Drawings-Code Plans 31 pages.pdf
PDF 16 MB Posted
- Solicitation number
- 36C25520R0074-3
About this file
This solicitation is for corrective fire and life safety deficiency projects at the Harry S. Truman Memorial Veterans' Hospital located in Columbia, Missouri. The solicitation number is 36C25520R0074-3 and was issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 15. Key project details include renovating and upgrading fire alarm, sprinkler, and egress systems; replacing fire barriers and smoke partitions; and correcting other deficiencies to bring the facility into compliance with NFPA 101: Life Safety Code and other standards. The solicitation includes 31 pages of construction drawings detailing the specific corrective work. The response due date is not provided, and the period of performance or award date is also unspecified. Pricing terms and any set-asides or incumbent contractors are not mentioned.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PENTHOUSE
1967NORMALLY
UNOCCUPIED BUILDING
SERVICE EQUIPMENT
SUPPORT AREA
BASEMENT
19672008
(CH. 39)
EXISTG. BUSINESS
(CH. 39)
EXISTG. BUSINESS
(CH. 42)
EXISTG. STORAGE
(CH. 39)
EXISTG. BUSINESS
1ST FLOOR
19672008
(CH. 21)
EXISTG. AMB, CARE
(CH. 19)
EXISTG. HEALTH
CARE
(CH. 19)
EXISTG. HEALTH CARE
(CH. 19)
EXISTG. HEALTH CARE
(CH 21)
EXISTG.
AMB. CARE
(CH 19)
EXISTG.
HEALTH
CARE
2ND FLOOR
(CH. 19)
EXISTG. HEALTH
CARE
(CH. 21)
EXISTG. AMB. CARE
(CH. 19) EXISTG.
HEALTH CARE
(CH 21)
EXISTG.
AMBULATORY
CARE
3RD FLOOR
(CH. 19)
EXISTG. HEALTH CARE
(CH. 21)
EXISTG. AMBULATORY
CARE
(CH. 19)
EXISTG.
HEALTHCARE
INTERSTITIAL
SPACE
4TH - 6TH FLOORS
4TH FLOOR - (CH. 19)
EXISTG. HEALTH CARE
5TH & 6TH FLOOR -
(CH. 39)
EXISTG. BUSINESS
CODE NOTES
NOTE: THESE DWGS DO NOT INCLUDE IBC BUILDING CODE
INFORMATION
1. DRAWING PURPOSE: NFPA CODE COMPLIANCE
2. FACILITY REVIEWED FOR COMPLIANCE WITH THE FOLLOWING
CODES:
2018 NFPA 101 LIFE SAFETY CODE
CHAPTER 19 - EXISTING HEALTHCARE OCCUPANCY
CHAPTER 21 - EXISTING AMBUL HEALTHCARE OCCUPANCY
CHAPTER 39 - EXISTING BUSINESS OCCUPANCIES
3. OWNER:
HARRY S TRUMAN MEMORIAL HOSPITAL
800 HOSPITAL DR
COLUMBIA, MO 65201
PH (573) 814-6000
4. DATE DEVELOPED: 4/5/16
6. ARCHITECTS SEAL: SEE STAMP IN TITLEBLOCK
7. FIRE SERVICE: CITY OF COLUMBIA FIRE DEPARTMENT
8. INSPECTION: JCHO; CITY OF COLUMBIA
9. OCCUPANCY GROUP TYPE:
5. ARCHITECT:
M+HFG
142 N MOSELY ST STE 300
WICHITA, KS 67212
PH (316) 262-2500
OCCUPANCY 1
OCCUPANCY 2
OCCUPANCY 3
OCCUPANCY 4
- HEALTHCARE
- AMBULATORY HEALTH CARE
- BUSINESS
- STORAGE
10. CONSTRUCTION TYPE:
OCCUPANCY 1, 2 & 3 - NFPA TYPE II (222)
OCCUPANCY 4 - NFPA TYPE II (000)
11a. BUILDING 1 - OCCUPANCY 1 - FLOOR AREA
ACTUAL:
OCCUPANCY I - HEALTH
CARE
FIRST FLOOR
SECOND FLOOR
THIRD FLOOR
FOURTH FLOOR
FIFTH FLOOR
SIXTH FLOOR
LOWER PENTHOUSE
UPPER PENTHOUSE
???,??? SF
76,142 SF
75,957 SF
22,902 SF
4,322 SF
22,902 SF
22,902 SF
4,322 SF
TOTAL: 311,200 SF
OCCUPANCY 3 - BUSINESS
BASEMENT
GRAND TOTAL: 673,743 SF
NOTE: GROSS FLOOR AREA USED TO CALCULATE
SF PER NFPA 3.3.22.2.1 (INSIDE FACE OF
EXTERIOR WALLS WITH NO DEDUCTS FOR
HALLWAYS, STAIRS OR THICKNESS OF INTERIOR
WALLS)
11c. HEIGHT & AREA LIMITATIONS:
ALLOWABLE AREA: UNLIMITED
HEALTH CARE OCCUPANCY
ALLOWABLE HEIGHT /
STORIES
4 OR MORE
ACTUAL HEIGHT / STORIES 7 OCCUPIABLE
STORIES
BUSINESS OCCUPANCY
ALLOWABLE HEIGHT /
STORIES
N/R
11d. MINIMUM CONSTRUCTION REQUIREMENTS (A.8.2.1.2):
CONSTRUCTION
HEALTH CARE OCCUPANCY
BEARING WALLS:
A. EXTERIOR
B. INTERIOR
C. INT/EXT (ROOF ONLY)
OCCUPANCY 2 - AMBULATORY HEALTH CARE
FIRST FLOOR 42,158 SF
TOTAL: 110,844 SF
TYPE II
(222)
2 HR
2 HR
1 HR
NON-BEARING WALLS:
A. EXTERIOR
B. INTERIOR
0 HR
NON-
COMBUSTIBLE
COLUMNS:
A. SUPPORT FLOORS
B. SUPPORT ROOF ONLY
2 HR
1 HR
BEAMS/GIRDERS/TRUSSES:
A. EXTERIOR:
B. INTERIOR:
2 HR
1 HR
FLOOR CONSTRUCTION: 2 HR
ROOF CONSTRUCTION: 1 HR
NOTE: ENTIRE FACILITY IS FULLY SPRINKLED
12. ACTIVE FIRE SAFETY FEATURES:
(A) AUTOMATIC SUPPRESSION SYSTEMS:
- SPRINKLER SYSTEM (FULLY SPRINKLED)
- EXHAUST HOOD IN KITCHEN - U.L. 300 COMPLIANT
- AUTOMATIC AIR-HANDLING SHUT-DOWN
(B) FIRE ALARM SYSTEM - SIMPLEX, ADDRESSABLE, AUTO DIAL-UP
(C) GENERATOR POWERED EMERGENCY LIGHTING, GENERATOR
POWERED EXIT LIGHTING.
(D) SMOKE DETECTORS AT ALL CORRIDORS, ALL SMOKE DOORS AND
MISC AREAS AS REQ'D (ALSO IN SOME DUCTS)
(E) PORTABLE EXTINGUISHERS
13. WATER SUPPLY: CITY OF COLUMBIA
VA EQUIVALENCY:
VA ALLOWED 100'-0" DEAD END CORRIDORS IN B OCCUPANCY
AREAS
OCCUPANCY 4 - STORAGE
BUILDING 1 - OCCUPANCY 2, 3 & 4 - FLOOR AREA
ACTUAL:
11b. BUILDING 2 FLOOR AREA ACTUAL:
OCCUPANCY 4 - STORAGE
BASEMENT 14,193 SF
BASEMENT 158,877 SF
SUB-BASEMENT 32,825 SF
2ND FLOOR 41,821 SF
TYPE II
(000)
0 HR
0 HR
0 HR
0 HR
NON-
COMBUSTIBLE
0 HR
0 HR
0 HR
0 HR
0 HR
0 HR
TOTAL: 204,681 SF
3RD FLOOR 26,865 SF
LEGEND
BUILDING & LIFE SAFETY REQUIREMENTS
DESCRIPTION
WALL
RATING
NEW
PARTITION KEY NFPA 101-2018
OPENINGS DAMPERS
RATING RFRNC. TYPE RFRNC.
BUILDING SEPARATION:
FIRE BARRIER
2 HR
90 MIN
OCCUPANCY/AREA SEPARATION
FIRE BARRIER
2 HR
90 MIN
HORIZONTAL EXIT (& REFUGE AREA)
FIRE BARRIER
2 HR
90 MIN
VERT. OPG. (EXIT ENCLSR/SHAFT)
FIRE BARRIER
(2 HR = 4 OR MORE STORIES)
(1 HR = LESS THAN 4 STORIES)
(1/2 HR = EXIST. ENCL. IN EXIST BLD'G)
1 HR
2 HR
60 MIN
90 MIN
HAZ./INCIDENTAL USE
FIRE BARRIER
1 HR 45 MIN
HAZ./INCIDENTAL USE
SMOKE PARTITIONS
(SPRINKLERED)
NR-
RESIST
SMK
NR
SELF OR AUTO
CLOSING
SUBDIVIDING SPACES
SMOKE BARRIER (I-2 OCCUPANCY)
20 MIN
1/2
HR
1 HR
SUITE SEPARATION
SMOKE PARTITION
NR
*NR
SELF OR AUTO
CLOSING
EXIT ACCESS CORRIDORS (I-2)
SMOKE PARTITIONS (SPRINKLERED)
NR-
RESIST
SMK
NR
EXIT ACCESS CORRIDORS (B & AHC)
NON-RATED PARTITIONS
NR
NR
1 HR
VERT. OPG. (SHAFT)
FIRE BARRIER 60 MIN
1 HR
2 HR
60 MIN
90 MINEXIT PASSAGEWAY (HORIZ.)
FIRE BARRIER
6.1.14.4.1 19.1.3.5.1
7.2.4.1.3 (1) 19.1.3.8 19.2.2.5 7.1.3.2.1
19.3.1.1-8 8.6
8.7.1 19.3.2.1
8.5
8.4.2 19.2.5.7.1.4
8.4.2 19.3.6.2
21.3.6 35.3.6
19.3.1
7.2.6
8.2.1.3
8.6
19.2.2.7
8.6
19.3.2.1.2
19.3.7.3
7.2.1.4.1 7.2.4.3.7 8.3.4 19.2.2.5, 1-4
8.3.3.2.2 TBL
19.2.2.2
7.1.3.2 (9)
8.3.3.2.2 TBL
19.3.2.1.3
8.3.3.2.2 TBL
8.5.4 19.3.7.8
8.3.3.2.2 TBL
19.2.2.2.
