Drawings.pdf

PDF 29 MB Posted

Attached to
3910--Pneumatic Tubes Campus Wide Salisbury VAMC
Solicitation number
36C24623B0030
Issued by

About this file

This document provides details for a federal solicitation notice seeking bids for a pneumatic tubes campus wide project at the Salisbury VAMC. The Department of Veterans Affairs is soliciting bids from contractors to provide all labor, materials, equipment, and services necessary to design, produce, and expand an existing pneumatic tube system across five buildings on the VA medical center campus in Salisbury, North Carolina. The project scope includes installing pneumatic tube pathways and associated equipment, millwork, carpentry, painting, plumbing, HVAC, fire suppression, electrical, and communications systems. All work must be completed within 210 calendar days of receiving a notice to proceed and shall comply with provided specifications and drawings. The contractor will also provide user training, maintenance training, and a train the trainer program. The estimated construction value is between $2,000,000 and $5,000,000. Bids are due by March 23, 2023 and the solicitation is anticipated to be a total service-disabled veteran owned small business set-aside.

View the file

Other files

File Type Posted
36C24623B0030 0003.docx DOCX document
36C24623B0030 0002.docx DOCX document
36C24623B0030 0001.docx DOCX document
659-22-202_SOW_20221115.pdf PDF
36C24623B0030_1.docx DOCX document
Specifications.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

659-22-202

I

A

F

H

G

E

PEDS WALKWAY

PEDS WALKWAY

11/16/22

GROUND FLOOR - BUILDING 20

FIRST FLOOR - BUILDING 20

SECOND FLOOR - BUILDING 20

GROUND FLOOR - BUILDING 21

FIRST FLOOR - BUILDING 21

FIRST FLOOR - BUILDING 43

TO BLDG. #2

TO BLDG. #5

SET SCREW WITH

LOCKNUT

MINIMUM ROD

INSERTION IS 1/2"

NOTES:

1. SUBSTITUTE BEAM CLAMP WHERE REQUIRED TO ANCHOR TO BEAMS, IN

LIEU OF ANCHORS THROUGH CONCRETE.

2. SET SCREW MUST BE TIGHTENED ONTO THE SLOPED SIDE OF THE I-BEAM,

CHANNEL OR ANGLE IRON FLANGE

JOINT INSTALLATION NOTES

• ENSURE TUBING JOINTS ARE STRAIGHT AND PROVIDE A GOOD SEAL. GAPS BETWEEN PIECES OF TUBING INDICATE THE TUBING IS NOT POSITIONED PROPERLY, AND CAN CAUSE THE OTHER END TO BE OUT OF ALIGNMENT OR CAN CAUSE CARRIERS TO BECOME

LODGED.

• ENSURE ALL JOINTS ARE PARALLEL AND COMPLETELY STRAIGHT, AND NO EDGES REMAIN THAT MAY DAMAGE CARRIERS OR

INTERFERE IN ANY WAY WITH CARRIER TRAVEL.

• REMOVE ANY BURRS FROM THE ENDS OF THE TUBING WITH A FILE.

• IF FLARING IS REQUIRED FOR A JOINT, ENSURE THE FLARE IS PREPARED BEFORE THE INSTALLATION.

• DRY-FIT EACH JOINT BEFORE APPLYING ADHESIVES OR TAPE, AND MARK THE POINT WHERE THE JOINT IS PROPERLY SEATED. IF A BOLTED COUPLING OR DRIVE SLEEVE IS USED, MARK THE LOCATION OF EITHER END OF THE COUPLING OR SLEEVE TO ENSURE THE

JOINT IS PROPERLY CENTERED.

• APPLY ADHESIVES PER MANUFACTURER INSTRUCTIONS. OBSERVE ALL WARNINGS AND INSTRUCTIONS ON THE ADHESIVE LABEL.

• DO NOT PERMIT EXCESS ADHESIVE TO COLLECT ON THE INSIDE OF THE TUBING (AFTER THE JOINT IS SECURED)

• AFTER SECURING THE JOINT, USE A GLUE BRUSH TO WIPE AWAY EXCESS ADHESIVE ON THE OUTSIDE OF THE JOINT.

• GLUE AND TAPE ALL SYSTEM TUBE JOINTS FOR A PROPER AIR SEAL. DO NOT GLUE JOINTS WHERE TUBING MEETS EQUIPMENT. ALL EQUIPMENT MUST BE ATTACHED WITH A BOLTED COUPLING TO ENSURE IT IS REMOVABLE FOR SERVICE.

• ENSURE TUBING REMAINS FREE OF ALL OBSTRUCTIONS. CHECK TUBING OR DEBRIS BEFORE MAKING FINAL CONNECTIONS.

• USE METALLIZED TAPE TO HOLD JOINTS TOGETHER WHILE THE ADHESIVE CURES.

• WARNING: NEVER USE HEAT TO RELEASE ADHESIVES. HEATING ADHESIVES MAY EMIT TOXIC FUMES. ONLY USE ADHESIVE REMOVAL

METHODS APPROVED BY THE ADHESIVE MANUFACTURER.

