This sources sought notice requests information from potential contractors to provide ceiling lifts and installation services at the Harry S. Truman Memorial Veterans Hospital in Columbia, Missouri. The notice specifies that seven ceiling lifts rated for 770 pounds of lifting capacity be provided with fast motion, continuous-charge rail systems, integrated scales, and emergency lowering capabilities. The contractor must complete all work within 365 calendar days of award, including installation, inspection, and training services. Interested service-disabled veteran-owned small businesses are requested to respond with capability statements by February 5, 2021 to be considered for the anticipated total small business set-aside contract.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Drawings-589-335 VOL 4 Architectural- 60 Pages.pdf | ||
| 36C25521Q0128.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GENERAL NOTES
DESIGN CRITERIA:
1. CODES AND STANDARDS:
2015 IBC
2. DESIGN GRAVITY LOADS:
DEAD LOADS:
FLOOR:
DEAD LOAD: 80 PSF
ROOF:
DEAD LOAD: 80 PSF
LIVE LOADS:
FLOOR:
LIVE LOAD: 40 PSF PATIENT ROOMS
100 PSF PUBLIC SPACES
100 PSF ROOF/FUTURE SECOND FLOOR
ROOF:
MINIMUM LIVE LOAD: 20 P.S.F. PLUS ALLOWANCE FOR DRIFTED SNOW
GROUND SNOW LOAD: Pg = 20 P.S.F.
SNOW EXPOSURE FACTOR: Ce = 0.9
SNOW LOAD IMPORTANCE FACTOR: 1.0
SNOW THERMAL FACTOR: Ct = 1.0
3. WIND LOAD:
BASIC WIND SPEED: 115 M.P.H.
RISK CATGEORY II
WIND LOAD IMPORTANCE FACTOR FOR WALLS 1.0
WIND EXPOSURE: B
BUILDING CATEGORY: ENCLOSED
WIND EXPOSURES:
COMPONENTS AND CLADDING WIND PRESSURES(PSF):
ZONE 1: +11, -27.0
ZONE 2: +10, -42
ZONE 3: +10, -63
ZONE 4: +14.5, -15.8
ZONE 5: +25, -36.0
FOR NORTH AND WEST WALLS. - ALL COMPONENTS TO BE DESIGNED FOR
+ 30.0 PSF MINIMUM WIND PRESSURE
INTERNAL PRESSURE COEFFICIENT: + 0.18
4. SEISMIC LOAD:
SPECTRAL ACCELERATIONS: Ss = 0.168
SPECTRAL ACCELERATIONS: S1 = 0.093
DESIGN SPECTRAL RESPONSE ACCELERATION: Sds = 0.134 DESIGN SPECTRAL RESPONSE ACCELERATION: Sd1 = 0.105
OCCUPANCY CATEGORY: III
SEISMIC DESIGN CATEGORY: B
SITE CLASS: C
SITE COEFFICIENTS:Fa = 1.22 Fv =1.7
5. COMPONENT IMPORTANCE FACTOR:
Ip = 1.5
6. BASIC STRUCTURAL SYSTEMS:
A.) FRAME SYSTEM.
7. SEISMIC - RESISTING SYSTEM:
A.) STEEL SYSTEM NOT SPECIFICALLY DETAILED FOR SEISMIC RESISTANCE.
R = 3 Cd = 3
B.) ANALYSIS PROCEDURE: EQUIVALANT LATERAL FORCE PROCEDURE
8. FUTURE EXPANSION:
PROVISIONS HAVE BEEN MADE FOR ONE ADDITIONAL FLOOR.
1. THE FOUNDATION HAS BEEN DESIGNED IN ACCORDANCE WITH THE RECOMMENDATIONS
MADE ON THE GEOTECHNICAL EXPLORATION REPORT BY: MIDWEST TESTING
ENGINEERING CONSULTING SERVICES, LTD. DATED: JUNE 15, 2017.
2. BACKFILLING:
A. DO NOT BACKFILL PIT WALLS UNTIL ADEQUATE TEMPORARY BRACING IS INSTALLED.
B. BACKFILL UNDER FOUNDATION WITH CONCRETE OR AS APPROVED BY THE
COR AND SUCCESSFULLY REVIEWED BY SOILS ENGINEER.
3. SOIL MODULUS OF SUBGRADE REACTION ( Ks ) = 125 POUNDS PER CUBIC INCH. THE
SUBGRADE MUST BE IMPROVED PER ONE OF THE OPTIONS OUTLINED IN THE
GEOTECHNICAL REPORT.
1. FOOTINGS SHALL BEAR ON SOIL CAPABLE OF SUSTAINING A NET BEARING PRESSURE
UNDER FULL SERVICE LIVE AND DEAD LOAD AS FOLLOWS:
3000 PSF FOR CONTINUOUS STRIP FOOTINGS
3000 PSF FOR COLUMN SPREAD FOOTINGS
2. TOP OF FOOTING ( TOF ) ELEVATIONS ARE SHOWN ON THE PLANS.
3. FOOTINGS MAY BE EARTH FORMED.
4. ALL BEARING MATERIAL SHALL BE INSPECTED BY A QUALIFIED TECHNICIAN AND
APPROVED BY THE COR PRIOR TO CONCRETE PLACEMENT. A QUALIFIED
TECHNICIAN SHALL PROVIDE HIS/HER RECOMMENDATION AS TO THE SUITABILITY
OF THE BEARING MATERIAL THAT REQUIRES VA/COR'S APPROVAL. FOOTING
ELEVATIONS SHALL BE ADJUSTED AS REQUIRED.
5. BOTTOM OF EXTERIOR FOOTINGS SHALL BEAR A MINIMUM OF 2'-6" BELOW FINAL
GRADE.
6. FROST DEPTH = 2'-6"
7. SLIDING RESISTANCE ( VALUES INCLUDE A 1.50 SAFETY FACTOR )
8. PASSIVE EQUIVALENT FLUID PRESSURE = 175 PCF.
9. COEFFICIENT OF FRICTION = 0.25
DESIGN:
FOUNDATIONS:
SPREAD FOOTINGS:
1. CONCRETE SHALL HAVE A 28-DAY COMPRESSIVE STRENGTH AND DENSITY, IN ACCORDANCE
WITH THE FOLLOWING:
STRENGTH DENSITY WATER/ SACKS OF CEMENT
P.S.I. P.C.F. CEMENT RATIO PER YARD
FILL SLABS & STAIR PAN FILL 3000 45 0.50 5 1/2 MINIMUM
SLABS ON METAL DECK: 3500 145 0.50 5 3/4 MINIMUM
ALL OTHER CONCRETE U.N.O: 4000 145 0.45 TO 0.48 6 MINIMUM
2. SLAB ON GRADE TO 1 1/2" MAXIMUM AGGREGATE SIZE. FOR 6" AND 10" SLABS PER
MANUFACTURER SPECIFICATION TO BE VA/COR APPROVED AFTER SUCCESSFUL REVIEW BY
ENGINEER.
3. REINFORCING SHALL CONFORM TO A.S.T.M. A615, GR. 60, INCLUDING TIES AND STIRRUPS.
4. WELDED WIRE FABRIC SHALL CONFORM TO A.S.T.M. A185.
5. ALL REINFORCING SHALL BE DETAILED, FABRICATED AND PLACED, IN ACCORDANCE WITH
LATEST A.C.I. DETAILING MANUAL (SP-66).
6. ALL REINFORCING SHALL BE SUPPORTED IN FORMS, SPACED WITH NECESSARY
ACCESSORIES AND SHALL BE SECURELY WIRED TOGETHER, IN ACCORDANCE WITH LATEST
C.R.S.I. "MANUAL OF STANDARD PRACTICE". DO NOT STICK DOWELS INTO WET CONCRETE.
TIE IN PLACE PRIOR TO START OF CONCRETE PLACEMENT.
7. MINIMUM CONCRETE COVER, UNLESS NOTED OTHERWISE:
A.) UNFORMED SURFACE IN CONTACT WITH THE GROUND: 3 IN.
B.) FORMED SURFACES EXPOSED TO EARTH OR WEATHER: 1 1/2 IN. FOR #5 BAR OR
SMALLER 2 IN FOR #6 BAR OR LARGER
C.) FORMED SURFACES NOT EXPOSED TO EARTH OR WEATHER:
1. WALLS, SLABS: 3/4 IN.
2. BEAMS, GIRDERS AND COLUMNS (TO TIES OR STIRRUPS): 1 1/2 IN.
8. ALL CONSTRUCTION JOINTS SHOWN ON DRAWINGS SHALL BE INCORPORATED INTO THE
STRUCTURE, UNLESS THEIR ELIMINATION IS APPROVED BY THE VA/COR AND AS SUCCESSFULLY
REVIEWED BY THE ENGINEER. ADDITIONAL CONSTRUCTION JOINTS, REQUIRED TO FACILITATE
CONSTRUCTION, SHALL BE LOCATED AT POINTS OF MINIMUM SHEAR AND SHALL BE DETAILED ON
SHOP DRAWINGS. REINFORCEMENT SHALL PASS CONTINUOUSLY THROUGH THE JOINT. ALL
CONSTRUCTION JOINTS SHALL BE ROUGHENED TO A DEPTH OF 1/4". FOR VERTICAL
CONSTRUCTION JOINTS IN BEAMS, SLABS, WALLS, ETC. IT IS ACCEPTABLE TO USE "STAYFORM".
9. ALL ABUTTING CONCRETE MEMBERS SHALL BE DOWELED TOGETHER, UNLESS POURED
MONOLITHICALLY. DOWELS SHALL BE EQUAL IN SIZE AND SPACING TO THE REINFORCING
IN THE ADJACENT MEMBER.
10. PROVIDE CONTINUOUS REINFORCEMENT AROUND CORNERS AND AT INTERSECTIONS AND
THROUGH: CONSTRUCTION JOINTS, CONTROL JOINTS, CONTRACTION JOINTS, AND JOINTS
BETWEEN ALL ABUTTING MEMBERS.
11. UNLESS OTHERWISE SHOWN IN THE ARCHITECTURAL DRAWINGS, PROVIDE 3/4" CHAMFERS
AT ALL EDGES THAT ARE EXPOSED TO VIEW IN THE FINISHED STRUCTURE.
12. SEE ARCHITECTURAL DRAWINGS FOR DOOR AND WINDOW OPENINGS, DRIP SLOTS,
REGLETS, MASONRY ANCHORS, PRECAST BEARING LEDGES, BRICK LEDGE ELEVATIONS
AND FOR MISCELLANEOUS EMBEDDED PLATES, BOLTS, ANCHORS, ANGLES, ETC.
13. REFER TO ARCHITECTURAL DRAWINGS FOR CONCRETE FINISHES. WHERE FINISH IS NOT
SPECIFIED, CONFORM TO REQUIREMENTS OF A.C.I. 301.
14. MECHANICAL, PLUMBING, AND ELECTRICAL DRAWINGS SHALL BE REFERRED TO FOR
DRAINS, SLEEVES, OUTLET BOXES, CONDUIT, ANCHORS, ETC. THE VARIOUS TRADES ARE
RESPONSIBLE FOR PLACING THEIR ITEMS.