8.3.3.2.2 TBL
8.3.3.2.2 TBL
8.3.3.2.2. TBL
8.7.1.3 8.4.3 19.3.2.1.3
19.3.6.3.2 8.4.3
19.3.6.3 8.4.3
N/A
FIRE
90 MIN
FIRE
90 MIN
FIRE
90 MIN
NOT
ALLOWED
UNLESS
SERVING
STAIR
ONLY
N/A
VARIES
SMOKE
90 MIN
VARIES
VARIES
NONE
N/A
NOT
ALLOWED
8.3.4.8 9.2.1
8.3.4.8 9.2.1
8.3.4.8 9.2.1 7.2.4.3.5
N/A
8.5.5.3 19.3.7.3(2)
8.6.4.5
N/A
N/A
8.4.4
8.4.4 8.4.6.2
8.4.4.1 8.4.6.2 19.3.6.4.2
N/A
SYMBOLS
NO. OCC. EXITING
(SMALLER ROOMS)
MAXIMUM OCCUPANCY
AREA
OCC. LOAD
FACTOR
FIRE ALARM CONTROL PANEL
FIRE SYSTEM ANNUNCIATOR ALARM
ANNUNCIATOR PANEL
FACP
FSA
FAA
REQ'D. EXIT WIDTH
NO. OF OCC. EXITING
ACTUAL EXIT
WIDTH
NO. OF OCC./
NO. OF EXITS
1:50
10/1
2"
34"
FEC
FP
PROPERTY LINE
STARTING
LOCATION
TRAVEL DISTANCE
TRAVEL PATH
FE
FIRE EXTINGUISHER CABINET
FIRE PULL STATION
FIRE EXTINGUISHER
NOTES
[A] DAMPERS ARE NOT REQUIRED IN DUCT PENETRATIONS OF
SMOKE BARRIERS WHERE HVAC SYSTEMS ARE FULLY DUCTED
(19.3.7.3x2)
[B] AIR TRANSFER OPENINGS IN SMOKE PARTITIONS SHALL
HAVE DAMPERS (NFPA 8.2.4.4.3)
[C] SMOKE DAMPERS ARE NOT REQUIRED WHERE OPENINGS IN
DUCT ARE LIMITED TO A SINGLE SMOKE COMPARTMENT &
DUCTS ARE MADE OF STEEL
[D] TRANSFER GRILLES REGARDLESS OF WHETHER THEY ARE
PROTECTED
ARE NOT ALLOWED IN THESE DOORS OR WALLS (NFPA 19.3.6.4)
TD = XX
VICINITY MAP
NO SCALE
PROJECT LOCATION
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
117 PIERCE ST, SUITE 110
SIOUX CITY, IOWA 51101
712.252.4014
142 N. MOSLEY ST.
WICHITA, KANSAS 67202
316.262.2500
303 S. TOPEKA
WICHITA, KANSAS 67202
316.262.2691
G001
CODE PLANS - TITLE SHEET
CORRECT FIRE & LIFE
SAFETY DEFICIENCIES -
LIFE SAFETY PLANS
800 HOSPITAL DRIVE COLUMBIA, MO 65201
01-31-2020
589A4-19-104
CORRECT FIRE & LIFE SAFETY DEFICIENCIES -
LIFE SAFETY PLANS
HARRY S. TRUMAN MEMORIAL VETERANS' HOSPITAL
DEPT OF VETERANS AFFAIRS
800 HOSPITAL DRIVE COLUMBIA, MO 65201
100% CONSTRUCTION DOCUMENTS
100% CONSTRUCTION DOCUMENTS
SHEET INDEX
Sheet Number Sheet Name
G001 CODE PLANS - TITLE SHEET
LS000 CODE PLAN - SITE
LS000.5 CODE PLAN - SUB BASEMENT OVERALL
LS001 CODE PLAN - BASEMENT OVERALL
LS001.1 CODE PLAN - BASEMENT AREA A
LS001.2 CODE PLAN - BASEMENT AREA B
LS001.3 CODE PLAN - BASEMENT AREA C
LS001.4 CODE PLAN - BASEMENT AREA D
LS001.5 CODE PLAN - BASEMENT AREA E
LS100 CODE PLAN - FIRST FLOOR OVERALL
LS100.1 CODE PLAN - FIRST FLOOR AREA A
LS100.2 CODE PLAN - FIRST FLOOR AREA B
LS100.3 CODE PLAN - FIRST FLOOR AREA C
LS100.4 CODE PLAN - FIRST FLOOR AREA D
LS100.5 CODE PLAN - FIRST FLOOR AREA E
LS200 CODE PLAN - SECOND FLOOR OVERALL
LS200.1 CODE PLAN - SECOND FLOOR AREA A
LS200.2 CODE PLAN - SECOND FLOOR AREA B
LS200.3 CODE PLAN - SECOND FLOOR AREA C
LS200.4 CODE PLAN - SECOND FLOOR AREA D
LS200.5 CODE PLAN - SECOND FLOOR AREA E
LS300 CODE PLAN - THIRD FLOOR OVERALL
LS300.1 CODE PLAN - THIRD FLOOR AREA A
LS300.2 CODE PLAN - THIRD FLOOR AREA B
LS300.3 CODE PLAN - THIRD FLOOR AREA C
LS300.4 CODE PLAN - THIRD FLOOR AREA D
LS300.5 CODE PLAN - THIRD FLOOR AREA E
LS400 CODE PLAN - FOURTH FLOOR OVERALL
LS500 CODE PLAN - FIFTH FLOOR OVERALL
LS600 CODE PLAN - SIXTH FLOOR OVERALL
LS700 CODE PLAN - PENTHOUSE OVERALL
N
ARM
SIGNAL
A R M
S
IG
N A L
S
IG
N A L
A R M
ARM
SIGNAL
S
D
PARKING
HOSPITAL DRIVE
T
IG
E R
A V
E
ACCESSIBLE PARKING
E STADIUM
BLVD
M O
N K
D R
GENERAL STORAGE
BLDG. #16
BUTLER BUILDING
CHILLER PLANT BLDG.
#23
SHIPPING WAREHOUSE
PATIENT TOWER
PENTHOUSE
HOSPITAL
BUILDING
ACA BUILDING
BULK OXYGEN TANK
SPEED BUMP TYP.
TRANSFORMERS
FD CONNECTION
BLDG. 19
BLDG. 21
MAINTENANCE SHED #15
FD CONNECTION
FACILITIES
MANAGEMENT
BUILDING #22
PARKING GARAGE
FENCE
STAFF PARKING
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
117 PIERCE ST, SUITE 110
SIOUX CITY, IOWA 51101
712.252.4014
142 N. MOSLEY ST.
WICHITA, KANSAS 67202
316.262.2500
303 S. TOPEKA
WICHITA, KANSAS 67202
316.262.2691
LS000
CODE PLAN - SITE
CORRECT FIRE & LIFE
SAFETY DEFICIENCIES -
LIFE SAFETY PLANS
800 HOSPITAL DRIVE COLUMBIA, MO 65201
01-31-2020
589A4-19-104
100% CONSTRUCTION DOCUMENTS
1" = 20'-0"
8 - SITE - (PARENT)
N
FEC
F E
C
MECH. ROOM
AIR WAY
STORAGE
MECH. ROOM
CORRIDOR
STORAGE
BOILER
ROOM
STORAGE
PIPES MECH.
SHOP
STORAGE
STORAGE
STORAGE
ELEC. ROOM
MECH. ROOM
ACCESS
TUNNEL
OPEN TO
ABOVE
HATCHED AREAS ARE
UNPAVED CRAWLSPACE
HATCHED AREAS ARE
UNPAVED CRAWLSPACE
HATCHED AREAS ARE
UNPAVED CRAWLSPACE
LEGEND
BUILDING & LIFE SAFETY REQUIREMENTS
DESCRIPTION
WALL
RATING
NEW
PARTITION KEY
NFPA
101-2018
OPENINGS DAMPERS
RATING RFRNC. TYPE RFRNC.
BUILDING SEPARATION:
FIRE BARRIER2
HR
MIN
OCCUPANCY/AREA SEPARATION
FIRE BARRIER
HR
MIN
HORIZONTAL EXIT (& REFUGE AREA)
FIRE BARRIER2
HR
MIN
VERT. OPG. (EXIT ENCLSR/SHAFT)
FIRE BARRIER
(2 HR = 4 OR MORE STORIES)
(1 HR = LESS THAN 4 STORIES)
(1/2 HR = EXIST. ENCL. IN EXIST BLD'G)
1 HR
2 HR
MIN
MIN
HAZ./INCIDENTAL
USE
FIRE BARRIER
1 HR 45
MIN
HAZ./INCIDENTAL USE
SMOKE PARTITIONS
(SPRINKLERED)
NR-
RESIST
SMK
NR
SELF OR AUTO
CLOSING
SUBDIVIDING
SPACES
SMOKE BARRIER
(I-2 OCCUPANCY)
MIN
1/2 HR
1 HR
SUITE SEPARATION
SMOKE PARTITION
NR
*NR
SELF OR AUTO
CLOSING
EXIT ACCESS CORRIDORS (I-2)
SMOKE PARTITIONS (SPRINKLERED)
NR-
RESIST
SMK
NR
EXIT ACCESS CORRIDORS (B & AHC)
NON-RATED PARTITIONS
NR
NR
1 HR
VERT. OPG. (SHAFT)
FIRE BARRIER
MIN
1 HR
2 HR
MIN
MINEXIT PASSAGEWAY (HORIZ.)
FIRE BARRIER
6.1.14.4.1 19.1.3.5.1
7.2.4.1.3 (1) 19.1.3.8 19.2.2.5 7.1.3.2.1
19.3.1.1-8 8.6
8.7.1 19.3.2.1
8.5
8.4.2 19.2.5.7.1.4
8.4.2 19.3.6.2
21.3.6 35.3.6
19.3.1
7.2.6
8.2.1.3
8.6
19.2.2.7
8.6
19.3.2.1.2
19.3.7.3
7.2.1.4.1 7.2.4.3.7 8.3.4 19.2.2.5, 1-4
8.3.3.2.2 TBL
19.2.2.2
7.1.3.2 (9)
8.3.3.2.2 TBL
19.3.2.1.3
8.3.3.2.2 TBL
8.5.4 19.3.7.8
8.3.3.2.2 TBL
19.2.2.2.
8.3.3.2.2 TBL
8.3.3.2.2 TBL
8.3.3.2.2. TBL
8.7.1.3 8.4.3 19.3.2.1.3
19.3.6.3.2 8.4.3
19.3.6.3 8.4.3
N/A
FIRE 90
MIN
FIRE
90 MIN
FIRE
90 MIN
NOT
ALLOWED
UNLESS
SERVING
STAIR ONLY
N/A
VARIES
SMOKE
90 MIN
VARIES
VARIES
NONE
N/A
NOT
ALLO
WED
8.3.4.8 9.2.1
8.3.4.8 9.2.1
8.3.4.8 9.2.1 7.2.4.3.5
N/A
8.5.5.3 19.3.7.3(2)
8.6.4.5
N/A
N/A
8.4.4
8.4.4 8.4.6.2
8.4.4.1 8.4.6.2 19.3.6.4.2
N/A
SYMBOLS
NO. OCC. EXITING
(SMALLER ROOMS)
MAXIMUM OCCUPANCY
AREA
OCC.
LOAD
FACTOR
FIRE ALARM CONTROL PANEL
FIRE SYSTEM ANNUNCIATOR ALARM
ANNUNCIATOR PANEL
FACP
FSA
FAA
REQ'D. EXIT WIDTH
NO. OF OCC. EXITING
ACTUAL
EXIT
WIDTH
NO. OF OCC./
NO. OF EXITS
1:50
10/1
2"
34"
FEC
FP
PROPERTY LINE
TD = XX
STARTING
LOCATION
TRAVEL DISTANCE
TRAVEL
PATH
FE
FIRE EXTINGUISHER CABINET
FIRE PULL STATION
FIRE EXTINGUISHER
NOTES
[A] DAMPERS ARE NOT REQUIRED IN DUCT PENETRATIONS
OF SMOKE BARRIERS WHERE HVAC SYSTEMS ARE FULLY
DUCTED (19.3.7.3x2)
[B] AIR TRANSFER OPENINGS IN SMOKE PARTITIONS SHALL
HAVE DAMPERS (NFPA 8.2.4.4.3)
[C] SMOKE DAMPERS ARE NOT REQUIRED WHERE
OPENINGS IN DUCT ARE LIMITED TO A SINGLE SMOKE
COMPARTMENT & DUCTS ARE MADE OF STEEL
[D] TRANSFER GRILLES, REGARDLESS OF WHETHER THEY
ARE PROTECTED, ARE NOT ALLOWED IN THESE DOORS OR
WALLS (NFPA 19.3.6.4)
10/1
2"
34"
SUB BASEMENT KEY PLAN
A
BC
D
E
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
117 PIERCE ST, SUITE 110
SIOUX CITY, IOWA 51101
712.252.4014
142 N. MOSLEY ST.
WICHITA, KANSAS 67202
316.262.2500
303 S. TOPEKA
WICHITA, KANSAS 67202
316.262.2691
LS000.5
CODE PLAN - SUB BASEMENT
OVERALL
CORRECT FIRE & LIFE
SAFETY DEFICIENCIES -
LIFE SAFETY PLANS
800 HOSPITAL DRIVE COLUMBIA, MO 65201
01-31-2020
589A4-19-104
100% CONSTRUCTION DOCUMENTS
Not to Scale
-1 - SUB BASEMENT - (PARENT)
N
BLDG. 1 - OCCUPANCY 1
SUB BASEMENT = 32,825 S.F.
OCCUPANCY TYPE - STORAGE
TYPE II (222) CONSTRUCTION
TOTAL OCCUPANTS ________
FLOORS BELOW THE STREET
FLOOR USED FOR OTHER THAN
BUSINESS OCCUPANCY SHALL
HAVE NO UNPROTECTED
OPENING TO BUSINESS
OCCUPANCY FLOORS.
