of2 03/13/2024WRK BID SET
PLAN
SCALE: 1"=10'
GRADING, UTILITY EROSION, AND SEDIMENT CONSTRUCTION NOTES:
1. SEED USED FOR TEMPORARY OR PERMANENT SEEDING SHALL BE COMPOSED OF ONE OF THE
FOLLOWING MIXTURES, UNLESS OTHERWISE AUTHORIZED:
A. VEGETATED CORRIDOR AREAS REQUIRE NATIVE SEED MIXES. SEE RESTORATION PLAN
FOR APPROPRIATE SEED MIX.
B. DWARF GRASS MIX (MINIMUM 100 LB/AC)
a. DWARF PERENNIAL RYEGRASS (80% BY WEIGHT)
b. CREEPING RED FESCUE (20% BY WEIGHT)
C. STANDARD HEIGHT GRASS MIX (MINIMUM 100 LB/AC)
a. ANNUAL RYEGRASS (40% BY WEIGHT)
b. TURF-TYPE FESCUE (60% BY WEIGHT)
2. SLOPES AND DISTURBED AREA TO RECEIVE TEMPORARY OR PERMANENT SEEDING SHALL HAVE
THE SURFACE ROUGHENED BY MEANS OF TRACK-WALKING OR THE USE OF OTHER APPROVED
IMPLEMENTS. SURFACE ROUGHENING IMPROVES SEED BEDDING AND REDUCES RUN-OFF
VELOCITY.
3. LONG TERM SLOPE AND DISTURBED AREAS STABILIZATION MEASURES SHALL INCLUDE THE
ESTABLISHMENT OF PERMANENT VEGETATIVE COVER VIA SEEDING WITH APPROVED MIX AND
APPLICATION RATE. SEE SPECIFICATIONS. IN ADDITION, ALL SLOPES OF 2:1 OR GREATER SHALL
RECEIVE MATTING.
4. SEEDING SHALL BE PERFORMED NO LATER THAN SEPTEMBER 1 FOR EACH PHASE OF
CONSTRUCTION. ROUGHEN AND SEED ALL DISTURBED SURFACES OUTSIDE OF CRUSHED ROCK
SURFACING TOP DRESSING.
5. TEMPORARY SLOPE AND DISTURBED AREA STABILIZATION MEASURES SHALL INCLUDE:
COVERING EXPOSED SOIL WITH PLASTIC SHEETING, STRAW MULCHING, WOOD CHIPS, OR
OTHER APPROVED MEASURES, IN ACCORDANCE WITH SECTION 31 22 13, ROUGH GRADING.
6. STOCKPILED SOIL OR STRIPPINGS SHALL BE HAULED OFFSITE. DURING "WET WEATHER"
PERIODS, STOCKPILES SHALL BE COVERED WITH PLASTIC SHEETING OR STRAW MULCH.
SEDIMENT FENCE IS REQUIRED AROUND THE PERIMETER OF THE STOCKPILE.
7. EXPOSED CUT OR FILL AREAS SHALL BE STABILIZED THROUGH THE USE OF TEMPORARY
SEEDING AND MULCHING, EROSION CONTROL BLANKETS OR MATS, MID-SLOPE SEDIMENT
FENCES OR WATTLES, OR OTHER APPROPRIATE MEASURES. SLOPES EXCEEDING 25% MAY
REQUIRE ADDITIONAL EROSION CONTROL MEASURES.
8. AREAS SUBJECT TO WIND EROSION SHALL USE APPROPRIATE DUST CONTROL MEASURES
INCLUDING THE APPLICATION OF A FINE SPRAY OF WATER, PLASTIC SHEETING, STRAW
MULCHING, OR OTHER APPROVED MEASURES.
9. CONSTRUCTION ENTRANCES SHALL BE INSTALLED AT THE BEGINNING OF CONSTRUCTION AND
MAINTAINED FOR THE DURATION OF THE PROJECT. ADDITIONAL MEASURES INCLUDING, BUT
NOT LIMITED TO, TIRE WASHES, STREET SWEEPING, AND VACUUMING MAY BE REQUIRED TO
INSURE THAT ALL PAVED AREAS IN THE VICINITY OF THE SITE USED FOR HAULING SOIL ARE
KEPT CLEAN FOR THE DURATION OF THE PROJECT.
10. SATURATED MATERIALS THAT ARE HAULED OFF-SITE MUST BE TRANSPORTED IN WATER-TIGHT
TRUCKS TO ELIMINATE SPILLAGE OF SEDIMENT AND SEDIMENT-LADEN WATER.
11. AN AREA SHALL BE PROVIDED FOR THE WASHING OUT OF CONCRETE TRUCKS IN A LOCATION
THAT DOES NOT PROVIDE RUN-OFF THAT CAN ENTER THE STORM WATER SYSTEM. IF THE
CONCRETE WASH-OUT AREA CAN NOT BE CONSTRUCTED GREATER THAN 50' FROM ANY
DISCHARGE POINT, SECONDARY MEASURES SUCH AS BERM OR TEMPORARY SETTLING PITS MAY
BE REQUIRED. THE WASH-OUT SHALL BE LOCATED WITHIN SIX FEET OF TRUCK ACCESS AND BE
CLEANED WHEN IT REACHES 50% OF THE CAPACITY.
EROSION AND SEDIMENT CONTROL BMP IMPLEMENTATION:
1. ALL BASE ESC MEASURES (INLET PROTECTION, PERIMETER SEDIMENT CONTROL, GRAVEL CONSTRUCTION ENTRANCES, ETC). MUST BE IN PLACE, FUNCTIONAL, AND APPROVED IN AN INITIAL INSPECTION, PRIOR TO
COMMENCEMENT OF CONSTRUCTION ACTIVITIES.
2. "STOCK PILE AREA" SHALL BE DESIGNATED PRIOR TO EXCAVATION CUT ACTIVITIES. ALL EXCAVATED
MATERIALS SHALL BE HAULED OFFSITE.