15. LAP SPLICES SHALL BE IN ACCORDANCE WITH THE FOLLOWING TABLE, UNLESS NOTED
OTHERWISE. WHERE CLASSES ARE NOT CALLED OUT ON DRAWINGS, USE CLASS "B" SPLICES.
SPLICES f'c = 4000 P.S.I., fy = 60,000 P.S.I.
NOTES:
1. TABLES ARE BASED ON C.R.S.I. CATEGORIES 4 AND 6.
WHERE MIN. SPACING IS 6 BAR DIAMETERS CENTER
TO CENTER AND WHERE MIN. CONCRETE COVER IS
ONE BAR DIAMETER USE CATEGORY 6 FOR
LONGITUDINAL BARS IN BEAM, COLUMNS AND INNER
LAYER OF WALL OR SLABS; USE CATEGORY 4 FOR ALL
OTHER BARS.
2. ALL SPLICES TO BE CLASS "B" TENSION SPLICE UNLESS
OTHERWISE NOTED.
3. SPLICE PLAIN WELDED WIRE REINFORCEMENT BY
LAPPING ONE FULL MESH SPACE PLUS 2 INCHES.
4. FOR LIGHT WEIGHT CONCRETE, MULTIPLY LENGTHS IN
TABLE BY 1.3.
5. FOR EPOXY COATED REINFORCEMENT, MULTIPLY
LENGTHS IN TABLE BY 1.5.
16. REFER TO MECHANICAL DRAWINGS FOR HOUSEKEEPING PADS AND INERTIA BASES AT
MECHANICAL EQUIPMENT.
17. REFER TO MECHANICAL DRAWINGS FOR UNDERFLOOR AND PERIMETER FOUNDATION
DRAIN.
18. BASE PLATES, ANCHOR BOLTS, SUPPORT ANGLES, ETC., BELOW GRADE SHALL BE
COVERED WITH A MINIMUM OF 3" CONCRETE.
19. PROVIDE CONTINUOUS WATERSTOP AT HORIZONTAL AND VERTICAL JOINTS AT
ELEVATOR PIT
20. WHERE REINFORCING IS NOT INDICATED OR DEFINED, INCLUDE FOR BID PURPOSES
ONLY.
A.) WALLS: #5 EACH WAY EACH FACE. SPACING IN INCHES = 140/(WALL THICKNESS IN
INCHES BUT NOT OVER 18"o.c.
B.) BEAMS: 1-#9 CONTINUOUS TOP AND BOTTOM FOR EACH 100 SQUARE INCHES OF
BEAM CROSS SECTIONAL AREA AND #4 STIRRUPS SPACED AT 1/2 OF BEAM DEPTH,
FULL LENGTH OF BEAM.
C.) COLUMNS: 1-#9 VERTICAL PER 50 SQUARE INCHES OF CROSS SECTIONAL AREA
AND #3 TIES @ 9"o.c
D.) SLABS: #5 EACH WAY TOP AND BOTTOM. SPACING IN INCHES = 100/(SLAB THICKNESS
IN INCHES) BUT NOT OVER 18"o.c.
ON SHOP DRAWINGS, INDICATE ABOVE REINFORCING AS "PER GENERAL NOTES". SUCH
REINFORCING MAY BE REVISED OR RELOCATED BY THE VA/COR AND AS SUCCESSFULLY
REVIEWED BY STRUCTURAL ENGINEER DURING SHOP DRAWING REVIEW.
21. PROVIDE CONCRETE EQUIPMENT PADS, INERTIA BASES AND CURBS AS NOTED
ELSEWHERE IN CONTRACT DOCUMENTS. UNLESS NOTED, DOWEL PADS WITH #4 x 0'-6" PROJECTING 3" FROM CONCRETE BELOW AT 18"o.c. EACH WAY. REINFORCE PADS WITH
#4@18 EACH WAY TOP AND BOTTOM.
22. MASONRY DOWELS: PROVIDE, PLACE, AND SPACE TO MATCH MASONRY REINFORCING.
23. PROVIDE STANDARD HOOKS ON BARS TERMINATING AT A CONCRETE FACE UNLESS
NOTED (E.G.: EDGES OF OPENINGS, SLAB EDGES, EXPANSION JOINTS, ENDS OF BEAMS,
AND AT: TOP, BOTTOM AND ENDS OF WALLS, ETC...).
24. PROVIDE (2)-#5 (MIN.) @ EACH SIDE OF OPENING. EXTEND 2'-0 BEYOND OPENINGS.
25. SEE MISC. NOTES FOR EPOXY / ADHESIVE ANCHORS.
26. PROVIDE CONTROL JOINT IN FOUNDATION WALLS @ 30'-0" O.C. MAX.
TENSION LAP SPLICE FOR TOP BARS, * GRADE 60
CLASS A, B, LAP SPLICE LENGTH (INCHES)
f'c = 3,000 P.S.I.
CLASS
BAR SIZE
#3
#11 - 100
*"TOP BARS" ARE DEFINED AS ANY BAR WITH MORE THAN 12" OF
CONCRETE CAST BELOW THE BAR.
CATEGORY 6 4 6
A B A B
4 6 4 6
A B
4 6 4 6
21 14 18 13 16
28 19 24 17 22
35 23 30 21 27
42 28 36 25 33
38 4950 3333 4243 3930 39 38
43 5666 3744 4857 3339 4351
48 6383 4256 5572 3850 4965
#10 - 81 58 106 76 5070 6592 4563 5982
71 130 93 6286 80112 5577 72101
TENSION LAP SPLICE FOR ALL OTHER BARS, * GRADE 60
CLASS A, B, LAP SPLICE LENGTH (INCHES)
f'c=5,000P.S.I.
CLASS
4BAR SIZE
#3 - 13
#4 - 17
#5 - 21
#6 - 25
#7 - 30
#8 - 39
#9 - 49
#11 - 77
CATEGORY 6 4 6
A B A B
4 6 4 6
A B
4 6 4 6
16 12 16 12 16
22 15 19 13 17
27 18 23 16 21
32 22 28 19 25
29 3839 2526 3333 2323 30 29
33 4351 2934 3744 2630 3339
37 4864 3243 4256 2938 3850
#10 - 63 45 81 58 3954 5070 3549 4563
55 100 71 4867 6286 4360 5577
COMPRESSION LAP SCHD.
LAP LENGTH (INCHES)
f'c = 3,000 P.S.I. OR GREATER
BAR SIZE
#3 12
#4 15
#5 19
#6 23
#7 26
#8 30
#9 34
#11 42
30 db
#10 38
CONCRETE:
f'c=3,000P.S.I.
f'c = 4,000 P.S.I. f'c = 5,000 P.S.I.
f'c=4,000P.S.I.
- 16
#4 - 22
#5 - 27
#6 - 32
#7 - 39
#8 - 51
#9 - 64
CONCRETE CONT:
COMPRESSION DOWEL EMBEDMENT: 22 BAR DIAMETERS
STRUCTURAL STEEL:
1. STEEL SHALL CONFORM TO THE FOLLOWING GRADES:
ALL WF (U.N.O.): A992 GRADE 50 (FY=50)
ALL ANGLE, BASE PLATES, CONN. PLATES (U.N.O.): A36 (FY=36)
STRUCTURAL PIPE: A53 (FY=35)
STRUCTURAL TUBE: A500 GRADE B (FY=46)
HEADED STUDS AWS D1.1, TYPE B
THREADED ROD A36
ANCHOR ROD F1554,GR36 OR 55 PER DETAILS
BOLTS A325 / F1852
ELECTRODES MATCHING STRENGTH, 70KS: MIN.
2. ALL STRUCTURAL STEEL SHALL BE DETAILED, FABRICATED AND ERECTED IN
ACCORDANCE WITH THE A.I.S.C. CODE OF STANDARD PRACTICE (AISC 303-10),
EXCEPT AS MODIFIED IN THESE NOTES AND THE PROJECT SPECIFICATIONS.
3. CONNECTIONS MAY BE BOLTED OR WELDED. THE FABRICATOR IS RESPONSIBLE FOR
THE DESIGN, OF CONNECTIONS NOT DESIGNED ON THE DRAWINGS. GENERALLY,
CONNECTIONS SHOWN ON THE STRUCTURAL DRAWINGS ARE SCHEMATIC AND ARE
ONLY INTENDED TO SHOW THE RELATIONSHIP OF MEMBERS CONNECTED. ANY
CONNECTION THAT IS NOT SHOWN OR IS NOT COMPLETELY DETAILED ON THE STRUCTURAL
DRAWINGS SHALL BE DESIGNED BY AN ENGINEER, REGISTERED IN THE STATE OF MISSOURI,
RETAINED BY THE FABRICATOR. COMPLETELY DETAILED MEANS THE FOLLOWING INFORMATION IS
SHOWN ON THE DETAIL:
A. ALL PLATE DIMENSIONS AND GRADES.
B. ALL WELD SIZES, LENGTHS, PITCHES, AND RETURNS.
C. ALL HOLE SIZES AND SPACINGS.
D. NUMBER AND TYPES OF BOLTS: WHERE BOLTS ARE SHOWN BUT NO NUMBER
IS GIVEN, THE CONNECTION HAS NOT BEEN COMPLETELY DETAILED.
E. WHERE PARTIAL INFORMATION IS GIVEN, IT SHALL BE THE MINIMUM
REQUIREMENT FOR THE CONNECTION.
DESIGN CALCULATIONS FOR TYPICAL BEAM CONNECTIONS AND ALL PRIMARY BRACING AND
HANGER CONNECTIONS SHALL BE SUBMITTED TO THE VA/COR FOR APPROVAL ALONG WITH THE
ENGINEER'S SUCCESSFUL REVIEW PRIOR TO FABRICATION.
4. CONNECTION DESIGN FORCES:
A. BEAMS, GREATER OF:
1. 55% OF TOTAL ALLOWABLE UNIFORM LOAD CAPACITY FROM A.I.S.C 9TH
EDITION TABLES FOR ALLOWABLE LOADS ON BEAMS, Wc/L
2. REACTIONS SHOWN ON DRAWINGS.
3. 10 KIPS.
B. MOMENT CONNECTIONS INDICATED ON THE DRAWINGS THUS:
DESIGN FOR MOMENT SHOWN OR, IF NOT SHOWN, DEVELOP MOMENT
CAPACITY OF MEMBER WITH fb = 0.66FY.
C. MAINTAIN TENSION CAPACITY OF COLUMNS, DIAGONALS AND MEMBERS
SUBJECT TO TENSION AT BOLT HOLES, NOTCHES, OR COPES.
D. CONNECTION FORCE NOTATION:
P = AXIAL FORCE IN KIPS: (+) TENSION, (-) COMPRESSION
V OR [ ] = SHEAR IN KIPS
M = MOMENT IN FOOT KIPS
T = TORSION IN FOOT KIPs
1. LOADS SHOWN INCLUDE COMPENSATION FOR CODE PERMITTED
STRESS INCREASES AND LOAD REDUCTIONS FOR CONNECTION DESIGN.
