DRAWINGS 4 - 4B MEDICAL CENTER SUPPORT SPACE.pdf
PDF 6 MB Posted
- Attached to
- Z1DA--Renovate 4B for Medical Center Support Space - 565-17-305 Previous Pre-solicitation 36C24622B0014
- Solicitation number
- 36C24622B0036
About this file
This federal contract opportunity solicitation seeks proposals for Project 565-17-305 to renovate approximately 9,300 square feet in Building 1, Wing B, Floor 4 at the Fayetteville Veterans Affairs Medical Center. The scope of work includes demolition, framing, mechanical, electrical, plumbing, and finish work. Proposals are due by the date specified in the solicitation. Specific requirements include preparing the site for construction; complying with VA security procedures; and performing work between 7:00 am and 5:00 pm Monday through Friday or as approved by the Contracting Officer's Representative. The contractor shall furnish all supervision, labor, materials, and equipment to complete the project in accordance with the plans and specifications.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Amendment 0003.docx | DOCX document | |
| 36C24622B0036 0003.docx | DOCX document | |
| 36C24622B0036 0002.docx | DOCX document | |
| 36C24622B0036 PRE BID ATTENDANCE.pdf | ||
| 36C24622B0036 0001.docx | DOCX document | |
| SPECIFICATIONS 4B MEDICAL CENTER SUPPORT SPACE.pdf | ||
| DRAWINGS 1 - 4B MEDICAL CENTER SUPPORT SPACE.pdf | ||
| 36C24622B0036.docx | DOCX document | |
| DRAWINGS 2 - 4B MEDICAL CENTER SUPPORT SPACE.pdf | ||
| DRAWINGS 3 - 4B MEDICAL CENTER SUPPORT SPACE.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
3/31/2022
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL CONSTRUCTION
DOCUMENTS
FULLY- SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Atriax, pllc
102 3rd Avenue, NE Hickory, NC 28601
P.O. Box 1629, Hickory, NC 28603
PH: 828-315-9962
www.atriaxgroup.com
RENOVATE 4B FOR MEDICAL
CENTER SUPPORT SPACE
Fayetteville VAMC Fayetteville, NC
565-17-305
Project Director
March 31, 2022Revisions: Date:
ELECTRICAL:
QUALITY CONSULTING ENGINEERS, LLC
6277-600 Carolina Commons Dr. #350 Indian Land, SC 29707
(P) 803.207.5450 djones@qualityconsultingengineers.com
MECHANICAL / PLUMBING:
SHULTZ ENGINEERING GROUP, PC
212 N. McDowell St, Suite 204 Charlotte, NC 28204
(P) 704.334.7363 www.shultzeg.com
MECHANICAL DETAILS
MH-203
WSC JKS 7 of 7
AutoCAD SHX Text
AutoCAD SHX Text
NTS
AutoCAD SHX Text
ACCESS SECTION FOR ROUND/OVAL DUCT
AutoCAD SHX Text
HOUSING WELDED TO DUCT SECTION
AutoCAD SHX Text
ROUND OR FLAT OVAL DUCT SECTION
AutoCAD SHX Text
COVER WITH HANDLE AND CHAIN RETAINER GASKETED AND PRESSURE SEALED
AutoCAD SHX Text
AutoCAD SHX Text
NTS
AutoCAD SHX Text
ROUND DUCT HANGERS
AutoCAD SHX Text 2500 [1133]
AutoCAD SHX Text 1320 [598]
AutoCAD SHX Text 420 [190]
AutoCAD SHX Text ONE 1 [25] x 18 GA STRAP
AutoCAD SHX Text 36 [900]
AutoCAD SHX Text
TWO 1/2 [13]%%C RODS
AutoCAD SHX Text
TWO 3/8 [10]%%C. RODS
AutoCAD SHX Text ONE 1 [25] x 16 GA STRAP
AutoCAD SHX Text 84 [2100]
AutoCAD SHX Text 60 [1500]
AutoCAD SHX Text 50 [1250]
AutoCAD SHX Text 700 [317]
AutoCAD SHX Text ONE 1 [25] x 22 GA STRAP
AutoCAD SHX Text
QUANTITY/SIZE
AutoCAD SHX Text
MAX. DUCT %%C
AutoCAD SHX Text 26 [650]
AutoCAD SHX Text
HANGER STRAPS OR RODS
AutoCAD SHX Text
MAX. LOAD
AutoCAD SHX Text LBS. [kg]
AutoCAD SHX Text 260 [119]
AutoCAD SHX Text
MAX.
AutoCAD SHX Text 144 [3600]
AutoCAD SHX Text IN. [mm]
AutoCAD SHX Text
SPACING
AutoCAD SHX Text IN. [mm]
AutoCAD SHX Text IN. [mm]
AutoCAD SHX Text 144 [3600]
AutoCAD SHX Text 144 [3600]
AutoCAD SHX Text 144 [3600]
AutoCAD SHX Text 144 [3600]
AutoCAD SHX Text NOTE: TABULATED DATA FROM SMACNA ALLOWS FOR DUCT REINFORCING AND INSULATION, BUT NO EXTERNAL LOAD.
AutoCAD SHX Text
BAND
AutoCAD SHX Text OVER 50" [1250mm]
AutoCAD SHX Text
HANGER RODS
AutoCAD SHX Text
BAND OF SAME SIZE AS HANGER STRAP
AutoCAD SHX Text
LOAD RATED FASTENERS
AutoCAD SHX Text 50" [1250mm] &UNDER
AutoCAD SHX Text DESIGNER'S NOTE: DESCRIBE OR DETAIL UPPER ATTACHMENTS APPLICABLE TO PARTICULAR PROJECTS.
AutoCAD SHX Text
AutoCAD SHX Text
NTS
AutoCAD SHX Text
FROM STRUCTURE
AutoCAD SHX Text
SAME AS DIFFUSER
AutoCAD SHX Text
INLET: 5'-0" MAX
AutoCAD SHX Text
FLEXIBLE DUCT SIZE
AutoCAD SHX Text
LENGTH.
AutoCAD SHX Text 12"
AutoCAD SHX Text
CEILING
AutoCAD SHX Text
SUPPORT SADDLE
AutoCAD SHX Text
VOLUME DAMPER W/
AutoCAD SHX Text
LOCKING QUAD
AutoCAD SHX Text
SADDLE
AutoCAD SHX Text
SHEET METAL
AutoCAD SHX Text
CONICAL OUTLET
AutoCAD SHX Text
BRANCH DUCT
AutoCAD SHX Text
FOR CHANGE OF
AutoCAD SHX Text
DIRECTION GREATER
AutoCAD SHX Text
USE RIGID ELBOWS
AutoCAD SHX Text
THAN 45%%D
AutoCAD SHX Text [300mm]
AutoCAD SHX Text
FLEXIBLE AIR DUCT CONNECTOR
AutoCAD SHX Text
SEE SPECIFICATIONS FOR CLAMPS AND SEALANT (TYP.)
AutoCAD SHX Text
TYPICAL DIFFUSER OR REGISTER IN LAY-IN CLG.
AutoCAD SHX Text
THERMAL INSULATION SEE SPECIFICATIONS
AutoCAD SHX Text
AutoCAD SHX Text
NTS
AutoCAD SHX Text ROOM THERMOSTAT/SENSOR WALL MOUNTED 48" [1200mm] AFF.
AutoCAD SHX Text
VARIABLE VOLUME AIR TERMINAL UNIT CONTROL DIAGRAM
AutoCAD SHX Text
AIR FLOW (CFM)
AutoCAD SHX Text
ROOM TEMPERATURE (°F)
AutoCAD SHX Text
HEATING MINIMUM
AutoCAD SHX Text
VAV BOX CONTROL SEQUENCE
AutoCAD SHX Text
SP
AutoCAD SHX Text
TU
AutoCAD SHX Text
RHC
AutoCAD SHX Text
HWS
AutoCAD SHX Text
HWR
AutoCAD SHX Text V-1
AutoCAD SHX Text
REHEAT COIL
AutoCAD SHX Text
AIR TERMINAL UNIT
AutoCAD SHX Text
AIR FLOW
AutoCAD SHX Text
TE
AutoCAD SHX Text
ATU CONTROLLER
AutoCAD SHX Text
PC
AutoCAD SHX Text
TE
AutoCAD SHX Text
AIR FLOW (CFM)
AutoCAD SHX Text
ROOM TEMPERATURE (°F)
AutoCAD SHX Text
HEATING MINIMUM
AutoCAD SHX Text
SP
AutoCAD SHX Text
NO DEADBAND
AutoCAD SHX Text
VAV BOX CONTROL SEQUENCE
AutoCAD SHX Text
W/DEADBAND
AutoCAD SHX Text 100%
AutoCAD SHX Text 100%
AutoCAD SHX Text
REHEAT FLOW
AutoCAD SHX Text
VAV AIR FLOW
AutoCAD SHX Text
VAV AIR FLOW
AutoCAD SHX Text
REHEAT FLOW
AutoCAD SHX Text A. UPON FALL IN SPACE TEMPERATURE THE VAV DAMPER WILL MODULATE TO MINIMUM POSITION. B. UPON FURTHER DROP IN SPACE TEMPERATURE VALVE V-1 WILL MODULATE TO MAINTAIN SET POINT + .5 F. THE + .5 F. THE .5° F. THE ADJUSTABLE TOLERANCE OF + .5 F HAS + .5 F HAS .5° F HAS BEEN SELECTED TO PREVENT VALVE HUNTING C. THE REVERSE SHALL OCCUR ON THE RISE IN SPACE TEMPERATURE.
AutoCAD SHX Text A. SET POINTS SHALL BE SET AS FOLLOWS: COOLING 75°F (ADJ) HEATING 70°F(ADJ) DEADBAND OF 5° F BETWEEN HEATING AND COOLING SET POINTS WILL BE MAINTAINED. B. UPON FALL IN SPACE TEMPERATURE THE VAV DAMPER WILL MODULATE TO MINIMUM POSITION. C. UPON FURTHER DROP IN SPACE TEMPERATURE VALVE V-1 WILL MODULATE TO MAINTAIN SET POINT + .5 F. THE + .5 F. THE .5° F. THE ADJUSTABLE TOLERANCE OF + .5 F HAS + .5 F HAS .5° F HAS BEEN SELECTED TO PREVENT VALVE HUNTING D. THE REVERSE SHALL OCCUR ON THE RISE IN SPACE TEMPERATURE.
