Drawings HVAC Phase 3_658-21-102.pdf
PDF 11 MB Posted
- Attached to
- Z1DA--Upgrade HVAC System Phase III Federal contract opportunity
- Solicitation number
- 36C24623B0018
About this file
This document outlines a federal contract opportunity for upgrading an HVAC system. The solicitation number is 36C24623B0018 and concerns Project Number 658-21-102 to upgrade the HVAC system in Phase III at a Veterans Affairs facility within Veterans Integrated Service Network 6. The project involves providing drawings for the HVAC system upgrade, as indicated by the attached PDF file. The contracting agency is the Department of Veterans Affairs Veterans Health Administration. No further details are provided on response dates, pricing terms, or other requirements.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| S07 Bid Abstract 3-10-2023.pdf | ||
| S06 36C24623B0018 0006.pdf | ||
| 36C24623B0018 0006_1.docx | DOCX document | |
| 36C24623B0018 0005_1.docx | DOCX document | |
| Section 00 01 15 List of Drawings Sheets.pdf | ||
| S06 36C24623B0018 0005.pdf | ||
| 21157_VA Salem Upgrade_Replace HVAC Phase III_SES_2020_ALL.pdf | ||
| S06 36C24623B0018 0004.pdf | ||
| 36C24623B0018 0004_1.docx | DOCX document | |
| S06 36C24623B0018 0003.pdf | ||
| 36C24623B0018 0003_1.docx | DOCX document | |
| S05 Questions and Answers for Upgrade HVAC Sys. Phase 3.pdf | ||
| S06 36C24623B0018 0002.pdf | ||
| 36C24623B0018 0002_1.docx | DOCX document | |
| S04 Site Visit for HVAC Sys. Phase 3_1-12-23.pdf | ||
| S06 36C24623B0018 0001.pdf | ||
| 36C24623B0018 0001_1.docx | DOCX document | |
| Specifications HVAC Phase 3_658-21-102.pdf | ||
| 36C24623B0018_2.docx | DOCX document | |
| S02 36C24623B0018_Upgrade HVAC Phase 3.pdf |
Show all 20
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% SUBMITTAL
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
Engineer of Record:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
2A
PROJECT AREA
KEY PLAN
PLAN NORTH TRUE NORTH
01/20/2022
B
IM
/2
V
A S a le m U p g ra d e
R e p la c e H
V A
C P h a s e
I
II
/2
V A
S a le m
U p g ra d e
R e p la c e
H V
A C
P h a s e
I
II
S E
S
.r v t
/2
/2
:1
:2
A
M
G000
COVER SHEET
SPECIALIZED ENGINEERING
SOLUTIONS
1300 Baxter Street Suite 355
Charlotte, NC 28204
(704)348-3097
REPLACE HVAC PHASE III
1970 Roanoke Blvd, Salem, VA 24153
658-21-102
01/20/22
REPLACE HVAC PHASE III
1970 Roanoke Blvd, Salem, VA 24153
SHEET INDEX - MECHANICAL
Sheet Number Sheet Name
M000 MECHANICAL SYMBOLS AND ABBREVIATIONS
MD100 PHASE 1 - DUCTWORK DEMOLITION
MD101 PHASE 2 - DUCTWORK DEMOLITION
MD102 PHASE 1 - MECHANICAL ROOF DEMOLITION
MD103 PHASE 2 - MECHANICAL ROOF DEMOLITION
MH200 PHASE 1 - DUCTWORK
MH201 PHASE 2 - DUCTWORK
MP200 SUB BASEMENT - PIPING
MP201 LEVEL 01 - PIPING
M200 PHASE 1 - MECHANICAL ROOF PLAN
M201 PHASE 2 - MECHANICAL ROOF PLAN
M300 MECHANICAL COORDINATION PLAN
M500 MECHANICAL DETAILS
M501 MECHANICAL DETAILS
M600 MECHANICAL SCHEDULES
M601 MECHANICAL CONTROLS
Grand total: 16
SHEET INDEX - ARCHITECTURAL
Sheet NUmber Sheet Name
A-101 ROOF PLAN
A-501 DETAILS
Grand total: 2
SHEET INDEX - ELECTRICAL
Sheet Number Sheet Name
E000 ELECTRICAL SYMBOLS AND ABBREVIATIONS
E100 LEVEL 1 - ELECTRICAL DEMOLITION
EP200 LEVEL 1 - POWER
EP201 ROOF - POWER
E500 ONE-LINE DIAGRAM
E600 ELECTRICAL DETAILS
Grand total: 6
SHEET INDEX - STRUCTURAL
Sheet Number Sheet Name
S100 PARTIAL ROOF PLANS
S300 GENERAL NOTES
S500 FRAMING DETAILS
Grand total: 3
SHEET INDEX - LIFE SAFETY
Sheet Number Sheet Name
LS100 LIFE SAFETY PLAN
Grand total: 1
SHEET INDEX - GENERAL
Sheet Number Sheet Name
G000 COVER SHEET
Grand total: 1
Revisions: Date:
C
B
A
D
E
22' - 6" 22' - 6" 22' - 6" 22' - 6" 22' - 6"
S100
S100
HVAC DUCT ROUTED ACROSS
WAREHOUSE ROOFTOP,
COORDINATE SIZE AND
LOCATION WITH MEP
PREFABRICATED OR
SPECIALTY STAIR
OVER DUCTWORK,
BY OTHERS
2 3 4
C
B
A
EX. OPENINGS
TO REMAIN
EX. CONCRETE
JOISTS
NEW AHU
(12.5 KIPS +/-)
22' - 6" 22' - 6"
/8
/2
/8
15' - 10 1/2" 25' - 1 1/2" 4' - 0"
/2
W X
W X
W24X84
W24X68
W
X
W12X26
W24X68
W16X36
W
X
1 1/4" X 1/8" TYPE 19-4
BAR GRATING (GALV.)
S500
/8
/2
1'
/8
6' - 0" 2' - 2 7/8"
S500
S500
TYP
TYP
TYP
5' - 0" 4' - 0" 16' - 0" 4' - 0" 16' - 0"
ACCESS LADDER
AT EA. PLATFORM,
BY OTHERS
W
X
W
X
W24X68
W
X
W
X
NEW ERV
(4.0 KIPS +/-)
S500
S500 TYP
2 3
D
E
EL. 117' - 0 1/4"
EL. 127' - 0 1/4"
WAREHOUSE ROOF
TOP OF SLAB
LEVEL 2
TOP OF SLAB
STAIR LANDING
EL. 130'-6 1/4"
S500
S500
D
E
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A/E:Structural Engineer:
O
WE
LTH O V
A
P F
I N E
N
R
I G
A
E
L
C M M O
N A
F
IRG
IN
I
DOUGLAS G
FITZPATRICK
Lic. No. 041192
R O
SS
O N
E E
C U s e rs
\j h a d s e l\ D o c u m e n ts \C
D
S tr u c t_
R e v it
H V
A C
P h a s e I
II
.r v t
/1
/2
:3
:3
P
M
S100
PARTIAL ROOF PLANS
SPECIALIZED ENGINEERING
SOLUTIONS
1300 Baxter Street, Suite 355
Charlotte, NC 28204
(704) 348-3097
FITZPATRICK ENGINEERING
GROUP
19520 West Catawba Ave, Suite 311
Cornelius, NC 28031
704-987-9114
REPLACE HVAC PHASE III
1970 Roanoke Blvd, Salem, VA 24153
268-21-102
1/8" = 1'-0"S100
1 WAREHOUSE ROOF
3/16" = 1'-0"S100
2 ENLARGED PLAN - AHU
1/4" = 1'-0"S100
3 ENLARGED PLAN - ACCESS STAIR
PLAN NOTES:
1. STAIR LOCATION TO BE FIELD LOCATED TO COORDINATE POST LOCATIONS WITH
WAREHOUSE ROOF JOISTS.
2. STAIR DESIGN IS TO BE BY STIAR FABRICATOR. SEE ARCHITECTURAL FOR STAIR LAYOUT
AND SIMENSIONING NOT SHOWN.
3. CONTRACTOR TO LOCATE SLAB REINFORCEMENT IN AT 2ND FLOOR POST LOCATIONS
PRIOR TO DRILLING ANCHOR HOLES AND INSTALLING ANCHORAGE.
PLAN NOTES:
1. SEE MECHANICAL FOR UNIT INFORMATION. CONTRACTOR TO VERIFY
UNIT DIMENSIONS AND WEIGHTS PRIOR TO STEEL FABRICATION.
2. EX. REINFORCEMENT IS NOT TO BE CUT DURING POST INSTALLATION.
3. AHU ATTACHMENT IS TO BE BY SUPPLIER. .PLAN NOTES:
1. CONFIGURATION SHOWN IS BASED ON ORIGINAL STRUCTURAL DRAWINGS (VA RECORD
SET). STRUCTURAL CONFIGURATION IS TO BE VERIFIIED BY CONTRACTOR PRIOR TO THE
START OF WORK.
2. PREFABRICATED STAIR OVER ROOF DUCTWORK IS BY OTHERS.
Revisions: Date: 01/20/22 DJF JMH
GENERAL NOTES
1. THE CONTRACT STRUCTURAL DRAWINGS AND SPECIFICATIONS REPRESENT THE FINISHED STRUCTURE, AND DO NOT INDICATE THE METHOD OR MEANS OF CONSTRUCTION. THE CONTRACTOR SHALL SUPERVISE AND DIRECT THE WORK AND SHALL BE SOLELY RESPONSIBLE FOR ALL CONSTRUCTION MEANS, METHODS, PROCEDURES, TECHNIQUES, SEQUENCE AND SAFETY. THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ALL REQUIRED TEMPORARY BRACING AND SHORING DURING CONSTRUCTION TO MAINTAIN THE STABILITY OF THE STRUCTURE. CONSTRUCTION LOADS SHALL NOT EXCEED THE CAPACITY OF THE
INSTALLED STRUCTURE AT ANY TIME.
2. THE ENGINEER DOES NOT HAVE CONTROL OR CHARGE OF, AND SHALL NOT BE RESPONSIBLE FOR
CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES OR PROCEDURES, FOR SAFETY
PRECAUTIONS AND PROGRAMS IN CONNECTION WITH THE WORK. FOR THE ACTS OR OMISSIONS OF THE CONTRACTOR, SUBCONTRACTOR, OR ANY OTHER PERSONS PERFORMING ANY OF THE WORK, OR THE FAILURE OF ANY OF THEM TO CARRY OUT THE WORK IN ACCORDANCE WITH THE CONTRACT DOCUMENTS.
