DRAWINGS 4 - 4B MEDICAL CENTER SUPPORT SPACE.pdf

PDF 6 MB Posted

Attached to
Z1DA--Renovate 4B for Medical Center Support Space - 565-17-305 Previous Pre-solicitation 36C24622B0014
Solicitation number
36C24622B0036
Issued by

About this file

This federal contract opportunity solicitation seeks proposals for Project 565-17-305 to renovate approximately 9,300 square feet in Building 1, Wing B, Floor 4 at the Fayetteville Veterans Affairs Medical Center. The scope of work includes demolition, framing, mechanical, electrical, plumbing, and finish work. Proposals are due by the date specified in the solicitation. Specific requirements include preparing the site for construction; complying with VA security procedures; and performing work between 7:00 am and 5:00 pm Monday through Friday or as approved by the Contracting Officer's Representative. The contractor shall furnish all supervision, labor, materials, and equipment to complete the project in accordance with the plans and specifications.

View the file

Other files

File Type Posted
Amendment 0003.docx DOCX document
36C24622B0036 0003.docx DOCX document
36C24622B0036 0002.docx DOCX document
36C24622B0036 PRE BID ATTENDANCE.pdf PDF
36C24622B0036 0001.docx DOCX document
SPECIFICATIONS 4B MEDICAL CENTER SUPPORT SPACE.pdf PDF
DRAWINGS 1 - 4B MEDICAL CENTER SUPPORT SPACE.pdf PDF
36C24622B0036.docx DOCX document
DRAWINGS 2 - 4B MEDICAL CENTER SUPPORT SPACE.pdf PDF
DRAWINGS 3 - 4B MEDICAL CENTER SUPPORT SPACE.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

3/31/2022

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FINAL CONSTRUCTION

DOCUMENTS

FULLY- SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Atriax, pllc

102 3rd Avenue, NE Hickory, NC 28601

P.O. Box 1629, Hickory, NC 28603

PH: 828-315-9962

www.atriaxgroup.com

RENOVATE 4B FOR MEDICAL

CENTER SUPPORT SPACE

Fayetteville VAMC Fayetteville, NC

565-17-305

Project Director

March 31, 2022Revisions: Date:

ELECTRICAL:

QUALITY CONSULTING ENGINEERS, LLC

6277-600 Carolina Commons Dr. #350 Indian Land, SC 29707

(P) 803.207.5450 djones@qualityconsultingengineers.com

MECHANICAL / PLUMBING:

SHULTZ ENGINEERING GROUP, PC

212 N. McDowell St, Suite 204 Charlotte, NC 28204

(P) 704.334.7363 www.shultzeg.com

MECHANICAL DETAILS

MH-203

WSC JKS 7 of 7

AutoCAD SHX Text

AutoCAD SHX Text

NTS

AutoCAD SHX Text

ACCESS SECTION FOR ROUND/OVAL DUCT

AutoCAD SHX Text

HOUSING WELDED TO DUCT SECTION

AutoCAD SHX Text

ROUND OR FLAT OVAL DUCT SECTION

AutoCAD SHX Text

COVER WITH HANDLE AND CHAIN RETAINER GASKETED AND PRESSURE SEALED

AutoCAD SHX Text

AutoCAD SHX Text

NTS

AutoCAD SHX Text

ROUND DUCT HANGERS

AutoCAD SHX Text 2500 [1133]

AutoCAD SHX Text 1320 [598]

AutoCAD SHX Text 420 [190]

AutoCAD SHX Text ONE 1 [25] x 18 GA STRAP

AutoCAD SHX Text 36 [900]

AutoCAD SHX Text

TWO 1/2 [13]%%C RODS

AutoCAD SHX Text

TWO 3/8 [10]%%C. RODS

AutoCAD SHX Text ONE 1 [25] x 16 GA STRAP

AutoCAD SHX Text 84 [2100]

AutoCAD SHX Text 60 [1500]

AutoCAD SHX Text 50 [1250]

AutoCAD SHX Text 700 [317]

AutoCAD SHX Text ONE 1 [25] x 22 GA STRAP

AutoCAD SHX Text

QUANTITY/SIZE

AutoCAD SHX Text

MAX. DUCT %%C

AutoCAD SHX Text 26 [650]

AutoCAD SHX Text

HANGER STRAPS OR RODS

AutoCAD SHX Text

MAX. LOAD

AutoCAD SHX Text LBS. [kg]

AutoCAD SHX Text 260 [119]

AutoCAD SHX Text

MAX.

AutoCAD SHX Text 144 [3600]

AutoCAD SHX Text IN. [mm]

AutoCAD SHX Text

SPACING

AutoCAD SHX Text IN. [mm]

AutoCAD SHX Text IN. [mm]

AutoCAD SHX Text 144 [3600]

AutoCAD SHX Text 144 [3600]

AutoCAD SHX Text 144 [3600]

AutoCAD SHX Text 144 [3600]

AutoCAD SHX Text NOTE: TABULATED DATA FROM SMACNA ALLOWS FOR DUCT REINFORCING AND INSULATION, BUT NO EXTERNAL LOAD.

AutoCAD SHX Text

BAND

AutoCAD SHX Text OVER 50" [1250mm]

AutoCAD SHX Text

HANGER RODS

AutoCAD SHX Text

BAND OF SAME SIZE AS HANGER STRAP

AutoCAD SHX Text

LOAD RATED FASTENERS

AutoCAD SHX Text 50" [1250mm] &UNDER

AutoCAD SHX Text DESIGNER'S NOTE: DESCRIBE OR DETAIL UPPER ATTACHMENTS APPLICABLE TO PARTICULAR PROJECTS.

AutoCAD SHX Text

AutoCAD SHX Text

NTS

AutoCAD SHX Text

FROM STRUCTURE

AutoCAD SHX Text

SAME AS DIFFUSER

AutoCAD SHX Text

INLET: 5'-0" MAX

AutoCAD SHX Text

FLEXIBLE DUCT SIZE

AutoCAD SHX Text

LENGTH.

AutoCAD SHX Text 12"

AutoCAD SHX Text

CEILING

AutoCAD SHX Text

SUPPORT SADDLE

AutoCAD SHX Text

VOLUME DAMPER W/

AutoCAD SHX Text

LOCKING QUAD

AutoCAD SHX Text

SADDLE

AutoCAD SHX Text

SHEET METAL

AutoCAD SHX Text

CONICAL OUTLET

AutoCAD SHX Text

BRANCH DUCT

AutoCAD SHX Text

FOR CHANGE OF

AutoCAD SHX Text

DIRECTION GREATER

AutoCAD SHX Text

USE RIGID ELBOWS

AutoCAD SHX Text

THAN 45%%D

AutoCAD SHX Text [300mm]

AutoCAD SHX Text

FLEXIBLE AIR DUCT CONNECTOR

AutoCAD SHX Text

SEE SPECIFICATIONS FOR CLAMPS AND SEALANT (TYP.)

AutoCAD SHX Text

TYPICAL DIFFUSER OR REGISTER IN LAY-IN CLG.

AutoCAD SHX Text

THERMAL INSULATION SEE SPECIFICATIONS

AutoCAD SHX Text

AutoCAD SHX Text

NTS

AutoCAD SHX Text ROOM THERMOSTAT/SENSOR WALL MOUNTED 48" [1200mm] AFF.

AutoCAD SHX Text

VARIABLE VOLUME AIR TERMINAL UNIT CONTROL DIAGRAM

AutoCAD SHX Text

AIR FLOW (CFM)

AutoCAD SHX Text

ROOM TEMPERATURE (°F)

AutoCAD SHX Text

HEATING MINIMUM

AutoCAD SHX Text

VAV BOX CONTROL SEQUENCE

AutoCAD SHX Text

SP

AutoCAD SHX Text

TU

AutoCAD SHX Text

RHC

AutoCAD SHX Text

HWS

AutoCAD SHX Text

HWR

AutoCAD SHX Text V-1

AutoCAD SHX Text

REHEAT COIL

AutoCAD SHX Text

AIR TERMINAL UNIT

AutoCAD SHX Text

AIR FLOW

AutoCAD SHX Text

TE

AutoCAD SHX Text

ATU CONTROLLER

AutoCAD SHX Text

PC

AutoCAD SHX Text

TE

AutoCAD SHX Text

AIR FLOW (CFM)

AutoCAD SHX Text

ROOM TEMPERATURE (°F)

AutoCAD SHX Text

HEATING MINIMUM

AutoCAD SHX Text

SP

AutoCAD SHX Text

NO DEADBAND

AutoCAD SHX Text

VAV BOX CONTROL SEQUENCE

AutoCAD SHX Text

W/DEADBAND

AutoCAD SHX Text 100%

AutoCAD SHX Text 100%

AutoCAD SHX Text

REHEAT FLOW

AutoCAD SHX Text

VAV AIR FLOW

AutoCAD SHX Text

VAV AIR FLOW

AutoCAD SHX Text

REHEAT FLOW

AutoCAD SHX Text A. UPON FALL IN SPACE TEMPERATURE THE VAV DAMPER WILL MODULATE TO MINIMUM POSITION. B. UPON FURTHER DROP IN SPACE TEMPERATURE VALVE V-1 WILL MODULATE TO MAINTAIN SET POINT + .5 F. THE + .5 F. THE .5° F. THE ADJUSTABLE TOLERANCE OF + .5 F HAS + .5 F HAS .5° F HAS BEEN SELECTED TO PREVENT VALVE HUNTING C. THE REVERSE SHALL OCCUR ON THE RISE IN SPACE TEMPERATURE.

AutoCAD SHX Text A. SET POINTS SHALL BE SET AS FOLLOWS: COOLING 75°F (ADJ) HEATING 70°F(ADJ) DEADBAND OF 5° F BETWEEN HEATING AND COOLING SET POINTS WILL BE MAINTAINED. B. UPON FALL IN SPACE TEMPERATURE THE VAV DAMPER WILL MODULATE TO MINIMUM POSITION. C. UPON FURTHER DROP IN SPACE TEMPERATURE VALVE V-1 WILL MODULATE TO MAINTAIN SET POINT + .5 F. THE + .5 F. THE .5° F. THE ADJUSTABLE TOLERANCE OF + .5 F HAS + .5 F HAS .5° F HAS BEEN SELECTED TO PREVENT VALVE HUNTING D. THE REVERSE SHALL OCCUR ON THE RISE IN SPACE TEMPERATURE.