AutoCAD SHX Text
FE
AutoCAD SHX Text
AutoCAD SHX Text
NTS
AutoCAD SHX Text
DUCT CONNECTIONS - AIR TERMINAL UNITS
AutoCAD SHX Text
NOTE: 1. 2. 3. 4.
AutoCAD SHX Text RIGID STRAIGHT TERMINAL UNIT INLET LENGTH SHALL BE A MINIMUM OF 3 TIMES THE DIAMETER OF INLET A FLEXIBLE AIR DUCT CONNECTOR IS NOT MANDATORY FOR INLET TO THIS BOX, BUT ALLOWED TO ACCOMMODATE MINOR OFFSETS. MAXIMUM LENGTH 3'-0" [900mm]. A BRANCH DUCT SERVING AN INDIVIDUAL BOX MAY BE THE SAME SIZE AS THE BOX INLET, PROVIDED THE EQUIVALENT LENGTH OF THE BRANCH DUCT, AS SHOWN, DOES NOT EXCEED 10 FEET (3 METERS). FOR LONGER LENGTHS, INCREASE THE DUCT SIZE AND PROVIDE A DUCT TRANSITION TO MAINTAIN THE DUCT STATIC PRESSURE DROP AT OR BELOW 0.2"/100' [1.64Pa/m]. FLEXIBLE AIR DUCT CONNECTORS, WHEN USED FROM TERMINAL UNIT SUPPLY AIR DUCT TO DIFFUSER, SHALL NOT EXCEED 5'-0" [1500mm]. USE RIGID ELBOWS FOR CHANGE OF DIRECTION GREATER THAN 45°.COMPONENT ARRANGEMENT MAY VARY BY MANUFACTURER. PROVIDE INSULATION W/VAPOR BARRIER FOR CONNECTING DUCT SECTIONS.
AutoCAD SHX Text
AIR TERMINAL UNIT (CV OR VAV)
AutoCAD SHX Text
REHEAT COIL
AutoCAD SHX Text
SOUND ATTENUATOR SEE EQUIPMENT SCHEDULE
AutoCAD SHX Text
FLEXIBLE AIR DUCT CONNECTOR. SEE DETAIL
AutoCAD SHX Text
DIFFUSER (TYP.)
AutoCAD SHX Text
SEE SPECIFICATIONS FOR CLAMPS AND SEALANT (TYP.)
AutoCAD SHX Text
SEE NOTE 5
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text P
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text G
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text T
AutoCAD SHX Text L
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text N
AutoCAD SHX Text
AutoCAD SHX Text W
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text U
AutoCAD SHX Text A
AutoCAD SHX Text 17231
AutoCAD SHX Text
SEAL
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text N
AutoCAD SHX Text
AutoCAD SHX Text R
AutoCAD SHX Text J
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text C
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text H
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text A
AutoCAD SHX Text R
AutoCAD SHX Text L
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text O
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text A
CONSTRUCTION / PROJECT
LIMITS
2 HR FIRE WALL
1 HR FIRE WALL
1 HR FIRE / SMOKE WALL
E-001
ELECTRICAL - COVER SHEET
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY- SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Atriax, pllc
102 3rd Avenue, NE Hickory, NC 28601
P.O. Box 1629, Hickory, NC 28603
PH: 828-315-9962
www.atriaxgroup.com
RENOVATE 4B FOR MEDICAL
CENTER SUPPORT SPACE
Fayetteville VAMC Fayetteville, NC
565-17-305
Project Director
March 31, 2022Revisions: Date:
FINAL CONSTRUCTION
DOCUMENTSELECTRICAL:
QUALITY CONSULTING ENGINEERS, LLC
6277-600 Carolina Commons Dr. #350 Indian Land, SC 29707
(P) 803.207.5450 djones@qualityconsultingengineers.com
QCE PROJECT# 21007
MECHANICAL / PLUMBING:
SHULTZ ENGINEERING GROUP, PC
212 N. McDowell St, Suite 204 Charlotte, NC 28204
(P) 704.334.7363 www.shultzeg.com
DAJ GSB
Date: MARCH 31, 2022
Date: MARCH 31, 2022
AutoCAD SHX Text
WALL LEGEND
AutoCAD SHX Text
AutoCAD SHX Text
ENERGY SUMMARY
AutoCAD SHX Text 2013 ASHRAE 90.1 ENERGY CODE ELECTRICAL SYSTEM AND EQUIPMENT METHOD OF COMPLIANCE: (X)PRESCRIPTIVE ( )PERFORMANCE ( )ENERGY COST BUDGET LUMINAIRE SCHEDULE LAMP TYPE REQUIRED IN FIXTURE: SEE LUMINAIRE SCHEDULE SEE LUMINAIRE SCHEDULE NUMBER OF LAMPS IN FIXTURE: SEE LUMINAIRE SCHEDULE SEE LUMINAIRE SCHEDULE NUMBER OF BALLASTS IN FIXTURE: SEE LUMINAIRE SCHEDULE SEE LUMINAIRE SCHEDULE TOTAL WATTAGE PER FIXTURE: SEE LUMINAIRE SCHEDULE SEE LUMINAIRE SCHEDULE TOTAL INTERIOR LPD: 0.60 W/SF SPECIFIED VS. 1.21 W/SF ALLOWED 0.60 W/SF SPECIFIED VS. 1.21 W/SF ALLOWED MINIMUM EXTERIOR EFFICACY: NOT APPLICABLE NOT APPLICABLE EXTERIOR LIGHTING ZONE: NOT APPLICABLE NOT APPLICABLE PARKING AREAS: NOT APPLICABLE NOT APPLICABLE EXTERIOR ENTRY DOORS LPD: NOT APPLICABLE NOT APPLICABLE EXTERIOR ENTRY CANOPY LPD: NOT APPLICABLE NOT APPLICABLE EQUIPMENT SCHEDULES WITH MOTORS: SEE MECHANICAL DRAWINGS SEE MECHANICAL DRAWINGS MOTOR HORSEPOWER: SEE MECHANICAL DRAWINGS SEE MECHANICAL DRAWINGS NUMBER OF PHASES: SEE MECHANICAL DRAWINGS SEE MECHANICAL DRAWINGS MINIMUM EFFICIENCY: SEE MECHANICAL DRAWINGS SEE MECHANICAL DRAWINGS MOTOR TYPE: SEE MECHANICAL DRAWINGS SEE MECHANICAL DRAWINGS # OF POLES: SEE MECHANICAL DRAWINGS SEE MECHANICAL DRAWINGS PROJECT NEW/RENOVATION S.F.: 7,000 S.F. 7,000 S.F. INDOOR NON-EM FIXTURE CONTROL: OCCUPANCY SENSORS OCCUPANCY SENSORS OUTDOOR FIXTURE CONTROL: NOT APPLICABLENOT APPLICABLE
AutoCAD SHX Text
ABBREVIATIONS
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
TYPE
AutoCAD SHX Text
A, AMP
AutoCAD SHX Text
AC
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text
AF
AutoCAD SHX Text
AFC
AutoCAD SHX Text
AFF
AutoCAD SHX Text
AFG
AutoCAD SHX Text C
AutoCAD SHX Text
EF
AutoCAD SHX Text
EC
AutoCAD SHX Text
FA
AutoCAD SHX Text
FACP
AutoCAD SHX Text
AMPERE
AutoCAD SHX Text
ALTERNATING CURRENT
AutoCAD SHX Text
AMPERE FRAME
AutoCAD SHX Text
ABOVE FINISHED COUNTER
AutoCAD SHX Text
ABOVE FINISHED FLOOR
AutoCAD SHX Text
ABOVE FINISHED GRADE
AutoCAD SHX Text
CONDUIT
AutoCAD SHX Text
EXHAUST FAN
AutoCAD SHX Text
ELECTRICAL CONTRACTOR
AutoCAD SHX Text
G OR GND
AutoCAD SHX Text
GF, GFI
AutoCAD SHX Text
KVA
AutoCAD SHX Text
KW
AutoCAD SHX Text
MCB
AutoCAD SHX Text
NEC
AutoCAD SHX Text
OR PH
AutoCAD SHX Text
UON
AutoCAD SHX Text V
AutoCAD SHX Text W
AutoCAD SHX Text
WP
AutoCAD SHX Text
FIRE ALARM
AutoCAD SHX Text
FIRE ALARM CONTROL PANEL
AutoCAD SHX Text
GROUND
AutoCAD SHX Text
GROUND FAULT INTERRUPTER
AutoCAD SHX Text
KILOVOLT AMPERES
AutoCAD SHX Text
KILOWATTS
AutoCAD SHX Text
MAIN CIRCUIT BREAKER
AutoCAD SHX Text
PHASE
AutoCAD SHX Text
UNLESS OTHERWISE NOTED
AutoCAD SHX Text
VOLT(S)
AutoCAD SHX Text
WATTS OR WIRE
AutoCAD SHX Text
WEATHERPROOF
AutoCAD SHX Text P
AutoCAD SHX Text
POLE
AutoCAD SHX Text A
AutoCAD SHX Text
AIC
AutoCAD SHX Text
AMPERE INTERRUPTING CURRENT
AutoCAD SHX Text
CCT
AutoCAD SHX Text
CIRCUIT
AutoCAD SHX Text
MOCP
AutoCAD SHX Text
MAXIMUM OVERCURRENT PROTECTION
AutoCAD SHX Text