5. THE MINIMUM PLATE THICKNESS SHALL BE 3/8".
6. BOLTED CONNECTIONS:
A. MINIMUM BOLT DIAMETER = 3/4"
B. SLIP CRITICAL CONNECTIONS OF A325SC OR A490SC BOLTS SHALL BE USED
FOR ALL BOLTED CONNECTIONS OF BRACING MEMBERS, MOMENT
CONNECTIONS, CANTILEVERS, AND AS SHOWN ON THE DRAWINGS. OVERSIZED
AND LONG-SLOTTED HOLES ARE ALLOWED FOR FRICTION CONNECTIONS.
C. ALL OTHER BOLTED CONNECTIONS SHALL BE BEARING TYPE USING A325N OR
A490N BOLTS. OVERSIZED HOLES AND LONG-SLOTTED HOLES ARE NOT
ALLOWED UNLESS SHOWN ON THE DRAWINGS.
D. A307 BOLTS MAY BE USED WHERE INDICATED ON THE DRAWINGS.
E. PROTRUDING BOLT HEADS, SHAFTS OR NUTS SHALL NOT EXTEND INTO NOR
PROHIBIT THE APPLICATION OF ARCHITECTURAL FINISHES AND THEY SHALL
NOT EXTEND INTO NOR PROHIBIT THE PLACEMENT OF STEEL DECKING TO THE
CORRECT LINE AND ELEVATION.
F. THE FABRICATOR IS RESPONSIBLE FOR VERIFYING THE TENSION CAPACITY OF
AXIALLY LOADED MEMBERS AFTER A SECTION IS REDUCED FOR BOLT HEADS.
MEMBER SIZE MAY BE INCREASED OR CONNECTION PLATES ADDED AS
REQUIRED.
G. SHOP DRAWINGS SHALL INDICATE THE TYPE OF BOLT USED IN EACH
TYPES.
7. WELDED CONNECTIONS:
A. WELDS ARE CONTINUOUS UNLESS NOTED.
B. ALL FILLET WELDS: A.I.S.C. MINIMUM BUT NOT LESS THAN 1/8" UNLESS NOTED OTHERWISE.
C. ALL WELDING SHALL BE IN ACCORDANCE WITH THE "STRUCTURAL
WELDING CODE" (A.W.S. D1.1) PUBLISHED BY THE AMERICAN WELDING SOCIETY.
ELECTRODES FOR WELDING SHALL COMPLY WITH THE REQUIREMENTS
OF TABLE 3.1 OF (A.W.S. D1.1-10).
D. ALL GROOVE WELDS SHALL BE COMPLETE PENETRATION UNLESS NOTED OTHERWISE.
8. SPLICING OF STEEL MEMBERS, UNLESS SHOWN ON THE DRAWINGS, IS PROHIBITED
WITHOUT WRITTEN APPROVAL BY THE VA/COR AND AS SUCCESSFULLY REVIEWED BY
THE STRUCTURAL ENGINEER.
9. NO CHANGE IN SIZE OR POSITION OF THE STRUCTURAL ELEMENTS SHALL BE MADE OF
HOLES, SLOTS, CUTS, ETC., AND ARE NOT PERMITTED THROUGH ANY MEMBER UNLESS
THEY ARE DETAILED ON THE APPROVED SHOP DRAWINGS.
10. NO FINAL BOLTING OR WELDING SHALL BE MADE UNTIL AS MUCH OF THE STRUCTURE
HAS BEEN PROPERLY ALIGNED AND WILL THEREBY BE STIFFENED.
11. UNLESS NOTED OTHERWISE, BEAMS SHALL BEAR 8" MINIMUM ON CONCRETE OR
MASONRY. ANCHOR BEAMS TO MASONRY WITH A GOVERNMENT-TYPE ANCHOR.
12. FABRICATE ALL BEAMS WITH THE MILL CAMBER UP.
13. EXPANSION BOLTS:
UNLESS NOTED OTHERWISE, EXPANSION BOLTS SHALL HAVE THE FOLLOWING
MINIMUM ULTIMATE LOAD CAPACITIES WHEN DRILLED INTO CONCRETE WITH A
MINIMUM DESIGN STRENGTH OF 4000 P.S.I. ULTIMATE LOAD CAPACITIES SHALL
PROVIDE FOR A MINIMUM FACTOR OF SAFETY = 4.
DIAMETER SHEAR TENSION EFFECTIVE EMBEDMENT
1/2" 3570 LBS. 4040 LBS 3 1/4"
3/4" 7635 LBS 5075 LBS 3 3/4"
SEE SPECIFICATIONS
14. SHEAR STUDS: CONFORM TO A.W.S. D1.1-2010, SHOP WELD EXCEPT WHERE APPLIED
THROUGH METAL DECK.
15. TESTING OF EXPANSION BOLTS AND EPOXY ANCHORS.
A. EXPANSION BOLTS: THE CONTRACTOR SHALL TEST 25% OF ALL EXPANSION
BOLTS ACCORDING TO THE MANUFACTURER'S REQUIRED TORQUES.
B. EPOXY ANCHORS: THE CONTRACTOR SHALL TEST 25% OF ALL EPOXY ANCHORS
WITH PULL TEST EQUAL TO 150% TIMES THE ALLOWABLE BOLT TENSILE
CAPACITIES.
C. NOTE: THE EPOXY ANCHORS ARE TO BE STORED IN A COOL LOCATION
ACCORDING TO THE MANUFACTURES SPECIFICATIONS.
ADDITIONAL ADDL.
ALUMINUM ALUM.
ANCHOR BOLT A.B.
AND &
ANGLE L
ARCHITECTURAL ARCH.
AT @
BASEMENT BSMT.
BASE PLATE B. P.
BEAM BM.
BEARING BRG.
BETWEEN BETWN.
BLOCK BLK.
BOARD BD
BOTTOM BOT.
BOTTOM FACE B/FACE
BOTTOM OF METAL DECK BOD
BOTTOM OF FOOTING BOF
BOTTOM OF WALL BOW
BRICK BRK.
BRICK SHELF B/S
BRIDGING BRDG.
BUILDING BLDG.
CANTILEVER CANTL.
CAST IN PLACE C.I.P.
CEILING CLG.
CEMENT CEM.
CENTER LINE CL.
CENTER TO CENTER C/C
CENTERED CTR'D.
CLEAR CL. or CLR.
CONCRETE CONC
COLUMN COL.
CONNECTION CONN.
CONSTRUCTION CONST.
CONSTRUCTION JOINT C.J.
CONTINUOUS CONT.
CONTRACTOR CONTR.
CONTRACTING OFFICER CO
CONTRACTING OFFICER REPRESENTITIVE COR
DEAD LOAD D.L.
DECK DK.
DIAGONAL DIAG.
DIAMETER DIA.
DIMENSION DIM.
DOWELS DWLS.
DOWN DN.
DRAWINGS DWGS.
EACH EA.
EACH FACE E.F.
EACH WAY E.W.
ELECTRICAL ELECT.
ELEVATION EL.
ELEVATOR ELEV.
EMBEDDED EMBE'D.
EQUAL EQ
EQUIPMENT EQUIP.
EXISTING EXIST.
EXPANSION JOINT E.J.
EXTERIOR EXT.
FAR FACE F.F.
FINISH FIN.
FINISH FLOOR FIN. FLR.
FLOOR FL.
FOOTING FTG.
FOUNDATION FND.
FRAMING FRMG.
GALVANIZED GALV.
GAUGE GA.
GENERAL CONTRACTOR G.C.
GIRDER GIR.
GRADE GR.
GYPSUM GYP.
HEIGHT HT.
HIGH POINT H.P.
HORIZONTAL HORIZ.
INSIDE FACE I.F.
INTERIOR INT.
JOINT JT.or JNT.
JOIST JST.
STRUCTURAL ABBREVIATIONS:
KIP = 1000 lbs. K
KNOCKOUT KO
POUND lb.
LIGHT WEIGHT LT. WT.
LIVE LOAD L.L.
LONG LG.
LONGITUDINAL LONG.
LONG LEG HORIZONTAL L.L.H.
LONG LEG VERTICAL L.L.V.
LONG WAY L.W.
LOW POINT L.P.
MANUFACTURER MFG.
MARK MK.
MASONRY MAS.
MASONRY OPENING M.O.
MATERIAL MAT'L
MAXIMUM MAX.
MECHANICAL MECH
METAL MTL.
MINIMUM MIN.
MISCELLANEOUS MISC.
MOMENT CONNECTION M.C.
NEAR FACE N.F.
NOMINAL NOM.
NOT IN CONTRACT N.I.C.
NOT TO SCALE N.T.S.
ON CENTER O.C.
OPENING OPNG .
OPPOSITE HAND OPP.H.
OUTSIDE FACE O.F.
PANEL PNL.
PENTHOUSE P.H.
PLATE PL.
PLUMBING PLBG
PRECAST CONCRETE P.C.
PRE-ENGINEERED METAL BUILDING PEMB
POCKET PCK'T.
POST TENSION P.T.
RADIUS RAD.
RECTANGULAR RECT.
REFERENCE REF.
REFER TO RE:
REINFORCING REINF.
REQUIRED REQ'D
REVISION REV.
ROOF RF.
ROOM RM
SCHEDULE SCHD.
SECTION SECT.
SHORT WAY S.W.
SIMILAR SIM.
SLAB SL.
SLAB ON GRADE SOG
SPACE, SPACING, SPACES SPA.
SPECIFICATIONS SPECS
SQUARE SQ.
STANDARD STD.
STEEL STL.
STRUCTURE OR STRUCTURAL STRUC
SUPPORT SUPPT.
SYMMETRICAL SYMM.
THICKNESS THK.
TOP FACE T.FACE
TOP OF BRICK LEDGE T/BL
TOP OF FOOTING TOF
TOP OF CONCRETE TOC
TOP OF PIER TOP
TOP OF JOIST T/JST
TOP OF SLAB TSL
TOP OF STRUCTURAL STEEL TOS
TOP OF WALL TOW
TRUSS BEARING T/BRG.
TYPICAL TYP.
UNLESS NOTED OTHERWISE U.N.O.
VERTICAL VERT
VERIFY IN FIELD VIF
VERTICAL BRACE VB
WIND BRACE W.B.
WELDED WIRE FABRIC W.W.F.
WITH W/
1. METAL ROOF DECK SHALL COMPLY WITH THE REQUIREMENTS OF ANSI/SDI RD-2010
STANDARD FOR STEEL ROOF DECK.
2. PROJECT SPECIFICATIONS SEE PLANS FOR DECK TYPES AND GAUGES. METAL ROOF
DECK HAS BEEN DESIGNED TO FUNCTION AS A DIAPHRAGM FOR THE TRANSMISSION
OF LATERAL LOADS. CONNECTION OF DECK UNITS TO EACH OTHER AND TO
SUPPORTS SHALL BE DESIGNED BY THE DECK SUPPLIER CONSISTENT WITH THE
DECK PROPERTIES AND MANUFACTURER'S RECOMMENDATIONS.