STRAIGHT END

OF TUBE

BELL END

OF TUBE

SEE NOTES FOR JOINT

REQUIREMENTS

48"-50"

RADIUS

4" TUBING IS USED FOR AIR LINE

PIPING

6" 90° ELBOW6" 45° ELBOW

6" INLINE TEE

6" 90° BEND (58 1136 01)

(36.70 LBS)

4" STRAIGHT TUBE (27.40 LBS)

6" STRAIGHT TUBE (41.20 LBS)

6"

120" TYPICAL

4" 6"

13 1/2"

6"

6"

3/ 4"

6"

9"

5"

5"

6"

45.00°

/1

6"

/1 6"

M

AX

18 27/64"

69 15/16" MAX 6"

4" 90° BEND (58 1135 01)

24.48 LBS

(69 1/116" MAX 4")

(6

1/ 4"

M

AX

45° AIR LINE

ELBOW

7"

4" INLINE TEE

3/

8"

7 3/4"

ALL TUBING 16 GAUGE GALVANIZED STEEL

16 GAUGE GALVANIZED STEEL (POST FORMED WALL THICKNESS

OF .062 NOMINAL) AND MEETING ASTM A 653 COATING

DESIGNATION G90 OR G60. MATERIAL TO HAVE A ROCKWELL

HARDNESS OF B45 MINIMUM AFTER FORMING AND WELDING

6 3/4"

6"/4" INLINE TEE

12"

4"

6" 9"

12"8"

3/

8"

6"

4"

9"

7"

90° AIR LINE

ELBOW

/3 2"

3 2 1/3

2"

4" DRIVE SLEEVE

6" DRIVE SLEEVE

6"

5"

6"Ø PTUBE6"Ø PTUBE

4"Ø PTUBE4"Ø PTUBE

6X4 REDUCER

5"

4"Ø6"Ø

STRAIGHT HUB

4" & 6" BOLTED COUPLING

3X 5/8-16 HEX NUT

3X 5/8-16 BOLT 2.0 MIN LENGTH

GROUND STRIP TO BE PLACED

BETWEEN GASKET AND TUBE

WITH TAB FOLDED TO THE INSIDE.

6" OR 4"

3/

4"

6"

3/

4" F

O R

4"

CO

UP

LI

N

G

6"/4" INLINE PRV ASSEMBLY

6" OR 4"

FIELD BORE HOLES

MIN 6' ABOVE STATION NIPPLE

FIELD BORE PRV HOLES. PRV

FLAP AND CLAMPS

ORIENT FLAP UP

INSTALL BYPASS PIPE END

WITH LABEL UP

STANDARD 4" OR 6"

TUBING, FIELD CUT

BOLTED COUPLING CONNECTION TO

TRANSFER UNIT

FIELD BORE (2) 2 3/4" Ø

HOLES FOR 6" BYPASS PIPE

9" MIN. FROM HOLES TO

TRANSFER UNIT

STORAGE/BYPASS PIPE ASSEMBLY

65" MIN AS SHOWN

FIELD BORE (2) 1 7/8"Ø HOLES

FOR 4" BYPASS PIPE

9" MIN

BOLTED COUPLING CONNECTION

PRV 90

ACCEPTABLE

PRV LOCATION

WHEN PRV IS REQUIRED TO BE RELOCATED DUE TO

FIELD CONDITIONS, RELOCATE IN UPPER HALF OF BEND.

START OF RADIUS

ACCEPTABLE PRV LOCATION

PLAN VIEW

ELEVATION VIEW

VACUUM BYPASS VALVE

(IF APPLICABLE)

TO BLOWER

ZERO-LEVEL

TRANSFER UNIT

REDUCER (USED ON 6" SYSTEM)

VACUUM TEE

BOLTED COUPLING

NOTES:

A. STOPPING CHAMBER PIPING: 12' MIN, 15' PREFERRED

1. WHEN USING 4" SYSTEM, 15' REQUIRED BEFORE USING 4" AIRLINE FITTINGS

B. 6' BETWEEN VBV AND VACUUM TEE

C. 6' BETWEEN VACUUM TEE AND ZERO LEVEL TU

4" AIRLINE PIPING STOPPING CHAMBER "A"

4" AIRLINE PIPING

SYSTEM PIPING

6" AIRLINE 90

GLUED JOINT

"B"

"C"

ELEVATION VIEW

1/2" GAP AT JOINT

4" OR 6"Ø PNEUMATIC TUBE,

16 GAUGE GALVANIZED STEEL

36" MAX.

TRANSVERSE BRACING & LONGITUDINAL

BRACING (TYP) EA SIDE OF JOINT

4" OR 6"Ø SLIP JOINT

3/8"Ø ALL THREAD HANGER

ROD W/ STIFFENER

10'-0" MAX (TYP)

PNEUMATIC TUBE SUPPORT

±42"

BUILDING SEPARATION

BOLTED

COUPLING

PRV FLAP AND CLAMPS

ORIENT FLAP UP

STANDARD 4" OR 6"

TUBING, FIELD CUT

FIELD BORE (2) 2 3/4" Ø

HOLES FOR 6" PRV

- 7

/8

FIELD BORE (2) 1 7/8"Ø

HOLES FOR 4" PRV

- 3

/8

FIELD INSTALL FOR PRV 90,

INLINE PRV, OR

STORAGE/BYPASS PIPES

3/8" ALL THREAD HANGER ROD

AND HARDWARE

STEEL TEAR DROP HANGER4" OR 6" PNEUMATIC

TUBE

3/8" DROP-IN ANCHOR, TYPICAL

(SUBSTITUTE BEAM CLAMP WHERE

REQUIRED TO ANCHOR TO STEEL BEAMS)