NATIONAL ELECTRICAL CODE
AutoCAD SHX Text
N OR NEUT
AutoCAD SHX Text
NEUTRAL
AutoCAD SHX Text
NTS
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
OC
AutoCAD SHX Text
ON CENTER
AutoCAD SHX Text
PB
AutoCAD SHX Text
PUSHBUTTON SWITCH
AutoCAD SHX Text
TBB
AutoCAD SHX Text
TELECOMMUNICATIONS BACKBOARD
AutoCAD SHX Text
TC
AutoCAD SHX Text
TELECOMMUNICATIONS CONTRACTOR
AutoCAD SHX Text
TYP
AutoCAD SHX Text
TYPICAL
AutoCAD SHX Text
TRANSFORMER
AutoCAD SHX Text
GC
AutoCAD SHX Text
GENERAL CONTRACTOR
AutoCAD SHX Text
PC
AutoCAD SHX Text
PLUMBING CONTRACTOR
AutoCAD SHX Text
XFMR
AutoCAD SHX Text
MC
AutoCAD SHX Text
MECHANICAL CONTRACTOR
AutoCAD SHX Text
FPN
AutoCAD SHX Text
FUSE PER NAMEPLATE
AutoCAD SHX Text
EOL
AutoCAD SHX Text
END OF LINE (RESISTOR)
AutoCAD SHX Text
FPC
AutoCAD SHX Text
FIRE PROTECTION CONTRACTOR
AutoCAD SHX Text
LPD
AutoCAD SHX Text
LIGHTING POWER DENSITY
AutoCAD SHX Text
TP
AutoCAD SHX Text
TAMPER PROOF/RESISTANT
AutoCAD SHX Text
ADO
AutoCAD SHX Text
AUTOMATIC DOOR OPENER
AutoCAD SHX Text
RDO
AutoCAD SHX Text
REMOTE DOOR OPERATOR VIA RELEASE BUTTON
AutoCAD SHX Text
SC
AutoCAD SHX Text
SECURITY CONTRACTOR
AutoCAD SHX Text
1. WITHIN THE PROJECT AREA, REMOVE ALL CONDUIT, WIRING, DEVICES, EQUIPMENT, AND ANY OTHER ELECTRICAL APPURTENANCES RENDERED USELESS, CURRENTLY ABANDONED OR WITHIN THE PROJECT AREA, REMOVE ALL CONDUIT, WIRING, DEVICES, EQUIPMENT, AND ANY OTHER ELECTRICAL APPURTENANCES RENDERED USELESS, CURRENTLY ABANDONED OR ABANDONED DUE TO CONSTRUCTION PER PHASE. REMOVAL OF ABANDONED AND USELESS WIRING SHALL BE BACK TO THE SOURCE, EVEN IF OUTSIDE LIMITS OF CONSTRUCTION. ROUGH-IN SHALL BE REMOVED BACK TO FLUSH WITH CONCRETE. ANCHORS SHALL BE REMOVED OR CUT FLUSH TO SURFACE OF CONCRETE. 2. EXISTING LIGHTS/DEVICES/WIRING TO REMAIN SHALL BE RE-FED AS REQUIRED TO MAINTAIN CIRCUIT CONTINUITY PER PHASE. EXISTING LIGHTS/DEVICES/WIRING TO REMAIN SHALL BE RE-FED AS REQUIRED TO MAINTAIN CIRCUIT CONTINUITY PER PHASE. 3. COORDINATE REMOVAL AND FINAL DISPOSITION OF EQUIPMENT WITH BUILDING OWNER PER THE GEMS PROGRAM. OWNER HAS FIRST RIGHT OF REFUSAL OF EQUIPMENT. COORDINATE REMOVAL AND FINAL DISPOSITION OF EQUIPMENT WITH BUILDING OWNER PER THE GEMS PROGRAM. OWNER HAS FIRST RIGHT OF REFUSAL OF EQUIPMENT. 4. PROVIDE BLANK STAINLESS STEEL COVER PLATES FOR ANY EXISTING JUNCTION BOXES FLUSH IN WALL THAT CANNOT BE FILLED OR PATCHED. PROVIDE BLANK STAINLESS STEEL COVER PLATES FOR ANY EXISTING JUNCTION BOXES FLUSH IN WALL THAT CANNOT BE FILLED OR PATCHED. 5. CLOSELY COORDINATE SCHEDULING OF PHASING WITH BUILDING OWNER AND OTHER TRADES. CLOSELY COORDINATE SCHEDULING OF PHASING WITH BUILDING OWNER AND OTHER TRADES. 6. MAINTAIN THE EXISTING CIRCUITS THAT ARE RUNNING THROUGH THE AREA BEING RENOVATED OR DEMOLISHED AND THE AREA OF NEW CONSTRUCTION. MAINTAIN THE EXISTING CIRCUITS THAT ARE RUNNING THROUGH THE AREA BEING RENOVATED OR DEMOLISHED AND THE AREA OF NEW CONSTRUCTION. 7. REMOVE EXISTING LIGHTS, SENSORS, FIRE ALARM DEVICES, WIRELESS ACCESS POINT DEVICES, PAGING SPEAKERS, SECURITY, AND EQUIPMENT LOCATOR DEVICES AND RELOCATE INTO REMOVE EXISTING LIGHTS, SENSORS, FIRE ALARM DEVICES, WIRELESS ACCESS POINT DEVICES, PAGING SPEAKERS, SECURITY, AND EQUIPMENT LOCATOR DEVICES AND RELOCATE INTO NEW CEILING IN AREAS WHERE CEILINGS ARE BEING REPLACED, AND WHERE INDICATED. 8. CONTRACTOR SHALL PROVIDE SUPPLEMENTAL EXIT AND EMERGENCY LIGHTING AND ASSOCIATED WIRING, AS NEEDED FROM PHASE TO PHASE, TO MAINTAIN PATHS OF EGRESS THAT CONTRACTOR SHALL PROVIDE SUPPLEMENTAL EXIT AND EMERGENCY LIGHTING AND ASSOCIATED WIRING, AS NEEDED FROM PHASE TO PHASE, TO MAINTAIN PATHS OF EGRESS THAT MAY CHANGE AS THE PHASING DEVELOPS. REFER TO THE ARCHITECTURAL LIFE SAFETY PLANS. 9. ALL ELECTRICAL, COMMUNICATIONS, SECURITY, FIRE ALARM DEVICES, FIXTURES, WIRING, ROUGH-IN, SUPPORTS, ETC. TO BE DISCONNECTED AND REMOVED BACK TO SOURCE OR ALL ELECTRICAL, COMMUNICATIONS, SECURITY, FIRE ALARM DEVICES, FIXTURES, WIRING, ROUGH-IN, SUPPORTS, ETC. TO BE DISCONNECTED AND REMOVED BACK TO SOURCE OR NEXT DEVICE TO REMAIN FOR EACH PHASED AREA OF RENOVATION TO FACILITATE WORK REQUIRED IN EACH PHASE. THIS INCLUDES ALL ABANDONED CABLING, ROUGH-IN, SUPPORTS, ETC. BACK TO A CLEAN DECK ABOVE. PROVIDE BLANK COVERS OVER FLUSH MOUNTED BOXES TO REMAIN. EXTRA ALL THREAD, ANCHOR BOLTS, MACHINE BOLTS, ETC. SHALL BE CUT AND BURRS REMOVED NO MORE THAN 3-5 THREADS ABOVE THE NUT OR THREADED CONNECTION. A MINIMUM OF 2 THREADS SHALL EXTEND PAST THE NUT ON ALL CONNECTIONS. ABANDONED CIRCUIT BREAKERS SHALL BE TURNED OFF AND LABELED AS SPARE.
AutoCAD SHX Text
SELECTIVE DEMOLITION NOTES:
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
TYPE
AutoCAD SHX Text
SYMBOL LEGEND
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
TYPE
AutoCAD SHX Text EXIT LIGHTING FIXTURE CONNECTED TO LIFE SAFETY BRANCH. PROVIDE FACES AS INDICATED ON DRAWINGS. CONNECT TO A CONSTANT HOT CONDUCTOR AHEAD OF LOCAL SWITCH. REFER TO LIGHTING FIXTURE SCHEDULE FOR ADDITIONAL INFORMATION.
AutoCAD SHX Text
QUADRUPLEX CONVENIENCE RECEPTACLE, 20A, 120V, MOUNT 18" AFF, UON.
AutoCAD SHX Text DUPLEX RECEPTACLE, 20A, 120V. SUBSCRIPT 'TV' DENOTES FOR CONNECTION TO TELEVISION, MOUNTED AT HEIGHT INDICATED.
AutoCAD SHX Text
GF
AutoCAD SHX Text
WP
AutoCAD SHX Text DUPLEX CONVENIENCE RECEPTACLE, GROUND FAULT INTERRUPTING TYPE, 20A, 120V, MOUNT 46" AFF, UON. (OR 6" ABOVE COUNTER AS APPLICABLE).
AutoCAD SHX Text DUPLEX RECEPTACLE, WEATHER RESISTANT GROUND FAULT INTERRUPTING TYPE WITH WET WHILE IN USE COVERPLATE, 20A, 120V, MOUNT 18" AFF, UON.
AutoCAD SHX Text S
AutoCAD SHX Text X
AutoCAD SHX Text LIGHTING CONTROL SYSTEM, LOCAL OCCUPANCY SENSOR, DUAL TECH, LINE VOLTAGE, WALL MOUNTED AT 46" AFF WITH INTEGRAL ON/OFF PUSH-BUTTON. PROVIDE AUXILIARY CONTACTS FOR FAN CONTROL WHERE NOTED. '2B' SUBSCRIPT DENOTES 2 BUTTONS FOR 2 ZONES.
AutoCAD SHX Text
OS
AutoCAD SHX Text
XXX
AutoCAD SHX Text SURFACE MOUNTED PANELBOARD 208/120 VOLT. DESIGNATION AS NOTED. REFER TO PANELBOARD SCHEDULES FOR ADDITIONAL INFORMATION.
AutoCAD SHX Text
TBB
AutoCAD SHX Text TELECOMMUNICATIONS BACKBOARD, 3/4" THICK X 8' HIGH X LENGTH PER PLANS, UON. BACKBOARD SHALL BE FIRE RATED.