3. LAP DECK 4" MINIMUM AT SPLICES CENTERED ON SUPPORT.
4. DO NOT SUSPEND POINT LOADS FROM DECK INCLUDING HANGERS FOR: CEILINGS,
PIPES, DUCTS, EQUIPMENT, ETC... CONTRACTOR INSTALLING SUCH POINT LOADS
SHALL PROVIDE SUB-FRAMING TO TRANSFER LOAD TO STRUCTURE SUPPORTING
DECK.
5. FABRICATE DECK UNITS IN LENGTHS TO SPAN THREE OR MORE SUPPORT SPACINGS.
6. MINIMUM YIELD STRENGTH = 33 K.S.I.
7. 1 1/2" DEEP (WIDE RIB DECK) AND ROLLED OF STEEL SHEETS CONFORMING TO
A.S.T.M. 7. A653 GRADE NO METAL ROOF DECK SHALL HAVE SECTION PROPERTIES
PER FOOT OF WIDTH LESS THAN THE FOLLOWING:
18 GAUGE I .292 INCH(4), S (POSITIVE) .318 INCH(3), S (NEGATIVE) .327 INCH(3)
20 GAUGE I .212 INCH(4), S (POSITIVE) .234 INCH(3), S (NEGATIVE) .247 INCH(3)
22 GAUGE I .169 INCH(4), S (POSITIVE) .186 INCH(3), S (NEGATIVE) .192 INCH(3)
8. DECKING MANUFACTURER SHALL COORDINATE SIZE AND LOCATION OF ROOF
OPENINGS WITH ARCHITECTURAL AND MECHANICAL DRAWINGS.
METAL ROOF DECK:
1. THE CONTRACTOR SHALL PLACE CONCRETE FOR SLABS SO THAT THE FINISH SURFACE IS
SCREEDED LEVEL WITH AN ELEVATION WITHIN 1/4" OF THE TOP OF SLAB ELEVATION
SHOWN ON THE PLANS.
2. SLABS SHALL HAVE A TROWELED FINISH AND AS A MINIMUM BE TRUE PLANES WITHIN 1/2"
IN 10 FEET , AS DETERMINED BY A 10 FOOT STRAIGHTEDGE PLACED ANYWHERE ON THE
SLAB IN ANY DIRECTION.
3. CONSIDERATION SHALL BE GIVEN TO SEQUENCING OF CONCRETE PLACEMENT SO AS
TO CONTROL FINISH ELEVATIONS WITHIN THE SPECIFIED LIMITS. NO MORE THAN 1/2"
OF ADDITIONAL CONCRETE THICKNESS SHALL BE POURED TO MAINTAIN FLOOR
FLATNESS OR LEVELNESS. IF SUCH A SITUATION OCCURS G.C. SHALL STOP POUR,
LET DECK HARDEN AND FINISH WITH A TOPPING SLAB.
CONCRETE SLABS ON METAL DECK:
1. DEPTH OF DECK AND SLAB, TYPE OF DECK, STEEL GAUGES AND SLAB REINFORCING ARE
SHOWN ON THE PLANS.
2. UNLESS NOTED OTHERWISE, TEMPORARY SHORING OF COMPOSITE DECK IS NOT REQUIRED
FOR ANTICIPATED CONSTRUCTION LOAD (WET CONCRETE WEIGHT PLUS 20 P.S.F.
CONSTRUCTION LOAD). SEE SPECIFICATIONS FOR DEFLECTION LIMITATION.
3. CONTRACTOR SHALL FURNISH THE ADDITIONAL CONCRETE DUE TO WET CONCRETE
DEFLECTION OF THE COMPOSITE DECK AND BEAMS.
4. THE DECK ACTING COMPOSITELY WITH THE SLAB, SHALL BE CAPABLE OF SUPPORTING BOTH
THE FINAL DESIGN LIVE LOAD AND SUPERIMPOSED DEAD LOAD SPECIFIED ON THESE
DRAWINGS NO METAL FLOOR DECK USED IN THE BUILDING SHALL HAVE SECTION PROPERTIES
PER FOOT OF WIDTH LESS THAN THE FOLLOWING:
18 GAUGE I .557 INCH(4), S (POSITIVE) .495 INCH(3), S (NEGATIVE) .504 INCH(3
20 GAUGE I .409 INCH(4), S (POSITIVE) .341 INCH(3), S (NEGATIVE) .346 INCH(3)
6. CONTRACTOR SHALL COORDINATE SIZE AND LOCATION OF FLOOR AND ROOF OPENINGS WITH
ARCHITECTURAL AND MECHANICAL DRAWINGS.
7. WELD STUDS THROUGH METAL DECK.
8. ELECTRICAL CONDUIT SHALL BE ROUTED BELOW METAL DECK. NO CONDUIT, PIPING, JUNCTION
BOXES, OR OTHER ITEMS SHALL BE ALLOWED TO BE EMBEDDED IN CONCRETE SLAB.
9. DECK SUPPLIER TO PROVIDE DECK CLOSURE WHERE REQUIRED FOR CONCRETE POUR.
10. COMPOSITE DECK SHALL COMPLY WITH ANSI/SDI C-2011 STANDARD FOR COMPOSITE STEEL
FLOOR DECK-SLABS.
COMPOSITE METAL DECK:
1. NOTES APPLY TO MASONRY SHOWN ON STRUCTURAL DRAWINGS AND SHALL BE THE
MINIMUM REQUIREMENTS FOR MASONRY SHOWN ON THE ARCHITECTURAL DRAWINGS.
2. CONCRETE MASONRY:
A. COMPRESSIVE STRENGTH OF MASONRY, PRISM STRENGTH F'm = 2000
P.S.I. (MINIMUM) COMPRESSIVE STRENGTH OF CMU=2800 PSI).
B. CONCRETE MASONRY UNITS: A.S.T.M. C90, GRADE N, TYPE 1 - 2 CELL UNITS
LIGHTWEIGHT UNITS FOR INTERIOR WALLS.
REGULAR WEIGHT UNITS FOR EXTERIOR WALLS.
C. GROUT: A.S.T.M. C476-02
STRENGTH AT 28 DAYS = 125% OF F'm, 2500 P.S.I. MINIMUM.
D. MORTAR: A.S.T.M. C270-03
TYPE - S, HYDRATED LIME REQUIRED
3. REINFORCED MASONRY REQUIRES CONTINUOUS SPECIAL INSPECTION - SEE
SHEET S-002
4. REINFORCING: BARS SHALL CONFORM TO A.S.T.M. A615, GRADE 60, UNLESS NOTED ON
DRAWINGS. WIRES SHALL CONFORM TO A.S.T.M. A82
5. DOWELS FROM C.I.P. CONCRETE SHALL MATCH THE VERTICAL REINFORCEMENT IN THE
WALL ABOVE UNLESS NOTED OTHERWISE AND LAPPED BOTH ENDS. SUCH DOWELS SHALL
BE FURNISHED BY THE CONCRETE CONTRACTOR.
6. WHEN A FOUNDATION DOWEL DOES NOT LINE UP WITH A VERTICAL BLOCK CORE, IT
SHALL NOT BE SLOPED MORE THAN ONE HORIZONTAL IN 6 VERTICAL. DOWELS MAY BE
GROUTED INTO A CELL IN VERTICAL ALIGNMENT, EVEN THOUGH IT IS IN AN ADJACENT
CELL TO THE VERTICAL WALL REINFORCING.
7. SPLICED REINFORCING SHALL BE LAPPED AS NOTED BELOW. SPLICED BARS SHALL BE
WIRED TOGETHER.
#5 BARS, USE 3'-0" LAP
#6 BARS, USE 4'-6" LAP
#7 BARS, USE 5'-3" LAP
8. VERTICAL BARS SHALL BE HELD IN POSITION AT TOP AND BOTTOM AND AT INTERVALS
NOT EXCEEDING 72 DIAMETERS OF THE REINFORCING.
9. VERTICAL REINFORCING BARS SHALL HAVE A MINIMUM CLEARANCE OF 3/4 OF AN INCH
FROM THE MASONRY OR ADJACENT BARS AND NOT LESS THAN ONE BAR DIAMETER
BETWEEN BARS NOT SPLICED.
10. VERTICAL GROUTING MAY BE EITHER "LOW LIFT" OR "HIGH LIFT" AT THE CONTRACTOR'S
OPTION.
11. VERTICAL CELLS THAT WILL BE GROUTED SHALL HAVE VERTICAL ALIGNMENT TO
MAINTAIN A CONTINUOUS UNOBSTRUCTED CELL AREA NOT LESS THAN 2" x 3".
12. GROUTING SHALL BE STOPPED 1/2" BELOW THE TOP OF A COURSE SO AS TO FORM A KEY
AT THE POUR JOINT.
13. GROUTING OF MASONRY BEAMS OVER OPENINGS SHALL BE DONE IN ONE CONTINUOUS
OPERATION.
14. ALL BOLTS, ANCHORS, ETC., INSERTED IN THE WALLS, SHALL BE GROUTED SOLID INTO
POSITION.
15. ALL HORIZONTAL REINFORCING (JOINT REINFORCING AND REBAR) SHALL STOP AT
CONTROL JOINTS.
16. REFER TO ARCHITECTURAL DRAWINGS FOR LOCATIONS AND DETAILS OF DOOR AND
WINDOW OPENINGS FOR SPECIAL COURSING AND OTHER MASONRY DETAILS. THE
INFORMATION SHOWN ON THE STRUCTURAL DRAWINGS IS INTENDED TO DEFINE THE
STRUCTURAL REQUIREMENT ONLY.
17. MINIMUM WALL REINFORCING UNLESS NOTED OTHERWISE:
NOMINAL WALL VERTICAL HORIZONTAL JOINT BOND BEAM
THICKNESS REINFORCING WIRE REINFORCING REINFORCING
6" #5@32" OC 9 GA. E.F. @ 16 (2)-#5
8" #5@24" OC 9 GA. E.F. @ 16 (2)-#5
10" #6@24" OC 3/16 DIA. @ 16 (2)-#5
12" #5@16" OC 3/16 DIA. @ 16 (2)-#5
PROVIDE BOND BEAMS AT: BASE OF WALL, SILL LINES, BOTTOM EDGE OF OPENINGS
(EXTEND MINIMUM OF 2'-0" PAST OPENING), TOP OF WALLS, FLOOR LINES, ROOF LINES,
TOP OF PARAPETS, AND AT 10'-0"o.c. MAXIMUM BETWEEN BOND BEAMS. BOND BEAM
SHALL BE CONTINUOUS UNLESS NOTED OTHERWISE.
HORIZONTAL JOINT REINFORCING: WIRE LADDER TYPE.
18. PROVIDE VERTICAL WALL REINFORCING, SAME SIZE AS ADJACENT BAR, AT: CORNERS,
ENDS, JAMBS, EACH SIDE OF OPENING, AND EACH SIDE OF CONTROL AND EXPANSION
JOINTS.
