PDF 465 KB Posted

Attached to
Replace and install operating parts for sew age plant Carroll FOS
Solicitation number
W90VN921R0030
Issued by

View the file

Other files

File Type Posted
W90VN921R0030.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

HGFEDCBA

W.T

THIS PROJECT

LOCATION PLAN

(SEWAGE TRETMENT PLANT)

NOT TO SCALE

LOCATION : SEWAGE TRETMENT PLANT, CARROLL FOS (SEONG JU)

FEWR NO. : H20-10012-1J

HGFEDCBA

F

M M

PLUMBING PLAN (STP)

TANK

REDUCTION

OXYGEN

PLUMBING WORK (REF. DRAWING #2)

2. REPLACE WASTE WATER RETURN PIPES (30M L, STS 3T, 50A)

W/4EA CHECK VALVES (50MM DIA. STS. SWING CHECK VLAVE

10KG) AND STEEL ANGLE SUPPORTING BRACKESTS.

ANOXIC TANK

AGITATOR

AGITATOR

ANAEROBIC TANK

STAIR

UP

ENTERANCE

NOT TO SCALE

SB, FLANGE TYPE, KC 10K), 6EA BALL VALVES (STS 50MM DIA.,

LOCATION : SEWAGE TRETMENT PLANT, CARROLL FOS (SEONG JU)

FEWR NO. : H20-10012-1J

1. REPLACE 2 SETS RETURN PUMPS (ELECTRIC SUBMERSIBLE PUMP,

1HP, OUTPUT: 950W, ELECTRIC CAPACITY: 1450W, 1P-220V,

TOTAL SUCTION LIFT: 12M, MAX. PUMPING CAPACITY: 250L/MIN,

ENTRANCE AND EXIT PIPE SIZES: 50MM & 50MM PRESSURE HOSES

W/ CAM LOCK TYPE COUPLINGS.

3. REPLACE 2 SETS MAGNETIC DRIVES OF BACKWASHING PUMP

(OUTPUT: 300W, 3P-220/380V, 50/60HZ, ELECTRIC CAP.: 1.6/1.5(0.92/0.86A),

MAX. HEAD: 120/135 L/MIN, STD. CAP.: 50-6/70-9 L/MIN-M).

PLUMBING WORK (REF. DRAWING #2)

PLUMBING WORK (REF. DRAWING #2)

HGFEDCBA

F

M M

MECHANICAL PLAN (STP)

MECHANICAL WORK (REF. DRAWING #3)

5. REPLACE AUTO BAR SCREEN (PROCESSING CAP.:

50TON/H, SLOT: 100 O.C., DIM.: 400MM W X 920MM L

IP: 54, SF: 1.0, RPM: 1415/1705, INS:F, SUTY: CONT., AMPS:

2.3/1.2A, EFF.: 69/74%, WEIGHT: 7.1KG).

4. REPLACE 3 SETS SEPARATION MEMBRANE UNITS.

(REMARKS)

BY GOVERNMENT FURNISHED MATERIAL (GFM)

W/ FOLLOWING SPEC.

MODEL # SADF690, 126SM-04 MICRO METER,

SIZE: 700MM W X 1044MM L X 1250MM H,

MATERIAL: SEPARATOR PVD, STS 304 TYPE,

BURIED HEAVY CONSTRUCTION MEMBRANE.

MECHANICAL WORK (REF. DRAWING #3)

MECHANICAL WORK (REF. DRAWING #3)

7. REPLACE SIROCCO FAN (FAN & BLOWER,

SIZE: 1100MM X 40MM AQ., MOTOR: 3HP

4P X 220/380V, INCLUDE VIBRATION PROOF

RUBBER BASE).

MECHANICAL WORK (REF. DRAWING #3)

6. REPLACE 2 SETS ROOT BLOWERS (KFM ROTARY BLOWER,

SPEED: 1,300 RPM, CAP.: 8M3/MIN, MOTOR: 15KW, DIFFERENTIAL PRESSURE:

0.4KG/CM2, MODEL #: SL125, INCLUDED MOTOR, LOW PRESSURE

3 PHASE INDUCTION MOTOR, CLASSIFICATION: KMH 20HU, FRAME: 160L,

TYPE: TEFC, 15KW(20HP), 4P-380V-29A-60HZ, 1760MIN, S.F: 1.15, WEIGHT: 140KG,

BEARING (LOAD/HALF LOAD) 6309ZZ/6307ZZ.

STAIR

UP

ENTERANCE

NOT TO SCALE

X 1050MM H, ELECTRIC CAP.: 0.4KW, MOTOR: 0.4KW-4P

-220/380V-50/60HZ, SKG-0.4 TO 4, FRAME: 71M, TYPE: TEFC,

- THE SEPARATION MEMBRANE UNITS WILL BE PROVIDED

- THE 3 SETS SEPARATION MEMBRANE UNITS

ARE STOCKED IN BLDG. #565, CAMP CARROLL.

LOCATION : SEWAGE TRETMENT PLANT, CARROLL FOS (SEONG JU)

HGFEDCBA

F

M M

NOT TO SCALE

ELECTRICAL PLAN (STP)

FOR RETURN PUMPS.

EXISTING ELECTRIC WIRING SYSTEM

ELECTRIC PANEL BOARD

EXISTING M.C.C.P

ELECTRICAL WORK (REF. DRAWING #4)

8. REPLACE 2 EA BRANCH CIRCUIT BREAKERS (30A)

CIRCUIT INTERRUPTER (GFCI) AND LOAD CIRCUIT

ELECTRICAL WORK (REF. DRAWING #4)

9. REPLACE 2 SETS MAGNETIC MOTOR STARTERS (1HP, NEMA-1 TYPE)

W/ CIRCUIT BREAKERS, SELECTOR SWITCHES (HAND/OFF/AUTO SELECTOR

SWITCH AND TIMER), OPERATION LAMPS FOR ELECTRIC SUBMERSIBLE PUMP,

MANUFACTURED IN KOREA.

RETURN PUMP

STAIR

UP

ENTERANCE

BREAKER TYPE, MANUFACTURED IN KOREA.

W/NEW BCB (1P-20A-220V) INCLUDING GROUND FAULT

LOCATION : SEWAGE TRETMENT PLANT, CARROLL FOS (SEONG JU)

Carroll FOS-Model-001
Carroll FOS-Model-002
Carroll FOS-Model-003
Carroll FOS-Model-004