Text version
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
R-11SHEET OF
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
O & M
HOUSING DIV.
REVIEWED BY
UNITED STATES ARMY GARRISON DAEGU
ENGINEERING DIVISION, DESIGN & TECHNICAL REVIEW Br
DIRECTORATE OF PUBLIC WORK
HGFEDCBA
D - 20 - 15
CHON, HYON TAE
DESIGN REVIEW SIGNATURE
ORGANIZATION
USING AGENCY
36TH SIGNAL
MASTER PLN.
ENVIRONMENTAL
NAME SIGNATURE
O&M DIV.
FIRE DEPT.
SAFETY OFFICE
DPTMS(AT/FP)
188TH MP COM.
IND. HYGENIST
I1-00569-0J
UNIT #15746, APO AP 96218-5746
DRAWING NO.
CHIEF,
DESIGN & TECH. REVIEW Br.
E - 2
YI, TONG KI
AS SHOWN
1 1 OF 1R - 1
T I T L E S H E E T
TITLE SHEET
DATE: 06 JUL 20
INSTALL LED MARQUEES AT USAG DAEGU
INSTALL LED MARQUEES AT USAG DAEGU
E - 12
USAG DAEGU
PROJECT NO. I1-00569-0J, USAG DAEGU
ELECTRICAL
- CAMP CARROLL
LEGEND, NOTES, SCOPE OF WORK, ELECTRICAL SITE PLAN AND INSTALLATION DIAGRAM/ SPECIFICATION
ELECTRICAL SITE PLAN AND INSTALLATION DIAGRAM/ SPECIFICATION - CAMP WALKER
S-117
BLDG. #S-138
BLDG. #
S-135
BLDG. #
E/P
E/P
E/P
L/P
L/P
ELEC
D
L/P
S
ZONE
LOADING
(RCP, D=460, ASUUMED)
CANOPY
CANOPY
CANOPY
FHT
W/V
W/V
W/V
W
(P V C
D
A S
U U
M E
D
W (P
V C
D
A S
U U
M E
D
W
(PVC, D=150, ASUUMED)
W
(P V C
D
A S
U U
M E
D
(PVC, D=200)
S
(PE
, D
=110 )G
(PE, D=110)
G
(P E
D
G (P
E
D
G
HGFEDCBA
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
UNITED STATES ARMY GARRISON DAEGU
DIRECTORATE OF PUBLIC WORK
ENGINEERING DIVISION, DESIGN & TECHNICAL REVIEW Br
UNIT #15746, APO AP 96218-5746
DATE:
SIN, YS
SHEET OFAS SHOWN
KIM. CK
ELECTRICAL
CAMP CARROLL
SPECIFICATIONS FOR O&MA PROJECTS, AND SPECIFICATIONS.
ELECTRICAL CODE, NATIONAL ELECTRICAL SAFETY CODE, FIRE CODE, TECHNICAL STANDARD
ALL ELECTRICAL WORK SHALL CONFORM TO THE LATEST REQUIREMENTS OF THE NATIONAL
G E N E R A L N O T E S
1.
CONDUIT WHICH IS TO BE BONDED TO MAIN GROUNDING SYSTEM AT BOTH ENDS.
GROUNDING WIRE SHALL BE GREEN INSULATED COPPER WIRE IN RIGID GALVANIZED STEEL 2.
S C O P E O F W O R K
ELECTRICAL
A. CONSTRUCTION / ALTERNATE
1.
2.
INSTALL NEW POLE MOUNT MARQUEE INCLUDING ACCESSORIES AS SHOWN IN DRAWINGS.
FOR NEW MARQUEES AS SHOWN IN DRAWINGS.