COMPLIANCE NOTE
PER NFPA
39.3.1.2
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
F E
C F
E C
FEC
FEC
F E
C
F E
C
F E
C
FEC
FEC
FEC FEC
FEC
FEC
FEC
FEC
FEC
FEC
FEC
F E
C
FEC
F E
C
FEC
FEC
FEC
F E
C
FEC
FEC
F E
C
F E
C
F E
C
FEC
F E
C
FEC
F E
C
FEC
FEC
FEFEFE
FE
F E
FE
F E
FE
FE
F E
FE
F E
C
FEC
F E
C
JT
JT
JT
JT
JT
F E
C
FEC
IN VITRO
CELL TEST
LAB.
F016
MRI
CONTROL
F017
RADIOPHARMACEUTICAL
R&D
F018
CORR.
CBF3
HOT CELL
F020
CYLINDER
STG.
F015
RADIONUCLIDE
GENERATOR
LAB
F022
EQUIP. RM.
F023
GEN.
RADIOCHEMISTRY/
PEPTIDE
SYNTHESIS/
PEPTIDE
RADIOLABELING
F004
VEST.
F023A
GLASS WASH
F024
WORK ROOM
F026
CORR.
CBF2
VEST.
F025A
OFFICE
F025
TISSUE
CULTURE
(COLD)
F028A
IMMUNOLOGY
LAB.
F027
CYLINDER
STG.
F027A
TISSUE PREP.
(HOT)
F029
TISSUE
CULTURE
(HOT)
F029A
CAMERA
DARK RM.
F031
MICRO DARK
RM.
F032
OFFICE
F033
OFFICE
F034
ELECTRICAL
CLOSET
F001B
VEST.
F002A
RADIOPHARMACEUTICAL
R&D
F010
JAN.
F036
CHIEF
PHARM. SVC.
E002M
ELEC. ROOM
E009
TELE./ DATA.
E006
Room
E003B
ELEV. LOBBY
CBE5
STG.
E005
CORR.
CBE4
ELEV.
#11
ELEV. MACH.
RM.
E007
CONF. RM.
E002E
PROG.
SUPPORT,
R&D
E002C
WK. RM.
E002B
R.C.O., R&D
E002I
RSCH. SVC.
CORR
E002
STAGING RM.
E001D
ANTE RM.
E001C
ANIMAL
WARD
A027A
ANIMAL
WARD
A027
ANIMAL
WARD
A030
CORR.
CBA7
ANIMAL
WARD
A029
RSCH. WK.
RM.
A010
CLOSET
A010A
RADIOPHARMACY
RSCH.
A009
RADIOPHARMACY
RSCH.
A007
GLASS WASH
B051
PHARMACOLOGY
RSCH.
B048
PHARMACOLOGY
RSCH.
B042
OFFICE
B049
RSCH.
COMMON RM.
B045
OFFICE
B017
RSCH.
INVESTIGATOR
B022
RSCH.
INVESTIGATOR
B015
CORR.
CBA14
RADIOPHARMACY
RSCH.
A004
CORR.
CBA1
CHIEF
B006A
ASSOC.
CHIEF
B006B
RSCH.
INVESTIGATOR
B012
OFFICE
B010
ELEC.
CLOSET
B009A
ELEC.
CLOSET
B009B
LACTATION
B009
CLASSROOM
B007ON-CALL
ROOMS/LOUNGE
B011
OFFICE
B010A
OFFICE
B016
RADIOPHARMACY
RSCH.
A003
CORR.
CBA2
RADIOPHARMACY
RSCH.
A006
ONCOLOGY
RESCH.
A051 RADIOPHARMACEUTICAL
SCIENCES
RSCH.
A049
RADIOPHARMACEUTICAL
SCIENCES
RSCH.
A016A
CORR.
CBA10
RSCH. STG.
A054
RADIATION
LAB.
A052
RADIOPHARMACEUTICAL
SCIENCES
RSCH.
A050
RADIOPHARMACEUTICAL
SCIENCES
RSCH.
A047
DMARC
A060
CART WASH
(DIRTY)
A046
ELEC.
CLOSET
A047A
CORR.
CBA6
SHR./ LNGE.
A011
ANIMAL
X-RAY RM.
A015
DARK RM.
A015A
RADIOPHARMACEUTICAL
SCIENCES
RSCH.
A017
ANIMAL
WARD
A045
VMU OFFICE
A043
ANIMAL
WARD
A033
ANIMAL
WARD
A035
ANIMAL
WARD
A032
ANIMAL
WARD
A034
CORR.
CORR.
CBA9
CLOSET
A025BFIRE CL.
CBA2A
STG. RSCH.
SVC.
A033
FUTURE
ANIMAL
WARD
A037
EQUIP. STG.
A036ANIMAL
WARD
A039
ANIMAL
WARD
A040
LOUNGE
A063
CORR.
CBA11
CORR.
CBA17
SAFETY/EMERGENCY
D005A
OFFICE
D005
PAINT SHOP
D006
OFFICE
D004D
LAUNDRY &
MENDING
D004C
TELEPHONE
OPERATORS
D004L
TLT.
D004B
LAUNDRY
STORAGE
D004F
OFFICE
D004G
EQUIP. STG.
D003B
OFFICE
D004H
LINEN
D004
TECH. MED
REPAIR
D008
FURNITURE
STG.
D009
ELEC. SHOP
D007
CARPENTER
SHOP
D011
OFFICE
D010
TOOL STG.
D011A
KEY SHOP
D012
PIPE &
MECHANICS
SHOP
D016
FIRE SPKLR.
PUMP RM.
D017
OFFICE
D004K
OFFICE
D004J
OFFICE
D004I
EQUIP. STG.
D003C
STORAGE
D003D
CORR.
CBD7
STG.
D003A
STG.
D004O
LOST AND
FOUND
D004N
M. TLT.
D004A
TELEPHONE
OPERATOR
SUPER.
D004E
ENTR. VEST.
D004M
STAIR #5
D015
VEST.
D014
UNISEX TLT.
D013
ELEC.
CLOSET
CBD2B
CORR.
CBD2
BOILER
D018
A/C SHOP
D019C
CORR.
CBD1
REPRODUCTIVE
D002TRASH
D001
TRASH
D001B
JAN.
D001A
JAN.
D029
GROSS SPEC.
D028
LKR./ TLT.
RM.
D027
CORR.
CBD5
ELEV. MACH.
RM.
D025
E.C.C. OFFICE
D019A
STORAGE
D019B
CONTROL
CTR.
D019D
CORR.
D019
SWITCH
GEAR RM.
D020
AUTOPSY
D031
Room
CBD4
COLD RM.
D030
OFFICE
D024
TLT.
D019C
ST. LNGE.
C003A
OFFICE
C003B
TECH.
SUPERVISOR
OFFICE
C003C
TRANSFORMER
RM.
D023
ELEC.
CLOSET
D022
GENERATOR
D022A
ELEC. EQUIP.
D022D
PARALLELING
SWITCHGEAR
D022C
GENERATOR
D022B
SWING SHIFT
SUPERVISOR
C003D
PROGRAM
MANAGER
C003F
LOGISTICS.
VISN 15
SUPPLY
TECHS
C003
CANTEEN
OFFICE
C004C
LOGISTICS
STORAGE
C003E
STAIR #7
C006
OXYGEN STG.
C005A
PHARM. STG.
C004
STORAGE
C004A CANTEEN
STG.
C004B
PHARM. STG.
C004D
LOADING
DOCK
CBC1A
CORR.
CBC1
HAC
C009H
MOW OFFICE
C009I
MOW OFFICE
C009K
FOOD STG.
C009GCORR.
C009J
BIOMEDICAL
ENG.
C002
FOOD PREP
C009
REF.
C009D
JAN.
B002E
OFFICE
B002F
MECH.
C012
FOOD PREP./
COOK
B001B
CART CLEAN
B001C
SHEET
METAL SHOP
C013
LOGISTICS
OFFICE
W05
ELEC. RM.
G008
OFFICE
G019
CHIEF OF
SERVICE
C001A
TLT
B011H
DIETETICS
STG.
B002G
TRNG/BRK.
RM.
B002D
DIETETICS
OFFICE
B002A
RSCH. CORE
AREA
B019
CLOSET
B026A
TRANS. RM.
B027A
PULMONARY
RSCH.
B027
OFFICE
B033
STAIR #3
BO36A
ELEC.
CLOSET
B030
CORR.
CBB3
LAB.
B026
LAB.
B023
MECH. ROOM
E003A
MECH. ROOM
E003
FRZ.
F030A REF.
F030
ELEC.
CLOSET
F035
F.A.
CONTROL
PANEL
F035A
VEST.
F034A
TISSUE PREP.
(COLD)
F028
MRI ROOM
F019
CORR.
F015A
RADIO
PHARM./
PHARMAKINETIC
LAB.
F014
HOT LAB. 1
F021
COLD LAB.
F005
CONF. RM.
F001A
RECP.
F001
CORR.
CBF5
WORK ROOM
F002
OFFICE
F003
WORK ROOM
F006
OFFICE
F007
OFFICE
F008
OFFICE
F009
VEST.
F009A
SHARED
OFFICE
F011
VA-BIC PET/
SPECT/
CT/MOLECULAR
IMAGING
SUITE
F012
CORR.
CBF4
STG.
F013
STAIR #11
#11
JAN.
E012
ELEV. MACH.
RM.
E004
M. TLT.
E008
W. TLT.
E010 PHARM.
E001
STORAGE
E001G
STER./ IV
PREP.
E001B
NARCOTIC
VAULT
E001A
PHARM. SVC.
E002N
ANTI-COAGULATION
OFFICE
E002Q
ADMIN.
OFFICER
PHARM.
E002O
SUPV.
INPATIENT
PHARM.
E001F
OUTPATIENT
PHARM.
SUPV.
E001E
HALL
E001H
BREAK RM.
E002F
A.O., R&D
E002D
CORR.
CBE2
CORR.
CBE1
OFFICE
E002A
OFFICE
E002H
CLINICAL
RSCH.
E002J
M.F.M.R.
EXECUTIVE
DIR.
E002K
OFFICE
E002L
CORR.
CBE3
OPHTHALMOLOGY
RSCH.
B032
COLD RM.
B037A
COLD RM.
B037
STAIR
ACCESS
B036
SIGNAL
PANELS
B033A
JAN.
B034
CORR.
CBB3
PHARMACOLOGY
RSCH.
B039
OFFICE
B039A
HEALTH
PHYSICS LAB.
B050
RSCH.
OFFICE
B046
RSCH.
INVESTIGATOR
B047
OFFICE
B046A
RSCH.
INVESTIGATOR
B021
OFFICE
B006
OFFICE
B006C
CORR.
B020
OFFICE
B014
OFFICE
B018
OPHTHALMOLOGY
B031
OFFICE
B025B
RHEUMATOLOGY
RSCH.
B024
HAS
B013
CORR.
CBB1
ON-CALL RM.
#1
B011A
TLT
B011B
ON-CALL RM.
#2
B011C
ON-CALL RM.
#3
B011D
TLT
B011E
ON-CALL RM.
#4
B011F
ON-CALL RM.
#5
B001G
ELEC. ROOM
B011J
ON-CALL
ROOMS/LOUNGE
B011
CLEANING
AREA
B001A
VTS/TRVL
SUPERVISOR
B013A
ELEV. MACH.
RM.
G004A
EQUIP.
G004
ELEV.
#12
ELEV.
#13
ELEV.
#10
ELEV.
#9
ELEV.
#14
ELEV.
CONTROL
G015
CORR.
CBG6
CART WASH
G035
DIRTY
PROCESSING
G032
EQUIP.
G052B
ELEV.
CONTROL
G016
OFFICE &
SUPPLY
G051
STERILIZER
ACCESS
ROOM
G052C
ETO
STERILIZER
ACCESS
G045
STERILIZER
ACCESS
G043A
HALL
G046
ELEC. ROOM
G013
CORR.
CBG2
OFFICE
G019A
STG
G019B
OFFICE
G019C
SHOWER
G040A
CONTROL
ROOM
G042
HALL
G037
HALL
G023
HALL
CBG4
CONFERENCE
R00M
G017
WOMEN'S
LOCKER
G024
MEN'S
LOCKER
G027
MEN'S
SHOWER
G027A WOMEN'S
SHWR
G024B
STORAGE
G029
STORAGE
G030
CORR.