AutoCAD SHX Text BRANCH CIRCUIT, OR FEEDER WIRING, RUN IN CONDUIT AND CIRCUIT HOMERUN TO PANELBOARD INDICATED. SINGLE PHASE CIRCUIT SHALL CONTAIN 1 #12 PHASE CONDUCTOR, 1 #12 NEUTRAL CONDUCTOR AND 1 #12 GROUNDING CONDUCTOR IN 3/4" CONDUIT, MINIMUM. CONDUCTORS LARGER THAN #12, AND CONDUIT LARGER THAN 3/4", SHALL BE AS INDICATED. WHERE "MULTIPLE PHASED" ELECTRICAL LOADS ARE REQUIRED, PROVIDE ADDITIONAL PHASE AND NEUTRAL CONDUCTORS AS INDICATED. MULTIPLE SINGLE PHASE CONDUCTORS MAY BE GROUPED TOGETHER IN A COMMON CONDUIT AS ALLOWED AND IN ACCORDANCE WITH THE NEC. CONTRACTOR SHALL PROVIDE ADDITIONAL "SWITCH LEG" CONDUCTORS, AS REQUIRED TO ACHIEVE FIXTURE CONTROL INDICATED ON PLANS. PROVIDE DEDICATED NEUTRAL CONDUCTOR FOR EACH SINGLE POLE CIRCUIT BREAKER. GROUNDING CONDUCTORS SHALL BE SHARED IN ACCORDANCE WITH AND AS ALLOWED BY THE NEC. WHEN SHOWN DASHED, IT SHALL DENOTE WIRING UNDERGROUND OR ABOVE TILE CEILING OF FLOOR BELOW.
AutoCAD SHX Text
1LA-3 (FOR EXAMPLE)
AutoCAD SHX Text SWITCH, 20A, 120/277V, MOUNT 46" AFF, UON. NO SUBSCRIPT DENOTES SINGLE POLE SWITCH. DENOTES SINGLE POLE SWITCH. SUBSCRIPT '3' DENOTES THREE WAY SWITCH. DENOTES THREE WAY SWITCH. SUBSCRIPT '4' DENOTES FOUR WAY SWITCH. DENOTES FOUR WAY SWITCH. SUBSCRIPT 'D' DENOTES DIMMER SWITCH. SIZE PER LIGHT SOURCE AND LOAD. DENOTES DIMMER SWITCH. SIZE PER LIGHT SOURCE AND LOAD. SUBSCRIPT 'VS' DENOTES VACANCY SENSOR DUAL TECHNOLOGY, LINE VOLTAGE, WALL MOUNTED AT DENOTES VACANCY SENSOR DUAL TECHNOLOGY, LINE VOLTAGE, WALL MOUNTED AT 46" AFF WITH ADJUSTABLE TIME, INTEGRAL PUSH-BUTTON FOR MANUAL ON AND AUTOMATIC OFF, DEFAULT TO 15-MINUTE.
AutoCAD SHX Text
RECEPTACLE 20A, 120V, MOUNT 18" AFF, UON.
AutoCAD SHX Text
CONDUIT WITH BUSHING.
AutoCAD SHX Text
CONDUIT TURNED UP.
AutoCAD SHX Text
CONDUIT TURNED DOWN.
AutoCAD SHX Text
CONDUIT CONTINUED
AutoCAD SHX Text
DUPLEX CONVENIENCE RECEPTACLE, RED FINISH, 20A, 120V, MOUNT 18" AFF, UON.
AutoCAD SHX Text SURFACE OR RECESSED LIGHTING FIXTURE ON NORMAL BRANCH, SEPARATELY SWITCHED CIRCUIT. REFER TO LUMINAIRE SCHEDULE FOR ADDITIONAL INFORMATION.
AutoCAD SHX Text LIGHTING CONTROL SYSTEM, LOCAL OCCUPANCY SENSOR, DUAL TECH, CEILING MOUNTED. PROVIDE POWER PACK AND WIRING AS REQUIRED. PROVIDE AUXILIARY CONTACTS FOR FAN CONTROL WHERE NOTED.
AutoCAD SHX Text
OS
AutoCAD SHX Text
XXX
AutoCAD SHX Text FLUSH MOUNTED PANELBOARD, 208/120 VOLT. DESIGNATION AS NOTED. REFER TO PANELBOARD SCHEDULES FOR ADDITIONAL INFORMATION.
AutoCAD SHX Text
TELECOMMUNICATIONS STYLE COPPER GROUND BAR WITH STAND-OFF INSULATORS.
AutoCAD SHX Text JUNCTION BOX, PROVIDE STANDARD 4" SQUARE BY 1-1/2" DEEP BOX, UON. CEILING MOUNTED. SUBSCRIPT "OHP" DENOTES OVERHEAD PROJECTOR. COORDINATE EXACT LOCATION IN THE FIELD.
AutoCAD SHX Text J
AutoCAD SHX Text
EWC
AutoCAD SHX Text DUPLEX RECEPTACLE, GROUND FAULT INTERRUPTING TYPE, FOR ELECTRIC WATER COOLER 20A, 120V, COORDINATE MOUNTING HEIGHT WITH PLUMBING CONTRACTOR PRIOR TO ROUGH-IN.
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text SWITCHES UNDER COMMON FACEPLATE USED FOR DUAL SWITCHING OF LIGHT FIXTURE WITHIN SAME ROOM, WALL MOUNTED AT 46" AFF.
AutoCAD SHX Text
OS
AutoCAD SHX Text LIGHTING CONTROL SYSTEM, LOCAL OCCUPANCY SENSOR, IR, LINE VOLTAGE, WALL MOUNTED AT 96" AFF WITH ADJUSTABLE HEAD, U.O.N. PROVIDE POWER PACK AND WIRING AS REQUIRED. ADJUST AIMING IN THE FIELD. MINIMUM OF 45' COVERAGE.
AutoCAD SHX Text
XXX
AutoCAD SHX Text SURFACE MOUNTED PANELBOARD/SWITCHBOARD 480/277 VOLT. DESIGNATION AS NOTED. REFER TO PANEL/SWITCHBOARD SCHEDULES FOR ADDITIONAL INFORMATION.
AutoCAD SHX Text
XXX
AutoCAD SHX Text FLUSH MOUNTED PANELBOARD, 480/277 VOLT. DESIGNATION AS NOTED. REFER TO PANELBOARD SCHEDULES FOR ADDITIONAL INFORMATION.
AutoCAD SHX Text T
AutoCAD SHX Text
PAD MOUNTED TRANSFORMER. REFER TO RISER DIAGRAM FOR ADDITIONAL INFORMATION.
AutoCAD SHX Text DUPLEX CONVENIENCE RECEPTACLE, TAMPER PROOF/RESISTANT TYPE, 20A, 120V, MOUNT 18" AFF, UON.
AutoCAD SHX Text
TP
AutoCAD SHX Text SURFACE OR RECESSED EMERGENCY LIGHTING FIXTURE ON LIFE SAFETY BRANCH CIRCUIT, CONNECTED AHEAD OF LOCAL SWITCHING. REFER TO LUMINAIRE SCHEDULE FOR ADDITIONAL INFORMATION.
AutoCAD SHX Text
NOTE: NOT ALL SYMBOLS MAY BE USED.
AutoCAD SHX Text E
AutoCAD SHX Text J
AutoCAD SHX Text JUNCTION BOX, PROVIDE STANDARD 4" SQUARE BY 1-1/2" DEEP BOX, UON. WALL MOUNTED AT 18" AFF, UON. VERIFY MOUNTING HEIGHT IN THE FIELD. PROVIDE 3/4" C. UP TO CEILING. SUBSCRIPT 'SF' DENOTES SYSTEMS FURNITURE CONNECTION. SUBSCRIPT 'D', DENOTES VOICE/DATA CABLING/CONNECTIVITY AS NOTED. POWER WHIP TO BE PROVIDED BY FURNITURE PROVIDER AND INSTALLED BY E.C., E.C. TO PROVIDE 1-1/4" FLEXIBLE LIQUIDTIGHT CONDUIT FOR DATA WHIP. VERIFY EXACT LOCATION IN THE FIELD.