3. STRUCTURAL DRAWINGS ARE TO BE USED IN CONJUNCTION WITH ARCHITECTURAL AND OTHER CONTRACT DRAWINGS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION OF THE MOST CURRENT SET OF DRAWINGS. DISCREPANCIES, INCLUDING DIMENSIONS, SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT OR DESIGN ENGINEER PRIOR TO PROCEEDING WITH FABRICATION OR CONSTRUCTION.
4. ALL THINGS WHICH, IN THE OPINION OF THE CONTRACTOR, APPEAR TO BE DEFICIENCIES, OMISSIONS, CONTRADICTIONS OR AMBIGUITIES IN THE DESIGN DRAWINGS SHALL BE BROUGHT TO THE ATTENTION OF THE DESIGN ENGINEER PRIOR TO ORDERING, FABRICATION OR CONSTRUCTION. NO EXTRA CHARGE OR COMPENSATION WILL BE ALLOWED BY THE OWNER RESULTING FROM CONTRACTORS FAILURE TO COMPLY
WITH REQUIREMENT.
5. DETAILS / SECTIONS SHOWN ON DRAWINGS ARE TYPICAL AND MAY APPLY TO LOCATIONS OTHER THAN WHERE SPECIFICALLY MARKED ON THE PLANS. IF SECTIONS OR DETAILS DO NOT REPRESENT ALL REQUIRED CONDITIONS, THE ENGINEER SHALL BE CONTACTED FOR CLARIFICATION BY THE GENERAL CONTRACTOR.
6. IF EXISTING CONDITIONS MAKE IT NECESSARY TO REVISE STRUCTURAL DETAILS, NOTIFY DESIGN ENGINEER
BEFORE PROCEEDING WITH ANY CHANGES.
7. THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING ALL CONTRACT DRAWINGS AND LATEST ADDENDA AND SUBMITTING THESE DOCUMENTS TO SUBCONTRACTORS AND MATERIAL SUPPLIERS PRIOR TO THE SUBMITTAL OF SHOP DRAWINGS, FABRICATION OF ANY STRUCTURAL MEMBER AND ERECTION
IN THE FIELD.
8. THE GENERAL CONTRACTOR SHALL PROTECT EXISTING STRUCTURES AND UTILITY LINES FROM ALL
DAMAGE.
9. IF ANY CONFLICTS OCCUR BETWEEN THE NOTES, SPECIFICATIONS, AND DETAILS, THE MOST STRINGENT
REQUIREMENT SHALL GOVERN.
10. EQUIPMENT PADS ARE TO BE PROVIDED BY THE MECHANICAL OR ELECTRICAL CONTRACTORS REQUIRING THE PADS. PADS NOT SHOWN BY MECHANICAL OR ELECTRICAL ENGINEER SHALL BE 4" CONCRETE SLAB
ON GRADE WITH THICKENED EDGES.
11. DRAWINGS ISSUED FOR PERMIT/CONSTRUCTION ARE FOR PERMITTING ONLY. DRAWINGS MAY REQUIRED REVISIONS IN ORDER TO OBTAIN A CONSTRUCTION PERMIT AND/OR COORDINATION WITH OTHER TRADES.
DRAWINGS ARE TO BE ISSUED AND APPROVED FOR CONSTRUCTION PRIOR TO ANY BUILDING
CONSTRUCTION, MATERIAL MILL ORDERS, AND MATERIAL FABRICATION.
12. ALL WORK SHALL BE DONE IN ACCORDANCE WITH OSHA AND OWNER'S REGULATIONS.
13. ALL INSPECTIONS SHALL BE ACCORDING TO THE REFERENCED CODE OR INSPECTION PLAN PROVIDED.
14. FITZPATRICK ENGINEERING GROUP WELCOMES QUESTIONS OR CONCERNS REGARDING FRAMING OR DETAILS SHOWN IN THESE DOCUMENTS. PLEASE CALL AT 704-987-9114 FOR ASSISTANCE. IF THE PROJECT ENGINEER IS NOT AVAILABLE, PLEASE PROVIDE FEG JOB NUMBER 214976 TO ANOTHER ENGINEER TO HELP
ANSWER YOUR QUESTIONS.
DESIGN CRITERIA
1. BUILDING DESIGNED IN ACCORDANCE WITH THE U.S. DEPARTMENT OF VETERANS AFFAIRS STRUCTURAL
DESIGN MANUAL AND, BY REFERENCE:
a. THE 2021 INTERNATIONAL BUILDING CODE
b. MINIMUM DESIGN LOADS AND ASSOCIATED CRITERIA, ASCE 7-16
c. CONCRETE DESIGN - ACI 318-19
d. STEEL DESIGN AISC 360-16 EDITION
e. U.S. DEPARTMENT OF VETERANS AFFAIRS SEISMIC DESIGN REQUIREMENTS, H-18-8
f. U.S. DEPARTMENT OF VETERANS AFFAIRS PHYSICAL SECURITY DESIGN MANUAL FOR VA
LIFE-SAFETY PROTECTED FACILITIES
2. FLOOR LOADS:
a. LIVE –
i. TYPICAL FLOOR 100 PSF (REDUCIBLE) OR 1000 LB CONCENTRATED LOAD
NOTE : REGARDING DEFLECTIONS EXTERIOR AND INTERIOR NON-LOAD BEARING STEEL STUDS
STEEL STUD FRAMING FROM SLAB ON GRADE TO STEEL FLOOR OR ROOF SHALL BE DESIGNED
TO ACCOMMODATE VERTICAL DEFLECTION OF L/360 OF BEAM SPAN WITHOUT LOADING THE
STUDS. STUDS SPANNING BETWEEN FRAMED FLOORS SHALL BE DESIGNED FOR VERTICAL
MOVEMENT OF L/540 OF BEAM SPAN. WHERE THE HEAD OF A WINDOW OR CURTAIN WALL IS
SUPPORTED BY WALL FRAMING THAT IS RIGIDLY ATTACHED TO THE STRUCTURE, A DEFLECTION
HEAD SHALL BE PROVIDED MEETING THE SAME DEFLECTION CRITERIA AS NOTED ABOVE.
3. ROOF LOADS
a. LIVE - 20 PSF (REDUCIBLE), OR 300 LB POINT LOAD
b. PONDING:
i. STATIC HEAD 5"
ii. DYNAMIC HEAD 1"
iii. DESIGN LOAD = 31.2 PSF
4. ROOF SNOW LOAD
a. GROUND SNOW LOAD Pg = 30 PSF
b. FLAT-ROOF SNOW LOAD Pf = 25 PSF
c. SNOW EXPOSURE FACTOR Ce = 1.0
d. THERMAL FACTOR Ct = 1.0
e. SNOW LOAD IMPORTANCE FACTOR Is = 1.20
5. WIND LOADS DESIGNED IN ACCORDANCE WITH THE 2021 INTERNATIONAL BUILDING CODE AND ASCE 7-16.
a. BASIC WIND SPEED: = 121 MPH
b. WIND EXPOSURE: C
c. WIND BASE SHEAR: N/A
d. INTERNAL PRESSURE COEFFICIENT: GCPI = ±0.18
e. COMPONENTS AND CLADDING SHALL BE DESIGNED PER ASCE 7-16 TABLE 30.4-1
6. EARTHQUAKE DESIGN DATA
a. RISK CATEGORY: IV
b. MAPPED SPECTRAL RESPONSE ACCELERATIONS: SS = 0.197 S1 = 0.064
c. SPECTRAL RESPONSE COEFFICIENTS: SDS = 0.210 SD1 = 0.170
d. SITE CLASS: D
e. BASIC SEISMIC-FORCE-RESISTING SYSTEM:
i. ORDINARY REINFORCED CONCRETE SHEAR WALL
f. DESIGN BASE SHEAR: VEQXY = N/A
g. ANALYSIS PROCEDURE: EQUIVALENT LATERAL FORCE
h. SEISMIC DESIGN CATEGORY: C
i. SEISMIC IMPORTANCE FACTOR: IE = 1.50
j. SEISMIC RESPONSE COEFFICIENT: CS = 0.0379
k. RESPONSE MODIFICATION FACTOR: R = 4.0
STEEL
1. GENERAL SPECIFICATIONS (FABRICATION AND ERECTION):
a. STRUCTURAL STEEL SHALL BE DESIGNED, DETAILED, FABRICATED AND ERECTED IN ACCORDANCE WITH THE A.I.S.C. 'SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS', A.I.S.C. 'CODE OF STANDARD PRACTICE FOR
STEEL BUILDINGS AND BRIDGES'.
b. MATERIALS SHALL CONFORM TO THE FOLLOWING UNLESS NOTED OTHERWISE:
i. W AND WT SHAPES ASTM A992 GRADE 50
ii. CHANNELS, ANGLES, PLATES ASTM A36
iii. PIPES ASTM A53, GRADE B
iv. STEEL TUBES HSS ROUND ASTM A500, GRADE C, 46 KSI
v. STEEL TUBES HSS RECTANGULAR/SQUARE ASTM A500, GRADE C, 50 KSI
vi. ANCHOR RODS ASTM F1554, GRADE 36
vii. SHEAR STUD CONNECTORS ASTM A108, Fu=65 KSI
viii. BOLTS ASTM A325 OR A490, 3/4" DIAMETER (MIN.)
ix. ALL EXTERIOR STEEL SHALL BE HOT DIP GALVANIZED.
x. ALL WELDING ELECTRODES SHALL BE E70XX.
c. GENERAL CONTRACTOR TO PROVIDE TEMPORARY BRACING AND PRECAUTIONS NECESSARY TO WITHSTAND ALL CONSTRUCTION AND/OR WIND LOADS UNTIL ALL FIELD CONNECTIONS ARE COMPLETED
AND SHEAR WALLS OR DECKS ARE IN PLACE.
d. SPLICING OF THE STRUCTURAL STEEL IS PROHIBITED WITHOUT PRIOR APPROVAL OF THE STRUCTURAL
ENGINEER AS TO THE LOCATION AND TYPE OF THE SPLICE TO BE MADE.
e. STEEL FABRICATOR IS TO BE CERTIFIED BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC) FOR 'CONVENTIONAL STEEL BUILDING STRUCTURES'. ERECTOR IS TO BE CERTIFIED BY AISC AS A 'CERTIFIED STEEL
ERECTOR.'
f. WHERE NEW STEEL FRAMES INTO EXISTING STEEL, SIZE AND ELEVATION OF EXISTING STEEL SHALL BE
FIELD VERIFIED PRIOR TO FABRICATION OF NEW STEEL.
g. CONNECTIONS NOT DETAILED IN THE CONSTRUCTION DOCUMENTS SHALL BE DESIGNED BY FABRICATOR OR DETAILER. ALL CONNECTIONS SHALL BE SIGNED AND SEALED BY A PROFESSIONAL REGISTERED
ENGINEER.
h. STEEL STAIR SHALL BE DESIGNED BY A PROFESSIONAL REGISTERED ENGINEER UNLESS OTHERWISE NOTED. SHOP DRAWINGS INCLUDING PLANS, SECTIONS AND ATTACHMENTS TO STRUCTURE SHALL BE PROVIDED FOR REVIEW. MINIMUM LIVE LOAD 100 PSF OR 300 POUND CONCENTRATED LOAD ON A 4
SQUARE INCH AREA WHICHEVER PRODUCES A GREATER STRESS. LIMIT DEFLECTION TO L/360.
i. ALL CAMBER TO BE ORIENTATED UPWARD. ALL STEEL USED IN PARALLEL WITH JOIST SHALL HAVE SAME
CAMBER AS JOISTS.
j. ALL ALUMINUM AND STEEL MEMBERS TO BE TREATED OR PROPERLY SEPARATED TO PREVENT GALVANIC
AND CORROSIVE EFFECTS.
k. INDICATES MOMENT CONNECTION. PROVIDE CONTINUITY PLATES TO THE COLUMN FLANGES TO MATCH BEAM DEPTH. CONTINUITY PLATES TO MATCH BEAM FLANGE THICKNESS OR ½” MINIMUM WHICHEVER
IS GREATER.
l. STEEL SHOP DRAWINGS SHALL SHOW AND NOTE ALL MATERIALS REQUIRED WITH RELATIVE LOCATIONS AND SUFFICIENT DETAILS FOR PROPER FABRICATION AND ERECTION IN ACCORDANCE WITH ALL CONTRACT
DRAWINGS AND DOCUMENTS.