3/8" THREADED ROD & HARDWARE,

TYPICAL

TUBE CLAMP,

TYPICAL

THREADED RODS TO

STRUCTURE ABOVE

TEARDROP HANGER

TUBE SUPPORTS FROM STRUCTURE ABOVE

13/16 OR 1-5/8" STRUT SUPPORT, AS

REQUIRED BY INSTALLATION

3/8"-16 NC DROP IN ANCHOR,

TYPICAL

3/8"-16 NC DROP IN ANCHOR,

TYPICAL

BENDS TO BE

SUPPORTED AT EACH END

SUPPORT ON RADIUS OF BEND IF

FIELD CONDITIONS DICTATE

NOTES:

• TOP TUBE TO BE SUPPORTED IN TYPICAL APPROVED FASHION

• DOUBLE HANGER SHOULD BE WITHIN 18" FROM TOP TUBE SUPPORT

• RODS BETWEEN TEARDROP HANGERS ARE TO BE PLUMB AND LEVEL

• ATTAIN APPROVAL PRIOR TO HANGING

• ONLY HANG FROM PNEUMATIC TUBING, NO OTHER TRADES

PHD BAND HANGER

A

"A"

8"

12"

4" TUBE

6" TUBE

PHD BAND HANGER

6" TUBE/

4" TUBE

10"

BOTH 4" OR

BOTH 6"

4" OR 6"

FLOOR PENETRATION PLAN VIEWFLOOR PENETRATION SECTION VIEW

FIRE STOP

PENETRATION

AS REQUIRED

CORE DRILLED OR

SLEEVED HOLE

4" OR 6" O.D. STEEL PNEUMATIC TUBE

FIRE STOP PENETRATION

AS REQUIRED

ROW CLAMP

4" PNEUMATIC TUBE - 5" OR 6" TYPICAL SLAB PENETRATION

6" PNEUMATIC TUBE - 7" OR 8" TYPICAL SLAB PENETRATION

FLOOR PENETRATION PLAN VIEWFLOOR PENETRATION SECTION VIEW

FIRE STOP

PENETRATION

AS REQUIRED

1-5/8 X 1-5/8" STRUT

4 HOLE 90 BRACKET

3/8" ANCHOR BOLTS

CORE DRILLED OR

SLEEVED HOLE

4" OR 6" O.D. STEEL

PNEUMATIC TUBE

1-5/8 X 1-5/8" STRUT

3/8" ANCHOR BOLTS

FIRE STOP PENETRATION

AS REQUIRED

CHANNEL CLAMP

4" PNEUMATIC TUBE - 5" OR 6" TYPICAL SLAB PENETRATION

6" PNEUMATIC TUBE - 7" OR 8" TYPICAL SLAB PENETRATION

4 HOLE 90 BRACKET

/1 6"

MECHANICAL SHAFT

PLAN VIEW

MECHANICAL SHAFT

SECTION VIEW

SCHEDULED

SHAFT OPENING

4" OR 6" O.D. STEEL

PNEUMATIC TUBE

1-5/8 X 1-5/8" STRUT

3/8" ANCHOR BOLTS

CHANNEL CLAMP 3/8" ANCHOR BOLTS

1-5/8 X 1-5/8" STRUT

UNISTRUT OR EQUAL ANGLE FITTING

SCHEDULED SHAFT OPENING

4" OR 6" O.D. STEEL PNEUMATIC TUBE

OPENING

SCHEDULED

NOTES:

1.AS SHOWN:

4" TUBE = 24" - ADDITIONAL 6" PER EACH ADDITIONAL TUBE

6" TUBE = 34" - ADDITIONAL 8" PER EACH ADDITIONAL TUBE

2.AS SHOWN:

4" TUBE = 6"

6" TUBE = 8"

3.MAY VARY DUE TO STRUCTURAL REQUIREMENTS. VERIFY.

"A" "B"

4" 6"

5"

4" TUBE

6" TUBE 8"

"C"

NOTE 1

NOTE 1

"D"

NOTE 2

NOTE 2

C

A B

B B

A

D

"C" & "D" REPRESENT OVERALL

SHAFT OPENING SIZE

1" WD X 1/8" THICK GALVANIZED STEEL 4" OR 6"

TUBE CLAMP

3/8" THREADED ROD

NOTE:

TUBING TO BE SUPPORTED AT A MINIMUM OF EVERY 10'.

1 17/32" MIN

3" MIN FLUTE

3/8"16 NUT W/FLAT WASHER

1" WD X 1/8" THICK GALVANIZED STEEL 4" OR 6" ROW

CLAMP

3/8" THREADED ROD

3/8"16 NUT W/FLAT WASHER

3/8" 16 X 1" LG BOLT WITH FLAT WASHER

S H

E E

T N

U M

B E

R

SCALE

Phone: (800) 396-9666 www.swisslog-healthcare.com

As instruments of service, all designs, ideas, and information shown on these drawings are and shall remain the property of Swisslog Healthcare. No part thereof shall be copied, disclosed to others, or used in connection with any work or project other than the specific project for which they have been prepared and developed without the written consent of Swisslog Healthcare. Visual contact with these drawings shall constitute conclusive evidence of acceptance of these restrictions.