INSTALL NEW ELECTRICAL POWER SYSTEM INCLUDING SAFETY SWITCHES, WIRINGS AND ACCESSORIES
SCALE : 1 / 200- E01
P-1
L E G E N D
REMOVE EXST NEW
///// +++ WIRING CONCEALED IN UNDERGROUND
SAFETY SWITCH
///// WIRING OVERHEAD IN FREE AIR
INSTALLATION OUTLINE DIAGRAM
G
G
US ORIGIN MATERIAL:
- E01
D-1
EXISTING CONCRETE POLE
SCALE : NONE- E01
D-1 INSTALLATION DIAGRAM AND SPECIFICATION
SEE
NEW MARQUEE, POLE MOUNT TYPE,
E-01
INTERNET SITE (http//www.cckbid.com).
DATED FEBRURY 2, 2004 (ELECTRONIC VERSION OF THIS DOCUMENT CAN BE FOUND AT
REGISTER OF IMA-KORO PAMPHLET 420-1 "INSPECTION OF CONSTRUCTION CONTRACTS
ALL GENERIC US ORIGIN MATERIALS SHALL BE AS OFF-SHORE IN THE GENERIC SUBMITAL
INSTALL LED MARQUEES AT USAG DAEGU
22MM RMC
WITH NEW 3W-#8 AWG "THWN" IN
FROM EXISTING OVERHEAD WIRES
CONNECT AND DROP POWER LINES
ELECTRICAL SITE PLAN - CAMP CARROLL
SPECIFICATION OF MARQUEE
1.
2.
3.
4.
5.
6.
7.
8.
CONTROLLER - 1EA MAIN CONTROLLER AND 12EA SUB CONTROLLER
SPECIFICATION OF POLE
1.
2.
MATERIAL - GALVANIZED STEEL
SIZE - AS INDICATED
3. WEATHER PROOF FOR OUTDOOR INSTALLATION
9. PRODUCT INFORMATION: MODEL - P4 FULL COLOR ELECTRONIC DISPLAY, MANUFACTURE - BANDY LED CO. OR EQUIVALENT
OVERALL - 64RPGB, *NOMINAL SIZE: 30 LINES X 44 COLUMNS, FULL COLOR SINGLE SIDE DISPLAY
CONTROL PROTOCOL - TCP/IP (BOTH WIRED LAN AND WIRELESS WIFI)
SIZE - DISPLAY: 2816MM W X 1920MM H, HOUSING: 3000MM W X 2000MM H X 500MM D
DISPLAY RESOLUTION - 704 W X 480 H
DIAGRAM / SPECIFICATION - CAMP CARROLL
ELECTRICAL SITE PLAN, AND INSTALLATION
LEGEND, NOTES, SCOPE OF WORK,
I1-00569-0J
6 JUL 20
ELECTRICAL - INPUT POWER: 110V/ 220V 60HZ, POWER CONSUMPTION: 6600 WATT MAX, 3960 WATT AVERAGE (SETTING VOLTAGE: 220V)
SMPS - 22EA, 110V/ 220V AC TO 5V DC, 300W (SETTING VOLTAGE: 220V)
& 1-#10 AWG (G) IN 1-WAY CONCRETE ENCASED 22MM CONDUIT
NEW UNDERGROUND POWER LINES, 2-#8 AWG "THWN"
ELECTRONIC MARQUEE WITH CASE AND POLE
QUANTITY: 165EA (LINE - 15EA, COLUMN - 11EA)
MODULE - RPGB CHIP, 64EA W X 32EA H DOTS / MODULE, SIZE: 256MM W X 128MM H, PIXEL SPACE: 4MM, FULL COLOR, *NOMINAL SIZE IS CALCULATED BASE ON 16EA W X 16EA H DOTS / MODULE.