AutoCAD SHX Text

FE

AutoCAD SHX Text

AutoCAD SHX Text

NTS

AutoCAD SHX Text

DUCT CONNECTIONS - AIR TERMINAL UNITS

AutoCAD SHX Text

NOTE: 1. 2. 3. 4.

AutoCAD SHX Text RIGID STRAIGHT TERMINAL UNIT INLET LENGTH SHALL BE A MINIMUM OF 3 TIMES THE DIAMETER OF INLET A FLEXIBLE AIR DUCT CONNECTOR IS NOT MANDATORY FOR INLET TO THIS BOX, BUT ALLOWED TO ACCOMMODATE MINOR OFFSETS. MAXIMUM LENGTH 3'-0" [900mm]. A BRANCH DUCT SERVING AN INDIVIDUAL BOX MAY BE THE SAME SIZE AS THE BOX INLET, PROVIDED THE EQUIVALENT LENGTH OF THE BRANCH DUCT, AS SHOWN, DOES NOT EXCEED 10 FEET (3 METERS). FOR LONGER LENGTHS, INCREASE THE DUCT SIZE AND PROVIDE A DUCT TRANSITION TO MAINTAIN THE DUCT STATIC PRESSURE DROP AT OR BELOW 0.2"/100' [1.64Pa/m]. FLEXIBLE AIR DUCT CONNECTORS, WHEN USED FROM TERMINAL UNIT SUPPLY AIR DUCT TO DIFFUSER, SHALL NOT EXCEED 5'-0" [1500mm]. USE RIGID ELBOWS FOR CHANGE OF DIRECTION GREATER THAN 45°.COMPONENT ARRANGEMENT MAY VARY BY MANUFACTURER. PROVIDE INSULATION W/VAPOR BARRIER FOR CONNECTING DUCT SECTIONS.

AutoCAD SHX Text

AIR TERMINAL UNIT (CV OR VAV)

AutoCAD SHX Text

REHEAT COIL

AutoCAD SHX Text

SOUND ATTENUATOR SEE EQUIPMENT SCHEDULE

AutoCAD SHX Text

FLEXIBLE AIR DUCT CONNECTOR. SEE DETAIL

AutoCAD SHX Text

DIFFUSER (TYP.)

AutoCAD SHX Text

SEE SPECIFICATIONS FOR CLAMPS AND SEALANT (TYP.)

AutoCAD SHX Text

SEE NOTE 5

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text P

AutoCAD SHX Text R

AutoCAD SHX Text O

AutoCAD SHX Text G

AutoCAD SHX Text E

AutoCAD SHX Text G

AutoCAD SHX Text N

AutoCAD SHX Text A

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text T

AutoCAD SHX Text L

AutoCAD SHX Text I

AutoCAD SHX Text N

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text G

AutoCAD SHX Text N

AutoCAD SHX Text

AutoCAD SHX Text W

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text U

AutoCAD SHX Text A

AutoCAD SHX Text 17231

AutoCAD SHX Text

SEAL

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text N

AutoCAD SHX Text

AutoCAD SHX Text R

AutoCAD SHX Text J

AutoCAD SHX Text I

AutoCAD SHX Text N

AutoCAD SHX Text C

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text H

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text O

AutoCAD SHX Text A

AutoCAD SHX Text R

AutoCAD SHX Text L

AutoCAD SHX Text O

AutoCAD SHX Text N

AutoCAD SHX Text O

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text A

CONSTRUCTION / PROJECT

LIMITS

2 HR FIRE WALL

1 HR FIRE WALL

1 HR FIRE / SMOKE WALL

E-001

ELECTRICAL - COVER SHEET

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY- SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Atriax, pllc

102 3rd Avenue, NE Hickory, NC 28601

P.O. Box 1629, Hickory, NC 28603

PH: 828-315-9962

www.atriaxgroup.com

RENOVATE 4B FOR MEDICAL

CENTER SUPPORT SPACE

Fayetteville VAMC Fayetteville, NC

565-17-305

Project Director

March 31, 2022Revisions: Date:

FINAL CONSTRUCTION

DOCUMENTSELECTRICAL:

QUALITY CONSULTING ENGINEERS, LLC

6277-600 Carolina Commons Dr. #350 Indian Land, SC 29707

(P) 803.207.5450 djones@qualityconsultingengineers.com

QCE PROJECT# 21007

MECHANICAL / PLUMBING:

SHULTZ ENGINEERING GROUP, PC

212 N. McDowell St, Suite 204 Charlotte, NC 28204

(P) 704.334.7363 www.shultzeg.com

DAJ GSB

Date: MARCH 31, 2022

Date: MARCH 31, 2022

AutoCAD SHX Text

WALL LEGEND

AutoCAD SHX Text

AutoCAD SHX Text

ENERGY SUMMARY

AutoCAD SHX Text 2013 ASHRAE 90.1 ENERGY CODE ELECTRICAL SYSTEM AND EQUIPMENT METHOD OF COMPLIANCE: (X)PRESCRIPTIVE ( )PERFORMANCE ( )ENERGY COST BUDGET LUMINAIRE SCHEDULE LAMP TYPE REQUIRED IN FIXTURE: SEE LUMINAIRE SCHEDULE SEE LUMINAIRE SCHEDULE NUMBER OF LAMPS IN FIXTURE: SEE LUMINAIRE SCHEDULE SEE LUMINAIRE SCHEDULE NUMBER OF BALLASTS IN FIXTURE: SEE LUMINAIRE SCHEDULE SEE LUMINAIRE SCHEDULE TOTAL WATTAGE PER FIXTURE: SEE LUMINAIRE SCHEDULE SEE LUMINAIRE SCHEDULE TOTAL INTERIOR LPD: 0.60 W/SF SPECIFIED VS. 1.21 W/SF ALLOWED 0.60 W/SF SPECIFIED VS. 1.21 W/SF ALLOWED MINIMUM EXTERIOR EFFICACY: NOT APPLICABLE NOT APPLICABLE EXTERIOR LIGHTING ZONE: NOT APPLICABLE NOT APPLICABLE PARKING AREAS: NOT APPLICABLE NOT APPLICABLE EXTERIOR ENTRY DOORS LPD: NOT APPLICABLE NOT APPLICABLE EXTERIOR ENTRY CANOPY LPD: NOT APPLICABLE NOT APPLICABLE EQUIPMENT SCHEDULES WITH MOTORS: SEE MECHANICAL DRAWINGS SEE MECHANICAL DRAWINGS MOTOR HORSEPOWER: SEE MECHANICAL DRAWINGS SEE MECHANICAL DRAWINGS NUMBER OF PHASES: SEE MECHANICAL DRAWINGS SEE MECHANICAL DRAWINGS MINIMUM EFFICIENCY: SEE MECHANICAL DRAWINGS SEE MECHANICAL DRAWINGS MOTOR TYPE: SEE MECHANICAL DRAWINGS SEE MECHANICAL DRAWINGS # OF POLES: SEE MECHANICAL DRAWINGS SEE MECHANICAL DRAWINGS PROJECT NEW/RENOVATION S.F.: 7,000 S.F. 7,000 S.F. INDOOR NON-EM FIXTURE CONTROL: OCCUPANCY SENSORS OCCUPANCY SENSORS OUTDOOR FIXTURE CONTROL: NOT APPLICABLENOT APPLICABLE

AutoCAD SHX Text

ABBREVIATIONS

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

TYPE

AutoCAD SHX Text

A, AMP

AutoCAD SHX Text

AC

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text

AF

AutoCAD SHX Text

AFC

AutoCAD SHX Text

AFF

AutoCAD SHX Text

AFG

AutoCAD SHX Text C

AutoCAD SHX Text

EF

AutoCAD SHX Text

EC

AutoCAD SHX Text

FA

AutoCAD SHX Text

FACP

AutoCAD SHX Text

AMPERE

AutoCAD SHX Text

ALTERNATING CURRENT

AutoCAD SHX Text

AMPERE FRAME

AutoCAD SHX Text

ABOVE FINISHED COUNTER

AutoCAD SHX Text

ABOVE FINISHED FLOOR

AutoCAD SHX Text

ABOVE FINISHED GRADE

AutoCAD SHX Text

CONDUIT

AutoCAD SHX Text

EXHAUST FAN

AutoCAD SHX Text

ELECTRICAL CONTRACTOR

AutoCAD SHX Text

G OR GND

AutoCAD SHX Text

GF, GFI

AutoCAD SHX Text

KVA

AutoCAD SHX Text

KW

AutoCAD SHX Text

MCB

AutoCAD SHX Text

NEC

AutoCAD SHX Text

OR PH

AutoCAD SHX Text

UON

AutoCAD SHX Text V

AutoCAD SHX Text W

AutoCAD SHX Text

WP

AutoCAD SHX Text

FIRE ALARM

AutoCAD SHX Text

FIRE ALARM CONTROL PANEL

AutoCAD SHX Text

GROUND

AutoCAD SHX Text

GROUND FAULT INTERRUPTER

AutoCAD SHX Text

KILOVOLT AMPERES

AutoCAD SHX Text

KILOWATTS

AutoCAD SHX Text

MAIN CIRCUIT BREAKER

AutoCAD SHX Text

PHASE

AutoCAD SHX Text

UNLESS OTHERWISE NOTED

AutoCAD SHX Text

VOLT(S)

AutoCAD SHX Text

WATTS OR WIRE

AutoCAD SHX Text

WEATHERPROOF

AutoCAD SHX Text P

AutoCAD SHX Text

POLE

AutoCAD SHX Text A

AutoCAD SHX Text

AIC

AutoCAD SHX Text

AMPERE INTERRUPTING CURRENT

AutoCAD SHX Text

CCT

AutoCAD SHX Text

CIRCUIT

AutoCAD SHX Text

MOCP

AutoCAD SHX Text

MAXIMUM OVERCURRENT PROTECTION

AutoCAD SHX Text

NATIONAL ELECTRICAL CODE

AutoCAD SHX Text

N OR NEUT

AutoCAD SHX Text

NEUTRAL

AutoCAD SHX Text

NTS

AutoCAD SHX Text

NOT TO SCALE

AutoCAD SHX Text

OC

AutoCAD SHX Text

ON CENTER

AutoCAD SHX Text

PB

AutoCAD SHX Text

PUSHBUTTON SWITCH

AutoCAD SHX Text

TBB

AutoCAD SHX Text

TELECOMMUNICATIONS BACKBOARD

AutoCAD SHX Text

TC

AutoCAD SHX Text

TELECOMMUNICATIONS CONTRACTOR

AutoCAD SHX Text

TYP

AutoCAD SHX Text

TYPICAL

AutoCAD SHX Text

TRANSFORMER

AutoCAD SHX Text

GC

AutoCAD SHX Text

GENERAL CONTRACTOR

AutoCAD SHX Text

PC

AutoCAD SHX Text

PLUMBING CONTRACTOR

AutoCAD SHX Text

XFMR

AutoCAD SHX Text

MC

AutoCAD SHX Text

MECHANICAL CONTRACTOR

AutoCAD SHX Text

FPN

AutoCAD SHX Text

FUSE PER NAMEPLATE

AutoCAD SHX Text

EOL

AutoCAD SHX Text

END OF LINE (RESISTOR)