3. ALL "SEDIMENT BARRIERS (TO BE INSTALLED AFTER GRADING)" SHALL BE INSTALLED IMMEDIATELY
FOLLOWING ESTABLISHMENT OF FINISHED GRADE AS SHOWN ON THESE PLANS.
4. LONG TERM SLOPE STABILIZATION MEASURES "INCLUDING SEEDING, JUTE MATTING, WATTLES, AND ROCK
CHECK DAMS" SHALL BE IN-PLACE OVER ALL EXPOSED SOILS BY OCTOBER 1.
EXISTING CONTOURS (1')
EXISTING CONTOURS (5')
PROPOSED CONTOURS (1')
PROPOSED CONTOURS (5')
DRAINAGE FLOW DIRECTION
SEDIMENT FENCING
W/ PLASTIC MESH FENCE
STRAW WATTLES PER
DETAIL ON SHT ESC-3
LEGEND
TYPICAL EROSION CONTROL MEASURES
21-3133 MARCH 2024
CITY OF PENDLETON
WELL 11-11B
AS SHOWN of 65
ESC-2
SHEET
DG
BB
WRK
SITE PLAN
EROSION AND SEDIMENT CONTROL
PRESERVE NATURAL VEGETATION
AND TEMPORARY SEEDING AREA
GRADING OUTSIDE GRAVEL AREAS
SHALL BE PERMANENTLY SEEDED,
SEE SITE LAYOUT SHT C-2
PROTECT STEEP SLOPES W/
STRAW WATTLES
PROTECT DRAINAGE DITCH
W/ STRAW WATTLES
DISCHARGE LOCATION SHALL BE
PERMANENTLY SEEDED
EXIST GRAVEL ROAD AND WELL SITE
PROPERTY LINE
STOCKPILE LOCATION SHALL BE
PERMANENTLY SEEDED
NO. DATE BY REVISION
NOT TO SCALE
THEN DRAWING IS
NOT MEASURE 1"
IF THIS BAR DOES
NOTICE
CHECKED
DRAWN
DESIGNED
PROJECT NO.: SCALE: DATE:I:
\B
O I_
Pr oj ec ts
\2 1\
P en dl et on
W el l 1
1\ C A D
\S he et s\
-3
3-
O R -E
S C .d w g
ES
C -3
/1
/2
4:
P
M J
EF
FR
Y.
O
R
LA
N D
O
4.
1s
LM
S T ec h)
SHEET
20 1 of2 03/13/2024WRK BID SET
21-3133 MARCH 2024
CITY OF PENDLETON
WELL 11-11B
AS SHOWN of 65
ESC-3
SHEET
DG
BB
WRK
DETAILS
EROSION AND SEDIMENT CONTROL
IRR
IR
R
IRR
OHP
OHP
CO
M
COM
CO
M
COMCOM
OHP
O H
P
OHP
O H
P O
H P
O H
P O
H P
OHP
FM
FM
FM
NO. DATE BY REVISION
NOT TO SCALE
THEN DRAWING IS
NOT MEASURE 1"
IF THIS BAR DOES
NOTICE
CHECKED
DRAWN
DESIGNED
PROJECT NO.: SCALE: DATE:I:
\B
O I_
Pr oj ec ts
\2 1\
P en dl et on
W el l 1
1\ C A D
\S he et s\
-3
3-
O R -C
.d w g C -1
/1
/2
3:
P
M J
EF
FR
Y.
O
R
LA
N D
O
4.
1s
LM
S T ec h)
SHEET
20 1
NOTES:
1. THIS SHEET FOR INFORMATIONAL PURPOSES ONLY TO
PROVIDE OVERVIEW OF EXISTING ROADWAYS, EASEMENTS,
AND PROPOSED WELL SITE IN RELATION TO PROJECT AREA
AND DOES NOT IDENTIFY WORK OR MATERIALS REQUIRED
FOR CONSTRUCTION.
2. NO CONSTRUCTION TRUCK STAGING OR PARKING SHALL
BE ALLOWED ON SW HOUTAMA RD.
3. THE CONTRACTOR SHALL BE SOLELY AND COMPLETELY
RESPONSIBLE FOR CONDITIONS OF THE PROJECT SITE,
INCLUDING SAFETY OF ALL PERSONS AND PROPERTY,
DURING AND IN RELATION TO PERFORMANCE OF THE WORK.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR KEEPING
PROJECT CONSTRUCTION AREAS CLEAN OF DEBRIS, SAFE &
SECURE AT ALL TIMES. THIS REQUIREMENT SHALL APPLY
CONTINUOUSLY AND NOT BE LIMITED TO NORMAL WORKING
HOURS.
4. COORDINATE WITH WWTRRF STAFF TO LOCATE UTILITIES
IN PASTURE
5. FOR SITE GRADING PLAN, SEE SHEET C-3
6. FOR SITE PIPING PLAN, SEE SHEETS C-4 AND C-5
7. FOR SITE ESC AND PROJECT BOUNDARY, SEE SHEET ESC-1
CONSTRUCTION
STAGING AREA
SW 28TH ST
PROPOSED WELL 11B
SCALE: 1"=80'
PLAN
21-3133 MARCH 2024
CITY OF PENDLETON
WELL 11-11B
AS SHOWN of 65
C-1
SHEET
DG
BB
WRK
PROJECT OVERVIEW
SITE MAPPING AND GENERAL
CIVIL
TERESA EILERS
4362 SW MOUNTAMA RD
DOROTHY M NORDEN
P.O. BOX 727
PENDLETON, OR
ROD C ANDERSON
4201 SW 28TH DR
CITY OF PENDLETON
WASTEWATER TREATMENT
RESOURCE RECOVERY
FACILITY (WWTRRF)
SW HOUTAMA ROAD
WATERLINE PROJECT
(BY OTHERS)
ESTIMATED COM
LINES, FIELD LOCATE
ESTIMATED OHP,
FIELD LOCATE
ESTIMATED IRRIGATION,
FIELD LOCATE, SEE
NOTE 4
ESTIMATED FORCEMAIN,
FIELD LOCATE, SEE
NOTE 4
EXISTING WELL 11
WELL HEAD
PROPOSED WELL 11
NO. DATE BY REVISION
NOT TO SCALE
THEN DRAWING IS
NOT MEASURE 1"
IF THIS BAR DOES
NOTICE
CHECKED
DRAWN
DESIGNED
PROJECT NO.: SCALE: DATE:I:
\B
O I_
Pr oj ec ts
\2 1\
P en dl et on
W el l 1
1\ C A D
\S he et s\
-3
3-
O R -C
.d w g C -1
/1
/2
3:
P
M J
EF
FR
Y.