2. BOLTED CONNECTIONS:
a. ALL BOLTED CONNECTIONS SHALL BE DETAILED FOR REACTIONS IN KIPS (k) INDICATED ON PLAN. FOR LOADS NOT INDICATED ON PLAN OR SPECIFIED IN SHEET NOTES, PROVIDE A SHEAR CONNECTION WITH A MINIMUM 10 KIPS FOR LRFD AND 6 KIPS FOR ASD OR 60% OF MAXIMUM TOTAL UNIFORM LOAD SHOWN IN THE AISC MANUAL WHICHEVER IS GREATER. PROVIDE A MINIMUM NUMBER ROWS OF BOLTS AS INDICATED
BELOW FOR THE CORRESPONDING BEAM SIZES.
i. W8 AND W10 2 BOLTS
ii. W12 AND W14 3 BOLTS
iii. W16 AND W18 4 BOLTS
iv. W21 AND W24 6 BOLTS
v. W27 AND W30 7 BOLTS
b. BOLTS TO BE INSTALLED IN PROPERLY ALIGNED HOLES, TIGHTENED TO THE SNUG TIGHT CONDITION U.N.O.
THE SNUG TIGHT CONDITION IS DEFINED AS THE TIGHTNESS THAT EXISTS WHEN ALL PLIES IN A JOINT ARE IN FIRM CONTACT. THIS MAY BE ATTAINED BY A FEW IMPACTS OF AN IMPACT WRENCH OR THE FULL EFFORT OF
A MAN USING AN ORDINARY SPUD WRENCH.
c. SLIP-CRITICAL BOLTED CONNECTIONS SHALL CONFORM TO A.I.S.C. 'SPECIFICATIONS FOR STRUCTURAL JOINTS USING HIGH STRENGTH BOLTS', 2009 EDITION. SLIP CRITICAL BOLTED CONNECTIONS TO USE LOAD
INDICATOR WASHERS.
i. WHERE DIRECT TENSION INDICATORS ARE USED TESTING SHALL BE DONE IN ACCORDANCE
WITH AISC SPECIFICATIONS.
ii. WHERE BOLTING IS BY TURN-OF-NUT OR CALIBRATED WRENCH, THE INSPECTOR SHALL BE
PRESENT TO OBSERVE PROCEDURES AND/OR CHECK WRENCH CALIBRATION EACH DAY THAT
BOLTING IS BEING PERFORMED. HE WILL ALSO OBSERVE THAT BOLT SIZE, TYPE AND CONDITION OF THREAD AND LUBRICANT FOR BOLTS BEING INSTALLED IS CONSISTENT WITH THE BOLTS USED FOR
CALIBRATING THE WRENCHES THAT DAY.
iii. FOR BOLTED BRACE FRAMES UNLESS SHOWN OTHERWISE IN DETAILS PROVIDED IN
CONSTRUCTION DOCUMENTS.
d. HOLE TYPES AND WASHER REQUIREMENTS
i. STANDARD HOLES - STANDARD HOLES SHALL BE PROVIDED IN MEMBER-TO-MEMBER
CONNECTIONS, UNLESS OVERSIZED, SHORT-SLOTTED, OR LONG-SLOTTED CONNECTIONS ARE
CALLED FOR ON DESIGN DRAWINGS.
ii. OVERSIZED HOLES - OVERSIZED HOLES ARE PERMITTED IN ANY OR ALL PLIES OF SLIP-CRITICAL CONNECTIONS, BUT SHALL NOT BE PERMITTED IN BEARING-TYPE CONNECTIONS. HARDENED WASHERS
SHALL BE INSTALLED OVER ALL OVERSIZED HOLES.
iii. SHORT-SLOTTED HOLES - SHORT-SLOTTED HOLES ARE PERMITTED IN ANY OR ALL PLIES OF SLIP-CRITICAL OR BEARING-TYPE CONNECTIONS. THE SLOTS ARE PERMITTED WITHOUT REGARD TO DIRECTION OF LOADING IN SLIP-CRITICAL CONNECTIONS, BUT THE LENGTH SHALL BE NORMAL TO THE DIRECTION OF THE LOAD IN BEARING TYPE CONNECTIONS. WASHERS SHALL BE INSTALLED OVER SHORT-SLOTTED HOLES IN AN OUTER PLY. WHERE A325 OR A490 BOLTS ARE USED, WASHERS SHALL
BE HARDENED CONFORMING TO ASTM F436.
iv. LONG-SLOTTED HOLES - LONG-SLOTTED HOLES ARE PERMITTED IN ONLY ONE OF THE CONNECTED PARTS OF EITHER A SLIP-CRITICAL OR BEARING-TYPE CONNECTION AT AN INDIVIDUAL
FRAYING SURFACE. LONG-SLOTTED HOLES ARE PERMITTED WITHOUT REGARD TO DIRECTION OF
LOADING IN SLIP-CRITICAL CONNECTIONS, BUT THE LENGTH SHALL BE NORMAL TO THE DIRECTION OF THE LOAD IN BEARING TYPE CONNECTIONS. WHERE LONG-SLOTTEDHOLES ARE USED IN AN OUTER PLY, PLATE WASHERS OR A CONTINUOUS BAR WITH STANDARD HOLES, HAVING A SIZE SUFFICIENT TO COMPLETELY COVER THE SLOT AFTER INSTALLATION, SHALL BE PROVIDED. IN HIGH-STRENGTH
BOLTED CONNECTIONS, SUCH PLATEWASHERS OR CONTINUOUS BARS SHALL BE NOT LESS THAN
5/16" THICK AND SHALL BE OF STRUCTURAL GRADE MATERIAL, BUT NEED NOT BE HARDENED.
v. FOR A490 BOLTS GREATER THAN 1" IN DIAMETER A 5/16" MINIMUM THICKNESS HARDENED WASHER CONFORMING TO ASTM F436 SHALL BE USED UNDER BOTH THE HEAD AND THE NUT IN AN OVERSIZED HOLE OR IN AN OUTER PLY OF SLOTTED HOLES. MULTIPLE HARDENED WASHERS WITH A COMBINED THICKNESS EQUAL TO OR GREATER THAN 5/16" DO NOT SATISFY THIS REQUIREMENT.
vi. WHERE THE OUTER FACE OF THE BOLTED PARTS HAS A SLOPE GREATER THAN 1:20 WITH RESPECT TO A PLANE NORMAL TO THE BOLT AXIS, A HARDENED BEVELED WASHER SHALL BE USED
TO COMPENSATE FOR THE LACK OF PARALLELISM.
3. WELDED CONNECTIONS:
a. WELDED CONNECTIONS TO CONFORM TO A.W.S. D1.1 'STRUCTURAL WELDING CODE- STEEL'.
b. WELDING IS TO BE PERFORMED BY A WELDER QUALIFIED TO PERFORM THE SPECIFIED WELDS. QUALIFICATION OF THE WELDER SHALL BE DETERMINED BY TESTS AS PRESCRIBED IN SECTION 4, PART C, OF THE AMERICAN
WELDING SOCIETY - STRUCTURAL WELDING CODE - STEEL, A.W.S. D1.1.
c. WELD INSPECTION:
i. WELDS ARE TO BE INSPECTED BY A QUALIFIED INSPECTOR. A QUALIFIED INSPECTOR SHALL MAINTAIN CURRENT CERTIFICATION AS AN AMERICAN WELDING SOCIETY (A.W.S.) CERTIFIED WELDING INSPECTOR (CWI) IN ACCORDANCE WITH THE PROVISIONS OF A.W.S. QC1, 'STANDARD AND GUIDE FOR QUALIFICATION AND
CERTIFICATION OF WELDING INSPECTORS'.
ii. VISUAL INSPECTION
1. FOR ACCEPTABLE QUALIFICATION, WELDS SHALL MEET THE FOLLOWING:
a. THE WELD SHALL BE FREE OF CRACKS.
b. ALL CRATERS SHALL BE FILLED TO THE FULL CROSS SECTION OF THE WELD.
c. THE FACE OF THE WELD SHALL BE FLUSH WITH THE SURFACE OF THE BASE METAL, AND THE WELD SHALL MERGE SMOOTHLY WITH THE BASE METAL. UNDERCUT SHALL NOT EXCEED 1/32 IN. (1 mm).
WELD REINFORCEMENT SHALL NOT EXCEED 1/8 IN. (3 mm).
d. THE ROOT OF THE WELD SHALL BE INSPECTED, AND THERE SHALL BE NO EVIDENCE OF CRACKS, INCOMPLETE FUSION, OR INADEQUATE JOINT PENETRATION. A CONCAVE ROOT SURFACE IS
PERMITTED WITHIN THE LIMITS SHOWN BELOW, PROVIDED THE TOTAL WELD THICKNESS IS EQUAL TO
OR GREATER THAN THAT OF THE BASE METAL.
e. THE MAXIMUM ROOT SURFACE CONCAVITY SHALL BE 1/16 IN. (1.6 mm) AND THE MAXIMUM MELT- THROUGH SHALL BE 1/8 IN. (3 mm). FOR TUBULAR T-, Y-, AND K-CONNECTIONS, MELT THROUGH AT THE
ROOT IS CONSIDERED DESIRABLE AND SHALL NOT BE CAUSE FOR REJECTION.