CBG3
WAREHOUSE
BREAKOUT
AREA
W03
WAREHOUSE
W07
TOILET
W08
LOGISTICS
MANAGER
W09
CLOSET
W05B
SHIPPING
AND
RECEIVING
W02
PHARMACY
DRUG CACHE
W03A
CORR.
W03B
OFFICE
B001F
DISH CLEAN
B002
DISH CLEAN
B002K
CLOSET
B001E
DIETETICS
OFFICE
C009A
REF.
C009B
OFFICE
C009C
FRZ.
C009F
REF.
C009E
MECH. EQUIP.
C010
TLT.
C009M
TLT.
C009N
CORR.
C009J
OFFICE
C008
BIOMEDICAL
SUPV.
C002B
BIOMED
STORAGE
C002A
OI&T
C001
ELEV.
#8
ELEV.
#7
ELEV.
#4
ELEV.
#5
MECH.
CHASE
C001D
ELEV. LOBBY
A058
ELEV.
#3
ELEV.
#2
ELEV.
#1
CORR.
CBA13
BIOHAZARD
STG.
A057
CLOSET
A059A
MAIL RM.
A059
STAIR #1
A056
IT CLOSET
A056A
CLOSET
A054B
ELEC.
CLOSET
A053
RSCH.
INVESTIGATOR
A048
MEN'S
LOCKER
A063C
MEN'S TLT
A063B
FITNESS
A063A
WOMAN'S TLT
A063E
WOMAN'S
SHWR
A063F
WOMAN'S
LOCKER
A063G
MECH RM.
A038
STG.
A033B
STG. RSCH.
A033A
CORR.
CBA8
CAGE WASH
A041
F. TLT.
A001
M. TLT.
A002
PHY. RSCH.
A009A
ENDOCRINE/
HYPERTENSION
RSCH.
A019
ENDOCRINE/
HYPERTENSION
RSCH.
A020
RSCH.
OFFICE
A020A
OFFICE
A022
STAIR #4
A024A
JAN.
A025
CORR.
CBA5
STAIR CORR.
A024
PATHOGEN
FREE SUITE
A026
ANIMAL
WARD
A028
ANIMAL
WARD
A031
STG.
A042
STG.
A042A
OFFICE
A023A
NEURO.
SLEEP RSCH.
A023
SURG. SUITE
A021
ANIMAL
SURG.
A045A
NEURO.
SLEEP RSCH.
A018
COLD. RM.
A014
CORR.
CBA4
ENDOCRINE/
HYPERTENSION
RSCH.
A012
RSCH.INVESTIGATOR
A013
PHY. RSCH.
A008
ANIMAL
WARD
A008A
RSCH.
INVESTIGATOR
A005
OFFICE
A004A
RADIOPHARMACY
RSCH.
A055
OFFICE
A006A
OFFICE
A051A
RADIOPHARMACEUTICAL
SCIENCES
RSCH.
A016
BREAK ROOM
G018
WOMEN'S TLT
G024A
FILTER
EQUIPMENT
G052A
VESTIBULE
G031
ANTE ROOM
G059
CORR.
G055
STAIR #12
G060
ELEV. LOBBY
G026
CORR.
CBG5
MANUAL
WASH RM.
G032A
C/S WORK
AREA
G052
ENDOSCOPE
PROCESS.
G036
ELEV.
#15
STORAGE
G050
CLEAN
RECEIVING
BREAKOUT
G048
BULK STORE
RM
G047
CLEAN
PROCESSING
G043
MECH. RM.
G001
CORR.
G012
LOCKERS
G038
SHOWER
G038A
LOCKERS
G040
WAREHOUSE
W04A
WAREHOUSE
W04
WAREHOUSE
W05A
CANTEEN
STOCKROOM
W06
PROCESS
STORES
W01
STG.
C014
CORR.
CBC3
937/10
28.2"
46"
STAIR #1
850/16
15.9"
46"
937/10
28.2"
46"
937/10
28.2"
46"
850/16
15.9"
46"
850/16
15.9"
46"
247/2
24.6"
46"
STAIR #6
STAIR #7
STAIR #3
STAIR #11
STAIR #4
STAIR #5
RECEPTION
E002
MEN'S SHWR
A063D
MAKE-UP
A063H
KITCHEN
PREP. AREA
B001D
L S
.5
E
LS001.4 "D
LS001.3 "C
LS001.2 "B
LS001.5 "E
LS00
1.
1 "A
LS00
1.
2 "B
LS001.1 "A
LS001.3 "C
L S
.4
D
937/10
18.8"
69"
937/10
18.8"
46.5"
937/10
18.6"
40.5"
STAIR #7
EXITS THIS LEVEL
OPEN TO
BOILER RM
BELOW
EXIT
STAIR #9 EXITS
THIS LEVEL
STAIR #5 EXITS
THIS LEVEL
STAIR #6 EXITS
THIS LEVEL
BLDG 1 -
OCC. 3
BLDG 2 -
OCC. 4
BLDG 1 -
OCC. 3
BLDG 2 -
OCC. 4
COMPLIANCE NOTE PER NFPA
7.7.2
STAIR #1 SHALL BE
PERMITTED TO
DISCHARGE THROUGH
AREA OF LEVEL OF EXIT
DISCHARGE.
937/10
18.8"
69"
937/10
18.8"
61"
EXIT
NOT
AN
EXIT
937/10
18.6"
34.5"
29/2
3"
73"
TD = 105'-0"
TD = 141'-0"
T D
T D
TD = 147'-5"
TD = 261'-2"
T D
T D
T D
TD = 188'-8"
TD = 118'-6"
TD = 179'-6"
T D
471/13
10.8
42.5"
29/2
2.8"
40.5"
BASEMENT NOTE
MAXIMUM TRAVEL
DISTANCE TO EXIT = 300'-0"
IN BUSINESS OCCUPANCY
AREAS
(IF SPRINKLERED)
COMPLIANCE NOTE PER NFPA
19.1.3.7
ALL MEANS OF EGRESS FROM HEALTHCARE
OCCUPANCIES THAT TRAVERSE NON-
HEALTHCARE OCCUPANCIES SHALL
CONFORM TO THE REQUIREMENTS OF THE
CODE FOR HEATHCARE OCCUPANCIES.
BASEMENT NOTE
MAXIMUM TRAVEL
DISTANCE TO EXIT = 300'-0"
IN BUSINESS OCCUPANCY
AREAS
(IF SPRINKLERED)
CHILLER PLANT
PASSAGE UNDER
HOSPITAL DRIVE TO
OTHER HOSPITAL
LS001.2 "B
LS001.5 "E
L S
.3
C
L S
.2
B
TD = 165'-6
TD = 188'-8"
T D
247/2
24.8"
80"
247/2
24.8"
80"
STAIR #9
TOTAL OCCUPANTS EXIT THIS
AREA + 1/2 FROM LAB AREA
ELEV.
BLDG. 22
LEGEND
BUILDING & LIFE SAFETY REQUIREMENTS
DESCRIPTION
WALL
RATING
NEW
PARTITION KEY
NFPA
101-2018
OPENINGS DAMPERS
RATING RFRNC. TYPE RFRNC.
BUILDING SEPARATION:
FIRE BARRIER2
HR
MIN
OCCUPANCY/AREA SEPARATION
FIRE BARRIER
HR
MIN
HORIZONTAL EXIT (& REFUGE AREA)
FIRE BARRIER2
HR
MIN
VERT. OPG. (EXIT ENCLSR/SHAFT)
FIRE BARRIER
(2 HR = 4 OR MORE STORIES)
(1 HR = LESS THAN 4 STORIES)
(1/2 HR = EXIST. ENCL. IN EXIST BLD'G)
1 HR
2 HR
MIN
MIN
HAZ./INCIDENTAL
USE
FIRE BARRIER
1 HR 45
MIN
HAZ./INCIDENTAL USE
SMOKE PARTITIONS
(SPRINKLERED)
NR-
RESIST
SMK
NR
SELF OR AUTO
CLOSING
SUBDIVIDING
SPACES
SMOKE BARRIER
(I-2 OCCUPANCY)
MIN
1/2 HR
1 HR
SUITE SEPARATION
SMOKE PARTITION
NR
*NR
SELF OR AUTO
CLOSING
EXIT ACCESS CORRIDORS (I-2)
SMOKE PARTITIONS (SPRINKLERED)
NR-
RESIST
SMK
NR
EXIT ACCESS CORRIDORS (B & AHC)
NON-RATED PARTITIONS
NR
NR
1 HR
VERT. OPG. (SHAFT)
FIRE BARRIER
MIN
1 HR
2 HR
MIN
MINEXIT PASSAGEWAY (HORIZ.)
FIRE BARRIER
6.1.14.4.1 19.1.3.5.1
7.2.4.1.3 (1) 19.1.3.8 19.2.2.5 7.1.3.2.1
19.3.1.1-8 8.6
8.7.1 19.3.2.1
8.5
8.4.2 19.2.5.7.1.4
8.4.2 19.3.6.2
21.3.6 35.3.6
19.3.1
7.2.6
8.2.1.3
8.6
19.2.2.7
8.6
19.3.2.1.2
19.3.7.3
7.2.1.4.1 7.2.4.3.7 8.3.4 19.2.2.5, 1-4
8.3.3.2.2 TBL
19.2.2.2
7.1.3.2 (9)
8.3.3.2.2 TBL
19.3.2.1.3
8.3.3.2.2 TBL
8.5.4 19.3.7.8
8.3.3.2.2 TBL
19.2.2.2.
8.3.3.2.2 TBL
8.3.3.2.2 TBL
8.3.3.2.2. TBL
8.7.1.3 8.4.3 19.3.2.1.3
19.3.6.3.2 8.4.3
19.3.6.3 8.4.3
N/A
FIRE 90
MIN
FIRE
90 MIN
FIRE
90 MIN
NOT
ALLOWED
UNLESS
SERVING
STAIR ONLY
N/A
VARIES
SMOKE
90 MIN
VARIES
VARIES
NONE
N/A
NOT
ALLO
WED
8.3.4.8 9.2.1
8.3.4.8 9.2.1
8.3.4.8 9.2.1 7.2.4.3.5
N/A
8.5.5.3 19.3.7.3(2)
8.6.4.5
N/A
N/A
8.4.4
8.4.4 8.4.6.2
8.4.4.1 8.4.6.2 19.3.6.4.2
N/A
SYMBOLS
NO. OCC. EXITING
(SMALLER ROOMS)
MAXIMUM OCCUPANCY
AREA
OCC.
LOAD
FACTOR
FIRE ALARM CONTROL PANEL
FIRE SYSTEM ANNUNCIATOR ALARM
ANNUNCIATOR PANEL
FACP
FSA
FAA
REQ'D. EXIT WIDTH
NO. OF OCC. EXITING
ACTUAL
EXIT
WIDTH
NO. OF OCC./
NO. OF EXITS
1:50
10/1
2"
34"
FEC
FP
PROPERTY LINE
TD = XX
STARTING
LOCATION
TRAVEL DISTANCE
TRAVEL
PATH
FE
FIRE EXTINGUISHER CABINET
FIRE PULL STATION
FIRE EXTINGUISHER
NOTES
[A] DAMPERS ARE NOT REQUIRED IN DUCT PENETRATIONS
OF SMOKE BARRIERS WHERE HVAC SYSTEMS ARE FULLY
DUCTED (19.3.7.3x2)
[B] AIR TRANSFER OPENINGS IN SMOKE PARTITIONS SHALL
HAVE DAMPERS (NFPA 8.2.4.4.3)
[C] SMOKE DAMPERS ARE NOT REQUIRED WHERE
OPENINGS IN DUCT ARE LIMITED TO A SINGLE SMOKE
COMPARTMENT & DUCTS ARE MADE OF STEEL
[D] TRANSFER GRILLES, REGARDLESS OF WHETHER THEY
ARE PROTECTED, ARE NOT ALLOWED IN THESE DOORS OR
WALLS (NFPA 19.3.6.4)
10/1
2"
34"
BASEMENT KEY PLAN
A
BC
D
E
SMOKE
COMPARTMENT #0-0
170002 SF0-0
BASEMENT
19672008
(CH. 39)
EXISTG. BUSINESS
(CH. 39)
EXISTG. BUSINESS
(CH. 42)
EXISTG. STORAGE
(CH. 39)
EXISTG. BUSINESS
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
117 PIERCE ST, SUITE 110
SIOUX CITY, IOWA 51101
712.252.4014
142 N. MOSLEY ST.
WICHITA, KANSAS 67202
316.262.2500
303 S. TOPEKA
WICHITA, KANSAS 67202
316.262.2691
LS001
CODE PLAN - BASEMENT OVERALL
CORRECT FIRE & LIFE
SAFETY DEFICIENCIES -
LIFE SAFETY PLANS
800 HOSPITAL DRIVE COLUMBIA, MO 65201
01-31-2020
589A4-19-104
100% CONSTRUCTION DOCUMENTS
Not to Scale
0 - BASEMENT - (PARENT)
N
BLDG. 1 - OCCUPANCY 3
BASEMENT = 158,877 S.F.