O
R
LA
N D
O
4.
1s
LM
S T ec h)
SHEET
FACILITY LAYOUT POINTS
PT #
DESCRIPTION
WELL 11B WELL HEAD (BY OTHERS)
S CORNER OF WELL 11B
N CORNER OF WELL 11B
E CORNER OF WELL 11B FM VAULT
W CORNER OF WELL 11B FM VAULT
S CORNER OF WELL 11
N CORNER OF WELL 11
S CORNER OF WELL 11 FM VAULT
N CORNER OF WELL 11 FM VAULT
NORTHING
N:50126.95
N:50096.89
N:50133.94
N:50102.32
N:50098.27
N:50153.22
N:50169.94
N:50147.82
N:50153.69
EASTING
E:35457.38
E:35469.30
E:35453.47
E:35486.09
E:35475.93
E:35495.96
E:35478.52
E:35479.23
E:35475.96
ELEVATION
1004.80
1004.80
1004.80
1004.51
1004.68
1005.00
1005.12
1004.77
1004.85
FENCE LAYOUT POINTS
PT #
NORTHING
N:50162.44
N:50164.56
N:50090.04
N:50075.14
N:50074.34
EASTING
E:35463.40
E:35455.89
E:35434.80
E:35487.37
E:35494.76 X
X X
X X
X
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
IRR
CO
M
O H
P
OHP
O H
P
O H
P
FM
1004.25
1004.50
1004.75
1004.75
1004.50
.2
.7
.5
.2
1005.25
1005.50
1001 1000
REINSTALL CORNER
POSTS
DEMO FENCE.
SALVAGE CORNER
POSTS AND GATEAPPROX TRANSFORMER LOCATION,
SEE ELECTRICAL. TRANSFORMER
SHALL BE INSTALLED W/ CLEARANCES
AND BOLLARDS PER PACIFIC POWER
REMOVE TREE
REPLACE 200' OF FENCE, IN
KIND OR BETTER CENTERED ON
PTW DISCHARGE, SEE SHT C-4
FURNISH AND INSTALL
WELDED PIPE FENCE
CORNER, SEE NOTE 2
NO. DATE BY REVISION
NOT TO SCALE
THEN DRAWING IS
NOT MEASURE 1"
IF THIS BAR DOES
NOTICE
CHECKED
DRAWN
DESIGNED
PROJECT NO.: SCALE: DATE:I:
\B
O I_
Pr oj ec ts
\2 1\
P en dl et on
W el l 1
1\ C A D
\S he et s\
-3
3-
O R -C
.d w g C -2
/1
/2
3:
P
M J
EF
FR
Y.
O
R
LA
N D
O
4.
1s
LM
S T ec h)
SHEET
20 1
SCALE: 1"=10'
SITE PLAN
WELL 11,
SEE MECH & ARCH SHTS
TO WWTRRF
EXIST WELL 11 EQUIPMENT HOUSE
DEMOLISHED BY CITY
21-3133 MARCH 2024
CITY OF PENDLETON
WELL 11-11B
AS SHOWN of 65
C-2
SHEET
DG
BB
WRK
HORIZONTAL CONTROL PLAN
SITE LAYOUT AND
CIVIL
WELL 11B
SEE MECH &
ARCH SHTS
SEE NOTE 4
POTHOLED:
BEDROCK AT
995.76
POTHOLED:
BEDROCK AT
995.29
CONCRETE PAD,
TYP, SEE NOTE 1
NOTES:
1. CONCRETE PADS SHALL BE MIN. 6" THICK WITH #4 @ 12" O.C.
EA WAY. SLOPE AWAY FROM WELL HOUSE A MIN. OF 2 %. WIDTH
OF PADS SHALL EXTEND 4'-0" FROM WELL HOUSE AND BE 3"
WIDER THAN DOORWAYS. PROVIDE 6" THICK 34"-0 CRUSHED
ROCK, COMPACTED PER SPECIFICATIONS.
2. WELDED PIPE FENCE CORNERS SHALL MATCH EXISTING
CORNERS AT THE SOUTH END OF THE PROJECT. PAINT SHALL BE
SELECTED TO CLOSELY MATCH EXISTING CORNERS.
INSTALLATION SHALL INCLUDE CONCRETE EMBEDMENT OF
POSTS, PER MANUFACTURERS RECOMMENDATION.
3. NEW FENCE SHALL MATCH EXISTING FOUR-WIRE FENCE. FENCE
SHALL INCLUDE 7' GREEN T-POSTS PLACED APPROXIMATELY 8'
O.C. EVERY 4TH POST SHALL BE A 4" x 4" x 81
2' WOODEN POST,
2' MIN. EMBEDDED IN CONC. WIRE SHALL BE 9-GAUGE MIN.
GALVANIZED WIRE AT 1' O.C. VERTICALLY. ALL COMPONENTS TO
BE INSTALLED PER MANUFACTURERS RECOMMENDATIONS.
4. FINISHED SURFACE SHALL BE IMPORTED STRUCTURAL FILL,
TYPE A1, 34"-0", 12" THICK, OVER 160N MIRAFI GEOTEXTILE, OR
EQUAL.