AutoCAD SHX Text

FPC

AutoCAD SHX Text

FIRE PROTECTION CONTRACTOR

AutoCAD SHX Text

LPD

AutoCAD SHX Text

LIGHTING POWER DENSITY

AutoCAD SHX Text

TP

AutoCAD SHX Text

TAMPER PROOF/RESISTANT

AutoCAD SHX Text

ADO

AutoCAD SHX Text

AUTOMATIC DOOR OPENER

AutoCAD SHX Text

RDO

AutoCAD SHX Text

REMOTE DOOR OPERATOR VIA RELEASE BUTTON

AutoCAD SHX Text

SC

AutoCAD SHX Text

SECURITY CONTRACTOR

AutoCAD SHX Text

1. WITHIN THE PROJECT AREA, REMOVE ALL CONDUIT, WIRING, DEVICES, EQUIPMENT, AND ANY OTHER ELECTRICAL APPURTENANCES RENDERED USELESS, CURRENTLY ABANDONED OR WITHIN THE PROJECT AREA, REMOVE ALL CONDUIT, WIRING, DEVICES, EQUIPMENT, AND ANY OTHER ELECTRICAL APPURTENANCES RENDERED USELESS, CURRENTLY ABANDONED OR ABANDONED DUE TO CONSTRUCTION PER PHASE. REMOVAL OF ABANDONED AND USELESS WIRING SHALL BE BACK TO THE SOURCE, EVEN IF OUTSIDE LIMITS OF CONSTRUCTION. ROUGH-IN SHALL BE REMOVED BACK TO FLUSH WITH CONCRETE. ANCHORS SHALL BE REMOVED OR CUT FLUSH TO SURFACE OF CONCRETE. 2. EXISTING LIGHTS/DEVICES/WIRING TO REMAIN SHALL BE RE-FED AS REQUIRED TO MAINTAIN CIRCUIT CONTINUITY PER PHASE. EXISTING LIGHTS/DEVICES/WIRING TO REMAIN SHALL BE RE-FED AS REQUIRED TO MAINTAIN CIRCUIT CONTINUITY PER PHASE. 3. COORDINATE REMOVAL AND FINAL DISPOSITION OF EQUIPMENT WITH BUILDING OWNER PER THE GEMS PROGRAM. OWNER HAS FIRST RIGHT OF REFUSAL OF EQUIPMENT. COORDINATE REMOVAL AND FINAL DISPOSITION OF EQUIPMENT WITH BUILDING OWNER PER THE GEMS PROGRAM. OWNER HAS FIRST RIGHT OF REFUSAL OF EQUIPMENT. 4. PROVIDE BLANK STAINLESS STEEL COVER PLATES FOR ANY EXISTING JUNCTION BOXES FLUSH IN WALL THAT CANNOT BE FILLED OR PATCHED. PROVIDE BLANK STAINLESS STEEL COVER PLATES FOR ANY EXISTING JUNCTION BOXES FLUSH IN WALL THAT CANNOT BE FILLED OR PATCHED. 5. CLOSELY COORDINATE SCHEDULING OF PHASING WITH BUILDING OWNER AND OTHER TRADES. CLOSELY COORDINATE SCHEDULING OF PHASING WITH BUILDING OWNER AND OTHER TRADES. 6. MAINTAIN THE EXISTING CIRCUITS THAT ARE RUNNING THROUGH THE AREA BEING RENOVATED OR DEMOLISHED AND THE AREA OF NEW CONSTRUCTION. MAINTAIN THE EXISTING CIRCUITS THAT ARE RUNNING THROUGH THE AREA BEING RENOVATED OR DEMOLISHED AND THE AREA OF NEW CONSTRUCTION. 7. REMOVE EXISTING LIGHTS, SENSORS, FIRE ALARM DEVICES, WIRELESS ACCESS POINT DEVICES, PAGING SPEAKERS, SECURITY, AND EQUIPMENT LOCATOR DEVICES AND RELOCATE INTO REMOVE EXISTING LIGHTS, SENSORS, FIRE ALARM DEVICES, WIRELESS ACCESS POINT DEVICES, PAGING SPEAKERS, SECURITY, AND EQUIPMENT LOCATOR DEVICES AND RELOCATE INTO NEW CEILING IN AREAS WHERE CEILINGS ARE BEING REPLACED, AND WHERE INDICATED. 8. CONTRACTOR SHALL PROVIDE SUPPLEMENTAL EXIT AND EMERGENCY LIGHTING AND ASSOCIATED WIRING, AS NEEDED FROM PHASE TO PHASE, TO MAINTAIN PATHS OF EGRESS THAT CONTRACTOR SHALL PROVIDE SUPPLEMENTAL EXIT AND EMERGENCY LIGHTING AND ASSOCIATED WIRING, AS NEEDED FROM PHASE TO PHASE, TO MAINTAIN PATHS OF EGRESS THAT MAY CHANGE AS THE PHASING DEVELOPS. REFER TO THE ARCHITECTURAL LIFE SAFETY PLANS. 9. ALL ELECTRICAL, COMMUNICATIONS, SECURITY, FIRE ALARM DEVICES, FIXTURES, WIRING, ROUGH-IN, SUPPORTS, ETC. TO BE DISCONNECTED AND REMOVED BACK TO SOURCE OR ALL ELECTRICAL, COMMUNICATIONS, SECURITY, FIRE ALARM DEVICES, FIXTURES, WIRING, ROUGH-IN, SUPPORTS, ETC. TO BE DISCONNECTED AND REMOVED BACK TO SOURCE OR NEXT DEVICE TO REMAIN FOR EACH PHASED AREA OF RENOVATION TO FACILITATE WORK REQUIRED IN EACH PHASE. THIS INCLUDES ALL ABANDONED CABLING, ROUGH-IN, SUPPORTS, ETC. BACK TO A CLEAN DECK ABOVE. PROVIDE BLANK COVERS OVER FLUSH MOUNTED BOXES TO REMAIN. EXTRA ALL THREAD, ANCHOR BOLTS, MACHINE BOLTS, ETC. SHALL BE CUT AND BURRS REMOVED NO MORE THAN 3-5 THREADS ABOVE THE NUT OR THREADED CONNECTION. A MINIMUM OF 2 THREADS SHALL EXTEND PAST THE NUT ON ALL CONNECTIONS. ABANDONED CIRCUIT BREAKERS SHALL BE TURNED OFF AND LABELED AS SPARE.

AutoCAD SHX Text

SELECTIVE DEMOLITION NOTES:

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

TYPE

AutoCAD SHX Text

SYMBOL LEGEND

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

TYPE

AutoCAD SHX Text EXIT LIGHTING FIXTURE CONNECTED TO LIFE SAFETY BRANCH. PROVIDE FACES AS INDICATED ON DRAWINGS. CONNECT TO A CONSTANT HOT CONDUCTOR AHEAD OF LOCAL SWITCH. REFER TO LIGHTING FIXTURE SCHEDULE FOR ADDITIONAL INFORMATION.

AutoCAD SHX Text

QUADRUPLEX CONVENIENCE RECEPTACLE, 20A, 120V, MOUNT 18" AFF, UON.

AutoCAD SHX Text DUPLEX RECEPTACLE, 20A, 120V. SUBSCRIPT 'TV' DENOTES FOR CONNECTION TO TELEVISION, MOUNTED AT HEIGHT INDICATED.

AutoCAD SHX Text

GF

AutoCAD SHX Text

WP

AutoCAD SHX Text DUPLEX CONVENIENCE RECEPTACLE, GROUND FAULT INTERRUPTING TYPE, 20A, 120V, MOUNT 46" AFF, UON. (OR 6" ABOVE COUNTER AS APPLICABLE).

AutoCAD SHX Text DUPLEX RECEPTACLE, WEATHER RESISTANT GROUND FAULT INTERRUPTING TYPE WITH WET WHILE IN USE COVERPLATE, 20A, 120V, MOUNT 18" AFF, UON.

AutoCAD SHX Text S

AutoCAD SHX Text X

AutoCAD SHX Text LIGHTING CONTROL SYSTEM, LOCAL OCCUPANCY SENSOR, DUAL TECH, LINE VOLTAGE, WALL MOUNTED AT 46" AFF WITH INTEGRAL ON/OFF PUSH-BUTTON. PROVIDE AUXILIARY CONTACTS FOR FAN CONTROL WHERE NOTED. '2B' SUBSCRIPT DENOTES 2 BUTTONS FOR 2 ZONES.

AutoCAD SHX Text

OS

AutoCAD SHX Text

XXX

AutoCAD SHX Text SURFACE MOUNTED PANELBOARD 208/120 VOLT. DESIGNATION AS NOTED. REFER TO PANELBOARD SCHEDULES FOR ADDITIONAL INFORMATION.

AutoCAD SHX Text

TBB

AutoCAD SHX Text TELECOMMUNICATIONS BACKBOARD, 3/4" THICK X 8' HIGH X LENGTH PER PLANS, UON. BACKBOARD SHALL BE FIRE RATED.

AutoCAD SHX Text BRANCH CIRCUIT, OR FEEDER WIRING, RUN IN CONDUIT AND CIRCUIT HOMERUN TO PANELBOARD INDICATED. SINGLE PHASE CIRCUIT SHALL CONTAIN 1 #12 PHASE CONDUCTOR, 1 #12 NEUTRAL CONDUCTOR AND 1 #12 GROUNDING CONDUCTOR IN 3/4" CONDUIT, MINIMUM. CONDUCTORS LARGER THAN #12, AND CONDUIT LARGER THAN 3/4", SHALL BE AS INDICATED. WHERE "MULTIPLE PHASED" ELECTRICAL LOADS ARE REQUIRED, PROVIDE ADDITIONAL PHASE AND NEUTRAL CONDUCTORS AS INDICATED. MULTIPLE SINGLE PHASE CONDUCTORS MAY BE GROUPED TOGETHER IN A COMMON CONDUIT AS ALLOWED AND IN ACCORDANCE WITH THE NEC. CONTRACTOR SHALL PROVIDE ADDITIONAL "SWITCH LEG" CONDUCTORS, AS REQUIRED TO ACHIEVE FIXTURE CONTROL INDICATED ON PLANS. PROVIDE DEDICATED NEUTRAL CONDUCTOR FOR EACH SINGLE POLE CIRCUIT BREAKER. GROUNDING CONDUCTORS SHALL BE SHARED IN ACCORDANCE WITH AND AS ALLOWED BY THE NEC. WHEN SHOWN DASHED, IT SHALL DENOTE WIRING UNDERGROUND OR ABOVE TILE CEILING OF FLOOR BELOW.