19. CONTINUE VERTICAL REINFORCING FLOOR TO FLOOR (OR ROOF) AND EXTEND TO TOP OF
PARAPET.
20. CONTINUE REINFORCING THROUGH CONSTRUCTION JOINTS, AND AROUND CORNERS
UNLESS NOTED OTHERWISE.
21. PROVIDE STANDARD HOOKS ON BARS TERMINATING INTO MASONRY FACE: - IN WALLS AT
OPENINGS, HEADS, JAMBS, EXPANSION JOINTS, ENDS; - IN BEAMS AT TOP, BOTTOM, AND
ENDS.
22. SPLICE CONTINUOUS TOP BARS AT MID SPAN AND BOTTOM BARS OVER SUPPORT.
23. COORDINATE BLOCKOUTS, REVEALS, HOLES, OPENINGS, AND BUILT IN ITEMS WITH ALL
CONTRACT DOCUMENTS AND TRADES.
24. GROUT CELLS SOLID AT: REINFORCING, BOND BEAMS, INSERTS, ANCHORS, ELEVATOR
GUIDE RAILS, AND 24" BELOW BEARING POINT OF STEEL SECTIONS AND 12" TO EACH SIDE.
REINFORCED MASONRY:
1. ALL SIZING BASED ON STEEL STUD MANUFACTURERS ASSOCIATION (ICBO ER-4943P)
PRODUCT TECHNICAL INFORMATION.
2. AT NORTH AND WEST WALLS, STUD SPACING IS 16" MAX AND STUD THICKNESS IS 16 GA MIN
3 MATERIALS SHALL CONFORM TO THE FOLLOWING:
A. GALVANIZED MATERIAL:
1. ALL GALVANIZED STUDS 12, 14 AND 16 GAUGE (97, 68 AND 54 MIL) SHALL
BE FORMED FROM STEEL THAT CORRESPONDS TO THE MINIMUM REQUIREMENTS
OF ASTM A653 SS, GRADE 50, CLASS 1 OR 3 WITH A MINIMUM YIELD OF 50,000 PSI.
2. ALL GALVANIZED 18 AND 20 GAUGE (43 AND 33 MIL) STUDS; ALL GALVANIZED TRACK,
BRIDGING, END CLOSURES AND ACCESSORIES SHALL BE FORMED FROM STEEL THAT
CORRESPONDS TO THE REQUIREMENTS OF ASTM A653 SS, GRADE 33 WITH A
MINIMUM YIELD OF 33,000 PSI.
3. ALL GALVANIZED STUDS, TRACK, BRIDGING AND ACCESSORIES SHALL BE FORMED
FROM STEEL HAVING A GALVANIZED COATING MEETING THE REQUIREMENTS OF ASTM
A525.
B. PROPERTIES:
1. THE PHYSICAL AND STRUCTURAL PROPERTIES LISTED BY THE STEEL
STUD MANUFACTURER ASSOCIATION AND AISI DESIGN MANUAL SHALL
BE CONSIDERED THE MINIMUM PERMITTED FOR ALL FRAMING MEMBERS.
C. SUBSTITUTIONS:
1. ANY SUBSTITUTIONS MUST BE APPROVED IN WRITING PRIOR TO
DELIVERY, BY THE COR.
4. INSTALLATION OF STUDS SHALL BE AS PER ASTM C1007-00 "INSTALLATION OF LOAD
BEARING (TRANSVERSE AND AXIAL) STEEL STUDS AND ACCESSORIES", ASTM C955-00a
"SPECIFICATION FOR LOAD BEARING (TRANSVERSE AND AXIAL) STEEL STUDS, RUNNERS
TRACK), AND BRACING OR BRIDGING FOR SCREW APPLICATION OF GYPSUM BOARD AND
METAL PLASTER BASES", AND ASTM C754-00 "SPECIFICATION FOR INSTALLATION OF STEEL
FRAMING MEMBERS TO RECEIVE SCREW ATTACHED GYPSUM BOARD".
5. ALL FRAMING COMPONENTS SHALL BE CUT SQUARELY FOR ATTACHMENT TO
PERPENDICULAR MEMBERS, OR AS REQUIRED FOR AN ANGULAR FIT AGAINST ABUTTING
MEMBERS. MEMBERS SHALL BE HELD POSITIVELY IN PLACE UNTIL PROPERLY FASTENED.
6. ALL TRACK BUTT JOINTS, ABUTTING PIECES OF TRACK SHALL BE SECURELY ANCHORED
TO A COMMON STRUCTURAL ELEMENT, OR THEY SHALL BE BUTT-WELDED OR SPLICED
TOGETHER.
7. ALL STUD BRIDGING SHALL BE ATTACHED IN A MANNER TO PREVENT STUD ROTATION.
BRIDGING ROWS SHALL BE SPACED ACCORDING TO MANUFACTURE'S
RECOMMENDATION.
8. TEMPORARY BRACING SHALL BE PROVIDED UNTIL ERECTION IS COMPLETED.
9. STUD ENDS MUST BE SQUARELY SEATED AGAINST THE TRACK WEB. BOTH STUD FLANGES
MUST BE ATTACHED TO TRACK MEMBERS AT TOP AND BOTTOM.
10. STUD BRIDGING SHALL BE PROVIDED BY 1-1/2" COLD ROLLED U-CHANNEL. THE U-
CHANNEL MUST BE ATTACHED TO EACH STUD BY WELDING OR ATTACHING WITH CLIP
ANGLES AND SCREWS. HORIZONTAL STRAPPING AND SOLID BRIDGING WITH TRACK
MEMBERS CAN ALSO BE USED FOR BRIDGING.
THE FOLLOWING MINIMUM COLD FORMED STEEL ATTACHMENTS SHALL BE PROVIDED
U.N.O.:
TRACK TO STUD-----------------(1) - #10 TEK SCREW EACH FLANGE, EACH STUD
TRACK TO STRUCTURAL STEEL-----(1) - .145" DIA. POWER DRIVEN FASTENER @ 2'-8" O.C.
TRACK TO CONCRETE-------------(1) - .145" DIA. POWER DRIVEN FASTENER @ 16" O.C.
TRACK TO METAL DECK----------(1) - #10 TEK SCREW @ 1'-4" O.C.
TRACK TO MASONRY------------(1) - .145" DIA. POWER DRIVEN FASTENER @ 2'-8" O.C.
STUD TO STRUCTURAL STEEL------(1) - L2x 2x - 14 GA. CLIP ANGLE CONNECTION W/ (3) - #10
TEK SCREWS INTO METAL STUD AND (3) - .145" DIA. POWER DRIVEN FASTENERS INTO
STRUCTURAL STEEL OR (3) 1/4" TEK SCREWS INTO STRUCTURAL STEEL.
600 S 162 54
COLD-FORMED STEEL:
MEMBER DEPTH:
(EXAMPLE: 6" =
600 x 1/100 INCHES)
ALL MEMBER DEPTHS
ARE TAKEN IN 1/100 INCHES.
STYLE:
S = STUD OR JOIST SECTION
T = TRACK SECTIONS
FLANGE WIDTH:
(EXAMPLE: 1 5/8" = 1.625" =
162 x 1/100 INCHES)
ALL FLANGE WIDTHS
ARE TAKEN IN 1/100 INCHES.
MATERIAL THICKNESS:
(EXAMPLE: 0.054" = 54 MILS.
1MIL = 1/1000 INCH)
Engineering, Inc.
18207 Edison Avenue
Chesterfield, Missouri 63005
Phone: 636.530.7770 Fax: 636.530.7877
Missouri Certificate of Authority #NC 001244
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
BANCROFT ARCHITECTS + ENGINEERS Bancroft AE No.
700 Nicholas Blvd. Suite 300 Elk Grove Village, IL 60007
T:847.952.9362 www.bancroft-ae.com Department of Veterans Affairs
VA CONTRACT NO.
Revisions: Date
KEY PLAN:
N
18207 Edison Avenue Chesterfield, MO 63005 T (636) 530-7770 F (636) 530-7877 MO. Certificate of Authority #NC 001244
C :\U se r s
\jh of fm an n\ D oc um en ts
\2
3 7
_V A
C -C
LC
_R
1 5 _S
T R
U C
_j ho f fm an nU C
JP
Q
.r v t
5/ 7/
1 8
:3
5:
P M
STRUCTURAL GENERAL NOTES
16-123
HARRY S. TRUMAN VAMC
RELOCATE CLC
800 HOSPITAL DRIVE COLUMBIA, MO
05/11/18 MVV JMH
589-335
S-001
BID DOCUMENTS
VA255-16-C-0234
BID DOCUMENTS 05/11/18
05-11-1805-11-18
SPECIAL INSPECTION:
1. PERIODIC INSPECTION OF STEEL FABRICATOR'S SHOP FOR QUALITY CONTROL AND
FABRICATION PROCESSES THAT COMPLY WITH AISC CODE OF STANDARD PRACTICE.
2. PERIODIC INSPECTION OF BOLTED AND WELDED STEEL CONNECTIONS IN THE FIELD PER
AISC 360-10 CHAPTER N.
3. CONTINUOUS INSPECTION OF BOLTED AND WELDED STEEL CONNECTIONS IN THE FIELD
PER AISC 360-10 CHAPTER N FOR ALL THAT IS PART OF THE SEISMIC RESISTING SYSTEM.
4. PERIODIC INSPECTION OF CONCRETE MATERIALS, REINFORCING AND PLACEMENT SHALL
BE INSPECTED PER TABLE 1705.3 OF THE 2015 INTERNATIONAL BUILDING CODE.
5. PERIODIC INSPECTION OF MASONRY MATERIALS, REINFORCING & PLACEMENT SHALL BE
INSPECTED PER TABLE 4 AND TABLE 5 OF THE TMS 602-11.
6. INSPECTION OF SITE SOILS, FILL PLACEMENT, AND BEARING CAPACITIES BY A LICENSED
GEOTECHNICAL ENGINEER AS FOLLOWS:
A. OBSERVATION OF PROOF ROLLING FOR THE SITE PRIOR TO FILL PLACEMENT.
COMPACTION TESTING OF STRUCTURAL FILL PLACEMENT. LIFTS SHALL NOT
EXCEED 8".
B. COMPACT STRUCTURAL FILL TO 95% DRY DENSITY AS MEASURED BY THE
STANDARD PROCTOR METHOD, ASTM D-698.
C. PROVIDE BEARING TESTS AT EACH FOOTING LOCATION TO CONFIRM BEARING
CAPACITY.
7. PERIODIC SPECIAL INSPECTION IS REQUIRED DURING ALL WELDING OPERATIONS OF
ELEMENTS OF THE SEISMIC-FORCE-RESISTING SYSTEM.
8. SPECIAL INSPECTION IS NOT A SUBSTITUTE FOR INSPECTION BY A CITY/COUNTY
INSPECTOR OR THE COR.
