Drawings 503-25-104 Install Boiler Safety Devices.pdf
PDF 8 MB Posted
- Attached to
- Z2DA--SOURCES SOUGHT NOTICE ONLY 503-25-104 Install Boiler Safety Devices and Piping Altoona VAMC
- Solicitation number
- 36C24425Q0097
About this file
This document is a set of drawings and notes related to a federal contract opportunity to Install Boiler Safety Devices at the Altoona VA Medical Center.
The key details are:
- The contract opportunity has a Solicitation Number of 36C24425Q0097, and a NAICS code of 236220 for Commercial and Institutional Building Construction.
- The work involves replacing 8 existing safety/pressure relief valves in the Building 3 Boiler Room, including modifying connections, vents, and drain lines.
- Technical specifications are provided, including the manufacturer, model, size, set pressure, and capacity of the required replacement valves.
- This is currently a Sources Sought notice only, with responses due by 11:00 AM EST on November 26, 2024. If approved, a full solicitation may be issued later.
- The procurement is set aside for small businesses, including SDVOSB and VOSB firms. Companies must be registered in SAM to be eligible.
- Responses should provide company information, qualifications, and socioeconomic status.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24425Q0097_1.docx | DOCX document | |
| Combined Specifications 503-25-104.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Boiler Safety Project
B
A
C
D
E
F
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
100% BID DOCUMENTS
N O
R T H
1 2 08/08/2024
Job Numbers and Descriptions
MP-100
Drawing Notes
1) Refer to highlighted areas to see description of work.
2) Job numbers listed are referenced in other sheets throughout the drawing package.
3) Do not use this document as assurance that what is installed throughout the Boiler Plant match's what it shown on the drawings.
Contractor must field verify conditions.
503-25-104 Revision 0: 8/08/2024 KJC
JOB 1: There is an existing, brass threaded safety valve here also that will need replaced.
Connections will need modified to retrofit the new device, and vent stack will need modified due to the size difference of the SV.
JOB 2:Replace safety valve. Field verify measurements as the clearance from the piping to the roof insulation is minimal.
Evaluate if it would be more beneficial to install the new Safety Valve on the main line, rather than on the bypass line. Review method and location of installation with the VA before performing work. If alternate location of installation is deemed the best option, proper blanking/isolation of the original location is required.
Any insulation that is removed to perform work will need replaced.
JOB 3: remove existing safety valves (qty=2), modify connection points (flanged instead of threaded) ,cut back vent stack, install new SV, modify drain lines
JOB 4: remove existing safety valves (qty=2), modify connection points (flanged instead of threaded) ,cut back vent stack, install new SV's, modify drain lines.
JOB 5: remove existing safety valves (qty=2), modify connection points (flanged instead of threaded) ,cut back vent stack, install new SV's, modify drain lines
Revision 1: 9/20/2024 KJC
VHAALTChronK Rectangle JOB 3: remove existing safety valves (qty=2), modify connection points (flanged instead of threaded) ,cut back vent stack, install new SV, modify drain lines
VHAALTChronK Rectangle JOB 4: remove existing safety valves (qty=2), modify connection points (flanged instead of threaded) ,cut back vent stack, install new SV's, modify drain lines
VHAALTChronK Rectangle JOB 5: remove existing safety valves (qty=2), modify connection points (flanged instead of threaded) ,cut back vent stack, install new SV's, modify drain lines
VHAALTChronK Rectangle JOB 2: Replace safety valve. Field verify measurements as the clearance from the piping to the roof insulation is minimal. Evaluate if it would be more beneficial to install the new Safety Valve on the main line, rather than on the bypass line. Review method and location of installation with the VA before performing work. If alternate location of installation is deemed the best option, proper blanking/isolation of the original location is required.
Any insulation that is removed to perform work will need replaced.
VHAALTChronK Rectangle JOB 1: There is an existing, brass threaded safety valve here also that will need replaced. Connections will need modified to retrofit the new device, and vent stack will need modified due to the size difference of the SV.
VHAALTChronK Line
VHAALTChronK Line
VHAALTChronK Line
VHAALTChronK Line
VHAALTChronK Line
Boiler Safety Project
B
A
C
D
E
F
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
100% BID DOCUMENTS
2 2
MP-101
08/08/2024
Drawing Notes
1)Do not use this document as assurance that what is installed throughout the Boiler Plant match's what it shown on the drawings. Contractor must field verify conditions.
2)SV's, drain line modifications, and vent stack modifications. See information in notes 4 & 5 on SV's. Pictures of serial tags are also provided within this package.
3)6 of 8 safety valves to be replaced are shown on this sheet. The other two safety's and their locations (labeled as JOB 1 and JOB 2) can be found on marked up drawing MP-100.
4)Primary SV: Manufacturer= Kunkle, Model= 300LJG01-AS, Size=1.5", Set= 110psig, Capacity= 7749 PPH 5)Secondary SV: Manufacturer= Kunkle, Model= 300LJG01-AS, Size=1.5", Set= 115psig, Capacity= 7749 PPH
Mechanical - Boiler Safety Valves and Drain Lines
503-25-104
Revision 0: 8/08/2024 KJC
Revision 1: 9/20/2024 KJC
VHAALTChronK Rectangle SV's, drain line modifications, and vent stack modifications. See information below on SV's. Pictures of serial tags are also provided within this package.
Primary SV: Manufacturer= Kunkle, Model= 300LJG01-AS, Size=1.5", Set= 110psig, Capacity= 7749 PPH
Secondary SV: Manufacturer= Kunkle, Model= 300LJG01-AS, Size=1.5", Set= 115psig, Capacity= 7749 PPH
VHAALTChronK Rectangle SV's, drain line modifications, and vent stack modifications. See information below on SV's. Pictures of serial tags are also provided within this package.
Primary SV: Manufacturer= Kunkle, Model= 300LJG01-AS, Size=1.5", Set= 110psig, Capacity= 7749 PPH
Secondary SV: Manufacturer= Kunkle, Model= 300LJG01-AS, Size=1.5", Set= 115psig, Capacity= 7749 PPH
VHAALTChronK Rectangle SV's, drain line modifications, and vent stack modifications. See information below on SV's. Pictures of serial tags are also provided within this package.
Primary SV: Manufacturer= Kunkle, Model= 300LJG01-AS, Size=1.5", Set= 110psig, Capacity= 7749 PPH
Secondary SV: Manufacturer= Kunkle, Model= 300LJG01-AS, Size=1.5", Set= 115psig, Capacity= 7749 PPH
VHAALTChronK Sticky Note 6 of 8 safety valves to be replaced are shown on this sheet. The other two safety's and their locations (labeled as JOB 1 and JOB 2) can be found on marked up drawing MP-101.
VHAALTChronK Line
VHAALTChronK Line
VHAALTChronK Line