AutoCAD SHX Text
XX
AutoCAD SHX Text
GENERAL NOTES
AutoCAD SHX Text
1. ALL WORK SHALL CONFORM TO THE NATIONAL ELECTRICAL CODE, NFPA, STATE CODE, LOCAL AUTHORITY REQUIREMENTS, VA TIL GUIDELINES, VA HANDBOOKS, AND SPECIFICATIONS. ALL WORK SHALL CONFORM TO THE NATIONAL ELECTRICAL CODE, NFPA, STATE CODE, LOCAL AUTHORITY REQUIREMENTS, VA TIL GUIDELINES, VA HANDBOOKS, AND SPECIFICATIONS. 2. THE CONTRACTOR SHALL VISIT THE PREMISES AND THOROUGHLY FAMILIARIZE THEMSELVES WITH ALL DETAILS OF THE WORK AND WORKING CONDITIONS. VERIFY ALL FIELD CONDITIONS AND ADVISE THE ENGINEER OF ANY DISCREPANCY THAT MAY PREVENT OR HINDER THE THE CONTRACTOR SHALL VISIT THE PREMISES AND THOROUGHLY FAMILIARIZE THEMSELVES WITH ALL DETAILS OF THE WORK AND WORKING CONDITIONS. VERIFY ALL FIELD CONDITIONS AND ADVISE THE ENGINEER OF ANY DISCREPANCY THAT MAY PREVENT OR HINDER THE SPECIFIED WORK FROM BEING COMPLETED. 3. THE CONTRACTOR SHALL STUDY THE STRUCTURE AND FINISH CONDITIONS AFFECTING THEIR WORK AND SHALL COORDINATE THEIR WORK ACCORDINGLY. THE CONTRACTOR SHALL PROVIDE ALL ACCESSORIES, HANGERS, AND ANCHORS AS NECESSARY TO MEET SUCH CONDITIONS THE CONTRACTOR SHALL STUDY THE STRUCTURE AND FINISH CONDITIONS AFFECTING THEIR WORK AND SHALL COORDINATE THEIR WORK ACCORDINGLY. THE CONTRACTOR SHALL PROVIDE ALL ACCESSORIES, HANGERS, AND ANCHORS AS NECESSARY TO MEET SUCH CONDITIONS WITHOUT ANY ADDITIONAL COST TO THE GOV'T. 4. PRIOR TO ACCOMPLISHING ANY WORK IN ANY AREA, ALL WORK, ESPECIALLY OUTAGES, SHALL BE COORDINATED AND SCHEDULED AHEAD OF TIME WITH WRITTEN APPROVAL FROM THE GOVERNMENT. PRIOR TO ACCOMPLISHING ANY WORK IN ANY AREA, ALL WORK, ESPECIALLY OUTAGES, SHALL BE COORDINATED AND SCHEDULED AHEAD OF TIME WITH WRITTEN APPROVAL FROM THE GOVERNMENT. 5. PROPERLY SUPPORT ALL WORK AND EQUIPMENT INSTALLED UNDER THIS CONTRACT. STUDY ALL DRAWINGS, MANUFACTURER'S INSTRUCTIONS, AND CATALOG DATA TO DETERMINE HOW EQUIPMENT ACCESSORIES, AND RELATED ITEMS ARE TO BE SUPPORTED, MOUNTED, OR PROPERLY SUPPORT ALL WORK AND EQUIPMENT INSTALLED UNDER THIS CONTRACT. STUDY ALL DRAWINGS, MANUFACTURER'S INSTRUCTIONS, AND CATALOG DATA TO DETERMINE HOW EQUIPMENT ACCESSORIES, AND RELATED ITEMS ARE TO BE SUPPORTED, MOUNTED, OR SUSPENDED. PROVIDE ALL BOLTS, INSERTS, BRACKETS, STRUCTURAL SUPPORTS, AND ACCESSORIES FOR PROPER SUPPORT OF EQUIPMENT FURNISHED UNDER THIS CONTRACT. 6. ALL WORK SHOWN LIGHT AND SOLID IS EXISTING TO REMAIN. ALL WORK SHOWN BOLD AND SOLID ON A NEW WORK PLAN IS NEW. ALL WORK SHOW BOLD AND/OR DASHED ON A DEMOLITION PLAN IS EXISTING TO BE DEMOLISHED. ALL WORK SHOWN LIGHT AND SOLID IS EXISTING TO REMAIN. ALL WORK SHOWN BOLD AND SOLID ON A NEW WORK PLAN IS NEW. ALL WORK SHOW BOLD AND/OR DASHED ON A DEMOLITION PLAN IS EXISTING TO BE DEMOLISHED. 7. COORDINATE MOUNTING HEIGHT AND LOCATION OF ALL WALL MOUNTED EQUIPMENT WITH ARCHITECTURAL ELEVATIONS. COORDINATE MOUNTING HEIGHT AND LOCATION OF ALL WALL MOUNTED EQUIPMENT WITH ARCHITECTURAL ELEVATIONS. 8. THE DRAWINGS ARE DIAGRAMMATIC IN NATURE AND DO NOT SHOW ALL POSSIBLE CONDITIONS. THE INSTALLATION SHALL BE FULLY COORDINATED WITH ALL EXISTING ARCHITECTURAL AND STRUCTURAL ELEMENTS. CONTRACTOR SHALL FIELD VERIFY AND CONFIRM ALL EXISTING THE DRAWINGS ARE DIAGRAMMATIC IN NATURE AND DO NOT SHOW ALL POSSIBLE CONDITIONS. THE INSTALLATION SHALL BE FULLY COORDINATED WITH ALL EXISTING ARCHITECTURAL AND STRUCTURAL ELEMENTS. CONTRACTOR SHALL FIELD VERIFY AND CONFIRM ALL EXISTING CONDITIONS AND ALLOW FOR ALL OFFSETS, REROUTING, ETC. AT NO ADDITIONAL COST TO THE GOVERNMENT. SHOULD THE CONTRACTOR ENCOUNTER ANY EXISTING EQUIPMENT, PIPING, DUCTWORK, ELECTRICAL, ETC. THAT INTERFERES WITH NEW WORK INSTALLATION, THEY SHALL REMOVE, RELOCATE AND REINSTALL SAME AT NO ADDITIONAL COST TO THE GOVERNMENT. 9. ALL LOW VOLTAGE CABLING SHALL BE INSTALLED IN EITHER BASKET STYLE CABLE TRAY OR J-HOOKS, WITH THE EXCEPTION OF THE FIRE ALARM SYSTEM THAT MUST BE IN CONDUIT. NO CABLING SHALL BE SUPPORTED OFF OF CONDUITS, PIPING, DUCTWORK, SHARED ALL LOW VOLTAGE CABLING SHALL BE INSTALLED IN EITHER BASKET STYLE CABLE TRAY OR J-HOOKS, WITH THE EXCEPTION OF THE FIRE ALARM SYSTEM THAT MUST BE IN CONDUIT. NO CABLING SHALL BE SUPPORTED OFF OF CONDUITS, PIPING, DUCTWORK, SHARED SUPPORTS, ETC. NO CABLING SHALL BE DRAPED ACROSS OTHER EQUIPMENT, RACEWAYS, DUCTWORK, LIGHTS OR CEILING GRID. SUPPORT CABLING INDIVIDUALLY. 10. PROVIDE HOOK AND LOOP FASTENERS ON BUNDLES OF LIKE CABLES ON 10' CENTERS WITHIN BASKET CABLE TRAY, ON 3' CENTERS ON CABLE RUNWAY WITHIN THE TELECOM ROOM AND ON 6" CENTERS FROM RUNWAY TO FINAL TERMINATION WITH THE RESPECTIVE RACKS, PROVIDE HOOK AND LOOP FASTENERS ON BUNDLES OF LIKE CABLES ON 10' CENTERS WITHIN BASKET CABLE TRAY, ON 3' CENTERS ON CABLE RUNWAY WITHIN THE TELECOM ROOM AND ON 6" CENTERS FROM RUNWAY TO FINAL TERMINATION WITH THE RESPECTIVE RACKS, CABINETS, PUNCHDOWN BLOCKS, ETC. 11. FOR CABLING ROUTED ON WALLS WITHIN THE TELECOM ROOM THAT IS NOT TERMINATED INTO ONE OF THE RACKS, ROUTE CABLING ON WALL WITHIN D RINGS OR VERTICAL CABLE RUNWAY TO TRAIN CABLING TO AVOID SAGGING AND STRAINING. FOR CABLING ROUTED ON WALLS WITHIN THE TELECOM ROOM THAT IS NOT TERMINATED INTO ONE OF THE RACKS, ROUTE CABLING ON WALL WITHIN D RINGS OR VERTICAL CABLE RUNWAY TO TRAIN CABLING TO AVOID SAGGING AND STRAINING. 12. PROVIDE ALL LOW VOLTAGE POWER SUPPLIES AS REQUIRED TO SUPPORT THE LOW VOLTAGE SYSTEMS NEEDS. PROVIDE ALL LOW VOLTAGE POWER SUPPLIES AS REQUIRED TO SUPPORT THE LOW VOLTAGE SYSTEMS NEEDS. 13. THE LIGHTING CONTROLS AND LOW VOLTAGE SYSTEMS ARE TO BE COMMISSIONED AND FULLY TESTED BY A MANUFACTURER'S AUTHORIZED REPRESENTATIVE. THE LIGHTING CONTROLS AND LOW VOLTAGE SYSTEMS ARE TO BE COMMISSIONED AND FULLY TESTED BY A MANUFACTURER'S AUTHORIZED REPRESENTATIVE. 14. REFER TO ARCHITECTURAL LIFE SAFETY PLAN FOR THE LOCATION ALL FIRE RATED WALLS/PARTITIONS/BARRIERS AND APPLY THE APPROPRIATE UL FIRE PENETRATION DETAIL. REFER TO ARCHITECTURAL LIFE SAFETY PLAN FOR THE LOCATION ALL FIRE RATED WALLS/PARTITIONS/BARRIERS AND APPLY THE APPROPRIATE UL FIRE PENETRATION DETAIL. 15. CONTRACTOR TO SUBMIT QUALIFICATIONS FOR SUPERINTENDENT AND KEY PERSONNEL FOR EACH (SUB)CONTRACTOR AS PART OF THE SHOP DRAWING PROCESS. CONTRACTOR TO SUBMIT QUALIFICATIONS FOR SUPERINTENDENT AND KEY PERSONNEL FOR EACH (SUB)CONTRACTOR AS PART OF THE SHOP DRAWING PROCESS. 16. CONTRACTOR TO TAKE AND DOWN AND REPLACE EXISTING CEILINGS AS REQUIRED TO FACILITATE NEW CONDUIT/WIRING INSTALLATION THAT IS PART OF THIS PROJECT. CONTRACTOR TO TAKE AND DOWN AND REPLACE EXISTING CEILINGS AS REQUIRED TO FACILITATE NEW CONDUIT/WIRING INSTALLATION THAT IS PART OF THIS PROJECT. 17. CONTRACTOR TO PATCH ALL HOLES IN FLOOR/WALLS/CEILINGS, THAT WERE CREATED AS A RESULT OF THIS PROJECT, WITH APPROPRIATE MATERIALS. CONTRACTOR TO PATCH ALL HOLES IN FLOOR/WALLS/CEILINGS, THAT WERE CREATED AS A RESULT OF THIS PROJECT, WITH APPROPRIATE MATERIALS. 