AutoCAD SHX Text

1LA-3 (FOR EXAMPLE)

AutoCAD SHX Text SWITCH, 20A, 120/277V, MOUNT 46" AFF, UON. NO SUBSCRIPT DENOTES SINGLE POLE SWITCH. DENOTES SINGLE POLE SWITCH. SUBSCRIPT '3' DENOTES THREE WAY SWITCH. DENOTES THREE WAY SWITCH. SUBSCRIPT '4' DENOTES FOUR WAY SWITCH. DENOTES FOUR WAY SWITCH. SUBSCRIPT 'D' DENOTES DIMMER SWITCH. SIZE PER LIGHT SOURCE AND LOAD. DENOTES DIMMER SWITCH. SIZE PER LIGHT SOURCE AND LOAD. SUBSCRIPT 'VS' DENOTES VACANCY SENSOR DUAL TECHNOLOGY, LINE VOLTAGE, WALL MOUNTED AT DENOTES VACANCY SENSOR DUAL TECHNOLOGY, LINE VOLTAGE, WALL MOUNTED AT 46" AFF WITH ADJUSTABLE TIME, INTEGRAL PUSH-BUTTON FOR MANUAL ON AND AUTOMATIC OFF, DEFAULT TO 15-MINUTE.

AutoCAD SHX Text

RECEPTACLE 20A, 120V, MOUNT 18" AFF, UON.

AutoCAD SHX Text

CONDUIT WITH BUSHING.

AutoCAD SHX Text

CONDUIT TURNED UP.

AutoCAD SHX Text

CONDUIT TURNED DOWN.

AutoCAD SHX Text

CONDUIT CONTINUED

AutoCAD SHX Text

DUPLEX CONVENIENCE RECEPTACLE, RED FINISH, 20A, 120V, MOUNT 18" AFF, UON.

AutoCAD SHX Text SURFACE OR RECESSED LIGHTING FIXTURE ON NORMAL BRANCH, SEPARATELY SWITCHED CIRCUIT. REFER TO LUMINAIRE SCHEDULE FOR ADDITIONAL INFORMATION.

AutoCAD SHX Text LIGHTING CONTROL SYSTEM, LOCAL OCCUPANCY SENSOR, DUAL TECH, CEILING MOUNTED. PROVIDE POWER PACK AND WIRING AS REQUIRED. PROVIDE AUXILIARY CONTACTS FOR FAN CONTROL WHERE NOTED.

AutoCAD SHX Text

OS

AutoCAD SHX Text

XXX

AutoCAD SHX Text FLUSH MOUNTED PANELBOARD, 208/120 VOLT. DESIGNATION AS NOTED. REFER TO PANELBOARD SCHEDULES FOR ADDITIONAL INFORMATION.

AutoCAD SHX Text

TELECOMMUNICATIONS STYLE COPPER GROUND BAR WITH STAND-OFF INSULATORS.

AutoCAD SHX Text JUNCTION BOX, PROVIDE STANDARD 4" SQUARE BY 1-1/2" DEEP BOX, UON. CEILING MOUNTED. SUBSCRIPT "OHP" DENOTES OVERHEAD PROJECTOR. COORDINATE EXACT LOCATION IN THE FIELD.

AutoCAD SHX Text J

AutoCAD SHX Text

EWC

AutoCAD SHX Text DUPLEX RECEPTACLE, GROUND FAULT INTERRUPTING TYPE, FOR ELECTRIC WATER COOLER 20A, 120V, COORDINATE MOUNTING HEIGHT WITH PLUMBING CONTRACTOR PRIOR TO ROUGH-IN.

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text SWITCHES UNDER COMMON FACEPLATE USED FOR DUAL SWITCHING OF LIGHT FIXTURE WITHIN SAME ROOM, WALL MOUNTED AT 46" AFF.

AutoCAD SHX Text

OS

AutoCAD SHX Text LIGHTING CONTROL SYSTEM, LOCAL OCCUPANCY SENSOR, IR, LINE VOLTAGE, WALL MOUNTED AT 96" AFF WITH ADJUSTABLE HEAD, U.O.N. PROVIDE POWER PACK AND WIRING AS REQUIRED. ADJUST AIMING IN THE FIELD. MINIMUM OF 45' COVERAGE.

AutoCAD SHX Text

XXX

AutoCAD SHX Text SURFACE MOUNTED PANELBOARD/SWITCHBOARD 480/277 VOLT. DESIGNATION AS NOTED. REFER TO PANEL/SWITCHBOARD SCHEDULES FOR ADDITIONAL INFORMATION.

AutoCAD SHX Text

XXX

AutoCAD SHX Text FLUSH MOUNTED PANELBOARD, 480/277 VOLT. DESIGNATION AS NOTED. REFER TO PANELBOARD SCHEDULES FOR ADDITIONAL INFORMATION.

AutoCAD SHX Text T

AutoCAD SHX Text

PAD MOUNTED TRANSFORMER. REFER TO RISER DIAGRAM FOR ADDITIONAL INFORMATION.

AutoCAD SHX Text DUPLEX CONVENIENCE RECEPTACLE, TAMPER PROOF/RESISTANT TYPE, 20A, 120V, MOUNT 18" AFF, UON.

AutoCAD SHX Text

TP

AutoCAD SHX Text SURFACE OR RECESSED EMERGENCY LIGHTING FIXTURE ON LIFE SAFETY BRANCH CIRCUIT, CONNECTED AHEAD OF LOCAL SWITCHING. REFER TO LUMINAIRE SCHEDULE FOR ADDITIONAL INFORMATION.

AutoCAD SHX Text

NOTE: NOT ALL SYMBOLS MAY BE USED.

AutoCAD SHX Text E

AutoCAD SHX Text J

AutoCAD SHX Text JUNCTION BOX, PROVIDE STANDARD 4" SQUARE BY 1-1/2" DEEP BOX, UON. WALL MOUNTED AT 18" AFF, UON. VERIFY MOUNTING HEIGHT IN THE FIELD. PROVIDE 3/4" C. UP TO CEILING. SUBSCRIPT 'SF' DENOTES SYSTEMS FURNITURE CONNECTION. SUBSCRIPT 'D', DENOTES VOICE/DATA CABLING/CONNECTIVITY AS NOTED. POWER WHIP TO BE PROVIDED BY FURNITURE PROVIDER AND INSTALLED BY E.C., E.C. TO PROVIDE 1-1/4" FLEXIBLE LIQUIDTIGHT CONDUIT FOR DATA WHIP. VERIFY EXACT LOCATION IN THE FIELD.