2. AMOUNT OF WELDS TO BE INSPECTED IS AS FOLLOWS:
a. FILLET WELDS
- 10% OF ALL SHOP WELDS.
- 100% OF ALL FIELD WELDS.
b. FULL AND PARTIAL PENETRATION WELDS
- 100% OF ALL SHOP AND FIELD WELDS.
c. MINIMUM WELDS TO BE BY AISC AND/OR AWS, BUT NOT LESS THAN 3/16" E70XX CONTINUOUS
FILLET UNLESS OTHERWISE NOTED.
d. WHERE FIELD WELDING IS REQUIRED, WELD AREAS SHALL BE STRIPPED OF PAINT AND RUST. ALL
EXPOSED STEEL SHALL BE PAINTED AFTER WELDING.
4. PAINTING:
a. ALL STRUCTURAL STEEL AND MISCELLANEOUS STEEL IS TO HAVE ONE SHOP COAT OF GREY PRIMER PAINT.
STEEL IN CONTACT WITH CONCRETE, AT TOP OF FLANGE OF COMPOSITE BEAMS, AND BEAMS TO RECEIVE FIRE
PROOFING CEMENTITIOUS SPRAY SHALL NOT BE PAINTED.
b. HOT DIP GALVANIZE ALL STRUCTURAL STEEL ELEMENTS AND CONNECTIONS WHICH SHALL BE EXPOSED TO EXTERIOR CONDITIONS - WHETHER SPECIFIED ON THE DWGS OR NOT - AFTER FABRICATION. ITEMS SHALL INCLUDE
BUT NOT BE LIMITED TO
i. SHELF ANGLES OR PLATES AND LINTEL ANGLES OR PLATES
ii. ALL CLADDING (BUILDING SKIN) SUPPORT STEEL EXTENDING BEYOND THE WATERPROOFING MEMBRANE
iii. ALL PARAPET WALL SUPPORTING MEMBERS.
5. STEEL DECKING:
a. GALVANIZED DECK IS TO BE SIZE AND TYPE AS SHOWN ON DRAWINGS AND CONFORM TO ASTM A653-94.
STEEL.
b. PRIMER PAINTED DECK IS TO BE SIZE AND TYPE AS SHOWN ON DRAWINGS AND CONFORM TO ASTM A611.
c. CONNECTION REQUIREMENTS SHALL BE AS FOLLOWS UNLESS OTHERWISE NOTED ON DRAWINGS:
i. ATTACH DECK TO SUPPORT BEAMS, JOISTS OR PLATES WITH 5/8" PUDDLE WELDS AT 6" O.C
ii. SIDELAPS TO BE ATTACHED W/ #10 TEK SCREWS AT 12" O.C.
d. ALL FIELD WELDING OF DECK SHALL BE IN ACCORDANCE WITH ANSI/AWS D1.3 'STRUCTURAL WELDING CODE -
SHEET STEEL'
e. WELD METAL SHALL PENETRATE ALL LAYERS OF DECK MATERIAL AND SHALL HAVE GOOD FUSION TO THE SUPPORTING MEMBERS. CARE SHALL BE EXERCISED IN THE SELECTION OF ELECTRODES AND AMPERAGE TO
PROVIDE POSITIVE WELD AND PREVENT HIGH AMPERAGE BLOW HOLES.
f. ALL BLOW HOLES ARE TO BE REPAIRED BY DECK INSTALLER PRIOR TO INSTALLING ROOFING MATERIAL.
g. WELDING WASHERS SHALL BE USED ON ALL DECK UNITS WITH A STEEL THICKNESS LESS THAN 0.028 INCHES (22 GAGE). WELDING WASHERS SHALL BE A MINIMUM THICKNESS OF 0.056 INCHES,16 GAGE, AND HAVE A
NOMINAL 3/8" DIAMETER HOLE.
h. PROVIDE A MINIMUM EXTERIOR BERING LENGTH 2" AND MINIMUM INTERIOR BEARING LENGTH 4” OVER SUPPORTS.
i. END LAPS OF SHEETS SHALL BE A MINIMUM OF TWO INCHES AND SHALL OCCUR OVER SUPPORTS. ROOF SHALL BE ERECTED BEGINNING AT THE LOW SIDE TO ENSURE THAT END LAPS ARE SHINGLE FASHION. PROVIDE 1/4" BENT
PLATE AT ALL HIPS, SKEWED BEAMS, ETC.
j. POWDER ACTUATED DECK FASTENERS MAY BE USED IN LIEU OF WELDED CONNECTIONS PROVIDED DOCUMENTATION IN THE FORM OF TEST DATA, DESIGN CALCULATIONS OR DESIGN CHARTS ARE PROVIDED TO THE
ENGINEER FOR APPROVAL.
k. ROOF AND FLOOR OPENINGS NOT SHOWN ON PLANS SHALL BE FRAMED WITH 3 1/2" x 3 1/2" x 1/4" ANGLES.
l. DO NOT HANG MECHANICAL, PLUMBING, HVAC, FIRE SPRINKLERS, OR OTHERS DIRECTLY TO METAL DECK OR
METAL DECK WITH CONCRETE. CONTRACTOR TO PROVIDE SUPPORT BEAM FOR HANGERS.
POST INSTALLED ANCHORS
1. ADHESIVE ANCHORAGES HAVE BEEN SPECIFIED IN ACCORDANCE WITH HILTI DESIGN DATA. THE CONTRACTOR MAY SUBSTITUTE ANY OF THE BELOW LISTED MANUFACTURERS PROVIDED SIGNED AND SEALED CALCULATIONS ARE SUBMITTED FOR ENGINEER REVIEW. THE CALCULATIONS SHALL DEMONSTRATE THAT THE SUBSTITUTE
PRODUCT MEETS OR EXCEEDS THE STRENGTH OF THE BASIS OF DESIGN ANCHORAGE.
2. ANCHORAGE TO CONCRETE
a. ADHESIVE EPOXY ANCHORS SHALL BE TESTED AND QUALIFIED FOR USE IN ACCORDANCE WITH ACI355.4 AND ICC-ES AC308 AND MEET LOAD SPECIFIED SUCH AS: THE FOLLOWING OR EQUAL:
i. HILTI HIT-RE 500-V3 EPOXY ADHESIVE ANCHORING SYSTEM (ICC ESR-2322)
ii. HILTI HIT-HY 200 ADHESIVE (ICC ESR-3187)
iii. POWERS PE-1000+ (ICC ES ESR 2583)
iv. SIMPSON STRONG TIE "SET-XP" (ICC-ES ESR-2508)
v. OR EQUAL ADHERING TO ICC ES AC 308
NOTE: FOR HILTI PRODUCTS, STEEL ELEMENTS SHALL BE HILTI HAS-E CONTINUOUSLY THREADED ROD, HILTI HIS-N INTERNALLY THREADED INSERTS OR CONTINUOUSLY DEFORMED STEEL REBAR. FOR POWERS PRODUCTS, STEEL ELEMENTS SHALL BE ASTM A307-GRADE C, ASTM A 193 GRADE B7 TYPE 304 OR 316 STAINLESS STEEL (F 593, CONDITION CW) OR CONTINUOUSLY DEFORMED STEEL REBAR. FOR EQUAL PRODUCTS USE ACCORDING TO MANUFACTURER'S SPECIFICATIONS THAT MEET OR EXCEED LOADING
REQUIREMENTS.
b. MECHANICAL EXPANSION ANCHORS SHALL BE TESTED AND QUALIFIED FOR USE IN ACCORDANCE WITH
ACI 355.2 AND ICC-ES AC 193 AND MEET LOAD SPECIFIED SUCH AS:
i. HILTI KWIK BOLT - TZ ANCHORS (ICC ES ESR-1917)
ii. HILTI HSL-3 HEAVY DUTY SLEEVE ANCHORS (ICC ES ESR 1545)
iii. POWERS POWER-STUD SD-1 (ICC ES ESR 2818)
iv. POWERS POWER-BOLTS+
v. SIMPSON STRONG-TIE "TITEN-HD"(ICC-ES ESR 2713)
vi. SIMPSON STRONG TIE "STRONG BOLT 2" (ICC-ES ESR 3037)
vii. OR EQUAL ADHERING TO ICC ES AC 193.
c. MECHANICAL UNDERCUT ANCHORS SHALL BE TESTED AND QUALIFIED FOR USE IN ACCORDANCE WITH
ICC ES AC 193 AND MEET LOAD SPECIFIED SUCH AS:
i. HILTI HDA UNDERCUT ANCHORS
ii. POWERS ATOMIC+ UNDERCUT ANCHORS (ICC ES ESR 3067)
iii. OR EQUAL ADHERING TO ICC ES AC 193
d. CONCRETE SCREW ANCHORS SHALL BE TESTED AND QUALIFIED FOR USE IN ACCORDANCE WITH ICC ES
AC 193 AND MEET LOAD SPECIFIED SUCH AS:
i. HILTI KWIK HUS-EZ CONCRETE SCREW ANCHORS (ICC ES ESR 3027)
ii. POWERS WEDGE BOLT+ (ICC ES ESR 2526)
iii. OR EQUAL ADHERING TO ICC ES AC 193
3. ANCHORAGE TO SOLID GROUTED CONCRETE MASONRY
a. ADHESIVE (EPOXY) ANCHORS SHALL BE TESTED AND QUALIFIED FOR USE IN ACCORDANCE WITH ICC ES
AC58 AND MEET LOAD SPECIFIED SUCH AS:
i. HILTI HIT-HY 70 ADHESIVE ANCHORING SYSTEM (ICC ES ESR-3342) USING STEEL ELEMENTS HILTI
HAS-E CONTINUOUSLY THREADED ROD OR CONTINUOUSLY DEFORMED STEEL REBAR
ii. SIMPSON STRONG TIE "SET" (ICC ES ESR-1772)
iii. OR EQUAL ADHERING TO ICC ES AC 58
b. MECHANICAL ANCHORS SHALL BE TESTED AND QUALIFIED FOR USE IN ACCORDANCE WITH ISS ES AC01
OR ISS ES AC106 AND MEET LOAD SPECIFIED SUCH AS:
i. HILTI KWIK BOLT-3 EXPANSION ANCHORS, (ISS ES ESR-1385)
ii. POWER STUD SD-1 (ICC ES ESR -2966)
iii. SIMPSON STRONG TIE "TITEN HD" (ICC ES ESR-1056)
iv. SIMPSON STRONG TIE "WEDGE ALL" (ICC ES ESR 1396)
v. OR EQUAL ADHERING TO ICC ES ESR AC 106.