18. CONTRACTOR SHALL SUBMIT COORDINATION DRAWINGS FOR ALL WORK, INCLUDING CONDUIT AND CABLE TRAY ROUTINGS, TO BE INSTALLED UNDER THIS PROJECT CONTRACT. COORDINATION DRAWINGS SHALL INDICATE ALL STRUCTURE, EQUIPMENT AND ROUTING OF PIPING, CONTRACTOR SHALL SUBMIT COORDINATION DRAWINGS FOR ALL WORK, INCLUDING CONDUIT AND CABLE TRAY ROUTINGS, TO BE INSTALLED UNDER THIS PROJECT CONTRACT. COORDINATION DRAWINGS SHALL INDICATE ALL STRUCTURE, EQUIPMENT AND ROUTING OF PIPING, DUCTWORK, ELECTRICAL, CONTROLS, SPRINKLERS AND FIRE ALARM SYSTEM. NO WORK SHALL BE COMMENCED PRIOR TO RECEIPT OF APPROVAL COORDINATION DRAWINGS FROM COR. COORDINATION DRAWINGS SHALL BE AT SCALES OF 1/4" = 1'-0" AND INCLUDE PLANS AND ELEVATIONS. 19. CONTRACTOR SHALL CONFORM TO ICRA AND ILSM REQUIREMENTS OF THIS PROJECT AS MANDATED BY VA INFECTION CONTROL AND SAFETY DEPARTMENT. ALL DEMOLISHED EQUIPMENT SHALL FOLLOW THE VA GEMS GUIDELINES. CONTRACTOR SHALL UTILIZE A EDGEGUARD OR CONTRACTOR SHALL CONFORM TO ICRA AND ILSM REQUIREMENTS OF THIS PROJECT AS MANDATED BY VA INFECTION CONTROL AND SAFETY DEPARTMENT. ALL DEMOLISHED EQUIPMENT SHALL FOLLOW THE VA GEMS GUIDELINES. CONTRACTOR SHALL UTILIZE A EDGEGUARD OR EQUAL INFECTION CONTROL CONTROL CONTAINMENT WALL SOLUTION. 20. ALL RENOVATION WORK IN THIS PROJECT SHALL RESULT IN A SYSTEM THAT IS COMPLETE AND FULLY OPERATIONAL WITHOUT MISSING ANCILLARY COMPONENTS. ALL RENOVATION WORK IN THIS PROJECT SHALL RESULT IN A SYSTEM THAT IS COMPLETE AND FULLY OPERATIONAL WITHOUT MISSING ANCILLARY COMPONENTS. 21. ALL NEW CONDUITS SHALL BE INSTALLED TIGHT TO DECK OR AS HIGH AS POSSIBLE, UNLESS AN EXCEPTION IS REQUESTED BY THE CONTRACTING OFFICER AND GRANTED, IN WRITING, BY THE COR. ALL NEW CONDUITS SHALL BE INSTALLED TIGHT TO DECK OR AS HIGH AS POSSIBLE, UNLESS AN EXCEPTION IS REQUESTED BY THE CONTRACTING OFFICER AND GRANTED, IN WRITING, BY THE COR. 22. ALL RACEWAYS SHALL BE INSTALLED PARALLEL WITH WALLS, CEILINGS AND STRUCTURE AND SHALL BE INSTALLED ABOVE ALL OTHER UTILITIES. ALL RACEWAYS SHALL BE INSTALLED PARALLEL WITH WALLS, CEILINGS AND STRUCTURE AND SHALL BE INSTALLED ABOVE ALL OTHER UTILITIES. 23. EACH SYSTEMS CONDUITS/J-HOOKS/CABLE TRAYS TO BE SUPPORTED INDIVIDUALLY, TIGHT TO THE STRUCTURE, UNLESS REQUESTED BY THE CONTRACTING OFFICER AND APPROVED IN WRITING BY THE COR. EACH SYSTEMS CONDUITS/J-HOOKS/CABLE TRAYS TO BE SUPPORTED INDIVIDUALLY, TIGHT TO THE STRUCTURE, UNLESS REQUESTED BY THE CONTRACTING OFFICER AND APPROVED IN WRITING BY THE COR. 24. PROJECT SHALL BE COMPLETED IN PHASES PER THE ARCHITECTURAL DRAWINGS. PROJECT SHALL BE COMPLETED IN PHASES PER THE ARCHITECTURAL DRAWINGS. 25. CONNECT PAGING SPEAKERS TO THE EXISTING FACILITY SYSTEM. CONNECT PAGING SPEAKERS TO THE EXISTING FACILITY SYSTEM. 26. CONTRACTOR SHALL XRAY SCAN THE FLOOR BEFORE CORE DRILLING.CONTRACTOR SHALL XRAY SCAN THE FLOOR BEFORE CORE DRILLING.
AutoCAD SHX Text EQUIPMENT CONNECTION, AS NOTED. REFER TO EQUIPMENT CONNECTION SCHEDULE FOR DETAILS.
AutoCAD SHX Text FLOOR MOUNTED, 2-GANG, FLOOR BOX ASSEMBLY WITH (2) DUPLEX CONVENIENCE RECEPTACLES, 20A, 120V, AND 1 GANG COMMUNICATION PROVISIONS. SURFACE MOUNTED ON FLOOR, FINISH AS COORDINATED WITH THE ARCHITECT. LEGRAND CONNECTRAC OR EQUAL. PROVIDE ALL ANCILLIARY PARTS AND EQUIPMENT FOR A COMPLETE SYSTEM, INCLUDING THE UNDERCARPET RACEWAY. ROUTE UNDERCARPET POWER RACEWAY TO NEAREST WALL THEN TRANSITION TO 1-1/4"C INSTALLED AND CONCEALED IN WALL. COORDINATE EXACT LOCATION IN THE FIELD WITH FURNITURE INSTALLER.
AutoCAD SHX Text SPECIAL PURPOSE RECEPTACLE. CONFIRM EXACT NEMA CONFIGURATION AND REQUIREMENTS WITH EQUIPMENT PROVIDER. MOUNT 46" AFF, UON.
AutoCAD SHX Text TELECOMMUNICATIONS OUTLET AT 18" AFF, 4-11/16" SQUARE BY 2-1/8" DEEP BOX, UON. PROVIDE 1-1/4" CONDUIT STUBBED UP TO NEAREST ACCESSIBLE GRID CEILING WITH DATA CABLES AND JACKS IN SINGLE GANG FACEPLATE, UON. PROVIDE 12" SERVICE LOOP PRIOR TO DROPPING DOWN TO OUTLET.
AutoCAD SHX Text TELECOMMUNICATIONS OUTLET AT 46" AFF, 4-11/16" SQUARE BY 2-1/8" DEEP BOX, UON. PROVIDE 1-1/4" CONDUIT STUBBED UP TO NEAREST ACCESSIBLE GRID CEILING WITH DATA CABLES AND JACKS IN SINGLE GANG FACEPLATE, UON. PROVIDE 12" SERVICE LOOP PRIOR TO DROPPING DOWN TO OUTLET. SUBSCRIPT 'HW' DENOTES MOUNTED IN HEADWALL.
AutoCAD SHX Text
PAGING SYSTEM, FLUSH CEILING SPEAKER.
AutoCAD SHX Text S
AutoCAD SHX Text CATV SYSTEM, TELEVISION OUTLET, WITH F CONNECTOR AND RG-6 CABLE, WALL MOUNTED AT HEIGHT SAME AS ADJACENT RECEPTACLE.
AutoCAD SHX Text
TV
AutoCAD SHX Text FLOOR MOUNTED, 2-GANG, FLOOR BOX ASSEMBLY 1 GANG COMMUNICATION PROVISIONS. SURFACE MOUNTED ON FLOOR, FINISH AS COORDINATED WITH THE ARCHITECT. LEGRAND CONNECTRAC OR EQUAL. PROVIDE ALL ANCILLIARY PARTS AND EQUIPMENT FOR A COMPLETE SYSTEM, INCLUDING THE UNDERCARPET RACEWAY. ROUTE UNDERCARPET COMMUNICATIONS RACEWAY TO NEAREST WALL THEN TRANSITION TO 1-1/4"C INSTALLED AND CONCEALED IN WALL. COORDINATE EXACT LOCATION IN THE FIELD WITH FURNITURE INSTALLER.
AutoCAD SHX Text TELECOM AP OUTLET, FLUSH MOUNTED IN CEILING, 4-11/16"SQ X 2-1/8"D BOX. REFER TO DETAILS & RISER.
AutoCAD SHX Text
WAP
AutoCAD SHX Text WIREBASKET CABLE TRAY AS NOTED, FURNISHED, INSTALLED & SUPPORTED BY T.C., FOR INSTALLATION OF CABLING BY T.C., 12"W X 4"D, LOCATED MIN. OF 4" ABOVE ACCESS. CEILING, W/ 12" TOP & 36" SIDE CLEARANCE. PROVIDE ALL REQUIRED OFFSETS FOR CONTINUOUS RUN.
AutoCAD SHX Text TELECOM OUTLET SEMI-FLUSH MOUNTED ON SYSTEMS FURNITURE RACEWAY. PROVIDE SHARED 1-1/4" FLEXIBLE CONDUIT FROM SHARED 4-11/16"SQ. X 2-1/8"D BOX ON WALL, 1-1/4"C. TO J-HOOKS AND CONTINUE ON TO T.R. REFER TO OUTLET AND FACEPLATE DETAILS & RISER.
AutoCAD SHX Text TELECOMMUNICATIONS OUTLET, 4-11/16" SQUARE BY 2-1/8" DEEP BOX, UON. PROVIDE 1-1/4" CONDUIT STUBBED UP TO NEAREST ACCESSIBLE GRID CEILING WITH DATA CABLES AND JACKS IN SINGLE GANG FACEPLATE, UON. PROVIDE 12" SERVICE LOOP PRIOR TO DROPPING DOWN TO OUTLET. MOUNT NEXT TO ADJACENT RECEPTACLE.
TV
E-802
ELECTRICAL - DETAILS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY- SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Atriax, pllc
102 3rd Avenue, NE Hickory, NC 28601
P.O. Box 1629, Hickory, NC 28603
PH: 828-315-9962
www.atriaxgroup.com
RENOVATE 4B FOR MEDICAL
CENTER SUPPORT SPACE
Fayetteville VAMC Fayetteville, NC
565-17-305
Project Director
March 31, 2022Revisions: Date:
FINAL CONSTRUCTION
DOCUMENTSELECTRICAL:
QUALITY CONSULTING ENGINEERS, LLC
6277-600 Carolina Commons Dr. #350 Indian Land, SC 29707
(P) 803.207.5450 djones@qualityconsultingengineers.com
QCE PROJECT# 21007
MECHANICAL / PLUMBING:
SHULTZ ENGINEERING GROUP, PC
212 N. McDowell St, Suite 204 Charlotte, NC 28204
(P) 704.334.7363 www.shultzeg.com
DAJ GSB
Date: MARCH 31, 2022
Date: MARCH 31, 2022
O
R
A
F C
CEILING LINE
DRYWALL
FINISHED FLOOR
CONDUIT TO NEARBY CABLE TRAY ABOVE CEILING
BY E.C. AND CABLING BACK TO TELECOM RM ON
SAME FLOOR BY T.C.
INSULATED BUSHING
EMT CONNECTOR
P1 S1
LOW VOLTAGE BASE COMPARTMENT IN SYSTEMS
FURNITURE. FURNITURE IS TO BE BY THE FURNITURE
CONTRACTOR. COMMUNICATIONS CABLING, JACKS,
FACEPLATES, PATCH PANELS, TERMINATIONS, ETC. BY
T.C.