AutoCAD SHX Text

XX

AutoCAD SHX Text

GENERAL NOTES

AutoCAD SHX Text

1. ALL WORK SHALL CONFORM TO THE NATIONAL ELECTRICAL CODE, NFPA, STATE CODE, LOCAL AUTHORITY REQUIREMENTS, VA TIL GUIDELINES, VA HANDBOOKS, AND SPECIFICATIONS. ALL WORK SHALL CONFORM TO THE NATIONAL ELECTRICAL CODE, NFPA, STATE CODE, LOCAL AUTHORITY REQUIREMENTS, VA TIL GUIDELINES, VA HANDBOOKS, AND SPECIFICATIONS. 2. THE CONTRACTOR SHALL VISIT THE PREMISES AND THOROUGHLY FAMILIARIZE THEMSELVES WITH ALL DETAILS OF THE WORK AND WORKING CONDITIONS. VERIFY ALL FIELD CONDITIONS AND ADVISE THE ENGINEER OF ANY DISCREPANCY THAT MAY PREVENT OR HINDER THE THE CONTRACTOR SHALL VISIT THE PREMISES AND THOROUGHLY FAMILIARIZE THEMSELVES WITH ALL DETAILS OF THE WORK AND WORKING CONDITIONS. VERIFY ALL FIELD CONDITIONS AND ADVISE THE ENGINEER OF ANY DISCREPANCY THAT MAY PREVENT OR HINDER THE SPECIFIED WORK FROM BEING COMPLETED. 3. THE CONTRACTOR SHALL STUDY THE STRUCTURE AND FINISH CONDITIONS AFFECTING THEIR WORK AND SHALL COORDINATE THEIR WORK ACCORDINGLY. THE CONTRACTOR SHALL PROVIDE ALL ACCESSORIES, HANGERS, AND ANCHORS AS NECESSARY TO MEET SUCH CONDITIONS THE CONTRACTOR SHALL STUDY THE STRUCTURE AND FINISH CONDITIONS AFFECTING THEIR WORK AND SHALL COORDINATE THEIR WORK ACCORDINGLY. THE CONTRACTOR SHALL PROVIDE ALL ACCESSORIES, HANGERS, AND ANCHORS AS NECESSARY TO MEET SUCH CONDITIONS WITHOUT ANY ADDITIONAL COST TO THE GOV'T. 4. PRIOR TO ACCOMPLISHING ANY WORK IN ANY AREA, ALL WORK, ESPECIALLY OUTAGES, SHALL BE COORDINATED AND SCHEDULED AHEAD OF TIME WITH WRITTEN APPROVAL FROM THE GOVERNMENT. PRIOR TO ACCOMPLISHING ANY WORK IN ANY AREA, ALL WORK, ESPECIALLY OUTAGES, SHALL BE COORDINATED AND SCHEDULED AHEAD OF TIME WITH WRITTEN APPROVAL FROM THE GOVERNMENT. 5. PROPERLY SUPPORT ALL WORK AND EQUIPMENT INSTALLED UNDER THIS CONTRACT. STUDY ALL DRAWINGS, MANUFACTURER'S INSTRUCTIONS, AND CATALOG DATA TO DETERMINE HOW EQUIPMENT ACCESSORIES, AND RELATED ITEMS ARE TO BE SUPPORTED, MOUNTED, OR PROPERLY SUPPORT ALL WORK AND EQUIPMENT INSTALLED UNDER THIS CONTRACT. STUDY ALL DRAWINGS, MANUFACTURER'S INSTRUCTIONS, AND CATALOG DATA TO DETERMINE HOW EQUIPMENT ACCESSORIES, AND RELATED ITEMS ARE TO BE SUPPORTED, MOUNTED, OR SUSPENDED. PROVIDE ALL BOLTS, INSERTS, BRACKETS, STRUCTURAL SUPPORTS, AND ACCESSORIES FOR PROPER SUPPORT OF EQUIPMENT FURNISHED UNDER THIS CONTRACT. 6. ALL WORK SHOWN LIGHT AND SOLID IS EXISTING TO REMAIN. ALL WORK SHOWN BOLD AND SOLID ON A NEW WORK PLAN IS NEW. ALL WORK SHOW BOLD AND/OR DASHED ON A DEMOLITION PLAN IS EXISTING TO BE DEMOLISHED. ALL WORK SHOWN LIGHT AND SOLID IS EXISTING TO REMAIN. ALL WORK SHOWN BOLD AND SOLID ON A NEW WORK PLAN IS NEW. ALL WORK SHOW BOLD AND/OR DASHED ON A DEMOLITION PLAN IS EXISTING TO BE DEMOLISHED. 7. COORDINATE MOUNTING HEIGHT AND LOCATION OF ALL WALL MOUNTED EQUIPMENT WITH ARCHITECTURAL ELEVATIONS. COORDINATE MOUNTING HEIGHT AND LOCATION OF ALL WALL MOUNTED EQUIPMENT WITH ARCHITECTURAL ELEVATIONS. 8. THE DRAWINGS ARE DIAGRAMMATIC IN NATURE AND DO NOT SHOW ALL POSSIBLE CONDITIONS. THE INSTALLATION SHALL BE FULLY COORDINATED WITH ALL EXISTING ARCHITECTURAL AND STRUCTURAL ELEMENTS. CONTRACTOR SHALL FIELD VERIFY AND CONFIRM ALL EXISTING THE DRAWINGS ARE DIAGRAMMATIC IN NATURE AND DO NOT SHOW ALL POSSIBLE CONDITIONS. THE INSTALLATION SHALL BE FULLY COORDINATED WITH ALL EXISTING ARCHITECTURAL AND STRUCTURAL ELEMENTS. CONTRACTOR SHALL FIELD VERIFY AND CONFIRM ALL EXISTING CONDITIONS AND ALLOW FOR ALL OFFSETS, REROUTING, ETC. AT NO ADDITIONAL COST TO THE GOVERNMENT. SHOULD THE CONTRACTOR ENCOUNTER ANY EXISTING EQUIPMENT, PIPING, DUCTWORK, ELECTRICAL, ETC. THAT INTERFERES WITH NEW WORK INSTALLATION, THEY SHALL REMOVE, RELOCATE AND REINSTALL SAME AT NO ADDITIONAL COST TO THE GOVERNMENT. 9. ALL LOW VOLTAGE CABLING SHALL BE INSTALLED IN EITHER BASKET STYLE CABLE TRAY OR J-HOOKS, WITH THE EXCEPTION OF THE FIRE ALARM SYSTEM THAT MUST BE IN CONDUIT. NO CABLING SHALL BE SUPPORTED OFF OF CONDUITS, PIPING, DUCTWORK, SHARED ALL LOW VOLTAGE CABLING SHALL BE INSTALLED IN EITHER BASKET STYLE CABLE TRAY OR J-HOOKS, WITH THE EXCEPTION OF THE FIRE ALARM SYSTEM THAT MUST BE IN CONDUIT. NO CABLING SHALL BE SUPPORTED OFF OF CONDUITS, PIPING, DUCTWORK, SHARED SUPPORTS, ETC. NO CABLING SHALL BE DRAPED ACROSS OTHER EQUIPMENT, RACEWAYS, DUCTWORK, LIGHTS OR CEILING GRID. SUPPORT CABLING INDIVIDUALLY. 10. PROVIDE HOOK AND LOOP FASTENERS ON BUNDLES OF LIKE CABLES ON 10' CENTERS WITHIN BASKET CABLE TRAY, ON 3' CENTERS ON CABLE RUNWAY WITHIN THE TELECOM ROOM AND ON 6" CENTERS FROM RUNWAY TO FINAL TERMINATION WITH THE RESPECTIVE RACKS, PROVIDE HOOK AND LOOP FASTENERS ON BUNDLES OF LIKE CABLES ON 10' CENTERS WITHIN BASKET CABLE TRAY, ON 3' CENTERS ON CABLE RUNWAY WITHIN THE TELECOM ROOM AND ON 6" CENTERS FROM RUNWAY TO FINAL TERMINATION WITH THE RESPECTIVE RACKS, CABINETS, PUNCHDOWN BLOCKS, ETC. 11. FOR CABLING ROUTED ON WALLS WITHIN THE TELECOM ROOM THAT IS NOT TERMINATED INTO ONE OF THE RACKS, ROUTE CABLING ON WALL WITHIN D RINGS OR VERTICAL CABLE RUNWAY TO TRAIN CABLING TO AVOID SAGGING AND STRAINING. FOR CABLING ROUTED ON WALLS WITHIN THE TELECOM ROOM THAT IS NOT TERMINATED INTO ONE OF THE RACKS, ROUTE CABLING ON WALL WITHIN D RINGS OR VERTICAL CABLE RUNWAY TO TRAIN CABLING TO AVOID SAGGING AND STRAINING. 12. PROVIDE ALL LOW VOLTAGE POWER SUPPLIES AS REQUIRED TO SUPPORT THE LOW VOLTAGE SYSTEMS NEEDS. PROVIDE ALL LOW VOLTAGE POWER SUPPLIES AS REQUIRED TO SUPPORT THE LOW VOLTAGE SYSTEMS NEEDS. 13. THE LIGHTING CONTROLS AND LOW VOLTAGE SYSTEMS ARE TO BE COMMISSIONED AND FULLY TESTED BY A MANUFACTURER'S AUTHORIZED REPRESENTATIVE. THE LIGHTING CONTROLS AND LOW VOLTAGE SYSTEMS ARE TO BE COMMISSIONED AND FULLY TESTED BY A MANUFACTURER'S AUTHORIZED REPRESENTATIVE. 14. REFER TO ARCHITECTURAL LIFE SAFETY PLAN FOR THE LOCATION ALL FIRE RATED WALLS/PARTITIONS/BARRIERS AND APPLY THE APPROPRIATE UL FIRE PENETRATION DETAIL. REFER TO ARCHITECTURAL LIFE SAFETY PLAN FOR THE LOCATION ALL FIRE RATED WALLS/PARTITIONS/BARRIERS AND APPLY THE APPROPRIATE UL FIRE PENETRATION DETAIL. 15. CONTRACTOR TO SUBMIT QUALIFICATIONS FOR SUPERINTENDENT AND KEY PERSONNEL FOR EACH (SUB)CONTRACTOR AS PART OF THE SHOP DRAWING PROCESS. CONTRACTOR TO SUBMIT QUALIFICATIONS FOR SUPERINTENDENT AND KEY PERSONNEL FOR EACH (SUB)CONTRACTOR AS PART OF THE SHOP DRAWING PROCESS. 16. CONTRACTOR TO TAKE AND DOWN AND REPLACE EXISTING CEILINGS AS REQUIRED TO FACILITATE NEW CONDUIT/WIRING INSTALLATION THAT IS PART OF THIS PROJECT. CONTRACTOR TO TAKE AND DOWN AND REPLACE EXISTING CEILINGS AS REQUIRED TO FACILITATE NEW CONDUIT/WIRING INSTALLATION THAT IS PART OF THIS PROJECT. 17. CONTRACTOR TO PATCH ALL HOLES IN FLOOR/WALLS/CEILINGS, THAT WERE CREATED AS A RESULT OF THIS PROJECT, WITH APPROPRIATE MATERIALS. CONTRACTOR TO PATCH ALL HOLES IN FLOOR/WALLS/CEILINGS, THAT WERE CREATED AS A RESULT OF THIS PROJECT, WITH APPROPRIATE MATERIALS. 18. CONTRACTOR SHALL SUBMIT COORDINATION DRAWINGS FOR ALL WORK, INCLUDING CONDUIT AND CABLE TRAY ROUTINGS, TO BE INSTALLED UNDER THIS PROJECT CONTRACT. COORDINATION DRAWINGS SHALL INDICATE ALL STRUCTURE, EQUIPMENT AND ROUTING OF PIPING, CONTRACTOR SHALL SUBMIT COORDINATION DRAWINGS FOR ALL WORK, INCLUDING CONDUIT AND CABLE TRAY ROUTINGS, TO BE INSTALLED UNDER THIS PROJECT CONTRACT. COORDINATION DRAWINGS SHALL INDICATE ALL STRUCTURE, EQUIPMENT AND ROUTING OF PIPING, DUCTWORK, ELECTRICAL, CONTROLS, SPRINKLERS AND FIRE ALARM SYSTEM. NO WORK SHALL BE COMMENCED PRIOR TO RECEIPT OF APPROVAL COORDINATION DRAWINGS FROM COR. COORDINATION DRAWINGS SHALL BE AT SCALES OF 1/4" = 1'-0" AND INCLUDE PLANS AND ELEVATIONS. 19. CONTRACTOR SHALL CONFORM TO ICRA AND ILSM REQUIREMENTS OF THIS PROJECT AS MANDATED BY VA INFECTION CONTROL AND SAFETY DEPARTMENT. ALL DEMOLISHED EQUIPMENT SHALL FOLLOW THE VA GEMS GUIDELINES. CONTRACTOR SHALL UTILIZE A EDGEGUARD OR CONTRACTOR SHALL CONFORM TO ICRA AND ILSM REQUIREMENTS OF THIS PROJECT AS MANDATED BY VA INFECTION CONTROL AND SAFETY DEPARTMENT. ALL DEMOLISHED EQUIPMENT SHALL FOLLOW THE VA GEMS GUIDELINES. CONTRACTOR SHALL UTILIZE A EDGEGUARD OR EQUAL INFECTION CONTROL CONTROL CONTAINMENT WALL SOLUTION. 20. ALL RENOVATION WORK IN THIS PROJECT SHALL RESULT IN A SYSTEM THAT IS COMPLETE AND FULLY OPERATIONAL WITHOUT MISSING ANCILLARY COMPONENTS. ALL RENOVATION WORK IN THIS PROJECT SHALL RESULT IN A SYSTEM THAT IS COMPLETE AND FULLY OPERATIONAL WITHOUT MISSING ANCILLARY COMPONENTS. 21. ALL NEW CONDUITS SHALL BE INSTALLED TIGHT TO DECK OR AS HIGH AS POSSIBLE, UNLESS AN EXCEPTION IS REQUESTED BY THE CONTRACTING OFFICER AND GRANTED, IN WRITING, BY THE COR. ALL NEW CONDUITS SHALL BE INSTALLED TIGHT TO DECK OR AS HIGH AS POSSIBLE, UNLESS AN EXCEPTION IS REQUESTED BY THE CONTRACTING OFFICER AND GRANTED, IN WRITING, BY THE COR. 22. ALL RACEWAYS SHALL BE INSTALLED PARALLEL WITH WALLS, CEILINGS AND STRUCTURE AND SHALL BE INSTALLED ABOVE ALL OTHER UTILITIES. ALL RACEWAYS SHALL BE INSTALLED PARALLEL WITH WALLS, CEILINGS AND STRUCTURE AND SHALL BE INSTALLED ABOVE ALL OTHER UTILITIES. 23. EACH SYSTEMS CONDUITS/J-HOOKS/CABLE TRAYS TO BE SUPPORTED INDIVIDUALLY, TIGHT TO THE STRUCTURE, UNLESS REQUESTED BY THE CONTRACTING OFFICER AND APPROVED IN WRITING BY THE COR. EACH SYSTEMS CONDUITS/J-HOOKS/CABLE TRAYS TO BE SUPPORTED INDIVIDUALLY, TIGHT TO THE STRUCTURE, UNLESS REQUESTED BY THE CONTRACTING OFFICER AND APPROVED IN WRITING BY THE COR. 24. PROJECT SHALL BE COMPLETED IN PHASES PER THE ARCHITECTURAL DRAWINGS. PROJECT SHALL BE COMPLETED IN PHASES PER THE ARCHITECTURAL DRAWINGS. 25. CONNECT PAGING SPEAKERS TO THE EXISTING FACILITY SYSTEM. CONNECT PAGING SPEAKERS TO THE EXISTING FACILITY SYSTEM. 26. CONTRACTOR SHALL XRAY SCAN THE FLOOR BEFORE CORE DRILLING.CONTRACTOR SHALL XRAY SCAN THE FLOOR BEFORE CORE DRILLING.