Not To Scale

S H

E E

T N

A M

E

ABCD

12/2/2019 10:19:23 AM

C

C ad

G ro up \L ib ra ry

R ev it\ D et ai ls \S w is sl og

D et ai ls

0x v

.r vt

PT-300

Tubing & Support Details

Beam Clamp

Adhesive Joint Connection Detail

Transmission Components

Bolted Coupling

Inline PRV

Storage/Bypass Pipe

PRV 90

System Piping

Expansion Joint Detail

Field Bore PRV

Typical Tube & Bend Supports

2 Band Hanger Support

Tube Supports at Floor Row Clamps

Tube Supports at Floor

Tube Supports at Shafts

1" = 1'-0"

Tube Supports Row Clamps

ORIENT STUDS WITH FLAT SIDE

AGAINST STATION HOUSING

FINISHED WALL AND FRAMING BY

OTHERS

TUBES SUPPORTED

AT FLOOR BY SWISSLOG

STATION HOUSING (TYPICAL), REFER TO

STATION DETAILS FOR DIMENSIONS

CORES MAY BE POSITIONED INSIDE STATION

ENCLOSURE. SEE PLANS FOR ADDITIONAL INFORMATION.

4" PNEUMATIC TUBE - 5" OR 6" TYPICAL SLAB PENETRATION

6" PNEUMATIC TUBE - 7" OR 8" TYPICAL SLAB PENETRATION

A

B

B

FROM HOUSING

10" CLEAR MIN TYP

MIN - MAY VARY DEPENDING ON

STRUCTURAL REQUIREMENTS

6" TUBE:

A=10" MIN

B=10" MIN

4" TUBE:

A=8" MIN

B=8" MIN

ADJUSTABLE LEG

ASSEMBLY

CARRIER

STORAGE RACKS

PRESSURE RELIEF VALVE

(PRV) BEND

8" MINIMUM CLEARANCE REQUIRED

AROUND PRV FLAP

AREA ABOVE STATIONS WITHIN STATION ENCLOSURE

SHALL BE CLEAR TO DECK/STRUCTURE ABOVE.

COORDINATE WITH SWISSLOG TO BE KEPT CLEAR OF

OBSTRUCTIONS TO TUBING

WALLS AND FRAMING BY

GENERAL CONTRACTOR OR

OWNER

STATION ANCHORED TO SLAB

INLINE PRESSURE RELIEVE VALVE (PRV)

ASSEMBLY: FOR STATIONS FED

VERTICALLY FROM THE FLOOR ABOVE.

G.C. TO NOTCH TRACK TO FIT

STATION LEGS

CORES MAY BE POSITIONED INSIDE STATION

ENCLOSURE. SEE PLANS FOR ADDITIONAL INFORMATION.

BOLTED COUPLING

TRIM

FRAME

RECEIVE BIN

DISPATCHER

NIPPLE

SIDE

FRONT

CONTROL

PANEL

STATION FURR-IN BY

OTHERS. STUDS TO BE

ORIENTED WITH FLAT SIDE

AGAINST STATION HOUSING

STATION HOUSING (TYPICAL), REFER TO

EQUIPMENT DETAILS FOR DIMENSIONS

32 3/8"

D

8"

R

EF

ER

EN

C E

C

EI

LI

N

G

/4

/8

/2

/8

" R

.O

F ROUGH OPENING

E (MIN CLEAR)

1/2" MIN FROM TRIM PLATE TO

WALL CORNER, TYP

TOP

/8

/2

/8 " R

O

TOP

POWER CONDUIT ENTRY

COMMUNICATION

CABLE/CONDUIT

ENTRY

A

B

/8

C

1/

BOTTOM

3/

4"9"

POWER CONDUIT TO

ELECTRICAL PANEL

SIZE

4" 6"

A 26 1/8" 32 1/8"

B 4 7/8" 5 7/8"

C 28 3/4" 34 3/4"

D 11' 10 1/8" 11' 8 1/8"

/8

A = STATION HOUSING WIDTH

B = STATION HOUSING EDGE TO CENTER OF NIPPLE

C = TRIM RING WIDTH

D = FLOOR TO TOP OF PRV BEND *NOTE 1

E = CLEAR STATION ENCLOSURE WIDTH

F = ENCLOSURE ROUGH OPENING WIDTH

NOTE 1: VARIES PER FIELD CONDITIONS/CEILING HEIGHT

X'-X" MIN, X'-X" PREFERRED

E 28" 36"

F 26 1/4" 32 1/2"

DECK/STRUCTURE ABOVE

PRESSURE RELIEF VALVE (PRV):

PRV TO BE CLEAR OF OBSTRUCTIONS AND

ACCESSIBLE. WHEN STATION ENCLOSURE WALLS

ARE TO DECK AN ACCESS PANEL IS REQUIRED TO

ALLOW ACCESS TO THE PRV

6' M

IN

IF MOVED TO FLOOR ABOVE,

ACCESS PANEL REQUIRED, BY

OTHERS

STATION FURR-IN BY OTHERS. STUDS TO BE

ORIENTED WITH FLAT SIDE AGAINST

STATION HOUSING

STATION HOUSING

(TYPICAL), REFER TO

EQUIPMENT DETAILS FOR

DIMENSIONS

FLOOR

STATION ANCHORED TO SLAB

WALLS AND FRAMING BY OTHERS

PRESSURE RELIEF VALVE

(PRV) BEND

8" MINIMUM CLEARANCE

REQUIRED AROUND PRV

FLAP

AREA ABOVE STATIONS SHALL BE COORDINATED WITH SWISSLOG TO BE

KEPT CLEAR OF OBSTRUCTIONS TO TUBING

CORES/SLEEVES MAY BE POSITIONED INSIDE STATION

ENCLOSURE. SEE PLANS FOR ADDITIONAL INFORMATION.