CAT6A
BLUE
CAT6A
BLUE
O
R
A
F C
CEILING LINE
DRYWALL
S
Q U
A R
E
2-1/8"
FINISHED FLOOR
BASE
COMPARTMENT
OF SYSTEMS FURNITURE
1-1/4" FLEX FROM BLANK COVER IN WALL BOX TO
SYSTEMS FURNITURE
BY E.C.
REFER TO SYSTEMS FURNITURE
OUTLET DETAIL THIS SHEET
1-1/4" CONDUIT TO ABOVE CEILING NEARBY CABLE TRAY BY
E.C., CABLING BY T.C.
INSULATED BUSHING
BY E.C.
EMT CONNECTOR, BY E.C.
EXTENDED DEPTH SYSTEMS FURNITURE FACEPLATE BY
T.C., COORDINATE WITH FURNITURE CONTRACTOR.
FURNITURE WILL PROVIDE A "KNOCK OUT" IN THE PANEL
BASE RACEWAY WHERE THE T.C. WILL PROVIDE THEIR
FACEPLATE.
SF
2 - 8 POSITION / 8 CONNECTOR CAT6A RJ 45
2 - BLANKS
2 - 4 PAIR CAT6A UTP CABLES (WHITE)
1 - MODULAR FURNITURE FACEPLATE
CONDUIT SCHEDULE:
UP TO 5 CAT6A CABLES = 3/4" CONDUIT
UP TO 8 CAT6A CABLES = 1" CONDUIT
UP TO 14 CAT6A CABLES = 1-1/4" CONDUIT
BOX SCHEDULE:
UP TO 5 CAT6A CABLES = 4"SQ. x 1-1/2"D
UP TO 8 CAT6A CABLES = 4-11/16"SQ. x 2-1/8"D
UP TO 14 CAT6A CABLES = 4-11/16"SQ. x 2-1/8"D
CONDUIT SCHEDULE:
UP TO 4 CAT6A CABLES = 1" CONDUIT
UP TO 8 CAT6A CABLES = 1-1/4" CONDUIT
AutoCAD SHX Text
AutoCAD SHX Text
8 POSITION / 8 CONNECTOR E1A/T1A-568B WIRING
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text W-O
AutoCAD SHX Text O
AutoCAD SHX Text W-G
AutoCAD SHX Text
BL
AutoCAD SHX Text
W-BL
AutoCAD SHX Text G
AutoCAD SHX Text
W-BR
AutoCAD SHX Text
BR
AutoCAD SHX Text
PAIR 1
AutoCAD SHX Text
PAIR 3
AutoCAD SHX Text
PAIR 2
AutoCAD SHX Text
PAIR 4
AutoCAD SHX Text
TELECOMMUNICATIONS - TYPICAL CAT6A RJ45 JACK
AutoCAD SHX Text
SCALE: N.T.S.
AutoCAD SHX Text
AutoCAD SHX Text
OUTLET LABEL
AutoCAD SHX Text
SINGLE GANG
AutoCAD SHX Text A
AutoCAD SHX Text
OUTLET RM # - 1
AutoCAD SHX Text B
AutoCAD SHX Text
FIBER CABLE
AutoCAD SHX Text
24 FIBER SM/MM
AutoCAD SHX Text F01 1-24
AutoCAD SHX Text
FIBER
AutoCAD SHX Text
SINGLE OR MULTIMODE
AutoCAD SHX Text
CABLE
AutoCAD SHX Text
BACKBONE CABLE LABEL
AutoCAD SHX Text 2A/G070 - 2/128
AutoCAD SHX Text
CABLE NUMBER
AutoCAD SHX Text
200PR 24 AWG
AutoCAD SHX Text C01 201-400
AutoCAD SHX Text
TERMINATION LOCATIONS
AutoCAD SHX Text
CABLE GAUGE
AutoCAD SHX Text
CABLE SIZE
AutoCAD SHX Text
TERMINATED COUNT
AutoCAD SHX Text
TMGB
AutoCAD SHX Text
ER1
AutoCAD SHX Text
TR
AutoCAD SHX Text
TBB
AutoCAD SHX Text
TBB
AutoCAD SHX Text
TELECOMMUNICATIONS ROOM
AutoCAD SHX Text
TGB
AutoCAD SHX Text
TGB
AutoCAD SHX Text
TELECOMMUNICATIONS MAIN GROUNDING BUSBAR
AutoCAD SHX Text
EQUIPMENT ROOM
AutoCAD SHX Text
GROUND BAR LABEL
AutoCAD SHX Text G070-R1-A-1
AutoCAD SHX Text
HORIZONTAL CABLE LABEL
AutoCAD SHX Text
TELECOMMUNICATIONS ROOM
AutoCAD SHX Text
PATCH PANEL
AutoCAD SHX Text Jacks shall be arranged and labeled according to their location in a room. They shall be arranged clockwise in ascending order around the room while standing in the doorway looking into the room. Jack number arrangements should work in clockwise order, as you enter the room. This labeling scheme adheres to the requirements outlined in the TIA/EIA 606 telecommunications standard. Labels on cables are to be the non-adhesive heat shrink style using a printer. Details are generic while nameplates shall be specific based on installed field conditions.
AutoCAD SHX Text A
AutoCAD SHX Text
PATCH PANEL LABEL
AutoCAD SHX Text
PATCH PANEL LETTER
AutoCAD SHX Text
OUTLET PORT LOCATION
AutoCAD SHX Text
JACK
AutoCAD SHX Text
RACK
AutoCAD SHX Text
2A/G070 - 143/BG120
AutoCAD SHX Text
TERMINATION LOCATIONS
AutoCAD SHX Text A
AutoCAD SHX Text G070-R2-A
AutoCAD SHX Text B
AutoCAD SHX Text
RACK DESCRIPTION AND NUMBER
AutoCAD SHX Text
DATA RACK R3
AutoCAD SHX Text
RACK LABEL
AutoCAD SHX Text
TELECOMMUNICATIONS - TYPICAL LABELING
AutoCAD SHX Text
SCALE: N.T.S.
AutoCAD SHX Text
AutoCAD SHX Text
1 - F TYPE CONNECTOR 1 - RG6U COAXIAL CABLE
AutoCAD SHX Text
AutoCAD SHX Text
TELECOMMUNICATIONS - TYPICAL CATV FACEPLATE
AutoCAD SHX Text
SCALE: N.T.S.
AutoCAD SHX Text
3 - 8-PIN RJ45 MODULAR CONNECTORS 3 - 4 PAIR CAT6A UTP CABLES
AutoCAD SHX Text
TYPICAL 3 PORT OIT FACEPLATE
AutoCAD SHX Text
SCALE: N.T.S.
AutoCAD SHX Text
AutoCAD SHX Text
INSTALLED ROOM NUMBER FOLLOWED BY SEQUENTIAL NUMBERING WITHIN ROOM
AutoCAD SHX Text
TELECOM ROOM SOURCE NUMBER FOLLOWED BACK RACK NUMBER AND PATCH PANEL NUMBER
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text
XXX
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text
XXX
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text
XXX
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text
XXX
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text
XXX
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text
XXX
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text
XXX
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text
XXX
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text
XXX
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text
XXX
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text
XXX
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text
XXX
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text
XXX
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text
XXX
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text
XXX
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text
XXX
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text
XXX
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text
XXX
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text
XXX
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text
XXX
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text
XXX
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text
XXX
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text
XXX
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text
XXX
AutoCAD SHX Text
PORT LABEL
AutoCAD SHX Text
TELECOMMUNICATIONS -
AutoCAD SHX Text J
AutoCAD SHX Text
TELECOMMUNICATIONS - SYSTEMS FURNITURE DETAIL
AutoCAD SHX Text
SCALE: N.T.S.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
TELECOMMUNICATIONS - TYPICAL SYSTEMS FURNITURE ROUGH-IN
AutoCAD SHX Text
SCALE: N.T.S.
AutoCAD SHX Text
TELECOMMUNICATIONS - TYPICAL WALL OUTLET ROUGH-IN
AutoCAD SHX Text
SCALE: N.T.S.
AutoCAD SHX Text
AutoCAD SHX Text
FACEPLATE LABEL
AutoCAD SHX Text
BLANK
AutoCAD SHX Text
BLUE JACK/BLUE CABLE
AutoCAD SHX Text D1
AutoCAD SHX Text
FACEPLATE LABEL
AutoCAD SHX Text D3
AutoCAD SHX Text
WHITE JACK/BLUE CABLE
AutoCAD SHX Text D2
BLUE JACK/BLUE CABLE
EC4B
ETR
J3
ETR
ES4B ETR
EC4A1
ETR
EC4A2
ETR
N4A1
ETR
N4A2
ETR
EE4A
ETR
ES4A
ETR
J2
ETR
ED-101
ELECTRICAL - FOURTH FLOOR PLAN -
DEMOLITION
SCALE: 1/8" = 1'-0"
ELECTRICAL - FOURTH FLOOR PLAN - DEMOLITION
A. REMOVE DEVICES, SYSTEMS, AND ASSOCIATED WIRING AND CONDUIT WITHIN THE AREA TO BE ALTERED OR AS REQUIRED TO
FACILITATE NEW CONSTRUCTION. WIRING AND CONDUIT SHALL BE REMOVED BACK TO NEAREST REMAINING DEVICE. ABANDONED
CIRCUIT BREAKERS SHALL BE TURNED OFF AND LABELED AS SPARE.
B. REMOVE ALL CONDUIT, FITTINGS, BOXES, SUPPORTS, WIRING, WIRING DEVICES, LOW VOLTAGE CABLING/DEVICES, EQUIPMENT
CONNECTIONS INCLUDING THE INDIVIDUAL ROOM THRU THE WALL UNITS, AND ANY OTHER ELECTRICAL APPURTENANCES
RENDERED USELESS OR ABANDONED DUE TO CONSTRUCTION, UNLESS OTHERWISE NOTED. REMOVAL OF ABANDONED AND
USELESS WIRING SHALL BE BACK TO THE SOURCE, EVEN IF OUTSIDE LIMITS OF CONSTRUCTION.
C. EXISTING DEVICES TO REMAIN SHALL BE RE-FED AS REQUIRED TO MAINTAIN CIRCUIT CONTINUITY.
D. COORDINATE REMOVAL AND FINAL DISPOSITION OF EQUIPMENT WITH BUILDING OWNER, PER THE VA GEMS GUIDELINES.
E. PROVIDE BLANK STAINLESS STEEL COVER PLATES FOR ANY EXISTING JUNCTION BOXES FLUSH IN WALL THAT CANNOT BE FILLED
OR PATCHED.