OCCUPANCY TYPE - BUSINESS
TYPE II (222) CONSTRUCTION
TOTAL OCCUPANTS 1060
FULLY SPRINKLERED
HAZARDOUS AREAS IN FULLY
SPRINKLERED BUILDINGS ARE
NOT REQUIRED TO BE
PROTECTED BY FIRE BARRIERS.
COMPLIANCE NOTE
PER NFPA
3.9.3.2.1 &
8.7.1.1 (2)
ALL MEANS OF EGRESS FROM
HEALTHCARE OCCUPANCIES THAT
TRAVERSE NON-HEALTHCARE
OCCUPANCIES SHALL CONFORM TO
THE REQUIREMENTS OF THE CODE
FOR HEATHCARE OCCUPANCIES.
COMPLIANCE NOTE
PER NFPA
19.1.2.4
BLDG. 2 - OCCUPANCY 4
BASEMENT = 14,193 S.F.
OCCUPANCY TYPE - STORAGE
TYPE II (000) CONSTRUCTION
TOTAL OCCUPANTS 29
FULLY SPRINKLERED
STORAGE OCCUPANCY
OCCUPANCY LOAD FACTOR N/A
(USED OCC. GROSS / 500)
14,193 / 500 = 29 OCC.
COMPLIANCE NOTE PER NFPA
7.3.1.2
14,775 SF / 500 = 30 OCC.
BUSINESS OCCUPANCY
OCCUPANCY LOAD FACTOR 150
158,877 / 150 = 1060 OCC.
COMPLIANCE NOTE PER NFPA
7.3.1.2
F E
C F
E C
FEC
FEC
F E
C
F E
C
F E
C
FEC
FEC
FEFEFE FE
F E
C
FEC
F E
C
FEC
IN VITRO
CELL TEST
LAB.
F016
MRI
CONTROL
F017
RADIOPHARMACEUTICAL
R&D
F018
CORR.
CBF3
HOT CELL
F020
CYLINDER
STG.
F015
RADIONUCLIDE
GENERATOR
LAB
F022
EQUIP. RM.
F023
GEN.
RADIOCHEMISTRY/
PEPTIDE
SYNTHESIS/
PEPTIDE
RADIOLABELING
F004
VEST.
F023A
GLASS WASH
F024
WORK ROOM
F026
CORR.
CBF2
VEST.
F025A
OFFICE
F025
TISSUE
CULTURE
(COLD)
F028A
IMMUNOLOGY
LAB.
F027
CYLINDER
STG.
F027A
TISSUE PREP.
(HOT)
F029
TISSUE
CULTURE
(HOT)
F029A
CAMERA
DARK RM.
F031
MICRO DARK
RM.
F032
OFFICE
F033
OFFICE
F034
ELECTRICAL
CLOSET
F001B
VEST.
F002A
RADIOPHARMACEUTICAL
R&D
F010
JAN.
F036
CHIEF
PHARM. SVC.
E002M
ELEC. ROOM
E009
TELE./ DATA.
E006
Room
E003B
ELEV. LOBBY
CBE5
STG.
E005
CORR.
CBE4
ELEV.
#11
ELEV. MACH.
RM.
E007
CONF. RM.
E002E
PROG.
SUPPORT,
R&D
E002C
WK. RM.
E002B
R.C.O., R&D
E002I
RSCH. SVC.
CORR
E002
STAGING RM.
E001D
ANTE RM.
E001C
ANIMAL
WARD
A027A
RSCH. WK.
RM.
A010
CLOSET
A010A
RADIOPHARMACY
RSCH.
A009
RADIOPHARMACY
RSCH.
A007
GLASS WASH
B051
PHARMACOLOGY
RSCH.
B048
PHARMACOLOGY
RSCH.
B042
CORR.
CBA14
RADIOPHARMACY
RSCH.
A003
CLOSET
A025BFIRE CL.
CBA2A
OFFICE
B033
STAIR #3
BO36A
MECH. ROOM
E003A
MECH. ROOM
E003
FRZ.
F030A REF.
F030
ELEC.
CLOSET
F035
F.A.
CONTROL
PANEL
F035A
VEST.
F034A
TISSUE PREP.
(COLD)
F028
MRI ROOM
F019
CORR.
F015A
RADIO
PHARM./
PHARMAKINETIC
LAB.
F014
HOT LAB. 1
F021
COLD LAB.
F005
CONF. RM.
F001A
RECP.
F001
CORR.
CBF5
WORK ROOM
F002
OFFICE
F003
WORK ROOM
F006
OFFICE
F007
OFFICE
F008
OFFICE
F009
VEST.
F009A
SHARED
OFFICE
F011
VA-BIC PET/
SPECT/
CT/MOLECULAR
IMAGING
SUITE
F012
CORR.
CBF4
STG.
F013
STAIR #11
#11
JAN.
E012
ELEV. MACH.
RM.
E004
M. TLT.
E008
W. TLT.
E010 PHARM.
E001
STORAGE
E001G
STER./ IV
PREP.
E001B
NARCOTIC
VAULT
E001A
PHARM. SVC.
E002N
ANTI-COAGULATION
OFFICE
E002Q
ADMIN.
OFFICER
PHARM.
E002O
SUPV.
INPATIENT
PHARM.
E001F
OUTPATIENT
PHARM.
SUPV.
E001E
HALL
E001H
BREAK RM.
E002F
A.O., R&D
E002D
CORR.
CBE2
CORR.
CBE1
OFFICE
E002A
OFFICE
E002H
CLINICAL
RSCH.
E002J
M.F.M.R.
EXECUTIVE
DIR.
E002K
OFFICE
E002L
CORR.
CBE3
COLD RM.
B037A
COLD RM.
B037
STAIR
ACCESS
B036
SIGNAL
PANELS
B033A
JAN.
B034
PHARMACOLOGY
RSCH.
B039
OFFICE
B039A
ELEV.
#10
ELEV.
#9
F. TLT.
A001
M. TLT.
A002
PHY. RSCH.
A009A
ENDOCRINE/
HYPERTENSION
RSCH.
A019
ENDOCRINE/
HYPERTENSION
RSCH.
A020
RSCH.
OFFICE
A020A
OFFICE
A022
STAIR #4
A024A
JAN.
A025
STAIR CORR.
A024
PATHOGEN
FREE SUITE
A026
937/10
28.2"
46"
937/10
28.2"
46"
247/2
24.6"
46"
STAIR #3
STAIR #11
STAIR #4
RECEPTION
E002
LS001.1
"A
LS001.2
"B
LS
001.1 "A"
LS
001.3 "C
EXIT
TD = 261'-2"
T D
T D
T D
PASSAGE UNDER
HOSPITAL DRIVE TO
OTHER HOSPITAL
L S
.3
C
L S
.2
B
T D
247/2
24.8"
80"
247/2
24.8"
80"
SMOKE
COMPARTMENT #0-0
170002 SF0-0
LEGEND
BUILDING & LIFE SAFETY REQUIREMENTS
DESCRIPTION
WALL
RATING
NEW
PARTITION KEY NFPA 101-2018
OPENINGS DAMPERS
RATING RFRNC. TYPE RFRNC.
BUILDING SEPARATION:
FIRE BARRIER
2 HR
90 MIN
OCCUPANCY/AREA SEPARATION
FIRE BARRIER
2 HR
90 MIN
HORIZONTAL EXIT (& REFUGE AREA)
FIRE BARRIER
2 HR
90 MIN
VERT. OPG. (EXIT ENCLSR/SHAFT)
FIRE BARRIER
(2 HR = 4 OR MORE STORIES)
(1 HR = LESS THAN 4 STORIES)
(1/2 HR = EXIST. ENCL. IN EXIST BLD'G)
1 HR
2 HR
60 MIN
90 MIN
HAZ./INCIDENTAL USE
FIRE BARRIER
1 HR 45 MIN
HAZ./INCIDENTAL USE
SMOKE PARTITIONS
(SPRINKLERED)
NR-
RESIST
SMK
NR
SELF OR AUTO
CLOSING
SUBDIVIDING SPACES
SMOKE BARRIER (I-2 OCCUPANCY)
20 MIN
1/2
HR
1 HR
SUITE SEPARATION
SMOKE PARTITION
NR
*NR
SELF OR AUTO
CLOSING
EXIT ACCESS CORRIDORS (I-2)
SMOKE PARTITIONS (SPRINKLERED)
NR-
RESIST
SMK
NR
EXIT ACCESS CORRIDORS (B & AHC)
NON-RATED PARTITIONS
NR
NR
1 HR
VERT. OPG. (SHAFT)
FIRE BARRIER 60 MIN
1 HR
2 HR
60 MIN
90 MINEXIT PASSAGEWAY (HORIZ.)
FIRE BARRIER
6.1.14.4.1 19.1.3.5.1
7.2.4.1.3 (1) 19.1.3.8 19.2.2.5 7.1.3.2.1
19.3.1.1-8 8.6
8.7.1 19.3.2.1
8.5
8.4.2 19.2.5.7.1.4
8.4.2 19.3.6.2
21.3.6 35.3.6
19.3.1
7.2.6
8.2.1.3
8.6
19.2.2.7
8.6
19.3.2.1.2
19.3.7.3
7.2.1.4.1 7.2.4.3.7 8.3.4 19.2.2.5, 1-4
8.3.3.2.2 TBL
19.2.2.2
7.1.3.2 (9)
8.3.3.2.2 TBL
19.3.2.1.3
8.3.3.2.2 TBL
8.5.4 19.3.7.8
8.3.3.2.2 TBL
19.2.2.2.
8.3.3.2.2 TBL
8.3.3.2.2 TBL
8.3.3.2.2. TBL
8.7.1.3 8.4.3 19.3.2.1.3
19.3.6.3.2 8.4.3
19.3.6.3 8.4.3
N/A
FIRE
90 MIN
FIRE
90 MIN
FIRE
90 MIN
NOT
ALLOWED
UNLESS
SERVING
STAIR
ONLY
N/A
VARIES
SMOKE
90 MIN
VARIES
VARIES
NONE
N/A
NOT
ALLOWED
8.3.4.8 9.2.1
8.3.4.8 9.2.1
8.3.4.8 9.2.1 7.2.4.3.5
N/A
8.5.5.3 19.3.7.3(2)
8.6.4.5
N/A
N/A
8.4.4
8.4.4 8.4.6.2
8.4.4.1 8.4.6.2 19.3.6.4.2
N/A
BASEMENT KEY PLAN
A
SYMBOLS
NO. OCC. EXITING
(SMALLER ROOMS)
MAXIMUM OCCUPANCY
AREA
OCC. LOAD
FACTOR
FIRE ALARM CONTROL PANEL
FIRE SYSTEM ANNUNCIATOR ALARM
ANNUNCIATOR PANEL
FACP
FSA
FAA
REQ'D. EXIT WIDTH
NO. OF OCC. EXITING
ACTUAL EXIT
WIDTH
NO. OF OCC./
NO. OF EXITS
1:50
10/1
2"
34"
FEC
FP
PROPERTY LINE
STARTING
LOCATION
TRAVEL DISTANCE
TRAVEL PATH
FE
FIRE EXTINGUISHER CABINET
FIRE PULL STATION
FIRE EXTINGUISHER
NOTES
[A] DAMPERS ARE NOT REQUIRED IN DUCT PENETRATIONS OF
SMOKE BARRIERS WHERE HVAC SYSTEMS ARE FULLY DUCTED
(18.3.7.3x2)
[B] AIR TRANSFER OPENINGS IN SMOKE PARTITIONS SHALL
HAVE DAMPERS (NFPA 8.2.4.4.3) (IBC 710.7)
[C] SMOKE DAMPERS ARE NOT REQUIRED WHERE OPENINGS IN
DUCT ARE LIMITED TO A SINGLE SMOKE COMPARTMENT &
DUCTS ARE MADE OF STEEL (IBC 716.5.5)
[D] TRANSFER GRILLES REGARDLESS OF WHETHER THEY ARE
PROTECTED
ARE NOT ALLOWED IN THESE DOORS OR WALLS (NFPA 18.3.6.4)
TD = XX
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
117 PIERCE ST, SUITE 110
SIOUX CITY, IOWA 51101
712.252.4014
142 N. MOSLEY ST.
WICHITA, KANSAS 67202
316.262.2500
303 S. TOPEKA
WICHITA, KANSAS 67202
316.262.2691
LS001.1
CODE PLAN - BASEMENT AREA A
CORRECT FIRE & LIFE
SAFETY DEFICIENCIES -
LIFE SAFETY PLANS
800 HOSPITAL DRIVE COLUMBIA, MO 65201
01-31-2020
589A4-19-104
100% CONSTRUCTION DOCUMENTS
3/32" = 1'-0"
0 - BASEMENT - AREA A
HAZARDOUS AREAS IN FULLY
SPRINKLERED BUILDINGS ARE
NOT REQUIRED TO BE
PROTECTED BY FIRE BARRIERS.