ADJUSTABLE LEG

ASSEMBLY

INLINE PRESSURE RELIEVE VALVE

(PRV) ASSEMBLY: FOR STATIONS FED

VERTICALLY FROM THE FLOOR ABOVE.

IF REQUIRED TO MOVE TO FLOOR

ABOVE, ACCESS PANEL REQUIRED

G.C. TO NOTCH TRACK TO FIT

STATION LEGS

BOLTED

COUPLING

(TYPICAL)

BOLTED COUPLING

/8 " R

.O

36" MIN CLEAR

/8

30 1/2"

8"

R

EF

ER

EN

C E

C

EI

LI

N

G14

/6

4"

34 23/32"

RIGHT SIDE FRONT

32 1/2" R.O.

POWER

CONDUIT

ENTRY

COMMUNICATION

CABLE / CONDUIT

ENTRY

32 17/64"

15 31/32" 8 5/32"

9 11/32"

34 21/32"

TOP

M

IN

2" MIN FROM TRIM RING TO WALL CORNER, TYP

TOP

2" MIN

TRIM RING WIDTH

2" MIN

STATION HOUSING

STATION FURR-IN BY OTHERS. STUDS TO BE

ORIENTED WITH FLAT SIDE AGAINST

STATION HOUSING

STATION HOUSING

(TYPICAL), REFER TO

EQUIPMENT DETAILS FOR

DIMENSIONS

WALLS AND FRAMING BY OTHERS

12 3/8"

" TOP

UNIT

CARRIER

STORAGE

HOUSINGS

5" BETWEEN

HOUSING

STATION

HOUSINGS

5" BETWEEN

RESET/SILENCE BUTTON

ARRIVAL AMBER

SIGNAL LIGHT

4"

2 1/8" 4 1/2"

1/

2"

RPI - Remote Personal Indicator CAI - Carrier Arrival Indicator

S H

E E

T N

U M

B E

R

SCALE

Phone: (800) 396-9666 www.swisslog-healthcare.com

As instruments of service, all designs, ideas, and information shown on these drawings are and shall remain the property of Swisslog Healthcare. No part thereof shall be copied, disclosed to others, or used in connection with any work or project other than the specific project for which they have been prepared and developed without the written consent of Swisslog Healthcare. Visual contact with these drawings shall constitute conclusive evidence of acceptance of these restrictions.

Not To Scale

S H

E E

T N

A M

E

ABCD

12/2/2019 10:19:35 AM

C

C ad

G ro up \L ib ra ry

R ev it\ D et ai ls \S w is sl og

D et ai ls

0x v

.r vt

PT-301

Station Details

Station Furring Options

Recessed Station

Ultra Station

Trim Ring Inside Corner Detail

Stations/Storage Unit Detail

RPI/CAI

STATION SPECIFICATIONS

Power provided to the station by others.

POWER REQUIREMENTS

110 VAC, 1 Ph, 3A, dedicated unswitched circuit, terminated inside the station-supplied duplex outlet.

Ultra Station: (2) station-supplied duplex outlets. (2) Data drops Swisslog recommends that each Ultra Station Port be placed on separate circuits.

CONTROL REQUIREMENTS

Ethernet Standard Protocol. Data drop required landed in each station housing, by others.

ENVIRONMENTAL REQUIREMENTS

Operating Temperature: 0° to 100° F Storage Temperature: -20° to 180° F Relative Humidity: 0% to 90%

Ultra Stations may have two (2) 6" nipples, two (2) 4" nipples, or one each of 6" and 4" nipples.

Weights:

Recessed/Nexus Station: 6" 240 lbs / 4" 200 lbs Nexus Station: 6" 500 lbs Ultra Station: 375 lbs Countertop Station: 150 lbs transmitted to countertop Wall Mount: 150 lbs transmitted to floor through vertical supports

Station Enclosure Framing:

Wall framing and GWB around station enclosure to stop above ceiling to allow access to Pressure Relief Valve (PRV). If wall(s) are required to go to deck, stop GWB above ceiling. If GWB also needs to go to deck, access panel required to access PRV. Access panel provided and installed by others

RECEIVE BASKET, SUPPLIED WITH MULTIPLE

RECEIVE OPTION

WALLS BY OTHERS

WALL MOUNT SUPPORTS ANCHORED

TO SLAB. (2) TYPICAL

DISPATCHER

RECEIVER

BOLTED COUPLING

28"

/8

7/

8"

15"

8"

R

EF

ER

EN

C E

C

EI

LI

N

G

/1

6"

Station - Wall Mount

EXISTING STATION, SHOWN FOR REFRENCE ONLY

RECEIVE BASKET, SUPPLIED WITH

MULTIPLE RECEIVE OPTION

MILLWORK/COUNTERTOP,

SUPPLIED BY OTHERS

CONTROL PANEL

DISPATCHER

SINGLE RECEIVER

(MULTIPLE RECEIVE OPTIONAL)

MULTIPLE RECEIVE OPTION

REQUIRES HOLE IN THE

COUNTER PROVIDED BY OTHERS

BOLTED COUPLING

28"

/8

7/

8"

15"

28"

C O

U N

TE

R

R

EF

ER

EN

C E

5/ 8" 14 3/8"

Station - Countertop

INSTALL A STRUT BRACE AT BETWEEN 30-60° (45°

PREFERRED) ANGLE TO THE AXIS OF THE

TRANSFER UNIT, TYP ONE EACH AXIS

3/8"-13NC THREADED ROD, ANCHORS,

AND HARDWARE AT (4) PLACES TYPICAL

3/8" DROP-IN ANCHOR, TYPICAL (SUBSTITUTE BEAM CLAMP

WHERE REQUIRED TO ANCHOR TO STEEL BEAMS - SEE DETAILS)

4 PORT SHOWN, 2 PORT AND 6 PORT SIMILAR

TRANSVERSE BRACE

LONGITUDINAL BRACE

CONTROL REQUIREMENTS:

4-conductor PVC insulated cable, #22 AWG shielded twisted pair with ground wire.