F. MAINTAIN THE EXISTING CIRCUITS THAT ARE RUNNING THROUGH THE AREA BEING RENOVATED OR DEMOLISHED AND THE AREA
OF NEW CONSTRUCTION.
G. TEMPORARILY SUPPORT ANY AND ALL EXISTING CEILING MOUNTED WIRELESS ACCESS POINT DEVICES, PAGING SPEAKERS, SECURITY CAMERAS, AND EQUIPMENT/STAFF/PATIENT LOCATOR DEVICES AND RELOCATE INTO NEW CEILINGS ACCORDING TO
NEW FLOOR PLAN LAYOUT.
H. NO WORK IN HATCHED AREAS.
GENERAL NOTES:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY- SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Atriax, pllc
102 3rd Avenue, NE Hickory, NC 28601
P.O. Box 1629, Hickory, NC 28603
PH: 828-315-9962
www.atriaxgroup.com
RENOVATE 4B FOR MEDICAL
CENTER SUPPORT SPACE
Fayetteville VAMC Fayetteville, NC
565-17-305
Project Director
March 31, 2022Revisions: Date:
FINAL CONSTRUCTION
DOCUMENTSELECTRICAL:
QUALITY CONSULTING ENGINEERS, LLC
6277-600 Carolina Commons Dr. #350 Indian Land, SC 29707
(P) 803.207.5450 djones@qualityconsultingengineers.com
QCE PROJECT# 21007
MECHANICAL / PLUMBING:
SHULTZ ENGINEERING GROUP, PC
212 N. McDowell St, Suite 204 Charlotte, NC 28204
(P) 704.334.7363 www.shultzeg.com
DAJ GSB
Date: MARCH 31, 2022
1. IT IS UNDERSTOOD THAT THE TELECOM CABLING AND ACCESS CONTROLS IN THIS AREA OF RENOVATION ROUTES BACK TO THIS
TELECOM ROOM. DEMOLISH ALL EXISTING TELECOM AND ACCESS CONTROL EQUIPMENT, WIRING, CONDUIT, ETC. BACK TO THIS
ROOM, UNLESS OTHERWISE NOTED.
2. IT IS UNDERSTOOD THAT THE FIRE ALARM AND NURSE CALL SYSTEM CABLING IN THIS AREA OF RENOVATION ROUTES BACK TO
THIS ROOM . DEMOLISH ALL EXISTING FIRE ALARM AND NURSE CALL EQUIPMENT, WIRING, CONDUIT, ETC. BACK TO BOTH OR
EITHER OF THESE TWO ROOMS, UNLESS OTHERWISE NOTED.
3. IT IS UNDERSTOOD THAT THE TV COAX CABLING IN THIS AREA OF RENOVATION ROUTES BACK TO THIS ROOM. DEMOLISH ALL
EXISTING TV EQUIPMENT, WIRING, CONDUIT, ETC. BACK TO BOTH OR EITHER OF THESE TWO ROOMS, UNLESS OTHERWISE NOTED.
4. IT IS UNDERSTOOD THAT THE EQUIPMENT/STAFF/PATIENT LOCATOR CABLING IN THIS AREA OF RENOVATION ROUTES BACK TO
THIS ROOM. DEMOLISH ALL EXISTING LOCATOR EQUIPMENT, WIRING, CONDUIT, ETC. BACK TO BOTH OR EITHER OF THESE TWO
ROOMS, UNLESS OTHERWISE NOTED.
5. IT IS UNDERSTOOD THAT THE NORMAL AND EMERGENCY CIRCUITS IN THIS AREA OF RENOVATION ROUTE BACK TO PANELS IN THIS
ROOM. DEMOLISH ALL EXISTING WIRING, CONDUIT, ETC. BACK TO BOTH OR EITHER OF THESE TWO ROOMS, UNLESS OTHERWISE
NOTED.
KEYNOTES:
X
AutoCAD SHX Text
SHAFT
AutoCAD SHX Text
E. CLT.
AutoCAD SHX Text
AutoCAD SHX Text
LINEN CHUTE
AutoCAD SHX Text
HAC
AutoCAD SHX Text
AutoCAD SHX Text
PATIENT TOILET
AutoCAD SHX Text 461A
AutoCAD SHX Text
FP
AutoCAD SHX Text
TELE COM. CLOSET
AutoCAD SHX Text 484A
AutoCAD SHX Text
TELE
AutoCAD SHX Text
COMM
AutoCAD SHX Text
CLOSET
AutoCAD SHX Text
AutoCAD SHX Text
NOURISHMENT KITCHEN
AutoCAD SHX Text
AutoCAD SHX Text
PATIENT TOILET
AutoCAD SHX Text 478A
AutoCAD SHX Text
PATIENT TOILET
AutoCAD SHX Text 469A
AutoCAD SHX Text
ANTE RM
AutoCAD SHX Text 462A
AutoCAD SHX Text
PATIENT TOILET
AutoCAD SHX Text 482A
AutoCAD SHX Text
STAFF TLT.
AutoCAD SHX Text
AutoCAD SHX Text
PATIENT TOILET
AutoCAD SHX Text 471A
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
TOILET
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
AutoCAD SHX Text
CLEAN LINEN
AutoCAD SHX Text
AutoCAD SHX Text
ELECTRICAL
AutoCAD SHX Text
AutoCAD SHX Text
SHAFT
AutoCAD SHX Text
STAIR WELL
AutoCAD SHX Text
AutoCAD SHX Text
TOILET
AutoCAD SHX Text
AutoCAD SHX Text
CONFRENCE RM
AutoCAD SHX Text
AutoCAD SHX Text
PATIENT RM
AutoCAD SHX Text
AutoCAD SHX Text
SOILED UTILITY
AutoCAD SHX Text
AutoCAD SHX Text
PATIENT RM
AutoCAD SHX Text
AutoCAD SHX Text
PATIENT TOILET
AutoCAD SHX Text 479A
AutoCAD SHX Text
PATIENT RM
AutoCAD SHX Text
AutoCAD SHX Text
PATIENT RM
AutoCAD SHX Text
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text
C4AW
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text
C4AN
AutoCAD SHX Text
STAIR
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
AutoCAD SHX Text
TOILET
AutoCAD SHX Text 473A
AutoCAD SHX Text
PATIENT RM
AutoCAD SHX Text
AutoCAD SHX Text
PATIENT RM
AutoCAD SHX Text
AutoCAD SHX Text
PATIENT RM
AutoCAD SHX Text
AutoCAD SHX Text
PATIENT RM
AutoCAD SHX Text
AutoCAD SHX Text
PATIENT RM
AutoCAD SHX Text
AutoCAD SHX Text
ELEVATOR
AutoCAD SHX Text
ELEVATOR
AutoCAD SHX Text
PATIENT RM
AutoCAD SHX Text
AutoCAD SHX Text
PATIENT TOILET
AutoCAD SHX Text 467A
AutoCAD SHX Text
PATIENT RM
AutoCAD SHX Text
AutoCAD SHX Text
PATIENT RM
AutoCAD SHX Text
AutoCAD SHX Text
TOILET
AutoCAD SHX Text 465A
AutoCAD SHX Text
PATIENT RM
AutoCAD SHX Text
AutoCAD SHX Text
NURSE STATION
AutoCAD SHX Text
AutoCAD SHX Text
MED RM
AutoCAD SHX Text
AutoCAD SHX Text
CONFERENCE RM
AutoCAD SHX Text
AutoCAD SHX Text
PATIENT RM
AutoCAD SHX Text
AutoCAD SHX Text
PATIENT RM
AutoCAD SHX Text
AutoCAD SHX Text
TOILET
AutoCAD SHX Text 462B
AutoCAD SHX Text
PATIENT RM
AutoCAD SHX Text
AutoCAD SHX Text
PATIENT RM
AutoCAD SHX Text
AutoCAD SHX Text
PATIENT TOILET
AutoCAD SHX Text 457A
AutoCAD SHX Text
PATIENT RM
AutoCAD SHX Text
AutoCAD SHX Text
PATIENT RM
AutoCAD SHX Text
AutoCAD SHX Text
PATIENT TOILET
AutoCAD SHX Text 459A
AutoCAD SHX Text
FEC
AutoCAD SHX Text
FEC
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text
DAY RM
AutoCAD SHX Text
AutoCAD SHX Text
ASST. CHIEF ENG. OFFICE
AutoCAD SHX Text 447A
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text
CHIEF ENG. OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
ADMIN. OFF. ENG. SERV.
AutoCAD SHX Text 485A
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text 484B
AutoCAD SHX Text
AutoCAD SHX Text
ELECTRICAL CLOSET
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text
C4AE
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text
C4AS
AutoCAD SHX Text
C4BN
AutoCAD SHX Text
C4BW
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text
C4BE
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text
C4BEE
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text
C4BS
AutoCAD SHX Text
C4AE
AutoCAD SHX Text P3
AutoCAD SHX Text P4
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
EXP. JT.
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
REC. THERAPY OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
PROJECT "4B" LIMITS
FEC
F E
C
F E
C
F E
C
F E
C
FEC
4A 4B
5 5.04.00.05.0
5 5.04.00.05.0
5 5.04.00.05.0
5 5.04.00.05.0
X1
A1
X1
X1
X1
X1
A1 A1 A1 A1 A1
A1
A1
A2
A2
A2
A2
A2
A2
A1
A1
A1
A1
A1
A1
A1
A1 A1
A1 A1 A1
A1
A1A1
A2 A2
A2A2
A2 A2
A2
A2
A2 A2
A2
A2
A2
A2A2A2
A2 A2 A2
A2A2A2A2
A2 A2 A2
A2A2A2
A2 A2 A2
A1 A1 A1 A1 A1
A1
A2A2
A2 A2
A1
A1A1
A1A2
A2A2
A2A2
A2A2
A2A2
A2
A2 A2
A2 A2
A2 A2
A2 A2
A2 A2
A2 A2
A2 A2
A2 A2
A2 A2
A2 A2
A2 A2
A2 A2
A2 A2A1
A1
A1
A1
A2
A…