COMPLIANCE NOTE
PER NFPA
3.9.3.2.1 &
8.7.1.1 (2)
BLDG. 1 - OCCUPANCY 3
BASEMENT = 158,877 S.F.
OCCUPANCY TYPE - BUSINESS
TYPE II (222) CONSTRUCTION
TOTAL OCCUPANTS 1060
FULLY SPRINKLERED
BUSINESS OCCUPANCY
OCCUPANCY LOAD FACTOR 150
158,877 / 150 = 1060 OCC.
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
FEC
FEC FEC
FEC
FEC
FEC
FEC
FEC
FEC
F E
C
F E
C
F E
C
FEC
F E
C
FEFE
FE
F E
FE
FE
F E
C
WK. RM.
E002B
R.C.O., R&D
E002I
ANIMAL
WARD
A027A
ANIMAL
WARD
A027
ANIMAL
WARD
A030
CORR.
CBA7
ANIMAL
WARD
A029
RSCH. WK.
RM.
A010
CLOSET
A010A
RADIOPHARMACY
RSCH.
A009
RADIOPHARMACY
RSCH.
A007
CORR.
CBA14
RADIOPHARMACY
RSCH.
A004
CORR.
CBA1
CHIEF
B006A
ASSOC.
CHIEF
B006B
RADIOPHARMACY
RSCH.
A003
CORR.
CBA2
RADIOPHARMACY
RSCH.
A006
ONCOLOGY
RESCH.
A051 RADIOPHARMACEUTICAL
SCIENCES
RSCH.
A049
RADIOPHARMACEUTICAL
SCIENCES
RSCH.
A016A
CORR.
CBA10
RSCH. STG.
A054
RADIATION
LAB.
A052
RADIOPHARMACEUTICAL
SCIENCES
RSCH.
A050
RADIOPHARMACEUTICAL
SCIENCES
RSCH.
A047
DMARC
A060
CART WASH
(DIRTY)
A046
ELEC.
CLOSET
A047A
CORR.
CBA6
SHR./ LNGE.
A011
ANIMAL
X-RAY RM.
A015
DARK RM.
A015A
RADIOPHARMACEUTICAL
SCIENCES
RSCH.
A017
ANIMAL
WARD
A045
VMU OFFICE
A043
ANIMAL
WARD
A033
ANIMAL
WARD
A035
ANIMAL
WARD
A032
ANIMAL
WARD
A034
CORR.
CORR.
CBA9
CLOSET
A025BFIRE CL.
CBA2A
STG. RSCH.
SVC.
A033
FUTURE
ANIMAL
WARD
A037
EQUIP. STG.
A036ANIMAL
WARD
A039
ANIMAL
WARD
A040
LOUNGE
A063
CORR.
CBA11
CORR.
CBA17
SAFETY/EMERGENCY
D005A
OFFICE
D005
PAINT SHOP
D006
OFFICE
D004D
LAUNDRY &
MENDING
D004C
TELEPHONE
OPERATORS
D004L
TLT.
D004B
LAUNDRY
STORAGE
D004F
OFFICE
D004G
EQUIP. STG.
D003B
OFFICE
D004H
LINEN
D004
TECH. MED
REPAIR
D008
FURNITURE
STG.
D009
ELEC. SHOP
D007
CARPENTER
SHOP
D011
OFFICE
D010
TOOL STG.
D011A
KEY SHOP
D012
PIPE &
MECHANICS
SHOP
D016
FIRE SPKLR.
PUMP RM.
D017
OFFICE
D004K
OFFICE
D004J
OFFICE
D004I
EQUIP. STG.
D003C
STORAGE
D003D
CORR.
CBD7
STG.
D003A
STG.
D004O
LOST AND
FOUND
D004N
M. TLT.
D004A
TELEPHONE
OPERATOR
SUPER.
D004E
ENTR. VEST.
D004M
STAIR #5
D015
VEST.
D014
UNISEX TLT.
D013
ELEC.
CLOSET
CBD2B
CORR.
CBD2
BOILER
D018
A/C SHOP
D019C
CORR.
CBD1
REPRODUCTIVE
D002TRASH
D001
TRASH
D001B
JAN.
D001A
JAN.
D029
GROSS SPEC.
D028
LKR./ TLT.
RM.
D027
CORR.
CBD5
ELEV. MACH.
RM.
D025
E.C.C. OFFICE
D019A
STORAGE
D019B
AUTOPSY
D031
COLD RM.
D030
OFFICE
D024
TLT.
D019C
ST. LNGE.
C003A
SUPV.
INPATIENT
PHARM.
E001F
OUTPATIENT
PHARM.
SUPV.
E001E
OFFICE
E002H
CLINICAL
RSCH.
E002J
M.F.M.R.
EXECUTIVE
DIR.
E002K
OFFICE
E002L
ELEV.
#4
ELEV.
#5
ELEV. LOBBY
A058
ELEV.
#3
ELEV.
#2
ELEV.
#1
CORR.
CBA13
BIOHAZARD
STG.
A057
CLOSET
A059A
MAIL RM.
A059
STAIR #1
A056
IT CLOSET
A056A
CLOSET
A054B
ELEC.
CLOSET
A053
RSCH.
INVESTIGATOR
A048
MEN'S
LOCKER
A063C
MEN'S TLT
A063B
FITNESS
A063A
WOMAN'S TLT
A063E
WOMAN'S
SHWR
A063F
WOMAN'S
LOCKER
A063G
MECH RM.
A038
STG.
A033B
STG. RSCH.
A033A
CORR.
CBA8
CAGE WASH
A041
F. TLT.
A001
M. TLT.
A002
PHY. RSCH.
A009A
ENDOCRINE/
HYPERTENSION
RSCH.
A019
ENDOCRINE/
HYPERTENSION
RSCH.
A020
RSCH.
OFFICE
A020A
OFFICE
A022
STAIR #4
A024A
JAN.
A025
CORR.
CBA5
STAIR CORR.
A024
PATHOGEN
FREE SUITE
A026
ANIMAL
WARD
A028
ANIMAL
WARD
A031
STG.
A042
STG.
A042A
OFFICE
A023A
NEURO.
SLEEP RSCH.
A023
SURG. SUITE
A021
ANIMAL
SURG.
A045A
NEURO.
SLEEP RSCH.
A018
COLD. RM.
A014
CORR.
CBA4
ENDOCRINE/
HYPERTENSION
RSCH.
A012
RSCH.INVESTIGATOR
A013
PHY. RSCH.
A008
ANIMAL
WARD
A008A
RSCH.
INVESTIGATOR
A005
OFFICE
A004A
RADIOPHARMACY
RSCH.
A055
OFFICE
A006A
OFFICE
A051A
RADIOPHARMACEUTICAL
SCIENCES
RSCH.
A016
937/10
28.2"
46"
STAIR #1
850/16
15.9"
46"
937/10
28.2"
46"
STAIR #4
STAIR #5
MEN'S SHWR
A063D
MAKE-UP
A063H
LS001.1
"A
LS001.2
"B
937/10
18.8"
69"
937/10
18.8"
46.5"
OPEN TO
BOILER RM
BELOW
STAIR #9 EXITS
THIS LEVEL
STAIR #5 EXITS
THIS LEVEL
COMPLIANCE NOTE PER NFPA
7.7.2
STAIR #1 SHALL BE
PERMITTED TO
DISCHARGE THROUGH
AREA OF LEVEL OF EXIT
DISCHARGE.
937/10
18.8"
69"
937/10
18.8"
61"
EXIT
NOT
AN
EXIT
TD = 188'-8"
TD = 118'-6"
TD = 179'-6"
LS
001.2 "B"
LS
001.5 "E"
L S
.3
C
L S
.2
B
247/2
24.8"
80"
STAIR #9
TOTAL OCCUPANTS EXIT THIS
AREA + 1/2 FROM LAB AREA
ELEV.
BLDG. 22
LEGEND
BUILDING & LIFE SAFETY REQUIREMENTS
DESCRIPTION
WALL
RATING
NEW
PARTITION KEY NFPA 101-2018
OPENINGS DAMPERS
RATING RFRNC. TYPE RFRNC.
BUILDING SEPARATION:
FIRE BARRIER
2 HR
90 MIN
OCCUPANCY/AREA SEPARATION
FIRE BARRIER
2 HR
90 MIN
HORIZONTAL EXIT (& REFUGE AREA)
FIRE BARRIER
2 HR
90 MIN
VERT. OPG. (EXIT ENCLSR/SHAFT)
FIRE BARRIER
(2 HR = 4 OR MORE STORIES)
(1 HR = LESS THAN 4 STORIES)
(1/2 HR = EXIST. ENCL. IN EXIST BLD'G)
1 HR
2 HR
60 MIN
90 MIN
HAZ./INCIDENTAL USE
FIRE BARRIER
1 HR 45 MIN
HAZ./INCIDENTAL USE
SMOKE PARTITIONS
(SPRINKLERED)
NR-
RESIST
SMK
NR
SELF OR AUTO
CLOSING
SUBDIVIDING SPACES
SMOKE BARRIER (I-2 OCCUPANCY)
20 MIN
1/2
HR
1 HR
SUITE SEPARATION
SMOKE PARTITION
NR
*NR
SELF OR AUTO
CLOSING
EXIT ACCESS CORRIDORS (I-2)
SMOKE PARTITIONS (SPRINKLERED)
NR-
RESIST
SMK
NR
EXIT ACCESS CORRIDORS (B & AHC)
NON-RATED PARTITIONS
NR
NR
1 HR
VERT. OPG. (SHAFT)
FIRE BARRIER 60 MIN
1 HR
2 HR
60 MIN
90 MINEXIT PASSAGEWAY (HORIZ.)
FIRE BARRIER
6.1.14.4.1 19.1.3.5.1
7.2.4.1.3 (1) 19.1.3.8 19.2.2.5 7.1.3.2.1
19.3.1.1-8 8.6
8.7.1 19.3.2.1
8.5
8.4.2 19.2.5.7.1.4
8.4.2 19.3.6.2
21.3.6 35.3.6
19.3.1
7.2.6
8.2.1.3
8.6
19.2.2.7
8.6
19.3.2.1.2
19.3.7.3
7.2.1.4.1 7.2.4.3.7 8.3.4 19.2.2.5, 1-4
8.3.3.2.2 TBL
19.2.2.2
7.1.3.2 (9)
8.3.3.2.2 TBL
19.3.2.1.3
8.3.3.2.2 TBL
8.5.4 19.3.7.8
8.3.3.2.2 TBL
19.2.2.2.