5VDC maximum open circuit voltage, 200 mA maximum short circuit current

1X4 Transfer Unit shown. 1x2 and 1x6 Units are similar.

COMMUNICATION CABLE

ENTRANCE

BACK VIEW

POWER CONDUIT ENTRANCE

BOTTOM

TOP

POWER ENTRY

COMMUNICATION

CABLE ENTRY

ACCESS PANEL MAY FACE

DOWN OR TO THE SIDE

SERVICE

ACCESS

B

F K

SERVICE

ACCESS

ACCESS PANEL:

TU MAY BE ROTATED VERTICAL.

SERVICE ACCESS AVAILABLE TO ONE

SIDE ONLY

FRONT BACK

SIDE

24"

ACCESS

TOP

SIZE

6" 4"

A 47" 43"

B 42" 38"

C 23 1/2" 18 1/2"

D 10 1/2"

8"

E 40 1/4" 36 1/4"

F 7 5/8" 5 5/8"

G 21" 16"

H 8"

5 1/2"

J 4 1/2" 3 3/4"

K 15" 12"

H G

H

A

E

D

C

J H

FR

O

N T

BA

C

K

BOTTOM

1/

2" 8"

27/32" 41 5/32"

ACCESS PANEL:

MAY FACE DOWN

OR TO THE SIDE

POWER ENTRY

COMMUNICATION

CABLE ENTRY

24" ACCESS

EITHER SIDE OR BOTTOM

SIDE ACCESS PREFERRED

TOP

D

E

E

B

A

G F

G

0 1

2 3

SERVICE ACCESS

ACCESS PANEL:

TU ROTATED TO ALLOW FOR BOTTOM ACCESS. ROTATE

SENSOR. PREFERRED TO HAVE POWER ENTRY SIDE

DOWN.

/2

SERVICE ACCESS

24" MIN

24" MIN

POWER ENTRY

COMMUNICATION CABLE ENTRY

SIZE

6"

6" Mini 4"

A 52 7/8"

44" 50 1/2"

B 47 1/4" 34 3/4" 44 1/2"

C 21 1/2" 18 7/8"

18"

D 21 1/2" 18 7/8"

18"

E 8" 8"

6 5/8"

F 17"

16 1/4" 13 1/2"

C

4" 1X4

6" 1X4

POWER ENTRY

COMMUNICATION

CABLE ENTRY

6" 1X4 Mini

SERVICE ACCESS

REQUIRED FOR MOTOR

BOLT ACCESS ON MINI

6"

J H J

H

G 2 1/4" 1 1/8" 2 1/4"

JJ

H 45 7/8" 33 7/8" 43 1/8"

J 11/16" 7/16" 11/16"

G R

N

BL

K

W

HTRING TERMINAL

3/16" QUICK CONNECT

WITH INSULATORS

GROUNDING STUD

CONDUIT CLAMP

CONDUIT FITTING

TYPE SVT OR SV CORD

RUBBER GROMMET SEAL

1/2" CONDUIT TO

TRANSFER UNIT

VACUUM BYPASS J-BOX

12"

12"

4" VACUUM BY PASS VALVE

6" VACUUM BY PASS VALVE

ELECTRICAL CONNECTION,

POWERED FROM TU

16 31/64"

6"

/1 6"

4"

3/

8"

13 1/2"

4"

12"

/1 6"

VACUUM BYPASS VALVE, SEE

DETAILS

CABLE TIES

FLEX CONDUIT (BY OTHERS)

TO 115 VAC ELECTRICAL POWER SOURCE

(BY OTHERS)

TRANSFER UNIT

ENCLOSURE

MOTOR CONTROL ASSEMBLY

POWER OUTLET FOR VACUUM

BYPASS VALVE

PLUG

115VAC POWER TERMINATIONS INSIDE J-BOX

SEE DETAILS

VACUUM BYPASS VALVE WIRING

1/

8"

2 13/64"

BAND CLAMP

DRILL (2) 2"Ø HOLES

INSTALL ON ALL OPEN TU PORTS

INSTALL WITH HOLES ORIENTED VERTICALLY

LOCK NUT

GROUNDING STUD

B

LK

W H

T

GRN

LOCK WASHER

RING TERMINAL

HEX NUT

CABLE CLAMP

VACUUM BYPASS GROUNDING STUD12

/4

8"

TRAFFIC ENHANCEMENT UNIT (TEU)

1. POWER AND DATA SUPPLIED TO CONTROL ENCLOSURE BY OTHERS

2. CONTROL ENCLOSURE MOUNTED BY SWISSLOG

3. DATA FROM CONTROL ENCLOSURE TO TEU BY SWISSLOG

4. SEE PRODUCT DATA SUBMITTAL FOR LOCATION OF DATA AND

POWER INTO ENCLOSURE

12 1/4"