AutoCAD SHX Text EQUIPMENT CONNECTION, AS NOTED. REFER TO EQUIPMENT CONNECTION SCHEDULE FOR DETAILS.

AutoCAD SHX Text FLOOR MOUNTED, 2-GANG, FLOOR BOX ASSEMBLY WITH (2) DUPLEX CONVENIENCE RECEPTACLES, 20A, 120V, AND 1 GANG COMMUNICATION PROVISIONS. SURFACE MOUNTED ON FLOOR, FINISH AS COORDINATED WITH THE ARCHITECT. LEGRAND CONNECTRAC OR EQUAL. PROVIDE ALL ANCILLIARY PARTS AND EQUIPMENT FOR A COMPLETE SYSTEM, INCLUDING THE UNDERCARPET RACEWAY. ROUTE UNDERCARPET POWER RACEWAY TO NEAREST WALL THEN TRANSITION TO 1-1/4"C INSTALLED AND CONCEALED IN WALL. COORDINATE EXACT LOCATION IN THE FIELD WITH FURNITURE INSTALLER.

AutoCAD SHX Text SPECIAL PURPOSE RECEPTACLE. CONFIRM EXACT NEMA CONFIGURATION AND REQUIREMENTS WITH EQUIPMENT PROVIDER. MOUNT 46" AFF, UON.

AutoCAD SHX Text TELECOMMUNICATIONS OUTLET AT 18" AFF, 4-11/16" SQUARE BY 2-1/8" DEEP BOX, UON. PROVIDE 1-1/4" CONDUIT STUBBED UP TO NEAREST ACCESSIBLE GRID CEILING WITH DATA CABLES AND JACKS IN SINGLE GANG FACEPLATE, UON. PROVIDE 12" SERVICE LOOP PRIOR TO DROPPING DOWN TO OUTLET.

AutoCAD SHX Text TELECOMMUNICATIONS OUTLET AT 46" AFF, 4-11/16" SQUARE BY 2-1/8" DEEP BOX, UON. PROVIDE 1-1/4" CONDUIT STUBBED UP TO NEAREST ACCESSIBLE GRID CEILING WITH DATA CABLES AND JACKS IN SINGLE GANG FACEPLATE, UON. PROVIDE 12" SERVICE LOOP PRIOR TO DROPPING DOWN TO OUTLET. SUBSCRIPT 'HW' DENOTES MOUNTED IN HEADWALL.

AutoCAD SHX Text

PAGING SYSTEM, FLUSH CEILING SPEAKER.

AutoCAD SHX Text S

AutoCAD SHX Text CATV SYSTEM, TELEVISION OUTLET, WITH F CONNECTOR AND RG-6 CABLE, WALL MOUNTED AT HEIGHT SAME AS ADJACENT RECEPTACLE.

AutoCAD SHX Text

TV

AutoCAD SHX Text FLOOR MOUNTED, 2-GANG, FLOOR BOX ASSEMBLY 1 GANG COMMUNICATION PROVISIONS. SURFACE MOUNTED ON FLOOR, FINISH AS COORDINATED WITH THE ARCHITECT. LEGRAND CONNECTRAC OR EQUAL. PROVIDE ALL ANCILLIARY PARTS AND EQUIPMENT FOR A COMPLETE SYSTEM, INCLUDING THE UNDERCARPET RACEWAY. ROUTE UNDERCARPET COMMUNICATIONS RACEWAY TO NEAREST WALL THEN TRANSITION TO 1-1/4"C INSTALLED AND CONCEALED IN WALL. COORDINATE EXACT LOCATION IN THE FIELD WITH FURNITURE INSTALLER.

AutoCAD SHX Text TELECOM AP OUTLET, FLUSH MOUNTED IN CEILING, 4-11/16"SQ X 2-1/8"D BOX. REFER TO DETAILS & RISER.

AutoCAD SHX Text

WAP

AutoCAD SHX Text WIREBASKET CABLE TRAY AS NOTED, FURNISHED, INSTALLED & SUPPORTED BY T.C., FOR INSTALLATION OF CABLING BY T.C., 12"W X 4"D, LOCATED MIN. OF 4" ABOVE ACCESS. CEILING, W/ 12" TOP & 36" SIDE CLEARANCE. PROVIDE ALL REQUIRED OFFSETS FOR CONTINUOUS RUN.

AutoCAD SHX Text TELECOM OUTLET SEMI-FLUSH MOUNTED ON SYSTEMS FURNITURE RACEWAY. PROVIDE SHARED 1-1/4" FLEXIBLE CONDUIT FROM SHARED 4-11/16"SQ. X 2-1/8"D BOX ON WALL, 1-1/4"C. TO J-HOOKS AND CONTINUE ON TO T.R. REFER TO OUTLET AND FACEPLATE DETAILS & RISER.

AutoCAD SHX Text TELECOMMUNICATIONS OUTLET, 4-11/16" SQUARE BY 2-1/8" DEEP BOX, UON. PROVIDE 1-1/4" CONDUIT STUBBED UP TO NEAREST ACCESSIBLE GRID CEILING WITH DATA CABLES AND JACKS IN SINGLE GANG FACEPLATE, UON. PROVIDE 12" SERVICE LOOP PRIOR TO DROPPING DOWN TO OUTLET. MOUNT NEXT TO ADJACENT RECEPTACLE.

TV

E-802

ELECTRICAL - DETAILS

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY- SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Atriax, pllc

102 3rd Avenue, NE Hickory, NC 28601

P.O. Box 1629, Hickory, NC 28603

PH: 828-315-9962

www.atriaxgroup.com

RENOVATE 4B FOR MEDICAL

CENTER SUPPORT SPACE

Fayetteville VAMC Fayetteville, NC

565-17-305

Project Director

March 31, 2022Revisions: Date:

FINAL CONSTRUCTION

DOCUMENTSELECTRICAL:

QUALITY CONSULTING ENGINEERS, LLC

6277-600 Carolina Commons Dr. #350 Indian Land, SC 29707

(P) 803.207.5450 djones@qualityconsultingengineers.com

QCE PROJECT# 21007

MECHANICAL / PLUMBING:

SHULTZ ENGINEERING GROUP, PC

212 N. McDowell St, Suite 204 Charlotte, NC 28204

(P) 704.334.7363 www.shultzeg.com

DAJ GSB

Date: MARCH 31, 2022

Date: MARCH 31, 2022

O

R

A

F C

CEILING LINE

DRYWALL

FINISHED FLOOR

CONDUIT TO NEARBY CABLE TRAY ABOVE CEILING

BY E.C. AND CABLING BACK TO TELECOM RM ON

SAME FLOOR BY T.C.

INSULATED BUSHING

EMT CONNECTOR

P1 S1

LOW VOLTAGE BASE COMPARTMENT IN SYSTEMS

FURNITURE. FURNITURE IS TO BE BY THE FURNITURE

CONTRACTOR. COMMUNICATIONS CABLING, JACKS,

FACEPLATES, PATCH PANELS, TERMINATIONS, ETC. BY

T.C.

CAT6A

BLUE

CAT6A

BLUE

O

R

A

F C

CEILING LINE

DRYWALL

S

Q U

A R

E

2-1/8"

FINISHED FLOOR

BASE

COMPARTMENT

OF SYSTEMS FURNITURE

1-1/4" FLEX FROM BLANK COVER IN WALL BOX TO

SYSTEMS FURNITURE

BY E.C.

REFER TO SYSTEMS FURNITURE

OUTLET DETAIL THIS SHEET

1-1/4" CONDUIT TO ABOVE CEILING NEARBY CABLE TRAY BY

E.C., CABLING BY T.C.

INSULATED BUSHING

BY E.C.

EMT CONNECTOR, BY E.C.

EXTENDED DEPTH SYSTEMS FURNITURE FACEPLATE BY

T.C., COORDINATE WITH FURNITURE CONTRACTOR.

FURNITURE WILL PROVIDE A "KNOCK OUT" IN THE PANEL

BASE RACEWAY WHERE THE T.C. WILL PROVIDE THEIR

FACEPLATE.