4. ANCHORAGE TO HOLLOW/MULTI-WYTHE MASONRY AND/OR CONCRETE MASONRY
a. ADHESIVE (EPOXY) ANCHORS SHALL BE TESTED AND QUALIFIED FOR USE IN ACCORDANCE WITH ICC ES
AC 58 AND MEET LOAD SPECIFIED SUCH AS:
i. HILTI HIT-HY 70 ADHESIVE ANCHORING SYSTEM (ES ESR3342) USING STEEL ELEMENTS HILTI HAS-E
CONTINUOUSLY THREADED ROD OR CONTINUOUSLY DEFORMED STEEL REBAR.
ii. POWERS T308+ ADHESIVE ANCHOR (ICC ES ESR-3149) BRICK MASONRY ONLY
iii. SIMPSON STRONG TIE "SET" (ICC ES ESR 1772) CONCRETE MASONRY ONLY OR EQUAL ADHERING
TO ICC ES 58
b. MECHANICAL ANCHORS SHALL BE TESTED AND QUALIFIED FOR USE IN ACCORDANCE WITH ICC ES AC
106 AND MEET LOAD SPECIFIED SUCH AS:
i. SIMPSON STRONG TIE "TITEN HD" - CONCRETE MASONRY ONLY
ii. OR EQUAL ADHERING TO ICC ES AC 106
5. INSTALLATION
a. CONTRACTOR SHALL BE RESPONSIBLE FOR INSTALLING ALL FASTENERS ACCORDING TO MANUFACTURER'S SPECIFICATIONS AND AS REQUIRED BY CODE. A PRE-CONSTRUCTION MEETING AND OR
TRAINING IS RECOMMENDED TO ENSURE PROPER INSTALLATIONS AT NO COST TO THE OWNER.
b. IF EXISTING CONDITIONS PREVENT INSTALLATION AS SHOWN ON DRAWINGS OR AS RECOMMENDED, CONTRACTOR SHALL CONTACT ENGINEER OR ANCHOR REPRESENTATIVE PRIOR TO INSTALLATION OF
ANCHORS FOR ALTERNATE RECOMMENDATION.
c. CONTRACTOR SHALL BE SURE ALL SURFACES ARE CLEAN AND ARE PREPARED ACCORDING TO
MANUFACTURER'S RECOMMENDATIONS.
d. ALL ANCHORS INSTALLATIONS SHALL BE PLUMB, NEAT AND LEVEL UNLESS OTHERWISE NOTED.
e. ARCHITECT/ENGINEER MAY REQUIRE PULLOUT OR SHEAR TESTS TO DETERMINE ADEQUACY OF
ANCHORS AT NO COST TO THE OWNER.
f. DESIGN BOND STRENGTH HAS BEEN BASED ON THE FOLLOWING CONDITIONS. ANY CHANGES SHALL BE
APPROVED BY ENGINEER PRIOR TO INSTALLATION.
i. CONCRETE TO BE CURED FOR AT LEAST 21 DAYS
ii. TEMPERATURE CATEGORY B ACCORDING TO ACI 355.4
iii. DRY HOLES
iv. HOLES DRILLED WITH A CARBIDE BIT
v. HOLE PREPARED ACCORDING TO MANUFACTURER'S INSTALLATION.
g. INSTALLERS FOR VERTICAL AND HORIZONTAL APPLICATION FOR TENSION LOADS SHALL BE CERTIFIED.
CERTIFICATIONS SHALL BE SUBMITTED WITH PRODUCT SUBMITTAL.
6. INSPECTION
a. ALL ANCHOR INSTALLATIONS REQUIRING CERTIFIED INSTALLER'S SHALL BE CONTINUOUSLY INSPECTED.
SHOP DRAWINGS
1. ALL SHOP DRAWINGS MUST BE REVIEWED AND STAMPED BY THE GENERAL CONTRACTOR PRIOR TO
SUBMITTAL.
2. THE GENERAL CONTRACTOR SHALL SUBMIT SHOP DRAWINGS TO ENGINEER FOR REVIEW OF THE
FOLLOWING APPLICABLE ITEMS:
a. ALL STRUCTURAL STEEL INCLUDING MISCELLANEOUS EMBEDMENTS. STEEL FABRICATION SHOP
DRAWINGS ARE TO BE SUBMITTED TO STRUCTURAL ENGINEER FOR APPROVAL PRIOR TO
FABRICATION. THE STRUCTURAL ENGINEER IS TO REVIEW DRAWINGS FOR COMPLIANCE WITH
DESIGN DOCUMENTS. ENGINEER IS TO REVIEW TYPE OF MATERIAL, MEMBER SIZES, AND
CONNECTIONS AND RETURN DRAWINGS TO THE STEEL FABRICATOR NOTING ANY
DISCREPANCIES. THE STEEL FABRICATOR IS RESPONSIBLE FOR ALL FABRICATION DIMENSIONS.
b. STRUCTURAL STEEL FRAMING CONNECTIONS(*).
c. STEEL STAIRS (*)
d. CONCRETE MIX DESIGNS.
e. COLD-FORMED METAL STUD, JAMBS, AND HEADERS AND/OR TRUSSES WITH CALCULATIONS. (*)
f. ANCHOR BOLT SUBMITTAL.
g. MECHANICAL EQUIPMENT REQUIRING STRUCTURAL SUPPORT.
h. CONCRETE CURING MATERIALS.
i. MECHANICAL ANCHOR SUBSTITUTIONS.
j. ARCHITECTURAL AND STRUCTURAL PRECAST ELEMENTS. (*)
k. HALFEN OR OTHER PRE-MANUFACTURED LINTELS. (*)
l. PRE-ENGINEERED METAL BUILDING MATERIALS. (*)
m. UNISTRUT DRAWINGS. (*)
n. MASONRY BLOCK.
o. FALL PROTECTION ANCHORAGE SYSTEM (*) ITEMS MARKED (*) SHALL HAVE SHOP DRAWINGS SEALED BY A PROFESSIONAL ENGINEER REGISTERED
IN THE STATE OF THE PROJECT LOCATION.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A/E:Structural Engineer:
O
WE
LTH O V
A
P F
I N E
N
R
I G
A
E
L
C M M O
N A
F
IRG
IN
I
DOUGLAS G
FITZPATRICK
Lic. No. 041192
R O
SS
O N
E E
C U s e rs
\j h a d s e l\ D o c u m e n ts \C
D
S tr u c t_
R e v it
H V
A C
P h a s e I
II
.r v t
/1
/2
:3
:3
P
M
S300
GENERAL NOTES
SPECIALIZED ENGINEERING
SOLUTIONS
1300 Baxter Street, Suite 355
Charlotte, NC 28204
(704) 348-3097
FITZPATRICK ENGINEERING
GROUP
19520 West Catawba Ave, Suite 311
Cornelius, NC 28031
704-987-9114
REPLACE HVAC PHASE III
1970 Roanoke Blvd, Salem, VA 24153
268-21-102
12" = 1'-0"S300
1 GENERAL NOTES
STAIR POST, BY
OTHERS
PL5/8"x12"x12"
POST BASEPLATE
/2
1" TO 2 1/2" TYP,
E X S
L A
B
T H
IC
K N
E S
S
FIELD DRILL BOLT HOLES
IN BASE PLATE AFTER
LOCATING REINFORCEMENT
EX. SLAB REINFORCEMENT, NOT
TO BE CUT, FIELD TO LOCATE
EA. WAY, BY FIELD
1/2" DIA. F1554, GR. 36 THREADED ROD W/
LEVELING NUT AND WASHER, HILTI-RE 500
V3 EPOXY OR APPR. EQUAL. AT 4" EMBEDMENT
N O
N -S
H R
IN
K G
R O
U T
REMOVE AND REPLACE ROOFING,
INSULATION AND MEMBRANE,
SLOPE AWAY FROM POST
/2
1'
1' - 0"
1 1/2"
STAIR POST AT WAREHOUSE
ROOF JOIST, TYP
REMOVE AND REPLACE ROOFING,
INSULATION AND MEMBRANE,
SLOPE AWAY FROM POST
1' - 4"
1 1/2"
(4) 1/2" DIA. F1154 Gr. 36
THREADED ROD THRU
ELEVATED SLAB
1/4" x 3" SQ. PL. WASHER AT
UNDERSIDE OF SLAB, TYP
JAMB NUT OR PEEN
THREADED BELOW SLAB
PL 5/8" x 12" x 1'-4", TYP
AT JOIST SUPPORTED
STAIR POST
N O
N -S
H R
IN
K G
R O
U T
C
1' - 10"
1'
11"
5 1/2" 7 1/2" 7" 2"
/2
/2
5/8" THICK BASE PLATE,
ADJUST LOCATION UP TO
1 1/2" IN EA. DIRECTION TO
AVOID EX. REINFORCEMENT
A
/2
/2
2" 7" 7 1/2" 7 1/2" 7" 2"
2' - 9"
5/8" THICK BASE PLATE,
ADJUST LOCATION UP TO 1 1/2"
IN EA. DIRECTION TO AVOID EX.
REINFORCEMENT
HORZ. SHORT SLOTTED HOLES
AT INTERIOR ANCHOR LOCATIONS
C
4' - 9"
BRACE WORK
POINT
L4X4X1/4 BRACE,TYP
AT MOMENT CONN.