5. FURNISH PERMANENT SEEDING OUTSIDE GRAVEL AREAS TO
THE EXISTING GRADE PER ESC SHEETS
6. SEE DETAIL 4, SHT C-7 FOR BUILDING FOUNDATION
REQUIREMENTS.
REINSTALL CORNER
POSTS AND GATE FEATHER GRAVEL INTO
EXIST ROAD PROFILE
APPROX GRADING
LIMITS PER SHT C-3
SEE NOTE 5
5'
5'
10'
WELL 11B FLOWMETER
VAULT, SEE SHT M-104
WELL 11 FLOW METER
VAULT, SEE SHT M-204
1004.72
1004.72
1004.89
1004.89
NO. DATE BY REVISION
NOT TO SCALE
THEN DRAWING IS
NOT MEASURE 1"
IF THIS BAR DOES
NOTICE
CHECKED
DRAWN
DESIGNED
PROJECT NO.: SCALE: DATE:I:
\B
O I_
Pr oj ec ts
\2 1\
P en dl et on
W el l 1
1\ C A D
\S he et s\
-3
3-
O R -C
.d w g C -2
/1
/2
3:
P
M J
EF
FR
Y.
O
R
LA
N D
O
4.
1s
LM
S T ec h)
SHEET
CO
M
O H
P
OHP
O H
P
O H
P
FM
1004.80+
1004.80+
1004.80+
1004.80+
1004.30+
1005.12+
1005.19+
1005.00+
1005.00+
1004.90+
1004.80+
1005.11+
1005.06+
1004.60+
1004.13+
1004.25
1004.50
1004.75
1004.75
1004.50
.2
.7
.5
.2
1005.25
1005.50
1001 1000
NO. DATE BY REVISION
NOT TO SCALE
THEN DRAWING IS
NOT MEASURE 1"
IF THIS BAR DOES
NOTICE
CHECKED
DRAWN
DESIGNED
PROJECT NO.: SCALE: DATE:I:
\B
O I_
Pr oj ec ts
\2 1\
P en dl et on
W el l 1
1\ C A D
\S he et s\
-3
3-
O R -C
.d w g C -3
/1
/2
3:
P
M J
EF
FR
Y.
O
R
LA
N D
O
4.
1s
LM
S T ec h)
SHEET
20 1
WELL 11B FLOW METER
VAULT, LID TO BE 12" MIN
ABOVE FG, SEE SHT M-7
TO WWTRRF
21-3133 MARCH 2024
CITY OF PENDLETON
WELL 11-11B
AS SHOWN of 65
C-3
SHEET
DG
JWO
WRK
SITE GRADING PLAN
CIVIL
NOTES:
1. GRADING SHOWN IS APPROXIMATE. CONTRACTOR SHALL
TRANSITION GRADING FROM THE SLOPES SHOWN AS REQUIRED.
WHERE PROPOSED GRADE AND EXISTING GRADE CONFLICT AND
RESULTS IN THE POTENTIAL PONDING OF WATER ON THE SITE
IMPROVEMENTS, CONTRACTOR SHALL GRADE TO ENSURE WATER
CAN DRAIN TO THE WEST AND SOUTH OF THE SITE.
2. CONTRACTOR SHALL VERIFY SPOT ELEVATIONS AND GRADING
WILL PROMOTE DRAINAGE AS SHOWN. IF DEVIATIONS EXIST
CONTRACTOR SHALL NOTIFY ENGINEER.
3. STRIP AND GRUB ALL AREAS TO BE EXCAVATED OR THAT WILL
RECEIVE FILL AS PART OF THE OS PROJECT.
FINAL FILL AND CUT SLOPES SHALL NOT EXCEED 1V:3H.
FF:1004.80
2%
APPROX TRANSFORMER
LOCATION, SEE ELECTRICAL
FF: 1005.00
APPROX GRADING LIMITS
2%
2%
2%
1%
SCALE: 1"=10'
SITE PLAN
1.
1V:5H
TO
G
RAD
E
15' 4%TO GRADE
5'
10%TO GRADE
5'
1.5%
1.5%
TO
G
RA
D
E
DITCH
WELL 11 FLOW METER VAULT
LID TO BE 12" MIN ABOVE FG
PTW DISCHARGE GRADING
PER DETAIL SHT C-7
NO. DATE BY REVISION
NOT TO SCALE
THEN DRAWING IS
NOT MEASURE 1"
IF THIS BAR DOES
NOTICE
CHECKED
DRAWN
DESIGNED
PROJECT NO.: SCALE: DATE:I:
\B
O I_
Pr oj ec ts
\2 1\
P en dl et on
W el l 1
1\ C A D
\S he et s\
-3
3-
O R -C
.d w g C -3
/1
/2
3:
P
M J
EF
FR
Y.
O
R
LA
N D
O
4.
1s
LM
S T ec h)
SHEET
CO
M
O H
P
OHP
O H
P
O H
P
FM 1"COP PW
1"
CO
P
PW
4"D
I PTW
4"D I D
8"DI PW
8"DI PTW 4"DI D
12"DI PTW
8" D
I
PW
16"DI PW
1"COP PW
"D
I
PW
1004.25
1004.50
1004.75
NO. DATE BY REVISION
NOT TO SCALE
THEN DRAWING IS
NOT MEASURE 1"
IF THIS BAR DOES
NOTICE
CHECKED
DRAWN
DESIGNED
PROJECT NO.: SCALE: DATE:I:
\B
O I_
Pr oj ec ts
\2 1\
P en dl et on
W el l 1
1\ C A D
\S he et s\
-3
3-
O R -C
.d w g C -4
/1
/2
3:
P
M J
EF
FR
Y.
O
R
LA
N D
O
4.