SF

2 - 8 POSITION / 8 CONNECTOR CAT6A RJ 45

2 - BLANKS

2 - 4 PAIR CAT6A UTP CABLES (WHITE)

1 - MODULAR FURNITURE FACEPLATE

CONDUIT SCHEDULE:

UP TO 5 CAT6A CABLES = 3/4" CONDUIT

UP TO 8 CAT6A CABLES = 1" CONDUIT

UP TO 14 CAT6A CABLES = 1-1/4" CONDUIT

BOX SCHEDULE:

UP TO 5 CAT6A CABLES = 4"SQ. x 1-1/2"D

UP TO 8 CAT6A CABLES = 4-11/16"SQ. x 2-1/8"D

UP TO 14 CAT6A CABLES = 4-11/16"SQ. x 2-1/8"D

CONDUIT SCHEDULE:

UP TO 4 CAT6A CABLES = 1" CONDUIT

UP TO 8 CAT6A CABLES = 1-1/4" CONDUIT

AutoCAD SHX Text

AutoCAD SHX Text

8 POSITION / 8 CONNECTOR E1A/T1A-568B WIRING

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text W-O

AutoCAD SHX Text O

AutoCAD SHX Text W-G

AutoCAD SHX Text

BL

AutoCAD SHX Text

W-BL

AutoCAD SHX Text G

AutoCAD SHX Text

W-BR

AutoCAD SHX Text

BR

AutoCAD SHX Text

PAIR 1

AutoCAD SHX Text

PAIR 3

AutoCAD SHX Text

PAIR 2

AutoCAD SHX Text

PAIR 4

AutoCAD SHX Text

TELECOMMUNICATIONS - TYPICAL CAT6A RJ45 JACK

AutoCAD SHX Text

SCALE: N.T.S.

AutoCAD SHX Text

AutoCAD SHX Text

OUTLET LABEL

AutoCAD SHX Text

SINGLE GANG

AutoCAD SHX Text A

AutoCAD SHX Text

OUTLET RM # - 1

AutoCAD SHX Text B

AutoCAD SHX Text

FIBER CABLE

AutoCAD SHX Text

24 FIBER SM/MM

AutoCAD SHX Text F01 1-24

AutoCAD SHX Text

FIBER

AutoCAD SHX Text

SINGLE OR MULTIMODE

AutoCAD SHX Text

CABLE

AutoCAD SHX Text

BACKBONE CABLE LABEL

AutoCAD SHX Text 2A/G070 - 2/128

AutoCAD SHX Text

CABLE NUMBER

AutoCAD SHX Text

200PR 24 AWG

AutoCAD SHX Text C01 201-400

AutoCAD SHX Text

TERMINATION LOCATIONS

AutoCAD SHX Text

CABLE GAUGE

AutoCAD SHX Text

CABLE SIZE

AutoCAD SHX Text

TERMINATED COUNT

AutoCAD SHX Text

TMGB

AutoCAD SHX Text

ER1

AutoCAD SHX Text

TR

AutoCAD SHX Text

TBB

AutoCAD SHX Text

TBB

AutoCAD SHX Text

TELECOMMUNICATIONS ROOM

AutoCAD SHX Text

TGB

AutoCAD SHX Text

TGB

AutoCAD SHX Text

TELECOMMUNICATIONS MAIN GROUNDING BUSBAR

AutoCAD SHX Text

EQUIPMENT ROOM

AutoCAD SHX Text

GROUND BAR LABEL

AutoCAD SHX Text G070-R1-A-1

AutoCAD SHX Text

HORIZONTAL CABLE LABEL

AutoCAD SHX Text

TELECOMMUNICATIONS ROOM

AutoCAD SHX Text

PATCH PANEL

AutoCAD SHX Text Jacks shall be arranged and labeled according to their location in a room. They shall be arranged clockwise in ascending order around the room while standing in the doorway looking into the room. Jack number arrangements should work in clockwise order, as you enter the room. This labeling scheme adheres to the requirements outlined in the TIA/EIA 606 telecommunications standard. Labels on cables are to be the non-adhesive heat shrink style using a printer. Details are generic while nameplates shall be specific based on installed field conditions.

AutoCAD SHX Text A

AutoCAD SHX Text

PATCH PANEL LABEL

AutoCAD SHX Text

PATCH PANEL LETTER

AutoCAD SHX Text

OUTLET PORT LOCATION

AutoCAD SHX Text

JACK

AutoCAD SHX Text

RACK

AutoCAD SHX Text

2A/G070 - 143/BG120

AutoCAD SHX Text

TERMINATION LOCATIONS

AutoCAD SHX Text A

AutoCAD SHX Text G070-R2-A

AutoCAD SHX Text B

AutoCAD SHX Text

RACK DESCRIPTION AND NUMBER

AutoCAD SHX Text

DATA RACK R3

AutoCAD SHX Text

RACK LABEL

AutoCAD SHX Text

TELECOMMUNICATIONS - TYPICAL LABELING

AutoCAD SHX Text

SCALE: N.T.S.

AutoCAD SHX Text

AutoCAD SHX Text

1 - F TYPE CONNECTOR 1 - RG6U COAXIAL CABLE

AutoCAD SHX Text

AutoCAD SHX Text

TELECOMMUNICATIONS - TYPICAL CATV FACEPLATE

AutoCAD SHX Text

SCALE: N.T.S.

AutoCAD SHX Text

3 - 8-PIN RJ45 MODULAR CONNECTORS 3 - 4 PAIR CAT6A UTP CABLES

AutoCAD SHX Text

TYPICAL 3 PORT OIT FACEPLATE

AutoCAD SHX Text

SCALE: N.T.S.

AutoCAD SHX Text

AutoCAD SHX Text

INSTALLED ROOM NUMBER FOLLOWED BY SEQUENTIAL NUMBERING WITHIN ROOM

AutoCAD SHX Text

TELECOM ROOM SOURCE NUMBER FOLLOWED BACK RACK NUMBER AND PATCH PANEL NUMBER

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text

XXX

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text

XXX

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text

XXX

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text

XXX

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text

XXX

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text

XXX

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text

XXX

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text

XXX

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text

XXX

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text

XXX

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text

XXX

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text

XXX

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text

XXX

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text

XXX

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text

XXX

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text

XXX

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text

XXX

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text

XXX

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text

XXX

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text

XXX

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text

XXX

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text

XXX

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text

XXX

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text

XXX

AutoCAD SHX Text

PORT LABEL

AutoCAD SHX Text

TELECOMMUNICATIONS -

AutoCAD SHX Text J

AutoCAD SHX Text

TELECOMMUNICATIONS - SYSTEMS FURNITURE DETAIL

AutoCAD SHX Text

SCALE: N.T.S.

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

TELECOMMUNICATIONS - TYPICAL SYSTEMS FURNITURE ROUGH-IN

AutoCAD SHX Text

SCALE: N.T.S.

AutoCAD SHX Text

TELECOMMUNICATIONS - TYPICAL WALL OUTLET ROUGH-IN

AutoCAD SHX Text

SCALE: N.T.S.

AutoCAD SHX Text

AutoCAD SHX Text

FACEPLATE LABEL

AutoCAD SHX Text

BLANK

AutoCAD SHX Text

BLUE JACK/BLUE CABLE

AutoCAD SHX Text D1

AutoCAD SHX Text

FACEPLATE LABEL

AutoCAD SHX Text D3

AutoCAD SHX Text

WHITE JACK/BLUE CABLE

AutoCAD SHX Text D2

BLUE JACK/BLUE CABLE

EC4B

ETR

J3

ETR

ES4B ETR

EC4A1

ETR

EC4A2

ETR

N4A1

ETR

N4A2

ETR

EE4A

ETR

ES4A

ETR

J2

ETR

ED-101

ELECTRICAL - FOURTH FLOOR PLAN -

DEMOLITION

SCALE: 1/8" = 1'-0"

ELECTRICAL - FOURTH FLOOR PLAN - DEMOLITION

A. REMOVE DEVICES, SYSTEMS, AND ASSOCIATED WIRING AND CONDUIT WITHIN THE AREA TO BE ALTERED OR AS REQUIRED TO

FACILITATE NEW CONSTRUCTION. WIRING AND CONDUIT SHALL BE REMOVED BACK TO NEAREST REMAINING DEVICE. ABANDONED

CIRCUIT BREAKERS SHALL BE TURNED OFF AND LABELED AS SPARE.

B. REMOVE ALL CONDUIT, FITTINGS, BOXES, SUPPORTS, WIRING, WIRING DEVICES, LOW VOLTAGE CABLING/DEVICES, EQUIPMENT

CONNECTIONS INCLUDING THE INDIVIDUAL ROOM THRU THE WALL UNITS, AND ANY OTHER ELECTRICAL APPURTENANCES

RENDERED USELESS OR ABANDONED DUE TO CONSTRUCTION, UNLESS OTHERWISE NOTED. REMOVAL OF ABANDONED AND

USELESS WIRING SHALL BE BACK TO THE SOURCE, EVEN IF OUTSIDE LIMITS OF CONSTRUCTION.

C. EXISTING DEVICES TO REMAIN SHALL BE RE-FED AS REQUIRED TO MAINTAIN CIRCUIT CONTINUITY.

D. COORDINATE REMOVAL AND FINAL DISPOSITION OF EQUIPMENT WITH BUILDING OWNER, PER THE VA GEMS GUIDELINES.

E. PROVIDE BLANK STAINLESS STEEL COVER PLATES FOR ANY EXISTING JUNCTION BOXES FLUSH IN WALL THAT CANNOT BE FILLED

OR PATCHED.

F. MAINTAIN THE EXISTING CIRCUITS THAT ARE RUNNING THROUGH THE AREA BEING RENOVATED OR DEMOLISHED AND THE AREA

OF NEW CONSTRUCTION.

G. TEMPORARILY SUPPORT ANY AND ALL EXISTING CEILING MOUNTED WIRELESS ACCESS POINT DEVICES, PAGING SPEAKERS, SECURITY CAMERAS, AND EQUIPMENT/STAFF/PATIENT LOCATOR DEVICES AND RELOCATE INTO NEW CEILINGS ACCORDING TO

NEW FLOOR PLAN LAYOUT.