D - 20 - 15
1 2
W/CLAMP AND GOUNDING WIRE 1-#12 AWG (G) IN 16MM RMC
NEW GROUND ROD, CLAD STEEL, 19MM DIA X 3,000 MM LG,
FUSIBLE WITH 40A FUSE
NEW SAFETY SWITCH, 2P-240V-60A, NEMA 3R ENCL,
HGFEDCBA
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
UNITED STATES ARMY GARRISON DAEGU
DIRECTORATE OF PUBLIC WORK
ENGINEERING DIVISION, DESIGN & TECHNICAL REVIEW Br
UNIT #15746, APO AP 96218-5746
DATE:
SIN, YS
SHEET OFAS SHOWN
KIM. CK
ELECTRICAL
SCALE : 1 / 500
S 15S-200
S-216T-213
S-452
T-720
T-721
T-722
GATE
S-68
S
PENNSYLVANIA AVENUE
CAMP WALKER
SPECIFICATION OF MARQUEE
1.
2. SIZE - DISPLAY: 2048MM W X 1024MM H, HOUSING: 2148MM W X 1124MM H X 350MM D
3.
4.
5.
6.
7.
8.
SCALE : NONE- E02
D-1
CONTROLLER - 1EA MAIN CONTROLLER AND 4EA SUB CONTROLLER
DISPLAY RESOLUTION - 512 W X 256 H
E/P E/P
G
EXISTING CONCRETE POLE
G
INSTALLATION OUTLINE DIAGRAM
SPECIFICATION OF POLE
INSTALLATION DIAGRAM AND SPECIFICATION
SEE
NEW MARQUEE, POLE MOUNT TYPE,
- E02
D-1
16MM RMC
WITH NEW 3W-#10 AWG "THHW" IN
FROM EXISTING OVERHEAD WIRES
CONNECT AND DROP POWER LINES
- E02
P-1
INSTALL LED MARQUEES AT USAG DAEGU
6 JUL 20
2-#10 AWG "THWN" & 1-#12 AWG (G) IN 22MM
NEW UNDERGROUND POWER LINES
ELECTRICAL SITE PLAN - CAMP WALKER
1.
2.
MATERIAL - GALVANIZED STEEL
SIZE - AS INDICATED
3. WEATHER PROOF FOR OUTDOOR INSTALLATION
9. PRODUCT INFORMATION: MODEL - P4 FULL COLOR ELECTRONIC DISPLAY, MANUFACTURE - BANDY LED CO. OR EQUIVALENT
OVERALL - 64RPGB, *NOMINAL SIZE: 16 LINES X 32 COLUMNS, FULL COLOR SINGLE SIDE DISPLAY
CONTROL PROTOCOL - TCP/IP (BOTH WIRED LAN AND WIRELESS WIFI)
I1-00569-0J
ELECTRICAL - INPUT POWER: 110/ 220V 60HZ, POWER CONSUMPTION: 3000 WATT MAX, 1800 WATT AVERAGE (SETTING VOLTAGE: 220V)
SMPS - 10EA, 110V/ 220V AC TO 5V DC, 300W (SETTING VOLTAGE: 220V)
QUANTITY: 64EA (LINE - 8EA, COLUMN - 8EA)
MODULE - RPGB CHIP, 64EA W X 32EA H DOTS / MODULE, SIZE: 256MM W X 128MM H, PIXEL SPACE: 4MM, FULL COLOR, *NOMINAL SIZE IS CALCULATED BASE ON 16EA W X 16EA H DOTS / MODULE.
D - 20 - 15
DIAGRAM / SPECIFICATION - CAMP WALKER
ELECTRICAL SITE PLAN, AND INSTALLATION
E-02
W/CLAMP AND GOUNDING WIRE 1-#12 AWG (G) IN 16MM RMC
NEW GROUND ROD, CLAD STEEL, 19MM DIA X 3,000 MM LG,
FUSIBLE WITH 20A FUSE
NEW SAFETY SWITCH, 2P-240V-30A, NEMA 3R ENCL,
W/CLAMP AND GOUNDING WIRE 1-#12 AWG (G) IN 16MM RMC
NEW GROUND ROD, CLAD STEEL, 19MM DIA X 3,000 MM LG,
| I1-00569-0J_T01 |