1s
LM
S T ec h)
SHEET
20 1
SCALE: 1"=10'
SITE PLAN
SEE SHT C-5 FOR
CONTINUATION
21-3133 MARCH 2024
CITY OF PENDLETON
WELL 11-11B
AS SHOWN of 65
C-4
SHEET
DG
BB
WRK
SITE PIPING PLAN
CIVIL
CONSTRUCT 4" DRAIN PARALLEL
WITH 8/12" DRAIN AT CONSTANT
SLOPE, DAYLIGHT IE=1000.5',
WITH 4" RUBBER CHECK VALVE,
TIDEFLEX OR EQUAL
NOTES:
1. RESTRAIN ALL FITTINGS, VALVES AND DUCTILE IRON PIPE,
INCLUDING WATERLINE, AND DRAIN LINES.
2. TRENCH SURFACE RESTORATION SHALL BE IMPORTED
STRUCTURAL FILL, TYPE A1, 34"-0", 4" THICK.
3. POTABLE WATER LINES SHALL HAVE A MINIMUM OF 3'-6" COVER.
4. PROVIDE CLSM FOR PIPE BEDDING FOR THE PIPE AS SHOWN IN
DASHED LINES. CLSM PIPE BEDDING TO BE PROVIDED A MINIMUM
OF 10' BEYOND ANY PTW OR DRAIN CROSSING OF PW.
NO PUMP-TO-WASTE DISCHARGE
IMPROVEMENTS SHALL BE MADE
EAST OF THE PROPERTY LINE
N50096.39 E35494.80
1-16" 11.25° BEND, MJ
N50094.67 E35516.25 1-16" V500, FLxMJ
1-16" TEE, FL
1-16"FLANGE ADABPTER
1-16"x8" RDCR, FL
1-12" FLANGE ADAPTER
1-TB DWG 408A, SHT C-6
1-VALVE BOX, DWG 402, SHT C-6
N50123.65 E35491.63 1-8"x4" TEE, MJ
1-8" SPOOL, PE
1-12"x8" ECC RDCR, MJ
N50095.36 E35507.63
1-1" TAPPING SADDLE
1-1" SERVICE LATERAL, DWG 409, SHT C-6
N50126.61 E35539.72
PUMP-TO-WASTE
DISCHARGE - END OF VALVE,
SEE DET 3, SHT C-7
N50141.35 E35478.09
1-8" 90° BEND, MJ
1-TB DWG 408A, SHT C-6
N50121.25 E35518.47
1-8" 11.25° BEND, MJ
N50129.09 E35520.72 2-8" V500, FLxMJ
1-8" TEE, FL
1-8" FLANGE ADAPTER
1-8" PLUG W/ ECOLOGY BLOCK
1-TB DWG 408A, SHT C-6
1-VALVE BOX, DWG 402, SHT C-6
N50140.75 E35480.17
1-1" TAPPING SADDLE
1-1" SERVICE LATERAL, DWG 409, SHT C-6
(NO METER)
SEE NOTE 4
8" DI PW AND 12" DI PTW
TRENCH TYP, DWG
103, SHT C-6, SEE
NOTE 2
1 4 2
1" COP PW TO
CHLORINE ANALYZER,
SEE MECH
2" CONDUIT W/ 12" CL
SEE MECH PIPE SCHEDULE
SEE NOTE 4
4" DI D AND 16" DI PW
4" PTW IE=1002.00
4" D IE=1002.02
8" PTW IE=1002.00
4" D IE=1001.77
10' MIN
NO. DATE BY REVISION
NOT TO SCALE
THEN DRAWING IS
NOT MEASURE 1"
IF THIS BAR DOES
NOTICE
CHECKED
DRAWN
DESIGNED
PROJECT NO.: SCALE: DATE:I:
\B
O I_
Pr oj ec ts
\2 1\
P en dl et on
W el l 1
1\ C A D
\S he et s\
-3
3-
O R -C
.d w g C -4
/1
/2
3:
P
M J
EF
FR
Y.
O
R
LA
N D
O
4.
1s
LM
S T ec h)
SHEET
O H P
OHP
OHP
1"
CO
P
PW
1"COP PW
4"DI D
8" D
I
PW
8"D
I PTW
4"D I D
12"D
I PTW
8"DI PW
"D
I
PW
1"
CO
P
PW
16"DI PW
A1+00 A2+00
A3+00
A1+00 A1+10 A1+20 A1+30 A1+40 A1+50 A1+60 A1+70 A1+80 A1+90 A2+00 A2+10 A2+20 A2+30 A2+40 A2+50 A2+60 A2+70 A2+80 A2+90 A3+00 A3+10 A3+20 A3+30 A3+40 A3+50
S
TA
A 3+
TE
E
S
TA
A 3+
"D I
PT
W
C R O
S S
IN
G
IE
.4
S
TA
A 3+
4"
D I
D C
R O
S S
IN
G
IE
.9
S
TA
TE
E
S
TA
A 1+
C O
N N
EC
T
TO
E
X
IS
T S
EE
N O
TE
S
TA
A 1+
EX
IS
T
G V
(C
LO
S
ED
S
TA
A 1+
EX
IS
T
TE
E
S
TA
PO
TH
O
LE
B
ED
R O
C K
EL
5.
NO. DATE BY REVISION
NOT TO SCALE
THEN DRAWING IS
NOT MEASURE 1"
IF THIS BAR DOES
NOTICE
CHECKED
DRAWN
DESIGNED
PROJECT NO.: SCALE: DATE:I:
\B
O I_
Pr oj ec ts
\2 1\
P en dl et on
W el l 1
1\ C A D
\S he et s\
-3
3-
O R -C
.d w g C -5
/1
/2
3:
P
M J
EF
FR
Y.
O
R
LA
N D
O
4.
1s
LM
S T ec h)
SHEET
20 1
SCALE: 1"=10'
PLAN
21-3133 MARCH 2024
CITY OF PENDLETON
WELL 11-11B
AS SHOWN of 65
C-5
SHEET
DG
BB
WRK
SITE PIPING PLAN CONT.
CIVIL
SEE SHT C-4 FOR
CONTINUATION
WELL 11B
REMOVE 16" CAP.