H. NO WORK IN HATCHED AREAS.

GENERAL NOTES:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY- SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Atriax, pllc

102 3rd Avenue, NE Hickory, NC 28601

P.O. Box 1629, Hickory, NC 28603

PH: 828-315-9962

www.atriaxgroup.com

RENOVATE 4B FOR MEDICAL

CENTER SUPPORT SPACE

Fayetteville VAMC Fayetteville, NC

565-17-305

Project Director

March 31, 2022Revisions: Date:

FINAL CONSTRUCTION

DOCUMENTSELECTRICAL:

QUALITY CONSULTING ENGINEERS, LLC

6277-600 Carolina Commons Dr. #350 Indian Land, SC 29707

(P) 803.207.5450 djones@qualityconsultingengineers.com

QCE PROJECT# 21007

MECHANICAL / PLUMBING:

SHULTZ ENGINEERING GROUP, PC

212 N. McDowell St, Suite 204 Charlotte, NC 28204

(P) 704.334.7363 www.shultzeg.com

DAJ GSB

Date: MARCH 31, 2022

1. IT IS UNDERSTOOD THAT THE TELECOM CABLING AND ACCESS CONTROLS IN THIS AREA OF RENOVATION ROUTES BACK TO THIS

TELECOM ROOM. DEMOLISH ALL EXISTING TELECOM AND ACCESS CONTROL EQUIPMENT, WIRING, CONDUIT, ETC. BACK TO THIS

ROOM, UNLESS OTHERWISE NOTED.

2. IT IS UNDERSTOOD THAT THE FIRE ALARM AND NURSE CALL SYSTEM CABLING IN THIS AREA OF RENOVATION ROUTES BACK TO

THIS ROOM . DEMOLISH ALL EXISTING FIRE ALARM AND NURSE CALL EQUIPMENT, WIRING, CONDUIT, ETC. BACK TO BOTH OR

EITHER OF THESE TWO ROOMS, UNLESS OTHERWISE NOTED.

3. IT IS UNDERSTOOD THAT THE TV COAX CABLING IN THIS AREA OF RENOVATION ROUTES BACK TO THIS ROOM. DEMOLISH ALL

EXISTING TV EQUIPMENT, WIRING, CONDUIT, ETC. BACK TO BOTH OR EITHER OF THESE TWO ROOMS, UNLESS OTHERWISE NOTED.

4. IT IS UNDERSTOOD THAT THE EQUIPMENT/STAFF/PATIENT LOCATOR CABLING IN THIS AREA OF RENOVATION ROUTES BACK TO

THIS ROOM. DEMOLISH ALL EXISTING LOCATOR EQUIPMENT, WIRING, CONDUIT, ETC. BACK TO BOTH OR EITHER OF THESE TWO

ROOMS, UNLESS OTHERWISE NOTED.

5. IT IS UNDERSTOOD THAT THE NORMAL AND EMERGENCY CIRCUITS IN THIS AREA OF RENOVATION ROUTE BACK TO PANELS IN THIS

ROOM. DEMOLISH ALL EXISTING WIRING, CONDUIT, ETC. BACK TO BOTH OR EITHER OF THESE TWO ROOMS, UNLESS OTHERWISE

NOTED.

KEYNOTES:

X

AutoCAD SHX Text

SHAFT

AutoCAD SHX Text

E. CLT.

AutoCAD SHX Text

AutoCAD SHX Text

LINEN CHUTE

AutoCAD SHX Text

HAC

AutoCAD SHX Text

AutoCAD SHX Text

PATIENT TOILET

AutoCAD SHX Text 461A

AutoCAD SHX Text

FP

AutoCAD SHX Text

TELE COM. CLOSET

AutoCAD SHX Text 484A

AutoCAD SHX Text

TELE

AutoCAD SHX Text

COMM

AutoCAD SHX Text

CLOSET

AutoCAD SHX Text

AutoCAD SHX Text

NOURISHMENT KITCHEN

AutoCAD SHX Text

AutoCAD SHX Text

PATIENT TOILET

AutoCAD SHX Text 478A

AutoCAD SHX Text

PATIENT TOILET

AutoCAD SHX Text 469A

AutoCAD SHX Text

ANTE RM

AutoCAD SHX Text 462A

AutoCAD SHX Text

PATIENT TOILET

AutoCAD SHX Text 482A

AutoCAD SHX Text

STAFF TLT.

AutoCAD SHX Text

AutoCAD SHX Text

PATIENT TOILET

AutoCAD SHX Text 471A

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

AutoCAD SHX Text

TOILET

AutoCAD SHX Text

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

AutoCAD SHX Text

STORAGE

AutoCAD SHX Text

AutoCAD SHX Text

CLEAN LINEN

AutoCAD SHX Text

AutoCAD SHX Text

ELECTRICAL

AutoCAD SHX Text

AutoCAD SHX Text

SHAFT

AutoCAD SHX Text

STAIR WELL

AutoCAD SHX Text

AutoCAD SHX Text

TOILET

AutoCAD SHX Text

AutoCAD SHX Text

CONFRENCE RM

AutoCAD SHX Text

AutoCAD SHX Text

PATIENT RM

AutoCAD SHX Text

AutoCAD SHX Text

SOILED UTILITY

AutoCAD SHX Text

AutoCAD SHX Text

PATIENT RM

AutoCAD SHX Text

AutoCAD SHX Text

PATIENT TOILET

AutoCAD SHX Text 479A

AutoCAD SHX Text

PATIENT RM

AutoCAD SHX Text

AutoCAD SHX Text

PATIENT RM

AutoCAD SHX Text

AutoCAD SHX Text

CORRIDOR

AutoCAD SHX Text

CORRIDOR

AutoCAD SHX Text

C4AW

AutoCAD SHX Text

CORRIDOR

AutoCAD SHX Text

C4AN

AutoCAD SHX Text

STAIR

AutoCAD SHX Text

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

AutoCAD SHX Text

STORAGE

AutoCAD SHX Text

AutoCAD SHX Text

TOILET

AutoCAD SHX Text 473A

AutoCAD SHX Text

PATIENT RM

AutoCAD SHX Text

AutoCAD SHX Text

PATIENT RM

AutoCAD SHX Text

AutoCAD SHX Text

PATIENT RM

AutoCAD SHX Text

AutoCAD SHX Text

PATIENT RM

AutoCAD SHX Text

AutoCAD SHX Text

PATIENT RM

AutoCAD SHX Text

AutoCAD SHX Text

ELEVATOR

AutoCAD SHX Text

ELEVATOR

AutoCAD SHX Text

PATIENT RM

AutoCAD SHX Text

AutoCAD SHX Text

PATIENT TOILET

AutoCAD SHX Text 467A

AutoCAD SHX Text

PATIENT RM

AutoCAD SHX Text

AutoCAD SHX Text

PATIENT RM

AutoCAD SHX Text

AutoCAD SHX Text

TOILET

AutoCAD SHX Text 465A

AutoCAD SHX Text

PATIENT RM

AutoCAD SHX Text

AutoCAD SHX Text

NURSE STATION

AutoCAD SHX Text

AutoCAD SHX Text

MED RM

AutoCAD SHX Text

AutoCAD SHX Text

CONFERENCE RM

AutoCAD SHX Text

AutoCAD SHX Text

PATIENT RM

AutoCAD SHX Text

AutoCAD SHX Text

PATIENT RM

AutoCAD SHX Text

AutoCAD SHX Text

TOILET

AutoCAD SHX Text 462B

AutoCAD SHX Text

PATIENT RM

AutoCAD SHX Text

AutoCAD SHX Text

PATIENT RM

AutoCAD SHX Text

AutoCAD SHX Text

PATIENT TOILET

AutoCAD SHX Text 457A

AutoCAD SHX Text

PATIENT RM

AutoCAD SHX Text

AutoCAD SHX Text

PATIENT RM

AutoCAD SHX Text

AutoCAD SHX Text

PATIENT TOILET

AutoCAD SHX Text 459A

AutoCAD SHX Text

FEC

AutoCAD SHX Text

FEC

AutoCAD SHX Text

CORRIDOR

AutoCAD SHX Text

DAY RM

AutoCAD SHX Text

AutoCAD SHX Text

ASST. CHIEF ENG. OFFICE

AutoCAD SHX Text 447A

AutoCAD SHX Text

CORRIDOR

AutoCAD SHX Text

CHIEF ENG. OFFICE

AutoCAD SHX Text

AutoCAD SHX Text

ADMIN. OFF. ENG. SERV.

AutoCAD SHX Text 485A

AutoCAD SHX Text

STORAGE

AutoCAD SHX Text 484B

AutoCAD SHX Text

AutoCAD SHX Text

ELECTRICAL CLOSET

AutoCAD SHX Text

CORRIDOR

AutoCAD SHX Text

C4AE

AutoCAD SHX Text

CORRIDOR

AutoCAD SHX Text

C4AS

AutoCAD SHX Text

C4BN

AutoCAD SHX Text

C4BW

AutoCAD SHX Text

CORRIDOR

AutoCAD SHX Text

C4BE

AutoCAD SHX Text

CORRIDOR

AutoCAD SHX Text

C4BEE

AutoCAD SHX Text

CORRIDOR

AutoCAD SHX Text

C4BS

AutoCAD SHX Text

C4AE

AutoCAD SHX Text P3

AutoCAD SHX Text P4

AutoCAD SHX Text

STORAGE

AutoCAD SHX Text

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

AutoCAD SHX Text

EXP. JT.

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

AutoCAD SHX Text

REC. THERAPY OFFICE

AutoCAD SHX Text

AutoCAD SHX Text

STORAGE

AutoCAD SHX Text

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

AutoCAD SHX Text

PROJECT "4B" LIMITS

FEC

F E

C

F E

C

F E

C

F E

C

FEC

4A 4B

5 5.04.00.05.0

5 5.04.00.05.0

5 5.04.00.05.0

5 5.04.00.05.0

X1

A1

X1

X1

X1

X1

A1 A1 A1 A1 A1

A1

A1

A2

A2

A2

A2

A2

A2

A1

A1

A1

A1

A1

A1

A1

A1 A1

A1 A1 A1

A1

A1A1

A2 A2

A2A2

A2 A2

A2

A2

A2 A2

A2

A2

A2

A2A2A2

A2 A2 A2

A2A2A2A2

A2 A2 A2

A2A2A2

A2 A2 A2

A1 A1 A1 A1 A1

A1

A2A2

A2 A2

A1

A1A1

A1A2

A2A2

A2A2

A2A2

A2A2

A2

A2 A2

A2 A2

A2 A2

A2 A2

A2 A2

A2 A2

A2 A2

A2 A2

A2 A2

A2 A2

A2 A2

A2 A2

A2 A2A1

A1

A1

A1

A2

A…