HSS6x6x1/4 POST
W/ 3/16" TOP CAP PL.,
TYP
/4
PL5/8"x12"x12"
POST BASEPLATE
EX. GIRDER AND COLUMN
REINFORCEMENT, NOT TO
BE CUT, FIELD TO LOCATE
1/2" DIA. F1554, GR. 36 THREADED ROD W/
LEVELING NUT AND WASHER, HILTI-RE 500
V3 EPOXY OR APPR. EQUAL. AT 4" EMBEDMENT
REMOVE AND REPLACE ROOFING, INSULATION,
AND MEMBRANE AT FRAME POST, SLOPE AWAY
FROM POST, TYP
1/2"
1/4" FULL DEPTH
STIFFENER AT
HANDRAIL POST
1/8 2-6 1/8 2-6
WRAP TOP/BTM
FLANGE, TYP
1'
1'
4" TOE PLATE
HSS1.900x0.188 GALVANIZED HAND
RAIL POST AT 4'-0" MAX SPACING
HSS1.900x0.145 GALVANIZED
HAND/MID RAIL, TYP
1 1/4x 1/8 TYPE 19-4 GALVANIZED STEEL GRATING, TYPICAL AT ELEVATED PLATFORMS
PROVIDE DOUBLE ANGLE BOLTED
CONNECTIONS AT BEAM TO BEAM
CONNECTIONS AT EQUIPMENT FRAME,
PROVIDE A MINIMUM OF 3/4" DIA. A325
BOLTS PER ROW AT EACH CONNECTION:
W24 - 5 BOLTS
W16 - 4 BOLTS
W12 - 3 BOLTS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A/E:Structural Engineer:
O
WE
LTH O V
A
P F
I N E
N
R
I G
A
E
L
C M M O
N A
F
IRG
IN
I
DOUGLAS G
FITZPATRICK
Lic. No. 041192
R O
SS
O N
E E
C U s e rs
\j h a d s e l\ D o c u m e n ts \C
D
S tr u c t_
R e v it
H V
A C
P h a s e I
II
.r v t
/1
/2
:3
:4
P
M
S500
FRAMING DETAILS
SPECIALIZED ENGINEERING
SOLUTIONS
1300 Baxter Street, Suite 355
Charlotte, NC 28204
(704) 348-3097
FITZPATRICK ENGINEERING
GROUP
19520 West Catawba Ave, Suite 311
Cornelius, NC 28031
704-987-9114
REPLACE HVAC PHASE III
1970 Roanoke Blvd, Salem, VA 24153
268-21-102
1 1/2" = 1'-0"S500
1 STAIR BASE AT SLAB
1" = 1'-0"S500
2 STAIR BASE AT JOIST
1 1/2" = 1'-0"S500
3 AHU FRAME BASE PLATE 1
1 1/2" = 1'-0"S500
4 AHU FRAME BASE PLATE 2
3/4" = 1'-0"S500
5 KNEE BRACE MOMENT FRAME
1 1/2" = 1'-0"S500
6 SECTION AT HAND RAIL
1 1/2" = 1'-0"S500
7 INTERIOR BEAM CONNECTIONS
2 3 4 5 6 7 8
C
B
A
D
E
F
I
20' - 2"
4'
- 9
1/ 2"
5'
- 8
1/ 2"
1'
- 6
3'
- 4 1/
2"
6' - 0" 6' - 0" 6' - 0" 6' - 0" 1' - 8 1/2"
2 3/4"4' - 0"2 3/4"
4' - 9 1/2" 11' - 0 1/4"
HIGH ROOF
ELEV. 0'-0"
PARAPET +25"
LOW ROOF
ELEV. -9'-11
LANDING
ELEV + 3'-1"
A-501
520 West Sixth Street Charlotte, NC 28202 T. +1 704 940 0501 F. +1 704 362 4602
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% SUBMITTAL
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD Engineer of Record:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
2A
PROJECT AREA
KEY PLAN
PLAN NORTH TRUE NORTH
BI
M
- V A
Sa le m U pg ra de _R ep la ce H
VA
C
P ha se
II
I/S al em V
A M ed ic al _R ep la ce H
VA
C
P ha se
II
I_ Ar ch _R
.rv t 1/
/2
6:
:5
PM
A-101
ROOF PLAN
SPECIALIZED ENGINEERING
SOLUTIONS
1300 Baxter Street, Suite 355 Charlotte, NC 28204
(704) 348-3097
REPLACE HVAC PHASE III
1970 Roanoke Blvd, Salem, VA 24153
658-21-102
01/20/2022
1/8" = 1'-0"1 ROOF PLAN
1/20/2022
1' - 8 1/2" 2"
8"
2" 6 2
5/3 2"
1 1/2" I.D. VERT. - GALV.
1 1/4" I.D. HORIZ. - GALV.
HSS 4X4X1/4" POST WITH CAP PLATE - GALV.
GALV. ANGLE 3X3 X 6" BOLT/WELD TO STINGER AND POST
1" GLAV. STL. GRATING WITH PREFORMED NOSING
AND 3" MIN. VERTICAL KICK PLATE
C 10 X 20 STRINGER - GALV.
EPDM BOOT FLASHING
NEW 60 MIL EPDM ROOFING AT PATCH OVER ROOF
INSULATION TO MATCH, MAINTAIN ANY VAPOR BARRIERS
WITHIN THE EXISTING SYSTEM
NEW 3/4" BEARING PLATE 8" X 18"
WITH THRU BOLTS TO
DUAL 3/4" BEARING PLATE 8" X 4"
EXISTING CONC. STEM AT 3'-0" O.C. TYP.
LOCATE THESE STEMS IN THE FIELD
4X4 POSTS AND BEARING PLATES TO CENTER
ON THESE STEMS
EXISTING INSULATION
2 3 4
E
20' - 2"2 3/4" 4' - 0" 1' - 1 3/4"
2 3 /4"
4' -0
3'
- 2 3/
4" 4'
- 7
4'
- 9
1/ 2"
2 3 /4"
4' -0
2 3
/4" 1'
- 0
4'
- 9
1/ 2"
5'
- 8
1/ 2"
1'
- 6
3'
- 4 1/
2"
6' - 0" 6' - 0" 6' - 0" 6' - 0" 1' - 8 1/2"
1'
- 8
1/ 2" 2 3/4" 4' - 0" 2 3/4"
4' - 9 1/2" 11' - 0 1/4"
ROOF STAIR
TREADS: 1" GALV. STEEL GRATING WITH FORMED NOSING
STRINGER: C10X20 GALV.
POSTS: HSS 4.00 X .25" GALV.
BEARING PLATES: SEE DETAILS
HANDRAILS : 1 1.2" I.D. GALV. PIPE
GUARDRAILS: VERTICALS 1 1/2" I.D. GALV. PIPE AT 5'-0" O.C.
TOP RAIL 1 1/2" I.D. PIPE
HORIZONTAL RAILS (3) 1 1/4" I.D.
ROOF WALKWAY PAD: BY CARLISLE FOR EPDM
BOOT FLASHING BY CARLISLE FOR EPDM
ROOFING MEMBRANE: MATCH EXISTING: 30 YEAR EPDM (11/2008) BAKER ROOFING
HIGH ROOF
ELEV. 0'-0"
PARAPET +25"
LOW ROOF
ELEV. -9'-11
22 T AT 11" = 22'-2"
23 R AT 6.78" = 13'-0" RISE
LANDING
ELEV + 3'-1"
5 T A
T
4'
-7
6 R A
T 6.1
7"
3' -1
" R
IS
E
A-501
A-501
9'
- 1
1" 2'
- 1
0"
3'
- 1
4" 7"
1" 2"
520 West Sixth Street Charlotte, NC 28202 T. +1 704 940 0501 F. +1 704 362 4602
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% SUBMITTAL
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD Engineer of Record:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
2A
PROJECT AREA
KEY PLAN
PLAN NORTH TRUE NORTH
BI
M
- V A
Sa le m U pg ra de _R ep la ce H
VA
C
P ha se
II
I/S al em V
A M ed ic al _R ep la ce H
VA
C
P ha se
II
I_ Ar ch _R
.rv t 1/
/2
6:
:5
PM
A-501
DETAILS
SPECIALIZED ENGINEERING
SOLUTIONS
1300 Baxter Street, Suite 355 Charlotte, NC 28204
(704) 348-3097
REPLACE HVAC PHASE III
1970 Roanoke Blvd, Salem, VA 24153
658-21-102
01/20/2022
1" = 1'-0"4 STAIR DETAILS
1/4" = 1'-0"1 STAIR ENLARGED PLAN
1/4" = 1'-0"2 STAIR SECTION - LOWER PART
1/4" = 1'-0"3 STAIR SECTION - HIGHER PART
1/20/2022
4 5 6 7 8 9
10 11 12 13
C
D
E
F
G
H
I
IMMEDIATE SUPPLY
DISTRIBUTION
BE-141
NEW EQUIPMENT DISTRIBUTION
BE-140
PHARMACY STORAGE
BE-104
BREAK
BE-110
TOILET
BE-106
STAFF TOILET
BE-111
OFFICE
BE-105
OFFICE
BE-105A
STAIR
NO-7
ENG CONTROL CENTER
BD-124
TRANSFORMER ROOM
BD-122
SVC BAY MECH STORAGE
BD-123A
SVC BAY
BD-123
ELECTRICAL
BD-122A
ELECTRICAL
BE-102
ELECTRICAL
BE-101
OFFICE
BE-135
Space
BD-103C-40
ELEVATOR
CL-2
ELEV EQUIP
BD-113
JANITOR
BE-164
SPD SERV CHIEF
BD-114C
OFFICE
BD-116
Space
BD-103C-48
CART STOR
BD-111
CLEAN HOLDING
BE-162
HD STORAGE
BD-112
CART WASH EQUIP
BD-110
VEST
BE-166
WOMEN'S LOCKER
BD-107A
STAFF BREAK
BD-109
HAC
BD-105
ANTE
CB-34
DOCK - SOILED
BE-160
WORK STATION
BE-148
DISCREPANCY HOLDING
BE-149
BULK CLEAN SUPPLY
BE-146
UNASSIGNED
BE-145
DELIVERY PROCESSING
BE-144
AUTO CART WASH
BD-104
ADMIN ASSIST
BD-115
Space
BD-103C-69
STAFF WORK SUPPLY
DISTRIBUTION
BE-136
CRASH CART BUILDING
BE-132
CORRIDOR
BE-137
CRASH CART STORAGE
BE-133
Space
BD-103C-74
Space
BD-103C-75
CART DRY
BD-117A
OFFICE
BE-134
TELE
BE-100
ELEVATOR
CL-1
ELECTRICAL
BD-100
STAFF WORK CASE CART
BE-161
ASSIST SERV CHIEF
BD-114
A&MM WAREHOUSE OFFICE
BD-117B
MED GAS STOR
BE-108
EXCESS PROPERTY STORAGE
BE-107
MECHANICAL ROOM
BE-103A
Space
BD-103C-88
DOCK - CLEAN
BE-109
Space
BD-103C-91
Space
BD-103C-92
CORRIDOR
CB-35A
HD STORAGE
BE-131
Space
BD-103C-95
ELEVATOR MACHINE
BE-103A
DECONTAM
BD-102A
SPD SCOPE REPROCESSING
BD-103B
EQUIPMENT STORAGE
BD-103C
CIRCULATION
BE-103
Space
BD-103C-101
MAIL ROOM
BE-150
M200
2 3 4 5 6 7 8 9 10 11 12 13
C
B
A
D
E
F
G
H
I
1 HOUR
2 HOUR
3 HOUR
FIRE RATING LEGEND
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% SUBMITTAL
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
Engineer of Record:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
2A
PROJECT AREA
KEY PLAN
PLAN NORTH TRUE NORTH
01/22/2022
B
IM
/2
V
A S a le m U p g ra d e
R e p la c e H
V A
C P h a s e
I
II
/2
V A
S a le m
U p g ra d e
R e p la c e
H V
A C
P h a s e
I
II
S E
S
.r v t
/1
/2
:2
:0
P
M
LS100
LIFE SAFETY PLAN
SPECIALIZED ENGINEERING
SOLUTIONS
1300 Baxter Street Suite 355
Charlotte, NC 28204
(704)348-3097
REPLACE HVAC PHASE III
1970 Roanoke Blvd, Salem, VA 24153
658-21-102
01/20/22
1/8" = 1'-0"
BASEMENT - LIFE SAFETY - EXISTING
CONTRACTOR REQUIREMENTS FOR THE
DEMOLITION OF, OR ADDITION TO, ANY PORTION
OF AIR, HYDRONIC OR STEAM SYSTEMS.