CONNECT TO EXIST
SEE NOTE 5
16" WATERLINE (SW HOUTAMA ROAD
WATERLINE PROJECT, BY CITY)
SEE NOTE 1
SW
8T H
S T
NOTES:
1. SW HOUTAMA ROAD WATERLINE
PROJECT DATUM IS 68.09' LOWER
THAN WELL 11B DATUM.
2. CONTRACTOR SHALL FIELD VERIFY
LOCATION OF THE EXISTING 16" CAP
FROM SW HOUTAMA ROAD PROJECT.
3. CONTRACTOR SHALL RESTRAIN
ALL PIPE, VALVES AND FITTINGS.
4. POTABLE WATERLINE SHALL HAVE
A MIN. OF 3'-6" COVER.
5. PREVIOUS WORK INCLUDED ONE
(1) PIPE LENGTH OF 16" DI PIPE.
CONTRACTOR SHALL CONNECT TO
THE EXISTING 16" DI PIPE AS
SHOWN. THE EXISTING PIPE LENGTH
IS UNTESTED AND HAS NOT BEEN
DISINFECTED. CONTRACTOR SHALL
TEST AND DISINFECT AGAINST THE
EXISTING 16" GATE VALVE
INCLUDING THE EXISTING PIPE
LENGTH PRIOR TO PLACING
WATERLINE IN SERVICE. DEPTH TO
THE EXISTING PIPE IS UNKNOWN,
CONTRACTOR SHALL POTHOLE TO
VERIFY DEPTH AND TRANSITION AS
REQUIRED.
6. TRENCH SURFACE RESTORATION
SHALL BE IMPORTED STRUCTURAL
FILL, TYPE A1, 34"-0", 4" THICK.
TRENCH TYP, DWG 103, SHT C-6,
SEE NOTES 3, 4 AND 6
DEFLECT PIPE AS REQ'D TO
CONNECT TO EXIST
EXIST PIPE
LENGTH OF 16" DI
SEE NOTE 5
EXIST 16' GATE
VALVE (CLOSED)
SEE NOTE 5
SCALE: 1"=10' HORIZ, 1"=5' VERT
PROFILE - 'A'
EXIST/FIN GRADE
REFERENCE KEY NOTES ON SHT C-4, TYP
16"DI PW
8"DI PW
NO. DATE BY REVISION
NOT TO SCALE
THEN DRAWING IS
NOT MEASURE 1"
IF THIS BAR DOES
NOTICE
CHECKED
DRAWN
DESIGNED
PROJECT NO.: SCALE: DATE:I:
\B
O I_
Pr oj ec ts
\2 1\
P en dl et on
W el l 1
1\ C A D
\S he et s\
-3
3-
O R -C
.d w g C -5
/1
/2
3:
P
M J
EF
FR
Y.
O
R
LA
N D
O
4.
1s
LM
S T ec h)
SHEET
FEBRUARY 2019 FEBRUARY 2019
FEBRUARY 2019
FEBRUARY 2019 FEBRUARY 2019
FEBRUARY 2019
NO. DATE BY REVISION
NOT TO SCALE
THEN DRAWING IS
NOT MEASURE 1"
IF THIS BAR DOES
NOTICE
CHECKED
DRAWN
DESIGNED
PROJECT NO.: SCALE: DATE:I:
\B
O I_
Pr oj ec ts
\2 1\
P en dl et on
W el l 1
1\ C A D
\S he et s\
-3
3-
O R -C
-D
ET
S .d w g
C -6
/2
1/
:5
PM
J
EF
FR
Y.
O
R
LA
N D
O
4.
1s
LM
S T ec h)
SHEET
20 1 of2 03/13/2024WRK BID SET
21-3133 MARCH 2024
CITY OF PENDLETON
WELL 11-11B
AS SHOWN of 65
C-6
SHEET
DG
BB
WRK
STANDARD DETAILS
CIVIL
THEN DRAWING IS
NOT MEASURE 1"
IF THIS BAR DOES
NOTICE
CHECKED
DRAWN
DESIGNED
PROJECT NO.: SCALE: DATE:I:
\B
O I_
Pr oj ec ts
\2 1\
P en dl et on
W el l 1
1\ C A D
\S he et s\
-3
3-
O R -C
-D
ET
S .d w g
C -7
/2
1/
:5
PM
J
EF
FR
Y.
O
R
LA
N D
O
4.
1s
LM
S T ec h)
SHEET
20 1 of2 03/13/2024WRK BID SET
NOTES:
1. FOR TEMPORARY BLOW-OFFS, CONTRACTOR TO PROVIDE TEMPORARY THRUST
RESTRAINT AS REQUIRED.
2. SEE SPECIFICATIONS REGARDING DISPOSAL/DECHLORINATION FOR
SUPERCHLORINATED WATER.
3. PROVIDE LARGER BLOW-OFF PIPING MATERIALS AT CONTRACTOR OPTION.
4. FOR CONCRETE CYLINDER PIPE OR STEEL PIPE, PROVIDE SIMILAR ASSEMBLY AT
TEST HEADS.
5. PROVIDE PIPING TO ACHIEVE 2.5 FTS IN WATERMAIN FOR FLUSHING,
2" MINIMUM.