8.3.3.2.2 TBL
8.3.3.2.2 TBL
8.3.3.2.2. TBL
8.7.1.3 8.4.3 19.3.2.1.3
19.3.6.3.2 8.4.3
19.3.6.3 8.4.3
N/A
FIRE
90 MIN
FIRE
90 MIN
FIRE
90 MIN
NOT
ALLOWED
UNLESS
SERVING
STAIR
ONLY
N/A
VARIES
SMOKE
90 MIN
VARIES
VARIES
NONE
N/A
NOT
ALLOWED
8.3.4.8 9.2.1
8.3.4.8 9.2.1
8.3.4.8 9.2.1 7.2.4.3.5
N/A
8.5.5.3 19.3.7.3(2)
8.6.4.5
N/A
N/A
8.4.4
8.4.4 8.4.6.2
8.4.4.1 8.4.6.2 19.3.6.4.2
N/A
BASEMENT KEY PLAN
B
SYMBOLS
NO. OCC. EXITING
(SMALLER ROOMS)
MAXIMUM OCCUPANCY
AREA
OCC. LOAD
FACTOR
FIRE ALARM CONTROL PANEL
FIRE SYSTEM ANNUNCIATOR ALARM
ANNUNCIATOR PANEL
FACP
FSA
FAA
REQ'D. EXIT WIDTH
NO. OF OCC. EXITING
ACTUAL EXIT
WIDTH
NO. OF OCC./
NO. OF EXITS
1:50
10/1
2"
34"
FEC
FP
PROPERTY LINE
STARTING
LOCATION
TRAVEL DISTANCE
TRAVEL PATH
FE
FIRE EXTINGUISHER CABINET
FIRE PULL STATION
FIRE EXTINGUISHER
NOTES
[A] DAMPERS ARE NOT REQUIRED IN DUCT PENETRATIONS OF
SMOKE BARRIERS WHERE HVAC SYSTEMS ARE FULLY DUCTED
(18.3.7.3x2)
[B] AIR TRANSFER OPENINGS IN SMOKE PARTITIONS SHALL
HAVE DAMPERS (NFPA 8.2.4.4.3) (IBC 710.7)
[C] SMOKE DAMPERS ARE NOT REQUIRED WHERE OPENINGS IN
DUCT ARE LIMITED TO A SINGLE SMOKE COMPARTMENT &
DUCTS ARE MADE OF STEEL (IBC 716.5.5)
[D] TRANSFER GRILLES REGARDLESS OF WHETHER THEY ARE
PROTECTED
ARE NOT ALLOWED IN THESE DOORS OR WALLS (NFPA 18.3.6.4)
TD = XX
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
117 PIERCE ST, SUITE 110
SIOUX CITY, IOWA 51101
712.252.4014
142 N. MOSLEY ST.
WICHITA, KANSAS 67202
316.262.2500
303 S. TOPEKA
WICHITA, KANSAS 67202
316.262.2691
LS001.2
CODE PLAN - BASEMENT AREA B
CORRECT FIRE & LIFE
SAFETY DEFICIENCIES -
LIFE SAFETY PLANS
800 HOSPITAL DRIVE COLUMBIA, MO 65201
01-31-2020
589A4-19-104
100% CONSTRUCTION DOCUMENTS
3/32" = 1'-0"
0 - BASEMENT - AREA B
HAZARDOUS AREAS IN FULLY
SPRINKLERED BUILDINGS ARE
NOT REQUIRED TO BE
PROTECTED BY FIRE BARRIERS.
COMPLIANCE NOTE
PER NFPA
3.9.3.2.1 &
8.7.1.1 (2)
BLDG. 1 - OCCUPANCY 3
BASEMENT = 158,877 S.F.
OCCUPANCY TYPE - BUSINESS
TYPE II (222) CONSTRUCTION
TOTAL OCCUPANTS 1060
FULLY SPRINKLERED
BUSINESS OCCUPANCY
OCCUPANCY LOAD FACTOR 150
158,877 / 150 = 1060 OCC.
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
JT
FEC
FEC
FEC
F E
C
FEC
F E
C
FE
FE
F E
FE
F E
JT
JT
JT
JT
JT
GLASS WASH
B051
PHARMACOLOGY
RSCH.
B048
PHARMACOLOGY
RSCH.
B042
OFFICE
B049
RSCH.
COMMON RM.
B045
OFFICE
B017
RSCH.
INVESTIGATOR
B022
RSCH.
INVESTIGATOR
B015
CORR.
CBA14
CORR.
CBA1
CHIEF
B006A
ASSOC.
CHIEF
B006B
RSCH.
INVESTIGATOR
B012
OFFICE
B010
ELEC.
CLOSET
B009A
ELEC.
CLOSET
B009B
LACTATION
B009
CLASSROOM
B007ON-CALL
ROOMS/LOUNGE
B011
OFFICE
B010A
OFFICE
B016
AUTOPSY
D031
Room
CBD4
COLD RM.
D030
OFFICE
D024
TLT.
D019C
HAC
C009H
MOW OFFICE
C009I
MOW OFFICE
C009K
FOOD STG.
C009GCORR.
C009J
BIOMEDICAL
ENG.
C002
FOOD PREP
C009
REF.
C009D
JAN.
B002E
OFFICE
B002F
MECH.
C012
FOOD PREP./
COOK
B001B
CART CLEAN
B001C
CHIEF OF
SERVICE
C001A
TLT
B011H
DIETETICS
STG.
B002G
TRNG/BRK.
RM.
B002D
DIETETICS
OFFICE
B002A
RSCH. CORE
AREA
B019
CLOSET
B026A
TRANS. RM.
B027A
PULMONARY
RSCH.
B027
OFFICE
B033
STAIR #3
BO36A
ELEC.
CLOSET
B030
CORR.
CBB3
LAB.
B026
LAB.
B023
OPHTHALMOLOGY
RSCH.
B032
COLD RM.
B037A
COLD RM.
B037
STAIR
ACCESS
B036
SIGNAL
PANELS
B033A
JAN.
B034
CORR.
CBB3
PHARMACOLOGY
RSCH.
B039
OFFICE
B039A
HEALTH
PHYSICS LAB.
B050
RSCH.
OFFICE
B046
RSCH.
INVESTIGATOR
B047
OFFICE
B046A
RSCH.
INVESTIGATOR
B021
OFFICE
B006
OFFICE
B006C
CORR.
B020
OFFICE
B014
OFFICE
B018
OPHTHALMOLOGY
B031
OFFICE
B025B
RHEUMATOLOGY
RSCH.
B024
HAS
B013
CORR.
CBB1
ON-CALL RM.
#1
B011A
TLT
B011B
ON-CALL RM.
#2
B011C
ON-CALL RM.
#3
B011D
TLT
B011E
ON-CALL RM.
#4
B011F
ON-CALL RM.
#5
B001G
ELEC. ROOM
B011J
ON-CALL
ROOMS/LOUNGE
B011
CLEANING
AREA
B001A
VTS/TRVL
SUPERVISOR
B013A
ELEV.
#12
CORR.
CBG3
OFFICE
B001F
DISH CLEAN
B002
DISH CLEAN
B002K
CLOSET
B001E
DIETETICS
OFFICE
C009A
REF.
C009B
OFFICE
C009C
FRZ.
C009F
REF.
C009E
MECH. EQUIP.
C010
TLT.
C009M
TLT.
C009N
CORR.
C009J
OFFICE
C008
BIOMEDICAL
SUPV.
C002B
BIOMED
STORAGE
C002A
OI&T
C001
ELEV.
#8
ELEV.
#7
ELEV.
#4
ELEV.
#5
MECH.
CHASE
C001D
CORR.
CBA13
CORR.
CBG5
937/10
28.2"
46"
STAIR #3
KITCHEN
PREP. AREA
B001D
LS
001.4 "D
LS
001.3 "C
LS
001.1 "A"
LS
001.3 "C
EXIT
NOT
AN
EXIT
T D
T D
T D
L S
.3
C
L S
.2
B
TD = 188'-8"
247/2
24.8"
80"
LEGEND
BUILDING & LIFE SAFETY REQUIREMENTS
DESCRIPTION
WALL
RATING
NEW
PARTITION KEY NFPA 101-2018
OPENINGS DAMPERS
RATING RFRNC. TYPE RFRNC.
BUILDING SEPARATION:
FIRE BARRIER
2 HR
90 MIN
OCCUPANCY/AREA SEPARATION
FIRE BARRIER
2 HR
90 MIN
HORIZONTAL EXIT (& REFUGE AREA)
FIRE BARRIER
2 HR
90 MIN
VERT. OPG. (EXIT ENCLSR/SHAFT)
FIRE BARRIER
(2 HR = 4 OR MORE STORIES)
(1 HR = LESS THAN 4 STORIES)
(1/2 HR = EXIST. ENCL. IN EXIST BLD'G)
1 HR
2 HR
60 MIN
90 MIN
HAZ./INCIDENTAL USE
FIRE BARRIER
1 HR 45 MIN
HAZ./INCIDENTAL USE
SMOKE PARTITIONS
(SPRINKLERED)
NR-
RESIST
SMK
NR
SELF OR AUTO
CLOSING
SUBDIVIDING SPACES
SMOKE BARRIER (I-2 OCCUPANCY)
20 MIN
1/2
HR
1 HR
SUITE SEPARATION
SMOKE PARTITION
NR
*NR
SELF OR AUTO
CLOSING
EXIT ACCESS CORRIDORS (I-2)
SMOKE PARTITIONS (SPRINKLERED)
NR-
RESIST
SMK
NR
EXIT ACCESS CORRIDORS (B & AHC)
NON-RATED PARTITIONS
NR
NR
1 HR
VERT. OPG. (SHAFT)
FIRE BARRIER 60 MIN
1 HR
2 HR
60 MIN
90 MINEXIT PASSAGEWAY (HORIZ.)
FIRE BARRIER
6.1.14.4.1 19.1.3.5.1
7.2.4.1.3 (1) 19.1.3.8 19.2.2.5 7.1.3.2.1
19.3.1.1-8 8.6
8.7.1 19.3.2.1
8.5
8.4.2 19.2.5.7.1.4
8.4.2 19.3.6.2
21.3.6 35.3.6
19.3.1
7.2.6
8.2.1.3
8.6
19.2.2.7
8.6
19.3.2.1.2
19.3.7.3
7.2.1.4.1 7.2.4.3.7 8.3.4 19.2.2.5, 1-4
8.3.3.2.2 TBL
19.2.2.2
7.1.3.2 (9)
8.3.3.2.2 TBL
19.3.2.1.3
8.3.3.2.2 TBL
8.5.4 19.3.7.8
8.3.3.2.2 TBL
19.2.2.2.
8.3.3.2.2 TBL
8.3.3.2.2 TBL
8.3.3.2.2. TBL
8.7.1.3 8.4.3 19.3.2.1.3
19.3.6.3.2 8.4.3
19.3.6.3 8.4.3
N/A
FIRE
90 MIN
FIRE
90 MIN
FIRE
90 MIN
NOT
ALLOWED
UNLESS
SERVING
STAIR
ONLY
N/A
VARIES
SMOKE
90 MIN
VARIES
VARIES
NONE
N/A
NOT
ALLOWED
8.3.4.8 9.2.1
8.3.4.8 9.2.1
8.3.4.8 9.2.1 7.2.4.3.5
N/A
8.5.5.3 19.3.7.3(2)
8.6.4.5
N/A
N/A
8.4.4
8.4.4 8.4.6.2
8.4.4.1 8.4.6.2 19.3.6.4.2
N/A
BASEMENT KEY PLAN
C
SYMBOLS
NO. OCC. EXITING
(SMALLER ROOMS)
MAXIMUM OCCUPANCY
AREA
OCC. LOAD
FACTOR
FIRE ALARM CONTROL PANEL
FIRE SYSTEM ANNUNCIATOR ALARM
ANNUNCIATOR PANEL
FACP
FSA
FAA
REQ'D. EXIT WIDTH
NO. OF OCC. EXITING
ACTUAL EXIT
WIDTH
NO. OF OCC./
NO. OF EXITS
1:50
10/1
2"
34"
FEC
FP
PROPERTY LINE
STARTING
LOCATION
TRAVEL DISTANCE
TRAVEL PATH
FE
FIRE EXTINGUISHER CABINET
FIRE PULL STATION
FIRE EXTINGUISHER
NOTES
[A] DAMPERS ARE NOT REQUIRED IN DUCT PENETRATIONS OF
SMOKE BARRIERS WHERE HVAC SYSTEMS ARE FULLY DUCTED
(18.3.7.3x2)
[B] AIR TRANSFER OPENINGS IN SMOKE PARTITIONS SHALL
HAVE DAMPERS (NFPA 8.2.4.4.3) (IBC 710.7)
[C] SMOKE DAMPERS ARE NOT REQUIRED WHERE OPENINGS IN
DUCT ARE LIMITED TO A SINGLE SMOKE COMPARTMENT &
DUCTS ARE MADE OF STEEL (IBC 716.5.5)
[D] TRANSFER GRILLES REGARDLESS OF WHETHER THEY ARE
PROTECTED
ARE NOT ALLOWED IN THESE DOORS OR WALLS (NFPA 18.3.6.4)
TD = XX
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
117 PIERCE ST, SUITE 110
SIOUX CITY, IOWA 51101
712.252.4014
142 N. MOSLEY ST.
WICHITA, KANSAS 67202
316.262.2500
303 S. TOPEKA
WICHITA, KANSAS 67202
316.262.2691
LS001.3
CODE PLAN - BASEMENT AREA C
CORRECT FIRE & LIFE
SAFETY DEFICIENCIES -
LIFE SAFETY PLANS
800 HOSPITAL DRIVE COLUMBIA, MO 65201
01-31-2020
589A4-19-104
100% CONSTRUCTION DOCUMENTS
3/32" = 1'-0"
0 - BASEMENT - AREA C
HAZARDOUS AREAS IN FULLY
SPRINKLERED BUILDINGS ARE
NOT REQUIRED TO BE
PROTECTED BY FIRE BARRIERS.