COVER SHEET NOTES:
THE FOLLOWING SHALL APPLY TO ALL MECHANICAL SYSTEMS AFFECTED BY CONSTRUCTION ACTIVITIES.
SYSTEMS INCLUDED BUT ARE NOT LIMITED TO HVAC, EXHAUST, EQUIPMENT, DUCTWORK, DUCTWORK ACCESSORIES, HYDRONICS, COILS, FILTERS, TEMPERATURE CONTROLS, LIFE SAFETY CONTROLS AND
PRESSURIZATION CONTROLS.
1. AIR QUALITY, QUANTITY AND PRESSURE RELATIONSHIPS SHALL COMPLY WITH THE LATEST, ANSI/ASHRAE/ASHE STANDARD 170 REQUIREMENTS.
2. COMPLY WITH THE FACILITY'S INFECTIOUS CONTROL RISK ASSESSMENT (ICRA) REQUIREMENTS.
3. MAINTAIN EXISTING AIR QUALITY REQUIREMENTS, AIR PRESSURIZATION AND OTHER UTILITY
REQUIREMENTS FOR OCCUPIED AREAS DURING ANY RENOVATION OR CONSTRUCTION.
4. DETERMINE AND VERIFY THE AREAS SERVED BY THE AFFECTED SYSTEMS.
5. TAKE AIR AND OR/ WATER BALANCE READINGS OF THE SYSTEMS BEING AFFECTED.
6. IF THERE ARE SPACES BEING SERVED OUTSIDE OF THE DEMOLITION OR ADDITION AREA, THE
FOLLOWING PROCEDURES MUST BE TAKEN:
a. TAKE AIR AND/OR WATER BALANCE READINGS AS NEEDED TO QUANTIFY THE AIR AND/OR
WATER FLOWS DELIVERED TO THE SYSTEMS OUTSIDE THE AFFECTED AREA.
b. DURING DEMOLITION, TAKE ALL NECESSARY MEASURES TO MAINTAIN THE CORRECT AIR
AND/OR WATER FLOWS TO THE SYSTEMS THAT ARE REMAINING.
c. AFTER THE COMPLETION OF DEMOLITION, VERIFY THAT AIR AND/OR WATER FLOWS ARE
CORRECT.
d. AFTER COMPLETING ANY ADDITIONS TO THE SYSTEM, VERIFY THAT AIR AND/OR WATER
FLOWS ARE CORRECT.
7. THE CONTRACTOR IS TO PROVIDE TEMPORARY AIR/AND OR WATER SYSTEMS AS NEEDED TO
MAINTAIN PROPER TEMPERATURE AND PRESSURE RELATIONSHIPS OF SPACES REQUIRED TO BE
OCCUPIED DURING CONSTRUCTION.
8. ALL TEMPORARY AIR SUPPLY SYSTEMS MUST UTILIZE FINAL FILTERS THAT ARE A MINIMUM OF 90% EFFICIENT (MERV 14). FINAL FILTERS MUST BE DOWNSTREAM OF ALL AIR SUPPLY COMPONENTS.
MECHANICAL GENERAL NOTES:
A. THESE NOTES APPLY TO ALL SHEETS CONTAINING HVAC, PIPING AND TEMPERATURE CONTROLS WORK.
REFER TO PROJECT SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS. WHERE A DISCREPANCY EXISTS BETWEEN THESE PLANS AND THE PROJECT SPECIFICATIONS, THE SPECIFICATION REQUIREMENTS SHALL
TAKE PRECEDENCE OVER THE DRAWINGS.
B. VERIFY THE EXISTING CONDITIONS AT THE PROJECT SITE BEFORE SUBMITTING COST PROPOSAL. BE ADVISED THAT LOCATIONS SHOWN ARE APPROXIMATE. AN ATTEMPT HAS BEEN MADE TO SHOW ALL PIPING, FIXTURES, DUCTWORK, AND OUTLETS. CONTRACTOR SHALL VISIT THE SITE TO VERIFY COMPONENTS, LOCATIONS AND SIZES SHOWN OR NOT SHOWN. ALL COMPONENTS NEED TO BE REMOVED IN THE
DEMOLITION AREA UNLESS NOTED ON THE DRAWINGS. IF DEVIATION BETWEEN EXISTING CONDITIONS AND
NEW WORK IS FOUND, CONTRACTOR SHALL NOTIFY ENGINEER.
C. IT IS MANDATORY THAT THE EXISTING BUILDING REMAIN IN CONTINUOUS AND NON-INTERRUPTED OPERATION DURING THE CONSTRUCTION OF THE ADDITIONS AND REMODELING/ALTERATION OF THE EXISTING BUILDING. SERVICES TO THE EXISTING BUILDING SHALL BE KEPT ON CONTINUOUS OPERATION EXCEPT DURING SCHEDULED SHUTDOWNS FOR EXTENSION OR MODIFICATION. PLAN TO COMPLETE SHUTDOWNS DURING OFF HOURS TO MINIMIZE IMPACT TO THE OWNER. COORDINATE SHUTDOWNS WITH THE OWNER A MINIMUM OF 14 DAYS PRIOR TO WORK. PROVIDE TEMPORARY SERVICES WHERE NECESSARY TO ACCOMPLISH ANY SHUTDOWN. THIS INCLUDES BUT IS NOT LIMITED TO STAFFING AND EQUIPMENT FOR FIRE WATCHES, PROVISIONS FOR BOTTLED WATER, AND TEMPORARY HEATING OR COOLING EQUIPMENT.
TEMPORARY MEASURES SHALL NOT BE REMOVED UNTIL THE PERMANENT SYSTEMS ARE OPERATIONAL AND
HAVE PASSED ALL REQUIRED TESTING.
D. REFER TO THE SPECIFICATIONS AND ARCHITECTURAL PLANS FOR PHASING REQUIREMENTS. DURING EACH PHASE THE CONTRACTOR SHALL COMPLETE ALL WORK LOCATED WITHIN THE BOUNDARY OF THAT PHASE.
ANY WORK AND THAT MUST BE COMPLETED IN THE AREA AFTER THAT AREA HAS BEEN TURNED OVER TO THE OWNER SHALL BE IDENTIFIED AT THE BEGINNING OF THE PHASE FOR EVALUATION AND ACCEPTANCE
OF THE OWNER.
E. CONTRACTOR SHALL BE RESPONSIBLE FOR THEIR OWN DEMOLITION, REMOVAL, CAPPING, STORING, ABANDONING, DISCONNECTING, RELOCATING AND RECONNECTION OF EXISTING EQUIPMENT AND MATERIAL.
ALL CUTTING, PATCHING, REPAIRING, REPLACEMENT AND REFINISHING SHALL MATCH THE EXISTING
CONSTRUCTION AS NEARLY AS POSSIBLE.
F. EXCEPT WHERE OTHERWISE SHOWN OR NOTED ON THE DRAWINGS AS "TO BE RETAINED, RELOCATED", ALL EXISTING EQUIPMENT AND MATERIAL IN AREAS TO BE REMODELED/ALTERED SHALL BE REMOVED WHERE THEY INTERFERE WITH PROPOSED NEW CONSTRUCTION AND/OR WITH PROPOSED USAGE OF SPACE BY
OWNER AS FOLLOWS:
a. REMOVE ANY PIPING PROTRUDING ABOVE FINISHED FLOOR OR THROUGH WALL AND CAP WITHIN 3
PIPE DIAMETERS OF NEAREST ACTIVE MAIN WITH MATERIAL TO MATCH EXISTING.
b. REMOVE ALL FIXTURES, CARRIERS, SUPPLY AND WASTE AND VENT PIPING, STEAM, HEATING HOT
WATER, HVAC SUPPLY, RETURN AND EXHAUST AS NOTED. CAP WITHIN 3 PIPE DIAMETERS OF
NEAREST ACTIVE MAIN. SUPPLY AND RETURN MAINS ON PIPING SYSTEMS CONVEYING WATER OR
GASES SHALL BE VALVED AND CAPPED
c. IN REMODELED/ALTERED AREAS, ANY PIPING OR DUCTWORK PASSING THROUGH THE REMODELED
AREAS TO SERVE (OR BEING SERVED FROM EXISTING ADJACENT, REMOTE, OR SURROUNDING
AREAS THAT ARE TO REMAIN) SHALL BE RETAINED AND KEPT OPERATIONAL AND SHALL BE
REROUTED IN ALL CASES WHERE THEY INTERFERE WITH ANY NEW WORK OR USAGE TO BE
ACCOMPLISHED IN THE REMODELED AREA.
d. REMOVE UNUSED OR ABANDONED HANGERS AND PATCH ABANDONED PENETRATIONS TO MATCH
EXISTING.
e. PENETRATIONS THROUGH EXISTING WALLS AND FLOORS FORMERLY OCCUPIED BY REMOVED PIPING
OR DUCTWORK SHALL BE PATCHED TO MATCH EXISTING CONSTRUCTION.
f. RE-SUPPORT ANY PIPING AND DUCTWORK THAT WAS SUPPORTED FROM BUILDING ELEMENTS
REMOVED AS PART OF THE WORK.
g. MAINTAIN CONTROL WIRING OR PNEUMATIC TUBING REQUIRED FOR THE CONTINUED PROPER
OPERATION OF THE BUILDING AUTOMATION SYSTEM.
G. ALL EXISTING EQUIPMENT BEING REMOVED WILL BE HANDED OVER TO OWNER FOR FIRST RIGHT OF SALVAGE. IF OWNER REFUSES SALVAGE ITEMS, REMOVING CONTRACTOR SHALL BE RESPONSIBLE FOR
DISPOSAL.
H. CONTRACTOR SHALL REFER TO THE DRAWINGS OF ALL TRADES TO FAMILIARIZE THEMSELVES WITH EXTENT OF WORK INCLUDING BUT NOT LIMITED TO WHERE NEW PARTITIONING IS BEING INSTALLED, WHERE EXISTING PARTITIONING IS BEING REMOVED, WHERE CEILINGS ARE BEING REMOVED AND/OR REPLACED, ETC.
I. THESE DRAWINGS ARE NECESSARILY DIAGRAMMATIC IN NATURE. NOT ALL FITTINGS, OFFSETS, VENTS OR DRAINS ARE SHOWN. THE CONTRACTOR SHALL INCLUDE ALL FITTINGS, OFFSETS, VENTS, DRAINS, AND
DEVICES REQUIRED TO PROVIDE A COMPLETE AND FUNCTIONING SYSTEM.