SCALE: NTS
TEMPORARY BLOW-OFF ASSEMBLY 2
WATERMAIN
ELBOW & HOSE FTG AS REQ'D
AWWA GV W/ OPERATING NUT
COLLAR TB W/ REINF &
PIPE CLAMPS AS REQ'D,
SEE NOTE 1
GALV ELBOW
GALV STL PIPE
MJ CAP W/ IPS
TAP W/ RETAINER GLAND
SCALE: NTS
INSULATED FLANGE JOINT DETAIL 1
INSUL SLV (LENGTH EQ TO 116" LESS THAN
INSIDE DIM BETW STL WASHERS)
INSUL WASHER
STL WASHER
INSUL GASKET
21-3133 MARCH 2024
CITY OF PENDLETON
WELL 11-11B
AS SHOWN of 65
C-7
SHEET
DG
BB
WRK
MISCELLANEOUS CIVIL DETAILS
CIVIL
SCALE: NTS
PUMP-TO-WASTE DISCHARGE 3
C-4
12" ECC RUBBER CHECK
VAVEL, FL
GRADE BACK TO
EXIST GR 2H:1V, TYP
EXIST GR
APPROX 5 CY MIN CL 50
RIPRAP, 1'-6" THK MIN
M
IN
IE=1002.00
15' MIN SETBACK FROM PROPERTY LINE
NOTES:
1. ALL PIPE SHALL BE RESTRAINED.
2. GRADE ALL EXCAVATIONS BACK TO THE
EXISTING GRADE AS SHOWN, RESTORATION
SHALL BE IMPORTED STRUCTURAL FILL, TYPE
A1, 3/4"-0", 4" THICK.
SCALE: NTS
BUILDING FOUNDATION DETAIL 4
NOTES:
1. CONTRACTOR SHALL NOTIFY OWNER
AND ENGINEER, IF UNCONSOLIDATED FILL
IS ENCOUNTERED DURING EXCAVATION
AND SUBGRADE PREPARATION.
2. SEE SPECIFICATION 31 23 23 - FILL
FOR ADDITIONAL REQUIREMENTS FOR
SUBGRADE PREPARATION AND FILL
PLACEMENT.
WALL, STEM WALL,
FOOTING AND CONC
SLAB, PER STRUCT SHTS
IMPORTED STRUCTURAL
FILL, TYPE A1, 34"-0",
6" THK MIN
SURFACE RESTORATION,
PER PLAN, SEE SHT C-2
SUBSOIL, TYPE S2 FILL,
TYP.
BUILDING SUBGRADE,
SEE NOTES 1 AND 2
P/L
SECTIONPLAN
3' M
IN
12' MIN
EXTEND AS REQ'D
TO MEET GRADE
1 TYP
GRADE BACK TO
EXIST GR 2H:1V,
TYP
12" ECC RUBBER CHECK
VAVEL, FL
6" MIN
TYP.
THEN DRAWING IS
NOT MEASURE 1"
IF THIS BAR DOES
NOTICE
CHECKED
DRAWN
DESIGNED
PROJECT NO.: SCALE: DATE:I:
\B
O I_
Pr oj ec ts
\2 1\
P en dl et on
W el l 1
1\ C A D
\S he et s\
-3
3-
O R -A
.d w g A -1
/1 /2
5:
P M
J
EF
FR
Y.
O R
LA
N D
O
4.
1s
LM
S T ec h)
SHEET
20 1 of2 03/13/2024WRK BID SET
CITY OF PENDLETON
WELL 11-11B
ARCHITECTURAL
WELL 11B
COVER SHEET
AS NOTED
A-101
15 65
WRK
TMB
DG
MARCH 202421-3133
DOOR SCHEDULE
NO. DOOR SIZE OPEN HARDWARE
FRAME
REMARKS
HEAD JAMB
1 3'-0"x7'-10" LHR GROUP 2 2" 2"
2 3'-0"x7'-10" RHR GROUP 2 2" 2" 3/4-HOUR FIRE-RATED DOOR.
3 4'-0"x7'-10" RHR GROUP 2 2" 2"
3/4-HOUR FIRE-RATED DOOR WITH FACTORY
INSTALLED 12" X 12" LOUVER. LOUVER TO HAVE A
SLOT INSIDE FOR CONTRACTOR/OR
FACTORY-PROVIDED SLIDING METAL PANEL TO SEAL
LOUVER. LABEL DOOR WITH 7.5" NFPA 704 12.5%
SODIUM HYPOCHLORITE FIRE DIAMOND.
4 3'-0"x7'-10" RHR GROUP 2 2" 2"
5 3'-0"x7'-10" LHR GROUP 2 2" 2"
6 8'-0"x8'-0" OVERHEAD NA - - CHAIN ON RIGHT
5'-0"x6'-0"
HATCH
NORTH/SOUTH NA MFR MFR
DOUBLE LEAF, ALUMINUM EQUIPMENT ROOF
HATCH
8 3'-0"X7'-10" RHR GROUP 1 2" 2"
1-1/2 HR MIN. FIRE-RATED DOOR WITH FACTORY
INSTALLED 10"x10" WINDOW. LABEL DOOR WITH
5" NFPA 704 12.5% SODIUM HYPOCHLORITE FIRE
DIAMOND.
MATERIAL FINISH SCHEDULE
ITEM MATERIAL COATING SYSTEM COLOR REMARKS
EXTERIOR WALLS CMU
SPLIT & SMOOTH FACE
CMU BLOCK, PER
ELEVATIONS
ROOFING METAL FACTORY COATING
TO BE SELECTED BY
OWNER
GUTTERS, FASCIA AND
STEEL
ARCHITECTURAL
FEATURES
METAL FACTORY COATING
TO BE SELECTED BY
OWNER
BLOCKOUT SOFFIT &
TRIM
METAL FACTORY COATING
TO BE SELECTED BY
OWNER
LOUVERS METAL COATING SYSTEM 101
TO BE SELECTED BY
OWNER
FACTORY PRIME
DOORS METAL COATING SYSTEM 101
TO BE SELECTED BY
OWNER
FACTORY PRIME
PUMP AND ELECTRICAL
ROOM INTERIOR
WALLS
CMU COATING SYSTEM 302
TO BE SELECTED BY
OWNER
CHLORINE ROOM
INTERIOR WALLS
CMU POLYMER PANELING WHITE
PUMP, ELECTRICAL,
AND CHLORINE ROOM
INTERIOR CEILING
GYPSUM COATING SYSTEM 304 WHITE
CONCRETE FLOORS CONC.