COMPLIANCE NOTE
PER NFPA
3.9.3.2.1 &
8.7.1.1 (2)
BLDG. 1 - OCCUPANCY 3
BASEMENT = 158,877 S.F.
OCCUPANCY TYPE - BUSINESS
TYPE II (222) CONSTRUCTION
TOTAL OCCUPANTS 1060
FULLY SPRINKLERED
BUSINESS OCCUPANCY
OCCUPANCY LOAD FACTOR 150
158,877 / 150 = 1060 OCC.
FEC
FEC
F E
C
LOGISTICS
OFFICE
W05
ELEC. RM.
G008
OFFICE
G019
ELEV. MACH.
RM.
G004A
EQUIP.
G004
ELEV.
#12
ELEV.
#13
ELEV.
#14
ELEV.
CONTROL
G015
CORR.
CBG6
CART WASH
G035
DIRTY
PROCESSING
G032
EQUIP.
G052B
ELEV.
CONTROL
G016
OFFICE &
SUPPLY
G051
STERILIZER
ACCESS
ROOM
G052C
ETO
STERILIZER
ACCESS
G045
STERILIZER
ACCESS
G043A
HALL
G046
ELEC. ROOM
G013
CORR.
CBG2
OFFICE
G019A
STG
G019B
OFFICE
G019C
SHOWER
G040A
CONTROL
ROOM
G042
HALL
G037
HALL
G023
HALL
CBG4
CONFERENCE
R00M
G017
WOMEN'S
LOCKER
G024
MEN'S
LOCKER
G027
MEN'S
SHOWER
G027A WOMEN'S
SHWR
G024B
STORAGE
G029
STORAGE
G030
CORR.
CBG3
WAREHOUSE
BREAKOUT
AREA
W03
WAREHOUSE
W07
TOILET
W08
LOGISTICS
MANAGER
W09
CLOSET
W05B
SHIPPING
AND
RECEIVING
W02
PHARMACY
DRUG CACHE
W03A
CORR.
W03B
BREAK ROOM
G018
WOMEN'S TLT
G024A
FILTER
EQUIPMENT
G052A
VESTIBULE
G031
ANTE ROOM
G059
CORR.
G055
STAIR #12
G060
ELEV. LOBBY
G026MANUAL
WASH RM.
G032A
C/S WORK
AREA
G052
ENDOSCOPE
PROCESS.
G036
ELEV.
#15
STORAGE
G050
CLEAN
RECEIVING
BREAKOUT
G048
BULK STORE
RM
G047
CLEAN
PROCESSING
G043
MECH. RM.
G001
CORR.
G012
LOCKERS
G038
SHOWER
G038A
LOCKERS
G040
WAREHOUSE
W04A
WAREHOUSE
W04
WAREHOUSE
W05A
CANTEEN
STOCKROOM
W06
PROCESS
STORES
W01
L S
.5
E
L S
.4
D
EXIT
BLDG 1 -
OCC. 3
BLDG 2 -
OCC. 4
937/10
18.6"
34.5"
29/2
3"
73"
TD = 141'-0"
T D
T D
TD = 147'-5"
471/13
10.8
42.5"
BASEMENT NOTE
MAXIMUM TRAVEL
DISTANCE TO EXIT = 300'-0"
IN BUSINESS OCCUPANCY
AREAS
(IF SPRINKLERED)
TD = 165'-6
LEGEND
BUILDING & LIFE SAFETY REQUIREMENTS
DESCRIPTION
WALL
RATING
NEW
PARTITION KEY NFPA 101-2018
OPENINGS DAMPERS
RATING RFRNC. TYPE RFRNC.
BUILDING SEPARATION:
FIRE BARRIER
2 HR
90 MIN
OCCUPANCY/AREA SEPARATION
FIRE BARRIER
2 HR
90 MIN
HORIZONTAL EXIT (& REFUGE AREA)
FIRE BARRIER
2 HR
90 MIN
VERT. OPG. (EXIT ENCLSR/SHAFT)
FIRE BARRIER
(2 HR = 4 OR MORE STORIES)
(1 HR = LESS THAN 4 STORIES)
(1/2 HR = EXIST. ENCL. IN EXIST BLD'G)
1 HR
2 HR
60 MIN
90 MIN
HAZ./INCIDENTAL USE
FIRE BARRIER
1 HR 45 MIN
HAZ./INCIDENTAL USE
SMOKE PARTITIONS
(SPRINKLERED)
NR-
RESIST
SMK
NR
SELF OR AUTO
CLOSING
SUBDIVIDING SPACES
SMOKE BARRIER (I-2 OCCUPANCY)
20 MIN
1/2
HR
1 HR
SUITE SEPARATION
SMOKE PARTITION
NR
*NR
SELF OR AUTO
CLOSING
EXIT ACCESS CORRIDORS (I-2)
SMOKE PARTITIONS (SPRINKLERED)
NR-
RESIST
SMK
NR
EXIT ACCESS CORRIDORS (B & AHC)
NON-RATED PARTITIONS
NR
NR
1 HR
VERT. OPG. (SHAFT)
FIRE BARRIER 60 MIN
1 HR
2 HR
60 MIN
90 MINEXIT PASSAGEWAY (HORIZ.)
FIRE BARRIER
6.1.14.4.1 19.1.3.5.1
7.2.4.1.3 (1) 19.1.3.8 19.2.2.5 7.1.3.2.1
19.3.1.1-8 8.6
8.7.1 19.3.2.1
8.5
8.4.2 19.2.5.7.1.4
8.4.2 19.3.6.2
21.3.6 35.3.6
19.3.1
7.2.6
8.2.1.3
8.6
19.2.2.7
8.6
19.3.2.1.2
19.3.7.3
7.2.1.4.1 7.2.4.3.7 8.3.4 19.2.2.5, 1-4
8.3.3.2.2 TBL
19.2.2.2
7.1.3.2 (9)
8.3.3.2.2 TBL
19.3.2.1.3
8.3.3.2.2 TBL
8.5.4 19.3.7.8
8.3.3.2.2 TBL
19.2.2.2.
8.3.3.2.2 TBL
8.3.3.2.2 TBL
8.3.3.2.2. TBL
8.7.1.3 8.4.3 19.3.2.1.3
19.3.6.3.2 8.4.3
19.3.6.3 8.4.3
N/A
FIRE
90 MIN
FIRE
90 MIN
FIRE
90 MIN
NOT
ALLOWED
UNLESS
SERVING
STAIR
ONLY
N/A
VARIES
SMOKE
90 MIN
VARIES
VARIES
NONE
N/A
NOT
ALLOWED
8.3.4.8 9.2.1
8.3.4.8 9.2.1
8.3.4.8 9.2.1 7.2.4.3.5
N/A
8.5.5.3 19.3.7.3(2)
8.6.4.5
N/A
N/A
8.4.4
8.4.4 8.4.6.2
8.4.4.1 8.4.6.2 19.3.6.4.2
N/A
BASEMENT KEY PLAN
D
SYMBOLS
NO. OCC. EXITING
(SMALLER ROOMS)
MAXIMUM OCCUPANCY
AREA
OCC. LOAD
FACTOR
FIRE ALARM CONTROL PANEL
FIRE SYSTEM ANNUNCIATOR ALARM
ANNUNCIATOR PANEL
FACP
FSA
FAA
REQ'D. EXIT WIDTH
NO. OF OCC. EXITING
ACTUAL EXIT
WIDTH
NO. OF OCC./
NO. OF EXITS
1:50
10/1
2"
34"
FEC
FP
PROPERTY LINE
STARTING
LOCATION
TRAVEL DISTANCE
TRAVEL PATH
FE
FIRE EXTINGUISHER CABINET
FIRE PULL STATION
FIRE EXTINGUISHER
NOTES
[A] DAMPERS ARE NOT REQUIRED IN DUCT PENETRATIONS OF
SMOKE BARRIERS WHERE HVAC SYSTEMS ARE FULLY DUCTED
(18.3.7.3x2)
[B] AIR TRANSFER OPENINGS IN SMOKE PARTITIONS SHALL
HAVE DAMPERS (NFPA 8.2.4.4.3) (IBC 710.7)
[C] SMOKE DAMPERS ARE NOT REQUIRED WHERE OPENINGS IN
DUCT ARE LIMITED TO A SINGLE SMOKE COMPARTMENT &
DUCTS ARE MADE OF STEEL (IBC 716.5.5)
[D] TRANSFER GRILLES REGARDLESS OF WHETHER THEY ARE
PROTECTED
ARE NOT ALLOWED IN THESE DOORS OR WALLS (NFPA 18.3.6.4)
TD = XX
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
117 PIERCE ST, SUITE 110
SIOUX CITY, IOWA 51101
712.252.4014
142 N. MOSLEY ST.
WICHITA, KANSAS 67202
316.262.2500
303 S. TOPEKA
WICHITA, KANSAS 67202
316.262.2691
LS001.4
CODE PLAN - BASEMENT AREA D
CORRECT FIRE & LIFE
SAFETY DEFICIENCIES -
LIFE SAFETY PLANS
800 HOSPITAL DRIVE COLUMBIA, MO 65201
01-31-2020
589A4-19-104
100% CONSTRUCTION DOCUMENTS
3/32" = 1'-0"
0 - BASEMENT - AREA D
HAZARDOUS AREAS IN FULLY
SPRINKLERED BUILDINGS ARE
NOT REQUIRED TO BE
PROTECTED BY FIRE BARRIERS.
COMPLIANCE NOTE
PER NFPA
3.9.3.2.1 &
8.7.1.1 (2)
BLDG. 1 - OCCUPANCY 3
BASEMENT = 158,877 S.F.
OCCUPANCY TYPE - BUSINESS
TYPE II (222) CONSTRUCTION
TOTAL OCCUPANTS 1060
FULLY SPRINKLERED
BUSINESS OCCUPANCY
OCCUPANCY LOAD FACTOR 150
158,877 / 150 = 1060 OCC.
COMPLIANCE NOTE PER NFPA
7.3.1.2
BLDG. 2 - OCCUPANCY 4
BASEMENT = 14,193 S.F.
OCCUPANCY TYPE - STORAGE
TYPE II (000) CONSTRUCTION
TOTAL OCCUPANTS 29
FULLY SPRINKLERED
STORAGE OCCUPANCY
OCCUPANCY LOAD FACTOR N/A
(USED OCC. GROSS / 500)
14,193 / 500 = 29 OCC.
JT
FEC
F E
C
FEC
F E
C
FEC
FE
F E
FIRE SPKLR.
PUMP RM.
D017
BOILER
D018
A/C SHOP
D019C
E.C.C. OFFICE
D019A
STORAGE
D019B
CONTROL
CTR.
D019D
CORR.
D019
SWITCH
GEAR RM.
D020
OFFICE
D024
TLT.
D019C
ST. LNGE.
C003A
OFFICE
C003B
TECH.
SUPERVISOR
OFFICE
C003C
TRANSFORMER
RM.
D…