9. SPECIAL INSPECTED WORK WHICH IS INSTALLED OR COVERED WITHOUT APPROVAL OF
LOCAL AND SPECIAL INSPECTORS ALONG WITH THE COR IS SUBJECT TO REMOVAL OR
EXPOSURE.
10. CONTRACTOR IS RESPONSIBLE FOR HIRING ALL SPECIAL INSPECTORS.
11. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO INFORM THE VA/COR AND THE
SPECIAL INSPECTOR OR INSPECTION AGENCY AT LEAST ONE WORKING DAY PRIOR TO
PERFORMING ANY WORK THAT REQUIRES SPECIAL INSPECTION. ANY WORK
PERFORMED WITHOUT REQUIRED SPECIAL INSPECTION IS SUBJECT TO REMOVAL.
12. SUBMIT WRITTEN REPORTS WITHIN TWO DAYS OF TESTING TO THE COR AND THE
ENGINEER OF RECORD.
13. DECK SHALL COMPLY WITH ANSI/SDI QA/QC STANDARD FOR QUALITY CONTROL AND
QUALITY ASSURANCE FOR INSTALLATION OF STEEL DECK.
TYPE
CONTINUOUS
SPECIAL
INSPECTION
PERIODIC
SPECIAL
INSPECTION
REFERENCED STANDARD IBC REFERENCE
1. INSPECTION REINFORCEMENT, AND VERIFYING PLACEMENT.
ASTM C 172
ASTM C 31
ACI 318: 26.4.5, 26.12
1908.10
ACI 318: 26.4.5
REQUIRED VERIFICATION AND INSPECTION OF CONCRETE CONSTRUCTION
ACI 318 Ch. 20, 25.2, 25.3 26.5.1-26.5.3
1908.4
2. REINFORCING BAR WELDING:
a. VERIFY WELDABILITY OF REINFORCING BARS OTHER THAN
ASTM A706;
b. INSPECT SINGLE-PASS FILLET WELDS, MAXIMUM 5/16"; AND
c. INSPECT ALL OTHER WELDS.
AWS D1.4
ACI 318: 26.5.4
TABLE 1705.3
3. INSPECT ANCHORS CAST IN CONCRETE.
5. VERIFYING USE OF REQUIRED DESIGN MIX. ACI 318: Ch. 19, 26.4.3, 26.4.4
1904.1, 1904.2, 1908.2, 1908.3
6. PRIOR TO CONCRETE PLACEMENT, FABRICATE SPECIMENS FOR
STRENGTH TEST, PERFORM SLUMP AND AIR CONTENT TESTS, AND
DETERMINE THE TEMPERATURE OF THE CONCRETE.
7. INSPECT CONCRETE PLACEMENT FOR PROPER APPLICATION
TECHNIQUES.
1908.6, 1908.7, 1908.8
8. VERIFY MAINTENANCE OF SPECIFIED CURING TEMPERATURE AND
TECHNIQUES.
ACI 318:
26.4.7-26.4.9
1908.9
ACI 318: 26.10.1 (b)
9. INSPECT FORMWORK FOR SHAPE, LOCATION AND DIMENSIONS OF
THE CONCRETE MEMBER BEING FORMED.
TABLE NOTES:
A. THE CONSTRUCTION INSPECTIONS LISTED ARE IN ADDITION TO THE CALLED INSPECTIONS REQUIRED BY IBC, AS AMENDED.
B. CONTINUOUS INSPECTION IS ALWAYS REQUIRED DURING THE PERFORMANCE OF THE WORK UNLESS OTHERWISE SPECIFIED.
C. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO INFORM THE VA/COR AND THE SPECIAL INSPECTOR OR INSPECTION AGENCY AT LEAST ONE WORKING DAY PRIOR TO PERFORMING ANY WORK THAT REQUIRES SPECIAL INSPECTION. ANY WORK PERFORMED WITHOUT REQUIRED SPECIAL INSPECTION IS SUBJECT TO REMOVAL.
D. SUBMIT WRITTEN REPORTS WITHIN TWO DAYS OF TESTING TO THE VA/COR AS WELL AS TO THE ENGINEER OF RECORD.
ACI 318: 17.8.2
4. INSPECT ANCHORS POST-INSTALLED IN HARDENED
CONCRETE MEMBERS.
a. ADHESIVE ANCHORS INSTALLED IN HORIZONTALLY OR
UPWARDLY INCLINED ORIENTATIONS TO RESIST SUSTAINED
TENSION LOADS
b. MECHANICAL ANCHORS AND ADHESIVE ANCHORS NOT DEFINED IN 4.a.
ACI 318: 17.8.2.4
ACI 318: 17.8.2
TYPE PERIODIC SPECIAL INSPECTION
1. VERIFY MATERIALS BELOW SHALLOW FOUNDATIONS ARE ADEQUATE TO
ACHIEVE THE DESIGN BEARING CAPACITY.
REQUIRED SPECIAL INSPECTIONS AND TESTS OF SOILS
TABLE 1705.6
CONTINUOUS SPECIAL INSPECTION
2. VERIFY EXCAVATIONS ARE EXTENDED TO PROPER DEPTH AND HAVE
REACHED PROPER MATERIAL.
3. PERFORM CLASSIFICATION AND TESTING OF COMPACTED FILL MATERIALS.
4. VERIFY USE OF PROPER MATERIALS, DENSITIES AND LIFT THICKNESSES
DURING PLACEMENT AND COMPACTION OF COMPACTED FILL.
5. PRIOR TO PLACEMENT OF COMPACTED FILL, INSPECT SUBGRADE AND
VERIFY THAT SITE HAS BEEN PREPARED PROPERLY.
Engineering, Inc.
18207 Edison Avenue
Chesterfield, Missouri 63005
Phone: 636.530.7770 Fax: 636.530.7877
Missouri Certificate of Authority #NC 001244
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
BANCROFT ARCHITECTS + ENGINEERS Bancroft AE No.
700 Nicholas Blvd. Suite 300 Elk Grove Village, IL 60007
T:847.952.9362 www.bancroft-ae.com Department of Veterans Affairs
VA CONTRACT NO.
Revisions: Date
KEY PLAN:
N
18207 Edison Avenue Chesterfield, MO 63005 T (636) 530-7770 F (636) 530-7877 MO. Certificate of Authority #NC 001244
C :\U se r s
\jh of fm an n\ D oc um en ts
\2
3 7
_V A
C -C
LC
_R
1 5 _S
T R
U C
_j ho f fm an nU C
JP
Q
.r v t
5/ 7/
1 8
:3
5:
P M
STRUCTURAL SPECIAL INSPECTIONS
16-123
HARRY S. TRUMAN VAMC
RELOCATE CLC
800 HOSPITAL DRIVE COLUMBIA, MO
05/11/18 MVV JMH
589-335
S-002
BID DOCUMENTS
VA255-16-C-0234
05-11-18
NOTES:
1. FILL JOINT WITH SEALANT.
2. SPACE CONTROL JOINTS EQUALLY OVER LONG SPANS. PLACE AT
EDGE OF DOOR OR WINDOW OPENINGS. DONT PLACE CONTROL
JOINTS IN THE MIDDLE OF WINDOW OR DOOR OPENINGS.
3. COORDINATE CONCRETE FINISH WITH ARCHITECTURAL DRAWINGS.
4. LIMIT CONTROL JOINT SPACING TO 30'-0" MAX.
5. CONTROL JOINTS IN CONCRETE WALL SHOULD COINCIDE WITH
MASONRY VENEER CONTROL JOINTS WHERE APPLICABLE.
CONCRETE WALLS DO NOT NEED A CONTROL JOINT AT EVERY
MASONRY WALL CONTROL JOINT.
TYPICAL CONTROL JOINT
3/4" MIN. CLEARANCE
3/4" MIN. CLEARANCE
OUTSIDE FACE
PANEL "B"
PANEL "A"
SEALANT / FILLER
PER ARCH
3/4" CHAMFER
PANEL "B"PANEL "A"
OUTSIDE FACE
SEALANT / FILLER
PER ARCH
SEALANT
1/2" C.J.
W A
L L E
A S
ID
E
/8
D E
P T
H O
F
1/4" 1/4"
ISOLATION JOINT
TOF= PER PLAN
COLUMN
PER PLAN
FINISH FLOOR
ELEVATION
PER PLAN
FTG PER PLAN
C L R
P E
R P
L A
N
P L A
N
P E
R
G R
O U
T
FTG REINF PER
FTG SCHEDULE
EXTEND CONT HORZ REINF
INTO SECOND POUR & LAP
t/ 3 t
POUR #1 POUR #2
CLASS B LAP TYP
WALL REINFORCMENT
1 1/2"
EXTEND CONT HORZ REINF
INTO SECOND POUR & LAP
t/ 3 t
POUR #1 POUR #2
WALL REINFORCMENT
1 1/2"
STEEL BASE PLATE
COLUMN - PER SCHEDULE
1/2" ISOLATION JOINT
(T
YP.)
3" C
LR
. M
IN
C.J. C.J.
C .J
C
.J
M
IN
NO PIPE SHALL PASS
THRU THE FOOTING PAD
POUR JOINT
FOOTING SHALL BE STEPPED SO THAT
THIS DIM. DOES NOT EXCEED 3'-0"
IN ANY CASE
1'-6" MIN
LOCATE PIPE
TRENCHES SO
THAT FOOTINGS
WILL NOT BE
UNDERMINED
BACK FILL AS
PER SPECS.
NO EXCAVATION
BELOW
THIS LINE
PLACE CONC. FILL AROUND SLEEVES
BEFORE POURING FOOTING PADS.
FILL SHALL BE SAME WIDTH AS FOOTING
AND FULL WIDTH OF PIPE TRENCH
PROVIDE MTL.
SLEEVES W/
I.D. 2" GREATER
THAN THE O.D.
OF THE PIPE
M
IN
M
IN
F
T G
FND
WALL
M A
X
CAST CONCRETE WALL
TYPICAL VERTICAL WALL
REINFORCING. PROVIDE 90 DEGREE
HOOKS @ BOTTOM OF OPENING
TYPICAL HORIZONTAL WALL
REINFORCING
CONT. HORIZ. BARS @ OPENING
REINFORCING
#3 CLOSED LOOP TIES @ VERT.
BAR SPACING
EACH SIDE EXTEND MIN 2'-0" PAST OPENING
1 1/2" COVER TYPICAL
HEAD OPENING
w w
TYP
8"
(4)-VERT BARS AT
WALL OPENING
WALL
OPENING
#3 TIES TYPICAL
AT HORIZONTAL BAR
SPACING
TYPICAL HORIZONTAL
WALL REINFORCING
TYPICAL VERTICAL WALL
REINFORCING
CAST CONCRETE WALL
T Y
P
IC
A L
/2
C O
V E
R
5" 1' - 3"
2" 3" 7" 6" 2"
COL. CL.