EXPOSED METALLIC
PIPING
DUCTILE IRON COATING SYSTEM 101
TO BE SELECTED BY
OWNER
EXPOSED PVC PIPING PVC COATING SYSTEM 104
TO BE SELECTED BY
OWNER
ZONING CODE INFORMATION
M-2 HEAVY INDUSTRIAL
BUILDING CODE INFORMATION
APPLICABLE CODES
2022 OREGON STRUCTURAL SPECIALTY CODE (OSSC)
2021 OREGON ENERGY EFFICIENCY CODE (OEESC)
2021 OREGON ELECTRICAL SPECIALTY CODE (OESC)
HEIGHTS AND AREAS PERMISSIBLE OSSC
FOR F-1/H-4 OCCUPANCY, TYPE VB CONSTRUCTION, NON-SPRINKLERED
PER TABLE 504.3, 40-FT HEIGHT
PER TABLE 504.4, 1-STORY ALLOWED
PER TABLE 506.2, 6,500 SQFT
PER TABLE 601, FIRE RESISTANCE RATING 0 HOURS
BUILDING SUMMARY
FIRE PROTECTION AND LIFE SAFETY SYSTEM
OCCUPANT LOAD
THERMAL ENVELOP AND OEESC
SEMIHEATED SPACE (HEATING OUTPUT >3.4 BTU/H-FT2 BUT <12 BTU/H-FT2)
ROOF INSULATION ENTIRELY ABOVE DECK R-15 REQUIRED, PROVIDING R-24
WALLS ABOVE GRADE MASS R-5.7C.I. REQUIRED, PROVIDING 8-INCH CMU W/ UNREINFORCED
CELLS INSULATED RU 6.62 TO 5.32 PER ASHRAE 90.1-2019, TABLE A3.1-3
SLAB ON GRADE UNHEATED INSULATION NOT REQUIRED
ENTRANCE DOORS: MAX U 0.77
BULDING OVERALL
DIMENSIONS
GROSS
AREA OCCUPANCY CONSTRUCTION
TYPE HEIGHT STORIES
WELL 11B 3'-4" x 25'-4" 794 SF F-1/H-4 VB 18 FT 1
SPACE/ROOM OCC.
CLASS
REQUIREMENT PROVIDED SYSTEM
PUMP ROOM F-1 NA NA
ELECTRICAL ROOM F-1 NA NA
SODIUM HYPOCHLORITE
ROOM H-4 VARIES
2HR MIN. FIRE-RATED INT. WALLS/CEILING, OSSC TABLE 706.4
1-1/2HR MIN. FIRE-RATED DOOR, OSSC TABLE 716.1(2)
1-HR FIRE-RATED DOORS/WALLS AT WALLS INTERSECTING FIRE
WALLS, OSSC 706.5.1
SPACE/ROOM OCC.
CLASS SF/OCC. AREA OCCS.
PUMP ROOM F-1 300 480 2
ELECTRICAL ROOM F-1 300 128 1
SODIUM HYPOCHLORITE
ROOM H-4 300 90 1
EXIT TRAVEL DISTANCE
26'
EXIT TRAVEL DISTANCE
12'
EXIT TRAVEL DISTANCE
15'
THEN DRAWING IS
NOT MEASURE 1"
IF THIS BAR DOES
NOTICE
CHECKED
DRAWN
DESIGNED
PROJECT NO.: SCALE: DATE:I:
\B
O I_
Pr oj ec ts
\2 1\
P en dl et on
W el l 1
1\ C A D
\S he et s\
-3
3-
O R -A
.d w g A -1
/1 /2
5:
P M
J
EF
FR
Y.
O R
LA
N D
O
4.
1s
LM
S T ec h)
SHEET
20 1 of2 03/13/2024WRK BID SET
NO. DATE BY REVISION
NOT TO SCALE
THEN DRAWING IS
NOT MEASURE 1"
IF THIS BAR DOES
NOTICE
CHECKED
DRAWN
DESIGNED
PROJECT NO.: SCALE: DATE:I:
\B
O I_
Pr oj ec ts
\2 1\
P en dl et on
W el l 1
1\ C A D
\S he et s\
-3
3-
O R -A
.d w g A -1
/1 /2
5:
P M
J
EF
FR
Y.
O R
LA
N D
O
4.
1s
LM
S T ec h)
SHEET
20 1 of2 03/13/2024WRK BID SET
CITY OF PENDLETON
WELL 11-11B
ARCHITECTURAL
WELL 11B
FLOOR PLAN
AS NOTED
A-102
16 65
WRK
TMB
DG
MARCH 202421-3133
ELECTRICAL
ROOM
SODIUM
HYPOCHLORITE
ROOM
31'-4"
NOTES:
1. SEE DOOR SCHEDULE ON SHEET A-101 FOR
ADDITIONAL DOOR INFORMATION.
2. ALL CMU CELLS NOT REQUIRED BY THE STRUCTURAL
DRAWINGS TO BE GROUTED SHALL BE FILLED WITH
FOAM INSULATION.
3. SOLAR TUBE LOCATION SHALL BE ADJUSTED AS
REQUIRED TO FIT WITHIN ROOF RAFTERS AND
CEILING JOISTS. ANNULAR SPACE BETWEEN
SOLARTUBE AND CEILING SHALL BE SEALED WITH
FIRE-RATED SEALANT MEETING OR EXCEEDING
THE FIRE-RESISTANCE RATING OF THE CEILING
SECTION.
4. FIRE SUPPRESSION SYSTEM SHOWN AS
SCHEMATIC, CONTRACTOR SHALL PROVIDE
FUNCTIONING SYSTEM PER SPECIFICATIONS. NOT
ALL FIRE SUPPRESSION SYSTEM COMPONENTS
SHOWN, CONTRACTOR SHALL COORDINATE
PLACEMENT OF SYSTEM COMPONENTS WITH
OTHER DISCIPLINES.
SCALE: NTS
2HR RATED CEILING SECTION
FRAMING PER…
This is the start of the file's text. The full file is on GovTribe.