J. PERFORM AIR AND FLUID BALANCE PRE-TEST ON ALL DISTRIBUTION EQUIPMENT AND ALL AIR OUTLETS IN THE AREA PRIOR TO COMMENCING WORK. SUBMIT PRE-TEST INFORMATION TO OWNER/ENGINEER.
K. PROVIDE ACCESS DOORS IN DUCTWORK AND/OR ARCHITECTURAL ELEMENTS WHERE REQUIRED TO ACCESS ALL EQUIPMENT REQUIRING MAINTENANCE AND ADJUSTMENT. THIS EQUIPMENT INCLUDES BUT IS NOT LIMITED TO SENSORS, DAMPERS, ACTUATORS, CONTROL DEVICES, VALVES, ETC. ACCESS DOORS SHALL BE SIZED TO PROVIDE APPROPRIATE ACCESS BASED ON HEIGHT OF ACCESS REQUIRED AND
ACTIVITY. INSTALL SUCH THAT ACCESS DOOR IS FULLY OPERABLE WITHOUT THE REMOVAL OF
ARCHITECTURAL ELEMENTS SUCH AS CEILING RUNNERS, SUPPORTS, ETC. INSTALL IN A LOCATION SUCH THAT STEPPING OR LEANING OVER PERMANENT EQUIPMENT OR FURNITURE IS NOT REQUIRED. WHERE ACCESS DOORS ARE REQUIRED IN ARCHITECTURAL ELEMENTS THAT PROVIDE A FIRE AND/OR SMOKE
RATING, ACCESS DOOR SHALL MAINTAIN THE REQUIRED RATING.
L. SEAL ALL WALL PENETRATIONS (DUCTWORK, PIPING, CONTROLS, CONDUITS, ETC.) WITH NON-COMBUSTIBLE MATERIAL. SEAL PENETRATIONS INTO ROOMS THAT REQUIRE PRESSURE CONTROL OR SOUND ISOLATION.
WITH NON-COMBUSTIBLE MATERIAL AND CAULK.
M. PIPING AND DUCTWORK SHALL NOT BE ROUTED OVER ELECTRICAL AND TELECOM ROOMS. WHERE ROUTING OVER SUCH ROOMS IS UNAVOIDABLE, CONTRACTOR SHALL COORDINATE WITH OWNER, DESIGN TEAM, AHJ, AND OTHER TRADES REGARDING LOCATION OF PANELS AND UTILITY ROUTING AND SHALL PROVIDE DRIP PANS UNDER ALL UTILITIES WITH MOISTURE SENSORS OR DRAIN PIPING AS REQUIRED BY THE
SPECIFICATIONS.
N. REMOVAL AND REINSTALLATION OF CEILINGS REQUIRED FOR THE COMPLETION OF WORK IS THE RESPONSIBILITY OF THE CONTRACTOR. CONTRACTOR SHALL REPAIR OR REPLACE ALL DAMAGED CEILING COMPONENTS TO MATCH EXISTING. WHERE AN IDENTICAL MATCH IS NO LONGER AVAILABLE, CONTRACTOR
SHALL PROVIDE A SIMILAR REPLACEMENT UPON APPROVAL FROM THE OWNER.
O. FLEXIBLE DUCTWORK SHALL HAVE A MAXIMUM LENGTH OF 48" REGARDLESS OF LENGTH SHOWN ON DRAWINGS. FLEX DUCT INSTALLATION SHALL BE AT TERMINAL ENDS ONLY. CONNECTIONS AT VAV BOX INLETS SHALL BE SOLID HARD DUCT. THE DUCTWORK AT ANY FIRE AND/OR FIRE SMOKE DAMPER SHALL BE
HARD DUCT.
P. LOCATE PIPING AND DUCTWORK IN EXTERIOR BUILDING WALLS ON THE WARM SIDE OF THE BUILDING AND VAPOR BARRIER. COORDINATE INSTALLATION OF BUILDING INSULATION TO RUN CONTINUOUS BETWEEN
PIPING AND BUILDING WALL.
Q. SUPPORT ALL DUCTWORK, PIPING AND EQUIPMENT FROM BUILDING STRUCTURE MEMBERS. ROUTE DUCT MAINS TIGHT TO STRUCTURE UNLESS NOTED OTHERWISE. HOLD PIPING TIGHT TO BOTTOM OF STRUCTURAL MEMBERS OR RUN THROUGH JOIST WEBS IF POSSIBLE. DO NOT USE WIRE OR PERFORATED METAL TO SUPPORT PIPING. DO NOT SUPPORT PIPING FROM OTHER PIPING, DUCTWORK, AND/OR ELECTRICAL CONDUITS. SUPPORT FROM BOTTOM CHORD OF BAR JOISTS ONLY AT PANEL POINTS. ALL COMPONENTS REQUIRING MAINTENANCE SHALL BE SUPPORTED IN SUCH A MANNER AS TO BE READILY ACCESSIBLE WITHOUT REMOVAL OF THE CEILING SYSTEM AND TO ALLOW FOR REMOVAL FROM THE SYSTEM WHEN SUCH
REMOVAL IS REQUIRED FOR MAINTENANCE.
R. PROVIDE CONSTRUCTION FILTERS ON AIR MOVING EQUIPMENT SERVING THE CONSTRUCTION AREA AS WELL AS ALL RETURN/EXHAUST DUCT PENETRATIONS COMING FROM THE CONSTRUCTION AREA. AT THE COMPLETION OF WORK, REMOVE ALL TEMPORARY AND CONSTRUCTION FILTERS AND PROVIDE NEW
FILTERS FOR ALL AIR MOVING EQUIPMENT.
S. PROTECT ALL DUCTWORK AND PIPING DURING CONSTRUCTION. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION. AT A MINIMUM, DUCTWORK AND PIPING ENDS SHALL BE COVERED AND SEALED TO PREVENT THE COLLECTION OF DUST AND DEBRIS. CLEAN ALL INTERIOR SURFACES PRIOR TO INSTALLATION AND PROTECT ONCE INSTALLED. MEDICAL GAS PIPING SHALL BE PROTECTED IN
ACCORDANCE WITH NFPA 99 REQUIREMENTS.
T. AT THE COMPLETION OF WORK, CLEAN ALL STRAINERS PROVIDED AS A PART OF THE WORK AS WELL AS PRIMARY SYSTEM STRAINERS LOCATED AT PUMPS WHERE SYSTEMS WERE EXTENDED. ON EXISTING
EQUIPMENT, COORDINATE WORK WITH OWNER.
U. PROVIDE INTERMEDIATE TESTING AND BALANCING AT THE COMPLETION OF EACH PHASE AND AS REQUIRED
TO MAINTAIN PROPER OPERATION OF SYSTEMS SERVING OCCUPIED AREAS OF THE FACILITY.
V. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL PIPING, EQUIPMENT AND DUCTWORK INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.
W. REFER TO SCHEDULES FOR SIZES OF FINAL RUNOUTS TO EQUIPMENT, FIXTURES, DIFFUSERS, GRILLES, AND TERMINAL DEVICES. FINAL RUNOUT SIZES LISTED SHALL BE USED TO WITHIN 10 EQUIVALENT DIAMETERS OF FINAL CONNECTION POINT. FINAL PIPING CONNECTION TO EQUIPMENT SHALL MATCH EQUIPMENT CONNECTION SIZE, PROVIDE TRANSITIONS AS REQUIRED. REFER TO DETAILS, DIAGRAMS AND SCHEMATICS
FOR ADDITIONAL FINAL CONNECTION REQUIREMENTS.
X. FOR DUCTWORK PENETRATING A ONE HOUR FIRE RATED WALL WHERE A FIRE DAMPER IS NOT SHOWN, PROVIDE U.L. LISTED THROUGH PENETRATION FIRE STOPPING SYSTEM THAT IS SPECIFIC TO THE WALL CONSTRUCTION ASSEMBLY AND COMPLIANT WITH ASTM E814. THE SYSTEM SHALL BE FIRE TESTED PER ASTM E119 AND COMPLY WITH EXCEPTION 1 OF 2018 IBC PART 717.5.2. INSTALL SYSTEM IN STRICT COMPLIANCE WITH THE FIRE STOPPING MANUFACTURER'S U.L. APPROVED DETAIL. WHERE EXISTING WALLS ARE BEING UPGRADED TO A ONE HOUR FIRE RATED WALL, PROVIDE U.L. LISTED THROUGH PENETRATION FIRE STOPPING SYSTEM FOR ALL NEW AND EXISTING PENETRATIONS. REFER TO THE ARCHITECTURAL LIFE SAFETY PLANS FOR LOCATIONS OF FIRE RATED WALLS. ALL DUCTWORK PENETRATIONS SHALL BE INSPECTED BY AN APPROVED THIRD PARTY INSPECTION AGENCY IN ACCORDANCE WITH ASTM E2174. THE
INSPECTION AGENCY SHALL BE PROCURED BY THE CONTRACTOR. DOCUMENTATION OF APPROVED
INSPECTION SHALL BE INCLUDED WITH PROJECT CLOSEOUT DOCUMENTATION.
Y. FIRE ALARM CONTRACTOR SHALL PROVIDE A DUCT SMOKE DETECTOR FOR EACH SMOKE OR FIRE/SMOKE DAMPER AS REQUIRED BY CODE. MECHANICAL CONTRACTOR SHALL COORDINATE THE LOCATION OF EACH
DUCT SMOKE DETECTOR AND SHALL INSTALL THEM IN THE DUCT.
Z. FOR ALL PIPING, CONDUIT, AND OTHER ITEMS PENETRATING A FIRE RATED WALL, PROVIDE U.L. LISTED THROUGH PENETRATION FIRE STOPPING SYSTEM THAT IS SPECIFIC TO THE WALL CONSTRUCTION ASSEMBLY AND COMPLIANT WITH ASTM E814. INSTALL SYSTEM IN STRICT COMPLIANCE WITH THE FIRE STOPPING MANUFACTURER'S U.L. APPROVED DETAIL. WHERE EXISTING WALLS ARE BEING UPGRADED TO FIRE RATED WALLS OR THE FIRE RATING IS BEING MODIFIED, PROVIDE U.L. LISTED THROUGH PENETRATION FIRE STOPPING SYSTEM FOR ALL NEW AND EXISTING PENETRATIONS. REFER TO THE ARCHITECTURAL LIFE
SAFETY PLANS FOR LOCATIONS OF FIRE RATED WALLS.
RECTANGULAR DUCTWORK
W = DIMENSION IN VIEW…
This is the start of the file's text. The full file is on GovTribe.