TEU CONTROL ENCLOSURE

FRONT VIEW LEFT VIEW RIGHT VIEW

TEU SENSOR

9"

4 1/2" 4 1/2"

BOLTED COUPLING

EACH SIDE OF TEU

S H

E E

T N

U M

B E

R

SCALE

Phone: (800) 396-9666 www.swisslog-healthcare.com

As instruments of service, all designs, ideas, and information shown on these drawings are and shall remain the property of Swisslog Healthcare. No part thereof shall be copied, disclosed to others, or used in connection with any work or project other than the specific project for which they have been prepared and developed without the written consent of Swisslog Healthcare. Visual contact with these drawings shall constitute conclusive evidence of acceptance of these restrictions.

Not To Scale

S H

E E

T N

A M

E

ABCD

12/2/2019 10:19:48 AM

C

C ad

G ro up \L ib ra ry

R ev it\ D et ai ls \S w is sl og

D et ai ls

0x v

.r vt

PT-302

Transfer Unit Details

Transfer Unit Support - (Sway Bracing)

Transfer Unit Wiring

Transfer Unit 1x2

Transfer Unit 1x4

Vacuum Bypass Valve

6" TU Port Cap

TEU - Traffic Enhancement Unit

TRANSFER UNIT SPECIFICATIONS

DRIVE MECHANISM

Electromechanical

POWER REQUIREMENTS

110 VAC, 1 Ph, 3A, dedicated unswitched circuit, terminated inside the equipment-supplied duplex outlet.

CONTROL REQUIREMENTS

Ethernet Standard Protocol. Data drop required landed in each TU, by others.

ENVIRONMENTAL REQUIREMENTS

Operating Temperature: 0° to 120° F Storage Temperature: -20° to 180° F Relative Humidity: 0% to 90% Maximum System Vacuum/Pressure: 4 psig Heat output: Approximately 130 BTU/hr

Weights:

1x2 Transfer Unit: 4" 125 lbs / 6" 165 lbs.

1x4 Transfer Unit: 4" 145 lbs / 6" 185 lbs.

1x4 Mini Transfer Unit: 95 lbs. (6" Only) 1x6 Transfer Unit: 4" 205 lbs. / 6" 250 lbs.

31"

/1 6"

28"

PLAN ELEVATION

30"

28"

PRESSURE SIDE VACUUM SIDE

A-A SECTION A-A

THROUGH BLOWER CONTROL CABINET

CONTROL

LOGIC AREA

DOOR SWINGS OPEN TO THE

LEFT

090-2675-01 BOARD

TB3

086-3493- ASSEMBLY

TB4

REV

12 VAC 5 VDC

GRN

SHIELD

BLK

WHT

TB1

RED

IN

TB2

OUT

A-A

INTERNAL VIBRATION

ISOLATION

FLEXIBLE HOSE

CONNECTION

*NOTE: SOME JURISDICTIONS REQUIRE 42" CLEAR.

CONSULT LOCAL AUTHORITIES.

SYSTEM AIR PIPING

BLOWER STAND

BY SWISSLOG

P

A

V

P R

E S

S U

R E

84"

2" 28" 2"

TO

S

TA

R

TE

R

" C

LE

AR

C

LE

AR

/6

4"

3/

NOTE: SCREEN BOX AND AIR LINES VERTICALLY SUPPORTED BY A FIELD FABRICATED STRUT SUPPORT ASSEMBLY AS DICTATED BY

INSTALLATION CONDITIONS.

12" 32" 40"

A T

M O

S P

H E

R E

V A

C U

U M

SCREENBOX

SCREENBOX

GLASS SIDE

SCREENBOX

ATMOSPHERE SCREENBOX

MUFFLERS ON PRESSURE

AND VACUUM

1/

4"

1/ 4"

42 3/8" 18" 7 1/4"

INSTALL AIRLINE PIPING

SUPPORT PER FIELD

CONDITIONS

LOCATION OF VFD

WHEN APPLICABLE

208-230

22.6 11.3

3 PHASE

VOLTAGE

(VAC)

FULL LOAD

CURRENT

(AMPS)

HP

6" BLOWER POWER

208-230

12.0 5.5 4.5

3 PHASE

VOLTAGE

(VAC)

FULL LOAD

CURRENT

(AMPS)

HP

4" BLOWER POWER

4.5 4.5 4.4

4" System:

Weight: 395 lbs.

With VFD: 405 lbs.

Heat Output: Approx. 9,000 BTU/hr Maximum Operating RPM 3,500 or 4,080 with VFD

6" System:

Weight: 285 lbs.

With VFD: 295 lbs.

Heat Output: Approx. 8,000 BTU/hr Maximum Operating RPM 3,520 or 4,080 with VFD

575 10.7 10.1

3 PHASE

VOLTAGE

(VAC)

FULL LOAD

CURRENT

(AMPS)

HP

6" BLOWER POWER 575 VAC 6" System:

Weight: 395 lbs.

With VFD: 405 lbs.