C O
L C
L
14"x20"x1 1/2" BASE PL.
w/ (6)-1 1/4"Ø F1554 (GRADE 105) ASTM
A325 ANCHOR RODS (15" EMBED)
1' - 8"
5/16 5/16
TYP
PL WASHER 1/2"x3"x3"
TYP EA ANCHOR ROD
(2) CONT. #4
CAST PL. 3/8" x 8" x 0'-8" w/ 1/2" DIA. x 6" LONG ANCHOR
BOLTS INTO CONCRETE
@ EACH STRINGER
STEEL STRINGER
1' - 4"
NOTE:
SEE ARCH DWGS.
FOR LOCATION AND TREAD-
RISER DIMENSIONS
6"
1" TYP.
1 1/2" SEAT
BREAK BOND
(ASPHALT PAPER
OR EQUAL)
#4 @ 12"O.C.
(1) -#4 TOP & BOTTOM
T Y
P T
O P
B
O T
T O
M
I N
T E
R
IO
R S
T A
IR
E
X T
E R
IO
R
S T
A
IR
.#4 @ 12" O.C.
EA. WAY (BOTTOM)
" M
IN
" C
O V
E R
E Q
U A
L
P L A
N
P E
R P
E R
P L A
N
EQUAL Z-BAR TO MATCH
FOOTING REINF.
P L A
N
P E
R
FOOTING STEP DIM.
TO HERE ON PLAN
FTG. REINF.
TOP OF FTG.
(2)-#4x4'-0" @ 45 DEG.
1' - 5 219/256"SPLICE ALL HORIZ. BARS AS
CLASS "B" LAP OR 2'-0" MIN.
STRAGGER SPLICES WHERE POSSIBLE
VERT. CONT. IN WALL
TOP OF FTG.
DOWELS, TYP.
S E
E P
L A
N F
O O
T
IN
G T
H
IC
K N
E S
S t"
S E
E P
L A
N
EQ. TO FTG. "t" DIM. TO HERE ON PLAN
E Q
E Q
EQ EQ
/2
/2
1 1/2"1 1/2"
12"x12"x1"
"b"
"a
5/16
BASE PLATE SIZE
"a" x "b" x "t"
"t " T
Y P
/2
G R
O U
T
S E
E S
C H
E D
M
IN
E M
B E
D
COL - PER SCHED
BP-1 (4)-3/4"Ø 2"x2"x1/4"
BASE PLATE
TYPE
ANCHOR RODS
(QUANTITY x DIA)
PLATE
WASHERS
BASE PLATE SCHEDULE
9"
MIN
EMBED
14"x14"x1 1/2"BP-2 (4)-3/4"Ø 2"x2"x1/4"
13"x13"x1 1/2"BP-3 (4)-3/4"Ø 2"x2"x1/4"
12x12x3/4"BP-4 (4)-3/4"Ø 2"x2"x1/4"
11"x6"x3/4"BP-5 (4)-3/4"Ø 2"x2"x1/4"
10"x10"x3/4"BP-6 (4)-3/4"Ø 2"x2"x1/4"
9"
9"
9"
9"
9"
A
PLATE
DETAIL
A
A
B
B
A
TYPE A
E Q
E Q
EQ EQ
/2
/2
1 1/2"1 1/2"
"b"
"a
5/16
COL - SEE SCHED
TYPE B
PLATE WASHER
PER SCHED
ANCHOR ROD
PER SCHED
WELD NUT TO
ANCH ROD - TYP
TYP ELEVATION VIEW
UNO ALL ANCHOR RODS TO BE F1554 (GR 36)
12"x12"x1 1/4"BP-7 (4)-3/4"Ø 2"x2"x1/4" 9" A
16"x16"x1 1/2"BP-8 (4)-3/4"Ø 2"x2"x1/4" 9" A
PLATE WASHER
PER SCHED
14"x14"x1"BP-9 (4)-3/4"Ø 2"x2"x1/4" 12" A
CONTROL
JOINT
CONTROL
JOINT
CONTROL
JOINT
CONTROL
JOINT
TYPICAL SLAB CONTROL
AND CONSTRUCTION JOINT DETAIL
TYPICAL CONSTRUCTION JOINT
DETAIL FOR SLAB ON GRADE
SEE PLAN
S E
E P
L A
N
SEE ARCH. DWGS. FOR
JOINT PATTERN
3/4" DIA. SMOOTH BAR x 18" LG.
SPACED 12"O.C. GREASE ONE
END TO PREVENT BOND
S E
E P
L A
N
TYPICAL CONTROL JOINT
DETAIL FOR SLAB ON GRADE
D
S E
E P
L A
N
JOINT MAY BE SAWN OR
FORMED WITH PLASTIC STIP
D /4
NOTES:
1. CONSTRUCTION AND/OR CONTROL. JOINTS ARE
INTERCHANGEABLE AT THE CONTRACTORS OPTION. SEE
PLANS FOR JOINT LOCATIONS.
2. SAW CUTTING OF JOINTS SHALL BE DONE AS SOON AS THE
CONCRETE SETS SUFFICIENTLY TO PERMIT CUTTING WITHOUT
CHIPPING, SPALLING OR TEARING, BETWEEN 2 AND 12 HOURS
AFTER COMPLETION OF FINISHING. THE SHORTER TIME IS
REQUIRED DURING HOTTER TEMPERATURES. SEE ACI 302.1R-15.
3. ACI RECOMMENDATION: PLACE SLABS IN LONG RECTANGULAR
STRIPS IN ALTERNATE PANELS. WIDTH OF STRIPS TO BE
12'-0" TO 15'-0".
SEE PLAN FOR
FOUNDATION INFO
PLACE SLAB ON 6 MIL.
VAPOR RETARDER, OVER
MINIMUM 1” DIAMETER ROCK
DEVOID OF FINES (FROST
DEPTH PER PLAN NOTES)
8" PAST DOOR SWING MIN.
ENTRY DOOR
CONSTRUCTION OR
CONTROL JOINT
SIDEWALK
P E
R C
IV
IL
M
IN
1'-4" 5"
1'-4" SLAB ON
GRADE
w/ WWF-
SEE PLAN#4 @
24"O.C.
6x6-W2.1xW2.1 W.W.F.
CONTRACTOR TO VERIFY
MECHANICAL
"t
"t
Engineering, Inc.
18207 Edison Avenue
Chesterfield, Missouri 63005
Phone: 636.530.7770 Fax: 636.530.7877
Missouri Certificate of Authority #NC 001244
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
BANCROFT ARCHITECTS + ENGINEERS Bancroft AE No.
700 Nicholas Blvd. Suite 300 Elk Grove Village, IL 60007
T:847.952.9362 www.bancroft-ae.com Department of Veterans Affairs
VA CONTRACT NO.
Revisions: Date
KEY PLAN:
N
18207 Edison Avenue Chesterfield, MO 63005 T (636) 530-7770 F (636) 530-7877 MO. Certificate of Authority #NC 001244
C :\U se r s
\jh of fm an n\ D oc um en ts
\2
3 7
_V A
C -C
LC
_R
1 5 _S
T R
U C
_j ho f fm an nU C
JP
Q
.r v t
5/ 7/
1 8
:3
5:
P M
STRUCTURAL TYPICAL FOUNDATION
DETAILS
16-123
HARRY S. TRUMAN VAMC
RELOCATE CLC
800 HOSPITAL DRIVE COLUMBIA, MO
05/11/18 MVV JMH
589-335
S-003
BID DOCUMENTS
VA255-16-C-0234
NOT TO SCALE3
TYP FOUNDATION WALL CONTROL JOINT
NOT TO SCALE6
TYPICAL EXPANSION JOINT DETAIL
NOT TO SCALE5
TYPICAL DETAIL OF INTERIOR HSS COLUMN AT
SPREAD FOOTING
NOT TO SCALE7
TYPICAL VERTICAL CONSTRUCTION JOINT IN
CONCRETE WALL
NOT TO SCALE18
TYPICAL ISOLATION JOINT DETAIL @ HSS
NOT TO SCALE9
TYPICAL PIPE TRENCH FOOTING DETAIL
NOT TO SCALE4
TYPICAL HEAD SECTION @ WALL OPENING
NOT TO SCALE8
TYPICAL JAMB REINFORCING @ WALL OPENING
NOT TO SCALE22
BASE PLATE DETAIL @ BRACE FRAME COLUMN UNO
NOT TO SCALE14
TYPICAL STL. STRINGER ON SLAB ON GRADE
NOT TO SCALE16
TYPICAL INTERIOR OR EXTERIOR CONCRETE SLAB ON GRADE STAIR
NOT TO SCALE13
TYPICAL STEP FOOTING DETAIL
NOT TO SCALE21
TYPICAL STEP WALL & FOOTING DETAIL AT CONT. STRIP FOOTING
NOT TO SCALE23
TYPICAL BASE PLATE DETAILS
NOT TO SCALE1
TYPICAL SLAB ON GRADE DETAILS
NOT TO SCALE11
TYPICAL ENTRY DETAIL FOR SLAB FROST HEAVE
PREVENTION
NOT TO SCALE15
TYPICAL DETAIL @ HOUSEKEEPING PAD FOR
MECHANICAL UNIT
(2)-#4 CONT
BRACE TOP OF WALL PER
STRUCTURAL DETAIL - 2/S-004
(2)-#4 CONT.
#5 VERT. BARS & DWLS.
@ 32" O.C. LAP 2'-0" @ SPLICES
(TYP. U.N.O.)
MASONRY WALL
PER PLAN
1' - 6" t t t
BEAMS PARALLEL TO PARTITIONS
8" CMU WALL
REINF. PER PLAN
L4x4x1/4 (6" LONG) @ 4'-0"O.C.
W/ 3/4" DIA EXP. BOLT
x 2 3/4" EMBED EA. SIDE
CAULK
PER ARCH
M
IN
/1
L4x4x1/4 (6" LONG) @ 4'-0"O.C.
EA. SIDE
8" CMU WALL
REINF. PER PLAN
8" CMU BOND BEAM W/
(2)-#5 CONT
BEAMS PERPENDICULAR TO PARTITIONS
TYPICAL BRACING FOR CMU
PARTITIONS @ BEAMS
1/4 2"
MASONRY
CONTROL JOINT
HORIZONTAL BOND BEAM
REINFORCING AT TOP OF WALL
HORIZONTAL BOND
BEAM REINFORCING
OPEN
OPEN
OPEN
TOP OF WALL
ROOF/FLOOR LINE
HORIZ. JOINT
REINF. @ 16"O.C.
TYP.
FLOOR LINE
CORNER/END
OF WALL
STEM WALL TOP
REINFORCING
FOOTING DOWELS TYP. DOOR OPENING
TO 16" WIDE
OPENING
OVER 16" WIDE
1 2 15
2 1
SEE 6/S-004
REINFORCING PER 5/S-004
(1)-#6 SILL BAR. EXTEND
2'-0" PAST OPENING.
(1)-#4 EACH SIDE OF OPENING
U.N.O. EXTEND 2'-0" PAST
OPENING.
WHEN "W" IS LESS THAN 2'-0"
AT 8" CMU WALL AND 3'-0" AT
12" CMU WALLS, ADD 1/4"
CLOSED TIE SETS AT 8"O.C.
NOTES:
16" MAX "W"
GREATER
16" OR
SEE PLAN FOR LOCATION, TYP.
2'-0" MIN FROM OPENING
8" CMU LINTEL W/(2)-#5
EXTEND BARS 2'-0" PAST
OPENING EXCEPT @ C.J.
LOCATIONS
MASONRY OPENING
PROVIDE
#2 TIES @
8" O.C. @
LOCATIONS
W/C.J.
C.J. WHERE
REQ'D
(2)-#5 FULL HEIGHT VERT
BARS TYPICAL
NOTE: @ LOCATIONS WITHOUT CONTROL JOINTS PROVIDE ADDITIONAL
JOINT REINF. @ FIRST 2 COURSES ABOVE LINTEL. EXTEND A
MINIMUM OF 2'-0" BEYOND OPENING
NOTE:
IF STRUCTURAL PLAN DRAWING REQUIRES
MORE REINFORCING THAN TYPICAL DETAIL,
PLAN DRAWING CONTROLS.
CMU WALL
(SEE PLAN)
FULL HEIGHT WALL REINFORCING
(MATCH PLAN OR WALL SECTION
FOR REQUIREMENT) PROVIDE
MATCHING DOWELS IN FOUNDATION
CMU WALL
(SEE PLAN)
AND DOOR MFR
COORDINATE OPENING
WIDTH WITH ARCH
WALL REINFORCEMENT
EXTEND TO UNDERSIDE
OF LINTEL
WALL REINFORCEMENT
EXTEND TO UNDERSIDE
OF LINTEL
NOTE: 1. FOR LOCATION AND CONSTRUCTION OF CONTROL
JOINTS, SEE ARCHITECTURAL DRAWINGS.
2. PROVIDE TOP BOND BEAM CONTINUOUS ACROSS,
CONTROL JOINT
CAULKING PER
ARCH
BACKER PER
ARCH
FULL HEIGHT WALL REINFORCING
MATCH PLAN OR WALL SECTION FOR
REINFORCING SIZE. PROVIDE
MATCHING DOWEL IN FOUNDATION
CMU WALL
PER PLAN
CONTROL JOINT MATERIAL
PER ARCH
#5 VERTS
ALTERNATE
CROSSING @
INTERSECTION
MASONRY STRAP ANCHORS
(1)-1/4"x 10 GAUGE, 30" LONG
W/3" RIGHT ANGLE BENDS @ EA.
END, @ 16" O.C. VERTICALLY
EMBED BENT ENDS IN CORES
FILLED W/MORTAR OR CONCRETE
ALTERNATE
CROSSING
INTERSECTION
CONTROL JOINT RAKE
OUT & CAULK
(2)-#5
VERT
SPAN
3'-8" TO 6'-0"
UP TO 3'-8"
BRICK VENEER LOOSE LINTEL SCHEDULE
L6x5x5/16 (LLH)
SIZE
L6x4x5/16 (LLH)
REMARKS
6'-0" TO 8'-0"L6x6x5/16
NOTE :
1. PROVIDE 8" BEARING AT EACH END.
2. PROVIDE GALVANIZED FINISH.
3. SEE ARCH. DRAWINGS FOR OPENING LOCATIONS.
(T Y
P
M A
X
INTERIOR WALL
PER ARCH DWGS
L3x3x1/4 CLIP w/ 3/4"Ø HILTI KWIK BOLT III
(4 3/4" EMBED)
5/16 3
3/16
L2x2x1/4
1/8" MOLDED SAFETY CAPS
TYP
CHANNEL SIDE RAIL BY
FABRICATOR - TYP
G R
O U
T S
O L
ID
F U
L L
H T
#5 FULL HT @ 8" OC (3 CELLS MIN)
TYP CENTERED @ GUIDE RAIL
SUPPORT LOCATIONS
DWLS INTO FND TO MATCH
CL GUIDE RAIL SUPPORT
BRACKETS PER ELEVATOR
MFR
C L R
T
Y P
SEE ARCH DWGS
FOR SIZE & LOCATION
SEE ELEVATOR PIT
SECTION FOR SLAB
THICKNESS & REINF.
#5 @ 12"O.C.
#5 BARS
#5 @ 12"O.C.
1' - 0"
CONDUIT HOLE CENTERED
IN REBAR SPACING
STACK MULTIPLE
HOLES
VERTICALY. LIMIT
THREE.
M
IN
C
L R
HORZ WALL REINF
PER WALL DETAIL
VERT WALL REINF
PER WALL DETAIL #5 x 4'-0" DIAGONALLY ALL
FOUR SIDES OF OPENING
OR GROUP OF OPENING
BENT PLATE OPTION
bf. "L" SEE PLAN
CONTINUOUS 3/8"
BENT PLATE AS
POUR STOP
FLOOR
THICKNESS, SEE
PLAN
1/2"Ø x 6" HD STUDS
@ 16" OC
SEE PLAN
TSL=
NOTE:
WHEN "L">bf/2 + 12", USE DECK SUPPORT EXTENSION
1/4
@ CORNERS
3/16 2-12
TYP
COMPOSITE STUDS ON
BM PER PLAN
Engineering, Inc.
18207 Edison Avenue
Chesterfield, Missouri 63005
Phone: 636.530.7770 Fax: 636.530.7877
Missouri Certificate of Authority #NC 001244
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
BANCROFT ARCHITECTS + ENGINEERS Bancroft AE No.
700 Nicholas Blvd. Suite 300 Elk Grove Village, IL 60007
T:847.952.9362 www.bancroft-ae.com Department of Veterans Affairs
VA CONTRACT NO.
Revisions: Date
KEY PLAN:
N
18207 Edison Avenue Chesterfield, MO 63005 T (636) 530-7770 F (636) 530-7877 MO. Certificate of Authority #NC 001244
C :\U se r s
\jh of fm an n\ D oc um en ts
\2
3 7
_V A
C -C
LC
_R
1 5 _S
T R
U C
_j ho f fm an nU C
JP
Q
.r v t
5/ 7/
1 8
:3
5:
P M
STRUCTURAL TYPICAL DETAILS
16-123
HARRY S. TRUMAN VAMC
RELOCATE CLC
800 HOSPITAL DRIVE COLUMBIA, MO
05/11/18 MVV JMH
589-335
S-004
BID DOCUMENTS
VA255-16-C-0234
NOT TO SCALE1
TYPICAL SLAB DETAIL @ NON-BEARING CMU WALL
& WALL REINFORCING
NOT TO SCALE2
TYPICAL BRACING OF CMU WALLS
NOT TO SCALE8
TYPICAL CMU WALL REINFORCING @ OPENINGS
NOT TO SCALE5
TYPICAL CMU BOND BEAM LINTEL
NOT TO SCALE6
TYPICAL REINFORCEMENT FOR OPENING IN CMU
WALL
NOT TO SCALE7
TYPICAL MASONRY CONTROL JOINT
NOT TO SCALE9
TYPICAL CMU WALL CORNER AND INTERSECTION
DETAIL
NOT TO SCALE10
BRICK VENEER LOOSE LINTEL SCHEDULE
NOT TO SCALE11
TYPICAL FIXED LADDER DETAIL
BID DOCUMENTS 05/11/18
NOT TO SCALE13
TYPICAL CMU REINF @ ELEVATOR GUIDE RAIL
SUPPORT
NOT TO SCALE14
TYPICAL SUMP DETAIL
SCALE: 1/2" = 1'-0"15
TYPICAL CONDUIT SLEEVE THRU CONC WALL
NOT TO SCALE16
POUR STOP @ TYPICAL INTERIOR SLAB CLOSURE
PLATE
NOTES:
1. ADAPTED FROM TABLE 10-9a, AISC STEEL CONTRUCTION MANUAL, THIRTEENTH EDITION.
2. ONLY A SINGLE VERTICAL ROW OF BOLTS IS PERMITTED.
3. THE DISTANCE FROM THE BOLT LINE TO THE WELD LINE, MUST BE
EQUAL TO OR LESS THAN 3 1/2".
4. STD OR SSL HOLES ARE PERMITTED TO BE USED. USE STD HOLES
ONLY @ FULL DEPTH SHEAR PLATES.
5. THE HORIZONTAL EDGE DISTANCE MUST BE EQUAL TO OR GREATER
THAN 1 1/2" FOR BOTH THE PLATE AND THE BEAM WEB.
6. THE VERTICAL EDGE DISTANCES MUST SATISFY AISC SPECIFICATION
TABLE J3.4 REQUIREMENTS FOR BOTH THE PLATE AND THE BEAM
WEB.
7. EDGE DISTANCES ARE MEASURED TO THE CENTER OF THE BOLT OR
SLOT.
8. BOLT SPACING SHALL BE 3".
9. BOLTS SHALL BE ASTM A325-N or X.
10. BEAMS WITH REACTIONS GREATER THAN THE ALLOWABLE LOADS IN
THE TABLE ARE TO BE DESIGNED BY THE CONNECTION ENGINEER.
W12, 10, 8 5 1/2" 2
W16, 14, 12 8 1/2" 3
W21, 18, 16 4
W24, 21, 18 5
W30, 27, 24 6
W33, 30, 27 7
W36, 33, 30 8
STEEL COLUMN
PER PLAN
11 1/2"
14 1/2"
17 1/2"
20 1/2"
23 1/2"
BEAM
SIZE
5/16" STEEL PLATE
LENGTH, L (IN.)
NUMBER OF
3/4" DIA. BOLTS
20.4
31.8
42.4
53.0
ALLOWABLE SHEAR
CAPACITY, KIPS (ASD)
63.6
74.2
84.7
STEEL BEAM
PER PLAN
SINGLE-PLATE
SHEAR CONNECTION
PER TABLE
1/4
TYP.
1 1/2"
STEEL BEAM
PER PLAN
(4) 3/4" Ø
A325-N BOLTS
1/2" THICK PLATE,
MIN. OR MATCH
BEAM FLANGE
THICKNESS
STEEL COLUMN
PER PLAN
WEB STIFFENERS
BOTH SIDES, MATCH
BEAM WEB
THICKNESS OR 3/8"
THICK MIN.
1/4
1/4
TYP.
1/4
TYP.
SEE PLAN
FOR SIZE
SINGLE PLATE
SHEAR CONN.
CL VARIES
WF STEEL BEAM
SEE PLAN
TOP BACKING BAR
TO REMAIN
BOTTOM BACKER BAR
TO BE REMOVED
AFTER WELDING.
VARIES
/4
M
IN
tbf OR 1/2"
LARGER OF
3 tbf tbf OR 1/2"
LARGER OF
3 tbf
/4
M
IN
NOTE: GRIND
SMOOTH & ADD
FILLET WELD
ONCE BACKER
BAR IS
REMOVED
CJP
TYP
F
IN
IS
H
C O
L U
M N
CL.
BEAM CONNECTION NOT
SHOWN FOR CLARITY
STIFF. PLATE 3/8" EACH
SIDE WEB, MATCH BEAM WIDTH
BEARING PLATE 3/4" WITH
(4)-3/4"Ø A325 BOLTS OR
PER…