Heat Output: Approx. 8,000 BTU/hr Maximum Operating RPM 3,540 or 4,080 with VFD

/4

4" AIRLINE

4" AIRLINE

MUFFLER

SCREEN BOX

6"5 1/8"6"

FRONT SIDE

4" AIRLINE

4" AIRLINE

SCREEN BOX5"

6 7/8"

4" AIRLINE

7" 7"

5 1/4"

S H

E E

T N

U M

B E

R

SCALE

Phone: (800) 396-9666 www.swisslog-healthcare.com

As instruments of service, all designs, ideas, and information shown on these drawings are and shall remain the property of Swisslog Healthcare. No part thereof shall be copied, disclosed to others, or used in connection with any work or project other than the specific project for which they have been prepared and developed without the written consent of Swisslog Healthcare. Visual contact with these drawings shall constitute conclusive evidence of acceptance of these restrictions.

Not To Scale

S H

E E

T N

A M

E

ABCD

12/2/2019 10:19:57 AM

C

C ad

G ro up \L ib ra ry

R ev it\ D et ai ls \S w is sl og

D et ai ls

0x v

.r vt

PT-303

Blower Details

Blower Stand

Blower Control Cabinet

Blower

Blower Muffler

Screen Box

Atmosphere Screen Box

BLOWER SPECIFICATIONS

POWER REQUIREMENTS

Shifter Valve Motor: 110 VAC, 1 Phase, 5.4 A, dedicated unswitched circuit, terminated inside the equipment-supplied duplex outlet.

Blower Motor: 200-230, 460, or 575 VAC, 3 Phase Electrical Disconnect Required, By Others

Size all circuit protection in accordance with local, state, and national electrical codes

CONTROL REQUIREMENTS

Ethernet Standard Protocol. Data drop required landed in each blower control box, by others.

ENVIRONMENTAL REQUIREMENTS

Operating Temperature: 0° to 120° F (-17.8° - 49° C) Storage Temperature: -20° to 180° F (-29° - 65° C) Relative Humidity: 0% to 90% Maximum Operating RPM: 3,500 Maximum System Vacuum/Pressure at 5000 ft / 1.5 km:

3.5 psig Maximum Output @ zero pressure and 500 ft: 330

SCFM

The general contractor or the owner shall supply adequate supply and relief air to blower locations to ensure that all environmental and airflow requirements are met.

Sound Levels:

Without Sound Package: 82 dbA With Sound Package: 72 dbA

Sound Package and VFD available as factory-installed option only

MAX. VACUUM/PRESSURE: (at 5000 ft)

3.5 psig

MAX. OUTPUT: (at zero pressure and 500 ft)

165 SCFM for 4-inch 330 SCFM for 6-inch

659-24-202 Pneumatic Tubes

Electrical and Data Locations

07/05/2022

Equip # Elect. Room Elect. Panel IT Closet/Rack

ST 114 1204 2C1A1A TU:

ST 115 1204 2C1A1A ST:

ST 214 1204 2C1A1A TEU:

TU 014 1204 2C1A1A

TU 027 1204 2C1A1A

ST 123 2176 2C1A1B

TU 011 2176 2C1A1B

TU 012 2176 2C1A1B

TU 013 2159 2C1A2B

ST 133 3177 2C1A1C

ST 134 3153 2C1A2C

TU 017 3153 2C1A2C

TU 016 3177 2C1A1C

ST 143 4167 2C1A1D

ST 144 4015 2EM7A

ST 153 5126 2C1A1E

ST 154 5104 2C1A2E

Equip # Elect. Room Elect. Panel IT Closet/Rack

TU 031 (TU 018) B4, G032 4SP A171

ST 310 (ST 116) A146 1C1 A171

ST 320 (ST 125) A246 2C1 A271

ST 330 (ST 135) A346 3C1

TU 302 (TU 019) A346 3C1

Equip # Elect. Room Elect. Panel IT Closet/Rack

Relocated/New TU 10 A-222 2CALA A-201

Blower 003 A-222 2CALA A-201

TU 032 (TU011) A-222 2CALA A-201

Equip # Elect. Room Elect. Panel IT Closet/Rack

TU 034 (TU 191) BA101 GLS1A BC118

ST 321 (ST 122) 2A101 2CR1A 2C114

Equip # Elect. Room Elect. Panel IT Closet/Rack

ST 211 1B104 ISLA 1B103

ST 212 1C136 EE1LW 1C135

ST 213 1D135 EE1CL 1D136

Blower 002 2B104 2SH (277/480V)

TU 020 2B104 EE2LA

ST 221

TU 021

ST 222

TU 022

ST 223

TU 023

Equip # Elect. Room Elect. Panel IT Closet/Rack

ST 201 SP121-43 EM1L 109

RPI 202

Location Elect. Room Elect. Panel IT Closet/Rack

TEU 26 B5 1012 CORR. SPswitchroom-5 EEPC 1017

TEU 25 B5 to B6 Tunnel "E" G007 5AA 1017

TEU 24 B6 to B42 Bridge B42, SP2A100 EEPA BC148

TEU 033 (TEU 190) B21 Tunnel "I" BC119 EEPA BC118

Building 20

FEED WITH RS-422 CABLE FROM STATION #201

Building 2

Legend

1190A

Transfer Unit

Recessed Station

Traffic Enhancement Unit

RR-Revised 7/12/2022

2176 or 2026

JS-Revised 7/14/2022

JS-Revised 9/19/22

JS-Revised 10/06/22

A371

Building 8

Building 21

Building 42

2A129

2B104 EE2LA 2B130

Building 43

Additional Locations for TEUs

2C136 EE2WI 2C135

2D135 EE2CL 2D136

File details come from the government source that posted it. Updated .